H3HK SERIES P7RE Package Electric Heater Kits Instruction Manual
- June 15, 2024
- H3HK SERIES
Table of Contents
H3HK SERIES P7RE Package Electric Heater Kits
INSTALLATION INSTRUCTIONS
PACKAGE ELECTRIC HEATER KITS
Installation of H3HK Heater Kits (208/240V & 460V) in Packaged Air
Conditioners & Packaged Heat Pumps.
IMPORTANT
ATTENTION INSTALLERS
- These instructions are primarily intended to assist qualified individuals experienced in the proper installation of this appliance. Some local codes require licensed installation/service personnel for this type equipment. All installations must be in accordance with these instructions and with all applicable national and local codes and standards.
- Read these instructions thoroughly before starting the installation. Return these instructions to the customer’s package for future reference.
IMPORTANT SAFETY INFORMATION
INSTALLER: Please read all instructions before servicing this equipment. Pay attention to all safety warnings and any other special NOTES highlighted in the manual. Safety markings are used frequently throughout this manual to designate a degree or level of seriousness and should not be ignored. WARNING indicates a potentially hazardous situation that if not avoided, could result in personal injury or death. CAUTION indicates a potentially hazardous situation that if not avoided, may result in minor or moderate injury or property damage.
WARNING
- Failure to follow safety warnings exactly could result in serious injury, death or property damage. Improper servicing could result in dangerous operation, serious injury, death or property damage.
- Before servicing, disconnect all electrical power to the unit.
- When servicing controls, label all wires prior to disconnecting. Reconnect wires correctly.
- reify proper operation after servicing.
WARNING
- Unless noted otherwise in these instructions, only factory authorized parts or accessory kits may be used with this product. Improper installation, service, adjustment, or maintenance may cause explosion, fire, electrical shock or other hazardous conditions which may result in personal injury or property damage
- Use caution when removing components or handling this product. Personal injury can occur from sharp metal edges present in all sheet metal constructed equipment.
GENERAL INFORMATION
- H3HK heater kits are approved for use in packaged air conditioners and packaged heat pumps when applied and installed according to these instructions. See Table 3 (page 7), Table 4 and Table 5 (page 8), Table 6 (page 9), Table 7 and Table 8 (page 10), Table 9 (page 11), Table 10 (page 12), Table 11 (page 13) and Table 12 (page 14) for approved H3HK air conditioner and heat pump applications. Refer to the National Electric Code (ANSI/NFPA 70) or in Canada the Canadian Electric Code Part 1 (CSA C.22.1) and applicable local codes for overcurrent protection and disconnect requirements.
Clearances to Combustibles
- All units are approved for zero clearance to combustibles when installed according to these instructions and other instructions included with the unit and other approved accessories. See Table 1, (page 4).
ELECTRICAL SUPPLY
- If the unit was previously installed without electric heat, the existing supply wiring may not be sufficient to handle the increased load. See the unit rating label or
- Table 12 (page 14), Table 13 (page 15), Table 14 (page 16), Table 15 and Table 16 (page 17), Table 17 (page 18), Table 18 (page 19), Table 19 and Table 20 (page 20), Table 21 (page 21), Table 22 (page 22), Table 23 (page 23) and Table 24 (page 24) for minimum circuit ampacities and maximum overcurrent protection ratings.
- Units with installed electric heat may be supplied by a single circuit or by multiple circuits. Additional accessory kits may be required if single circuit installation and/or circuit breakers are desired. See Figure 1 for kit identification and Table 1 for part numbers and accessory descriptions.
Circuit Options
- The units with electric heat may be wired for single or multiple circuits and may have circuit breakers or terminal blocks. NOTE: Circuit breakers installed in the unit are for short- circuit protection of the internal wiring and to serve as a unit disconnect. The circuit breakers DO NOT provide overcurrent protection of the
- supply wiring.
- • Overcurrent protection must be provided at the branch circuit distribution panel even if circuit breakers are not used in the units. It must be sized as shown in Table 12 (page 14), Table 13 (page 15), Table 14 (page 16), Table 15 and Table 16 (page 17), Table 17 (page 18), Table 18 (page 19), Table 19 and Table 20 (page 20),
- Table 21 (page 21), Table 22 (page 22), Table 23 (page 23) and Table 24 (page 24) or on the unit rating label and according to the National Electric Code, Canadian Electrical Code and applicable local codes. NOTE: In most cases the overcurrent protection specified on the unit rating label is less than the 60 amp rating of the
- circuit breakers used in the units. This is because the function of the overcurrent protection required at the distribution panel (field supplied) and the unit mounted breakers is different.
- • When circuit breakers are used they must be used on all circuits. Refer to Table 3 (page 7), Table 4 and Table 5 (page 8), Table 6 (page 9), Table 7 and Table 8 (page 10), Table 9 (page 11), Table 10 (page 12), Table 11 (page 13) and Table 12 (page 14) for the correct circuit breaker for the application.
- • If the number of circuits listed in Table 3 (page 7), Table 4 and Table 5 (page 8), Table 6 (page 9), Table 7 and Table 8 (page 10), Table 9 (page 11), Table 10 (page 12), Table 11 (page 13) and Table 12 (page 14) are more than 1, circuit breakers are required. If single circuit supply wiring is desired: Use the 4-pole circuit
- adapter kit (P/N 1039295) when two 2-pole circuit breakers are used. If 3 circuit breakers are used, a field supplied U.L. Listed 6-pole single circuit adaptor can be used. The single circuit adapter kits are not applicable to 3-phase units.
