HILTI CFS-BTS Bottom Track Seal Instructions

June 15, 2024
HILTI

HILTI CFS-BTS Bottom Track Seal

Product description

  • Preformed firestop solution for bottom-of-wall drywall joints — helps increase productivity on the job site and eliminate the need for slower, messier sealants.

Applications for use

  • Firestop, smoke, and sound seal for the bottom of the wall joints between bottom track and drywall to flat and metal deck concrete slabs
  • Tested and UL classified with standard 1-hour and 2-hour partition walls, resilient channel walls and shaft walls (5/8” and 1-1/4” available).

Advantages

  • Easier to install under real job site conditions — compressible firestop joint seal suitable for installation in temperatures as low as 14°F (-10°C)
  • Higher productivity — the preformed firestop replaces 5/8” drywall shims and works with kick-lifts to help save time and improve quality control of drywall install
  • Zero waste — controlled material cost / easier to bid
  • Sound and Leakage-rated joint seal — CFS-BTS firestop can provide STC ratings for fire/sound walls, and has been tested in accordance with L-rating compliance in smoke barrier walls (IBC)
  • Compliance with LEED green building regulations provides industry-leading low VOC, LEED 4.1, and Red List (LBC) compliance
  • No skilled labor required and may not be subjective to destructive testing.

Installation instructions

  • See Hilti literature or third-party listings for application and installation details.

Technical Data

Chemical basis XLPE foam
Color White / Red
Recommended Application temperature 14° to 122°F (-10° to 50°C)
Storage and transportation temperature range 14° to 122°F (-10° to 50°C)
Temperature resistance range 14° to 122°F (-10° to 50°C)
Surface burning characteristics (ASTM E84-96) Flame Spread: 0 Smoke

Development: 0
Surface burning characteristics (CAN/ULC-S102)| Flame Spread: 0 Smoke Development: 5
Mold and mildew performance| Class 0 (ASTM G21-96)
Tested In accordance with| UL 2079 (5th Edition), CAN/ULC S115, ASTM D3575 Suffix L (modified)
LEEDv4.1| CDPH Standard Method v1.2-2017 Compliant
LEED VOC| 1 g/L
Length| 72 in (6ft)
Acoustics performance| 63 (relates to specific construction) ASTM E90
Shelf Life| Unlimited
Joint Width| 1/4” – 3/4”

Product information

Order Information

Designation Sales pack quantity Item number

Bottom track seal CFS-BTS (5/8”) ①
| 70| 2331840
Bottom track seal CFS-BTS (1-1/4”) ②
| 70| 2331841

FILL, VOID OR CAVITY MATERIAL FOR USE IN JOINT SYSTEMS SEE UL FIRE RESISTANCE DIRECTORY.

Customer Support

Hilti Firestop
Saving lives through innovation and education

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals