Product description

  • Preformed firestop solution for bottom-of-wall drywall joints — helps increase productivity on the job site and eliminate the need for slower, messier sealants.

Applications for use

  • Firestop, smoke, and sound seal for the bottom of the wall joints between bottom track and drywall to flat and metal deck concrete slabs
  • Tested and UL classified with standard 1-hour and 2-hour partition walls, resilient channel walls and shaft walls (5/8” and 1-1/4” available).

Advantages

  • Easier to install under real job site conditions — compressible firestop joint seal suitable for installation in temperatures as low as 14°F (-10°C)
  • Higher productivity — the preformed firestop replaces 5/8” drywall shims and works with kick-lifts to help save time and improve quality control of drywall install
  • Zero waste — controlled material cost / easier to bid
  • Sound and Leakage-rated joint seal — CFS-BTS firestop can provide STC ratings for fire/sound walls, and has been tested in accordance with L-rating compliance in smoke barrier walls (IBC)
  • Compliance with LEED green building regulations provides industry-leading low VOC, LEED 4.1, and Red List (LBC) compliance
  • No skilled labor required and may not be subjective to destructive testing.

Installation instructions

  • See Hilti literature or third-party listings for application and installation details.

Technical Data

Chemical basis XLPE foam
Color White / Red
Recommended Application temperature 14° to 122°F (-10° to 50°C)
Storage and transportation temperature range 14° to 122°F (-10° to 50°C)
Temperature resistance range 14° to 122°F (-10° to 50°C)
Surface burning characteristics (ASTM E84-96) Flame Spread: 0 Smoke

Development: 0
Surface burning characteristics (CAN/ULC-S102)| Flame Spread: 0 Smoke Development: 5
Mold and mildew performance| Class 0 (ASTM G21-96)
Tested In accordance with| UL 2079 (5th Edition), CAN/ULC S115, ASTM D3575 Suffix L (modified)
LEEDv4.1| CDPH Standard Method v1.2-2017 Compliant
LEED VOC| 1 g/L
Length| 72 in (6ft)
Acoustics performance| 63 (relates to specific construction) ASTM E90
Shelf Life| Unlimited
Joint Width| 1/4” – 3/4”

Product information

Order Information

Designation Sales pack quantity Item number

Bottom track seal CFS-BTS (5/8”) ①
| 70| 2331840
Bottom track seal CFS-BTS (1-1/4”) ②
| 70| 2331841

FILL, VOID OR CAVITY MATERIAL FOR USE IN JOINT SYSTEMS SEE UL FIRE RESISTANCE DIRECTORY.