- • If circuit breakers are not being used, proceed to the Terminal Blocks section.
Circuit Breakers
- If circuit breakers are used for any circuit, they must be used for all circuits. Use one breaker for each circuit.
- See Table 3 (page 7), Table 4 and Table 5 (page 8), Table 6 (page 9), Table 7 and Table 8 (page 10), Table 9 (page 11), Table 10 (page 12), Table 11 (page 13) and Table 12 (page 14).
Breaker Attachment
- Install the circuit breaker mounting rail to the control panel with the 4 blunt tip screws provided.
Attaching to Bracket
- Attach the circuit breakers in the unit by hooking the bottom in the base of the circuit breaker onto the left rail of the bracket and rotating to the right. The circuit breaker should snap into place. Install the breakers so that the ON position is to the right. See Figure 2 (page 6) for component location.
HEATER KITS | DESCRIPTION | PART NUMBER |
---|---|---|
1 Phase 208/230v | H3HK005H-01C (5kW) | 917166C |
H3HK008H-01C (8kW) | 917167C | |
H3HK010H-01C (10kW) | 917168C | |
H3HK015H-01C (15kW) | 917169C | |
H3HK015H-21C (15kW) | 917172C | |
H3HK020H-01C (20kW) | 917170C | |
H3HK020H-21C (20kW) | 917173C | |
3 Phase 208/230v | H3HK-009Q-01C (9kW) | 903854C |
H3HK-015Q-01C (15kW) | 903855C | |
3 Phase 460v | H3HK-009S-01B (9kW) | 903850B |
H3HK-015S-01B (15kW) | 903851B |
Accessories
| 4-Pole Single Circuit Adaptor*| 1039295
Circuit Breaker, 1 Phase (2-Pole)| 913554
Circuit Breaker, 3 Phase (3-Pole)| 913740
- Single phase models only
Table 1. Heater Kits & Accessories
Breaker Removal
- Insert a screwdriver into the hole in the release tab and pull out while rotating the breaker out and to the left. The white release tab is located at the base of the breaker under the line side (right) terminals.
- Single Circuit Kit
(single phase only)
- Refer to the instructions included with the single circuit adapter kit for details on how to configure the adapter. Install the adapter as shown in the instructions in the line side (right) of the breakers. Proceed to the Element Installation section.
Terminal Blocks
- H3HK heater kits are shipped with a terminal block for small package units. For large package units the kit terminal block(s) will not be used. The electric heater kits will be wired to the existing factory installed terminal block. If the number of circuits indicated in Table 3 (page 7), Table 4 and Table 5 (page 8), Table 6 (page 9), Table 7 and Table 8 (page 10), Table 9 (page 11), Table 10 (page 12), Table 11 (page 13) and Table 12 (page 14) is 2 or 3, then the circuit breakers must be used. See Circuit Options section.
ELEMENT INSTALLATION
- The heater will not function properly if the elements are installed incorrectly.
Pre-Installation
- Remove the control box access panel. Locate the heater plug assembly (9 pin for single phase kits or 12 pin for 3 phase kits) and remove the jumper cap. Discard the jumper cap; it will not be used after installing the heater kits. Remove the heater close-off plate(s) in the electric heat panel. When installing single banks of
- heaters, position them closest to the blower. See Figure 2 (page 6).
Element Power Wiring
- Route the main power leads (heavy black & red wires) and the 9 or 12-pin heat plug through the access hole at the top of the control panel to the circuit breaker or terminal block.
- Connect the 9 or 12-pin heat kit plug to the heat accessory plug located in the control box. For connections, refer to the detailed wiring diagrams: Figure 4 (page 34), Figure 5 (page 35), Figure 6 (page 36), Figure 7 (page 37), Figure 8 (page 38), Figure 9 (page 39), Figure 10 (page 40), Figure 11 (page 41), Figure 12 (page 42),
- Figure 13 (page 43) and Figure 14 (page 44). Make sure all connections are secure.
- Select large package units have additional terminal blocks installed. The power leads from the heater kit should be attached to these terminal blocks.
- Wires needed to connect from terminal blocks to circuit breakers should be field supplied. The 6 inch leads are provided with the heater kit to connect the circuit breaker(s) to the compressor contactor. Mark the appropriate box on the unit rating plate with an “X” to indicate which heater kit has been installed. NOTE:
- Torque the circuit breaker lugs to 45 in-lbs.
Horizontal Supply & Return
- Install the heater kit with the limit control towards the top of the unit when using side supply and return duct openings.
Vertical Supply & Return
- Vertical Installation of 8 & 10 kW Heater Kits
- Install the heater kit with the limit towards the bottom of the unit. When installing single bank(s) of heater(s), position them closest to the blower.
- Rooftop applications with vertical ducts must have an elbow installed in the supply duct so that the elements are not directly over a supply grille.
-
Remove the two screws on the heater kit unit holding both heating element plates together if modifying the location of the element to be closer to the blower.
-
. Tilt the heating element plate forward to create clearance of contactor wires. Move it to the other side of the heating element bank and then back down, aligning the edge holes of the heating element plates.
NOTE : This allows the unit to be turned around so that both the element being closest to the blower and limit being towards the bottom of the unit conditions are satisfied. If the low voltage coil wires on the contactor need to be removed mark each wire prior to removal to ensure proper and easier reinstallation. -
Using the two screws removed in step 1, fasten the element close-off plates together.
Installation of 15 & 20 kW Heater Kit s
- The 15 & 20 kW heater kit includes a contactor bracket that must be mounted on the blower transition panels of the package equipment. Loosen the screw toward the middle of the transition panel enough so that the open slot on the bracket will slide into this screw. See Figure 2 (page 6).
- • If installing in a large package unit, the mounting screw for the front of this bracket will be on the top side of the blower transition panel closest to the supply duct opening.
• If installing in a small package unit, the mounting screw will be on the side of the blower transition. Remove this screw to allow the contactor bracket to slide into the back screw.
Reinstall the front screw and tighten the back screw firmly.
NOTE : Make sure the element support rod is inserted into the support
bracket. Fasten the heater with the same screws used to secure the close-off
plates. See Figure 3 (page 6).
Staged Heat
To stage the heat on the 15 kW or 20 kW heater kits, the factory set wiring
will need to be modified. The orange wire in Pin 2 on the heat accessory plug
will be re-routed. See the installation instructions supplied with the heat
pump or air conditioner for typical thermostat connections.
AIRFLOW
All heater kit temperature rise data in Table 25 (page 25), Table 26 & Table
27 (page 26), Table 28 (page 27), Table 29 (page 28), Table 30 (page 29),
Table 31 (page 30), Table 32 (page 31), Table 33 (page 32) and Table 34 (page
33) have been calculated using 10kW heaters (9kW for 3 phase units). For other
sized heater kits, use the following steps below to determine the heat rise
for your particular heater kit.
- Determine your CFM. NOTE: Find this data by locating your blower motor tap settings in the data supplied with the Installation Instructions.
- Locate your heater kits kW value and Btu/h in Table 2.
- Input the values into the following equation:
*TEMP RISE:∆T=(BTU/H)/(CFM1.08)**
NOTE: Generally the heat rise should be 30 – 40 degrees. Anything above 40
degrees should be avoided.
k W/H | BTU/H |
---|---|
5 | 17,060 |
8 | 27,297 |
9 | 30,709 |
10 | 34,121 |
15 | 51,182 |
20 | 68,242 |
Table 2. kW & BTU/h Ratings
EQUIPMENT COMPONENTS
HEATER KIT CROSS REFERENCE TABLES
*Heater Kit Cross References For Model ()P7RE / PPA3RE**
**MODEL| TONNAGE & PHASE| NOMINAL KW| HEATER KIT MODEL|
HEATER KIT PART NUMBER| BREAKERS REQUIRED
()P7RE| 1.5 Ton Single Phase| 5| H3HK005H-01C| 917166C| NONE
8| H3HK008H-01C| 917167C| NONE
10| H3HK010H-01C| 917168C| NONE
15| H3HK015H-01C| 917169C| 2
()P7RE PPA3RE| 2 Ton Single Phase| 5| H3HK005H-01C| 917166C| NONE
8| H3HK008H-01C| 917167C| NONE
10| H3HK010H-01C| 917168C| NONE
15| H3HK015H-01C| 917169C| 2
()P7RE PPA3RE| 2.5 Ton Single Phase| 5| H3HK005H-01C| 917166C| NONE
8| H3HK008H-01C| 917167C| NONE
10| H3HK010H-01C| 917168C| NONE
15| H3HK015H-01C| 917169C| 2
()P7RE PPA3RE| 3 Ton Single Phase| 5| H3HK005H-01C| 917166C| NONE
8| H3HK008H-01C| 917167C| NONE
10| H3HK010H-01C| 917168C| NONE
15| H3HK015H-01C| 917169C| 2
()P7RE PPA3RE| 3.5 Ton Single Phase| 5| H3HK005H-01C| 917166C| NONE
8| H3HK008H-01C| 917167C| NONE
10| H3HK010H-01C| 917168C| NONE
15| H3HK015H-01C| 917169C| 2
20| H3HK020H-01C| 917170C| 2
()P7RE PPA3RE| 4 Ton Single Phase| 5| H3HK005H-01C| 917166C| NONE
8| H3HK008H-01C| 917167C| NONE
10| H3HK010H-01C| 917168C| NONE
15| H3HK015H-01C| 917169C| 2
20| H3HK020H-01C| 917170C| 2
****(*)P7RE PPA3RE| ** 5 Ton Single Phase| 5| H3HK005H-01C|
917166C| NONE
8| H3HK008H-01C| 917167C| NONE
10| H3HK010H-01C| 917168C| NONE
15| H3HK015H-01C| 917169C| 2
20| H3HK020H-01C| 917170C| 2
*Table 3. ()P7RE / PPA3RE, Single Phase**
*Heater Kit Cross References For Model ()P7RF / PPA3RF**
**MODEL| TONNAGE & PHASE| NOMINAL KW| HEATER KIT MODEL|
HEATER KIT PART NUMBER| BREAKERS REQUIRED
(*)P7RF PPA3RF| **
2 Ton Single Phase
| 5| H3HK005H-01C| 917166C| NONE
8| H3HK008H-01C| 917167C| NONE
10| H3HK010H-01C| 917168C| NONE
15| H3HK015H-01C| 917169C| 2
**(*)P7RF PPA3RF| ** 3 Ton Single Phase| 5| H3HK005H-01C| 917166C|
NONE
8| H3HK008H-01C| 917167C| NONE
10| H3HK010H-01C| 917168C| NONE
15| H3HK015H-01C| 917169C| 2
**(*)P7RF PPA3RF| ** 4 Ton Single Phase| 5| H3HK005H-01C| 917166C|
NONE
8| H3HK008H-01C| 917167C| NONE
10| H3HK010H-01C| 917168C| NONE
15| H3HK015H-01C| 917169C| 2
20| H3HK020H-01C| 917170C| 2
**(*)P7RF PPA3RF**
| **** 5 Ton Single Phase| 5| H3HK005H-01C| 917166C| NONE
8| H3HK008H-01C| 917167C| NONE
10| H3HK010H-01C| 917168C| NONE
15| H3HK015H-01C| 917169C| 2
20| H3HK020H-01C| 917170C| 2
*Table 4. ()P7RF / PPA3RF, Single Phase**
*Heater Kit Cross References For Model ()P8SE / PPA3SE**
**MODEL| TONNAGE & PHASE| NOMINAL KW| HEATER KIT MODEL|
HEATER KIT PART NUMBER| BREAKERS REQUIRED
****(*)P8SE PPA3SE| ** 3 Ton Single Phase| 5| H3HK005H-01C| 917166C|
None
8| H3HK008H-01C| 917167C| None
10| H3HK010H-01C| 917168C| None
15| H3HK015H-01C| 917169C| 2
**(*)P8SE PPA3SE| ** 4 Ton Single Phase| 5| H3HK005H-01C| 917166C|
None
8| H3HK008H-01C| 917167C| None
10| H3HK010H-01C| 917168C| None
15| H3HK015H-01C| 917169C| 2
20| H3HK020H-01C| 917170C| 2
**(*)P8SE PPA3SE| ** 5 Ton Single Phase| 5| H3HK005H-01C| 917166C|
None
8| H3HK008H-01C| 917167C| None
10| H3HK010H-01C| 917168C| 2
15| H3HK015H-01C| 917169C| 2
20| H3HK020H-01C| 917170C| 3
**(*)P8SE PPA3SE| ** 3,4, & 5 TON
3 Phase, 208/230V
| 9| H3HK-009Q-01C| 903854C| None
15| H3HK-015Q-01C| 903855C| None
*()P8SE PPA3SE**| 3,4, & 5 TON
3 Phase, 460V
| 9| H3HK-009S-01B| 903850B| None
15| H3HK-015S-01B| 903851B| None
*Table 5. ()P8SE / PPA3SE, Single Phase & 3-Phase**
*Heater Kit Cross References For Model ()Q6SE / PPHH2SE**
**MODEL| TONNAGE, & PHASE| NOMINAL KW| HEATER KIT
MODEL| HEATER KIT PART NUMBER| BREAKERS REQUIRED
****(*)Q6SE PPH2SE| **
**** 2 Ton Single Phase
| 5| H3HK005H-01C| 917166C| None
8| H3HK008H-01C| 917167C| 2
10| H3HK010H-01C| 917168C| 2
15| H3HK015H-01C| 917169C| 3
**(*)Q6SE PPH2SE| ** 2.5 Ton Single Phase| 5| H3HK005H-01C| 917166C|
None
8| H3HK008H-01C| 917167C| 2
10| H3HK010H-01C| 917168C| 2
15| H3HK015H-01C| 917169C| 3
**(*)Q6SE PPH2SE| **
3 Ton Single Phase
| 5| H3HK005H-01C| 917166C| None
8| H3HK008H-01C| 917167C| 2
10| H3HK010H-01C| 917168C| 2
15| H3HK015H-01C| 917169C| 3
**(*)Q6SE PPH2SE| ** 3.5 Ton Single Phase| 5| H3HK005H-01C| 917166C|
2
8| H3HK008H-01C| 917167C| 2
10| H3HK010H-01C| 917168C| 2
15| H3HK015H-01C| 917169C| 3
20| H3HK020H-01C| 917170C| 3
**(*)Q6SE PPH2SE| **
**** 4 Ton Single Phase
| 5| H3HK005H-01C| 917166C| 2
8| H3HK008H-01C| 917167C| 2
10| H3HK010H-01C| 917168C| 2
15| H3HK015H-01C| 917169C| 3
20| H3HK020H-01C| 917170C| 3
**(*)Q6SE PPH2SE| ** 5 Ton Single Phase| 5| H3HK005H-01C|
917166C| 2
8| H3HK008H-01C| 917167C| 2
10| H3HK010H-01C| 917168C| 2
15| H3HK015H-01C| 917169C| 3
20| H3HK020H-01C| 917170C| 3
**(*)Q6SE PPH2SE| ** 3,4, & 5 TON,
3 Phase, 208/230V
| 9| H3HK-009Q-01C| 903854C| None
15| H3HK-015Q-01C| 903855C| 2
*()Q6SE PPH2SE| ** 3,4, & 5 TON,
3 Phase, 460V
| 9| H3HK-009S-01B| 903850B| None
15| H3HK-015S-01B| 903851B| None
*Table 6. ()Q6SE / PPH2SE, Single Phase & 3-Phase**
*Heater Kit Cross References For Model ()Q7RE / PPH3RE**
**MODEL| ****TONNAGE & PHASE| ****NOMINAL KW|
****HEATER KIT MODEL| ****HEATER KIT PART NUMBER| ****BREAKERS
REQUIRED
****(*)Q7RE PPH3RE| ** 2 Ton Single Phase| 5| H3HK005H-01C|
917166C| NONE
8| H3HK008H-01C| 917167C| 2
10| H3HK010H-01C| 917168C| 2
**(*)Q7RE PPH3RE| ** 2.5 Ton Single Phase| 5| H3HK005H-01C|
917166C| NONE
8| H3HK008H-01C| 917167C| 2
10| H3HK010H-01C| 917168C| 2
15| H3HK015H-01C| 917169C| 2
**(*)Q7RE PPH3RE| ** 3 Ton Single Phase| 5| H3HK005H-01C|
917166C| NONE
8| H3HK008H-01C| 917167C| 2
10| H3HK010H-01C| 917168C| 2
15| H3HK015H-01C| 917169C| 2
**(*)Q7RE PPH3RE| ** 3.5 Ton Single Phase| 5| H3HK005H-
01C| 917166C| NONE
8| H3HK008H-01C| 917167C| 2
10| H3HK010H-01C| 917168C| 2
15| H3HK015H-01C| 917169C| 2
20| H3HK020H-01C| 917170C| 3
**(*)Q7RE PPH3RE| ** 4 Ton Single Phase| 5| H3HK005H-01C|
917166C| 2
8| H3HK008H-01C| 917167C| 2
10| H3HK010H-01C| 917168C| 2
15| H3HK015H-01C| 917169C| 2
20| H3HK020H-01C| 917170C| 3
**(*)Q7RE PPH3RE| ** 5 Ton Single Phase| 5| H3HK005H-01C|
917166C| 2
8| H3HK008H-01C| 917167C| 2
10| H3HK010H-01C| 917168C| 2
15| H3HK015H-01C| 917169C| 2
20| H3HK020H-01C| 917170C| 3
Table 7. ()Q7RE / PPH3RE, Single PhasTable 7. ()Q7RE / PPH3RE, Single Phasee
*Heater Kit Cross References For Model ()Q7RF / PPH3RF**
**MODEL| TONNAGE & PHASE| NOMINAL KW| HEATER KIT
MODEL| HEATER KIT PART NUMBER| BREAKERS REQUIRED
****(*)Q7RF PPH3RF| ** 2 Ton Single Phase| 5| H3HK005H-01C|
917166C| NONE
8| H3HK008H-01C| 917167C| NONE
10| H3HK010H-01C| 917168C| 2
15| H3HK015H-01C| 917169C| 2
**(*)Q7RF PPH3RF| ** 3 Ton Single Phase| 5| H3HK005H-01C|
917166C| NONE
8| H3HK008H-01C| 917167C| 2
10| H3HK010H-01C| 917168C| 2
15| H3HK015H-01C| 917169C| 2
**(*)Q7RF PPH3RF**
| **** 4 Ton Single Phase| 5| H3HK005H-01C| 917166C| 2
8| H3HK008H-01C| 917167C| 2
10| H3HK010H-01C| 917168C| 2
15| H3HK015H-01C| 917169C| 2
20| H3HK020H-01C| 917170C| 3
*()Q7RF PPH3RF**
| **** 5 Ton Single Phase| 5| H3HK005H-01C| 917166C| 2
8| H3HK008H-01C| 917167C| 2
10| H3HK010H-01C| 917168C| 2
15| H3HK015H-01C| 917169C| 2
20| H3HK020H-01C| 917170C| 3
*Table 8. ()Q7RF / PPH3RF, Single Phase**
*Heater Kit Cross Reference For Model ()Q8SF / PPH3SF, Single Phase**
MODEL| TONNAGE & PHASE| NOMINAL
kW
| HEATER KIT MODEL| HEATER KIT PART NUMBER| BREAKERS REQUIRED
*()Q8SF PPH3SF**
| ****
2 Ton Single Phase
| 5| H3HK005H-01C| 917166C| None
8| H3HK008H-01C| 917167C| 2
10| H3HK010H-01C| 917168C| 2
15| H3HK015H-01C| 917169C| 3
**(*)Q8SF PPH3SF| **
**** 3 Ton Single Phase
| 5| H3HK005H-01C| 917166C| None
8| H3HK008H-01C| 917167C| 2
10| H3HK010H-01C| 917168C| 2
15| H3HK015H-01C| 917169C| 3
**(*)Q8SF PPH3SF| ** 4 Ton Single Phase| 5| H3HK005H-01C| 917166C|
None
8| H3HK008H-01C| 917167C| 2
10| H3HK010H-01C| 917168C| 2
15| H3HK015H-01C| 917169C| 3
*Table 9. ()Q8SF / PPH3SF, Single Phase**
*Heater Kit Cross Reference For Model ()P94RD**
MODEL| TONNAGE & PHASE| NOMINAL
kW
| HEATER KIT MODEL| HEATER KIT PART NUMBER| BREAKERS REQUIRED
*()P94RD-018K**
| 1.5 Ton Single Phase| 5| H3HK005H-01C| 917166C| NONE
8| H3HK008H-01C| 917167C| NONE
10| H3HK010H-01C| 917168C| NONE
15| H3HK015H-01C| 917169C| 2
**(*)P94RD-024K| ** 2 Ton Single Phase| 5| H3HK005H-01C| 917166C|
NONE
8| H3HK008H-01C| 917167C| NONE
10| H3HK010H-01C| 917168C| NONE
15| H3HK015H-01C| 917169C| 2
**(*)P94RD-030K**
| 2.5 Ton Single Phase| 5| H3HK005H-01C| 917166C| NONE
8| H3HK008H-01C| 917167C| NONE
10| H3HK010H-01C| 917168C| NONE
15| H3HK015H-01C| 917169C| 2
**(*)P94RD-036K| ** 3 Ton Single Phase| 5| H3HK005H-01C| 917166C|
NONE
8| H3HK008H-01C| 917167C| NONE
10| H3HK010H-01C| 917168C| NONE
15| H3HK015H-01C| 917169C| 2
**(*)P94RD-042K**
| 3.5 Ton Single Phase| 5| H3HK005H-01C| 917166C| NONE
8| H3HK008H-01C| 917167C| NONE
10| H3HK010H-01C| 917168C| NONE
15| H3HK015H-01C| 917169C| 2
20| H3HK020H-01C| 917170C| 2
**(*)P94RD-048K| ** 4 Ton Single Phase| 5| H3HK005H-01C| 917166C|
NONE
8| H3HK008H-01C| 917167C| NONE
10| H3HK010H-01C| 917168C| NONE
15| H3HK015H-01C| 917169C| 2
20| H3HK020H-01C| 917170C| 2
**(*)P94RD-060K| ** 5 Ton Single Phase| 5| H3HK005H-01C| 917166C|
NONE
8| H3HK008H-01C| 917167C| NONE
10| H3HK010H-01C| 917168C| NONE
15| H3HK015H-01C| 917169C| 2
20| H3HK020H-01C| 917170C| 2
*Table 10. ()P94RD, Single Phase**
*Heater Kit Cross Reference For Model ()Q94RD**
MODEL| TONNAGE & PHASE| NOMINAL
kW
| HEATER KIT MODEL| HEATER KIT PART NUMBER| BREAKERS REQUIRED
*()Q94RD-024K**
| 2 Ton Single Phase| 5| H3HK005H-01C| 917166C| None
8| H3HK008H-01C| 917167C| None
10| H3HK010H-01C| 917168C| 2
15| H3HK015H-01C| 917169C| 2
**(*)Q94RD-030K| ** 2.5 Ton Single Phase| 5| H3HK005H-01C| 917166C|
None
8| H3HK008H-01C| 917167C| None
10| H3HK010H-01C| 917168C| 2
15| H3HK015H-01C| 917169C| 2
**(*)Q94RD-036K| ** 3 Ton Single Phase| 5| H3HK005H-01C| 917166C|
None
8| H3HK008H-01C| 917167C| 2
10| H3HK010H-01C| 917168C| 2
15| H3HK015H-01C| 917169C| 2
**(*)Q94RD-042K**
| ****
**** 3.5 Ton Single Phase
| 5| H3HK005H-01C| 917166C| None
8| H3HK008H-01C| 917167C| 2
10| H3HK010H-01C| 917168C| 2
15| H3HK015H-01C| 917169C| 2
20| H3HK020H-01C| 917170C| 3
*()Q94RD-048K**
| ****
**** 4 Ton Single Phase
| 5| H3HK005H-01C| 917166C| 2
8| H3HK008H-01C| 917167C| 2
10| H3HK010H-01C| 917168C| 2
15| H3HK015H-01C| 917169C| 3
20| H3HK020H-01C| 917170C| 3
**(*)Q94RD-060K| **
**** 5 Ton Single Phase
| 5| H3HK005H-01C| 917166C| 2
8| H3HK008H-01C| 917167C| 2
10| H3HK010H-01C| 917168C| 2
15| H3HK015H-01C| 917169C| 3
20| H3HK020H-01C| 917170C| 3
*Table 11. ()Q94RD, Single Phase**
*Heater Kit Cross Reference For Model ()Q104SD**
MODEL| TONNAGE & PHASE| NOMINAL
kW
| HEATER KIT MODEL| HEATER KIT PART NUMBER| BREAKERS REQUIRED| FIGURE
*()Q104SD**
| 2 Ton Single Phase| 5| H3HK005H-01C| 917166C| None| _
8| H3HK008H-01C| 917167C| 2| 7
10| H3HK010H-01C| 917168C| 2| 7
15| H3HK015H-01C| 917169C| 2 or 3| 9 or 10
**(*)Q104SD| ** 2.5 Ton Single Phase| 5| H3HK005H-01C| 917166C|
None| _
8| H3HK008H-01C| 917167C| 2| 7
10| H3HK010H-01C| 917168C| 2| 7
15| H3HK015H-01C| 917169C| 2 or 3| 9 or 10
*()Q104SD**
| ****
3 Ton Single Phase
| 5| H3HK005H-01C| 917166C| None| _
8| H3HK008H-01C| 917167C| 2| 7
10| H3HK010H-01C| 917168C| 2| 7
15| H3HK015H-01C| 917169C| 2 or 3| 9 or 10
*()Q104SD**
| ****
3.5 Ton Single Phase
| 5| H3HK005H-01C| 917166C| 2| 5
8| H3HK008H-01C| 917167C| 2| 7
10| H3HK010H-01C| 917168C| 2| 7
15| H3HK015H-01C| 917169C| 3| 10
20| H3HK020H-01C| 917170C| 3| 12
*()Q104SD**
| ****
4 Ton Single Phase
| 5| H3HK005H-01C| 917166C| 2| 5
8| H3HK008H-01C| 917167C| 2| 7
10| H3HK010H-01C| 917168C| 2| 7
15| H3HK015H-01C| 917169C| 3| 10
20| H3HK020H-01C| 917170C| 3| 12
*()Q104SD**
| ****
5 Ton Single Phase
| 5| H3HK005H-01C| 917166C| 2| 5
8| H3HK008H-01C| 917167C| 2| 7
10| H3HK010H-01C| 917168C| 2| 7
15| H3HK015H-01C| 917169C| 3| 10
20| H3HK020H-01C| 917170C| 3| 12
*Table 12. ()Q104SD, Single Phase**
ELECTRICAL DATA
*MODEL ()P7RE / PPA3RE, SINGLE PHASE, 208/230V**
*MODEL ()P7RE / PPA3RE| ****HEATER KW| SINGLE CIRCUIT|
MULTIPLE SUPPLY CIRCUIT OPTION
****MCA| ****MOP| CIRCUIT A (COMPRESSOR & FAN)| CIRCUIT B
(BLOWER & HEATER)
MCA| MOP| MCA| MOP
018K| 0| 13.2| 15| —| —| —| —
5| 29.8| 30| —| —| —| —
8| 44.3| 45| —| —| —| —
10| 54.8| 60| —| —| —| —
15| 79.8| 80| 54.8| 60| 25| 30
024K| 0| 15.2| 20| —| —| —| —
5| 29.8| 30| —| —| —| —
8| 44.3| 45| —| —| —| —
10| 54.8| 60| —| —| —| —
15| 79.8| 80| 54.8| 60| 25| 30
030K| 0| 17.2| 25| —| —| —| —
5| 29.8| 30| —| —| —| —
8| 44.3| 45| —| —| —| —
10| 54.8| 60| —| —| —| —
15| 79.8| 80| 54.8| 60| 25.0| 30
036K| 0| 25.7| 40| —| —| —| —
5| 29.8| 40| —| —| —| —
8| 44.3| 45| —| —| —| —
10| 54.8| 60| —| —| —| —
15| 79.8| 80| 54.8| 60| 25.0| 30
042K| 0| 29.3| 45| —| —| —| —
5| 31.8| 45| —| —| —| —
8| 46.3| 50| —| —| —| —
10| 56.8| 60| —| —| —| —
15| 81.8| 90| 56.8| 60| 25| 30
20| 106.8| 110| 56.8| 60| 50| 60
048K| 0| 34.2| 50| —| —| —| —
5| 34.2| 50| —| —| —| —
8| 46.3| 50| —| —| —| —
10| 56.8| 60| —| —| —| —
15| 81.8| 90| 56.8| 60| 25| 30
20| 106.8| 110| 56.8| 60| 50| 60
060K**| 0| 38.9| 60| —| —| —| —
5| 38.9| 60| —| —| —| —
8| 48.3| 60| —| —| —| —
10| 58.8| 60| —| —| —| —
15| 83.8| 90| 58.8| 60| 25| 30
20| 108.8| 110| 58.8| 60| 50| 60
*Table 13. ()P7RE / PPA3RE, Single Phase**
*MODEL ()P7RF / PPA3RF, SINGLE PHASE, 208/230V**
*MODEL ()P7RF / PPA3RF| HEATER KW| SINGLE CIRCUIT| MULTIPLE
SUPPLY CIRCUIT OPTION
****MCA| ****MOP| CIRCUIT A (COMPRESSOR, BLOWER, & FAN)|
CIRCUIT B (HEATER ONLY)
MCA| MOP| MCA| MOP
X24K| 0| 19.4| 30| –| –| –| –
5| 29.8| 30| –| –| –| –
8| 43.3| 45| –| –| –| –
10| 54.8| 60| | | |
15| 79.8| 80| 54.8| 60| 25| 30
X36K| 0| 24.4| 35| –| –| –| –
5| 29.8| 35| –| –| –| –
8| 44.3| 45| –| –| –| –
10| 54.8| 60| –| –| –| –
15| 79.8| 80| 54.8| 60| 25| 30
X48K| 0| 35.7| 50| –| –| –| –
5| 35.7| 50| –| –| –| –
8| 46.3| 50| –| –| –| –
10| 56.8| 60| –| –| –| –
15| 81.8| 90| 56.8| 60| 25| 30
20| 106.8| 110| 56.8| 60| 50| 60
X60K**| 0| 45.2| 70| –| –| –| –
5| 45.2| 70| –| –| –| –
8| 46.3| 70| –| –| –| –
10| 56.8| 70| –| –| –| –
15| 81.8| 90| 56.8| 70| 25| 30
20| 106.8| 110| 56.8| 70| 50| 60
*Table 14. ()P7RF / PPA3RF, Single Phase**
*MODEL ()P8SE / PPA3SE, SINGLE PHASE, 208/230V**
**MODEL (*)P8SE / PPA3SE| ****HEATER INSTALLED NOMINAL KW|
SINGLE CIRCUIT| MULTIPLE SUPPLY CIRCUIT OPTION
****MCA| ****MOP| CIRCUIT A (COMPRESSOR, BLOWER, & FAN)|
CIRCUIT B (HEATER ONLY)| CIRCUIT C (HEATER ONLY)
MCA| MOP| MCA| MOP| MCA| MOP
X36K| 0| 28.5| 45| –| –| –| –| –| –
5| 29.8| 45| –| –| –| –| –| –
8| 44.3| 45| 28.5| 45| 39.6| 40| –| –
10| 54.8| 60| 28.5| 45| 50| 60| –| –
15| 79.8| 80| 28.5| 45| 79.8| 80| –| –
X48K| 0| 34.1| 50| –| –| –| –| –| –
5| 34.1| 50| –| –| –| –| |
8| 46.3| 50| 34.1| 50| 39.6| 40| |
10| 56.8| 60| 34.1| 50| 50| 60| |
15| 81.8| 90| 34.1| 50| 75| 80| |
15 (3 CIR)| | | 34.1| 50| 25| 30| 50| 60
20| 106.8| 110| 56.8| 60| 50| 60| |
20 (3 CIR)| | | 34.1| 50| 50| 60| 50| 60
X60K**| 0| 43.5| 70| –| –| –| –| –| –
5| 43.5| 70| –| –| –| –| –| –
8| 46.3| 70| 43.5| 70| 39.6| 40| –| –
10| 56.8| 70| 43.5| 70| 50| 60| –| –
15| 81.8| 90| 43.5| 70| 75| 80| –| –
15 (3 CIR)| | | 43.5| 70| 25| 30| 50| 60
20| 106.8| 110| 43.5| 70| 100| 110| |
20 (3 CIR)| | | 43.5| 70| 50| 60| 50| 60
*Table 15. ()P8SE / PPA3SE, Single Phase**
*MODEL ()P8SE / PPA3SE, 3-PHASE, 208/230V & 460V**
208/230V| 460V
*MODEL ()P8SE / PPA3SE| HEATER INSTALLED NOMINAL KW| SINGLE
CIRCUIT| HEATER INSTALLED NOMINAL KW| SINGLE CIRCUIT
MCA| MOP| MCA| MOP**
X36C
| 0| 19.8| 30| 0| 10.5| 15
9| 31.8| 35| 9| 16.5| 20
15| 49.9| 50| 15| 25.9| 30
X48C
| 0| 26| 40| 0| 12.5| 15
9| 33.8| 40| 9| 18.2| 20
15| 51.9| 60| 15| 27.7| 30
X60C
| 0| 28.6| 45| 0| 14.7| 20
9| 33.8| 45| 9| 18.2| 20
15| 51.9| 60| 15| 27.7| 30
*Table 16. ()P8SE / PPA3SE, 3-Phase**
*MODEL ()Q6SE / PPH2SE, SINGLE PHASE, 208/230V**
*MODEL ()Q6SE / PPH2SE| HEATER KW| SINGLE CIRCUIT| MULTIPLE SUPPLY CIRCUIT OPTION**
MCA
| ****
MOP
| CIRCUIT A (COMPRESSOR, BLOWER & FAN)| CIRCUIT B (HEATER ONLY)|
CIRCUIT C (HEATER ONLY)
MCA| MOP| MCA| MOP| MCA| MOP
X24K| 0| 22.7| 35| –| –| –| –| –| –
5| 47.7| 50| 22.7| 35| 25| 30| –| –
8| 62.3| 70| 22.7| 35| 39.6| 40| –| –
10| 72.7| 80| 22.7| 35| 50| 60| –| –
15| 97.7| 100| 22.7| 35| 75| 80| –| –
15 (3 circuit)| 97.7| 100| 22.7| 35| 50| 60| 25.0| 30
X30K| 0| 24.4| 40| –| –| –| –| –| –
5| 49.4| 60| 24.4| 40| 25| 30| –| –
8| 64| 70| 24.4| 40| 39.6| 40| –| –
10| 74.4| 80| 24.4| 40| 50| 60| –| –
15| 99.4| 100| 24.4| 40| 74.4| 80| –| –
15 (3 circuit)| 99.4| 100| 24.4| 40| 50| 60| 25.0| 30
X36K| 0| 28.5| 45| –| –| –| –| –| –
5| 53.5| 60| 28.5| 45| 25| 30| –| –
8| 68.1| 70| 28.5| 45| 39.6| 40| –| –
10| 78.5| 80| 28.5| 45| 50| 60| –| –
15| 103.5| 110| 28.5| 45| 75| 80| –| –
15 (3 circuit)| 103.5| 110| 28.5| 45| 50| 60| 25.0| 30
X42K| 0| 32.9| 50| –| –| –| –| –| –
5| 57.9| 70| 32.9| 50| 25| 30| –| –
8| 72.5| 80| 32.9| 50| 39.6| 40| –| –
10| 82.9| 90| 32.9| 50| 50| 60| –| –
15| 107.9| 110| 32.9| 50| 75| 80| |
15 (3 circuit)| 107.9| 110| 32.9| 50| 50| 60| 25.0| 30
20| 132.9| 150| 32.9| 50| 100| 110| |
20 (3 circuit)| 132.9| 150| 32.9| 50| 50| 60| 50.0| 60
X48K| 0| 37.2| 60| –| –| –| –| –| –
5| 62.2| 80| 37.2| 60| 25.0| 30| –| –
8| 76.8| 90| 37.2| 60| 39.6| 40| –| –
10| 87.2| 100| 37.2| 60| 50.0| 60| –| –
15| 112.2| 125| 37.2| 60| 75.0| 80| –| –
15 (3 circuit)| 112.2| 125| 37.2| 60| 50.0| 60| 25.0| 30
20| 137.2| 150| 37.2| 60| 100.0| 110| –| –
20 (3 circuit)| 137.2| 150| 37.2| 60| 50.0| 60| 50.0| 60
X60K| 0| 43.5| 70| –| –| –| –| –| –
5| 68.5| 90| 43.5| 70| 25.0| 30| –| –
8| 83.1| 100| 43.5| 70| 39.6| 40| –| –
10| 93.5| 110| 43.5| 70| 50.0| 60| –| –
15| 118.5| 125| 43.5| 70| 75.0| 80| –| –
15 (3 circuit)| 118.5| 125| 43.5| 70| 50.0| 60| 25.0| 30
20| 143.5| 150| 43.5| 70| 100.0| 110| –| –
20 (3 circuit)| 143.5| 150| 43.5| 70| 50.0| 60| 50.0| 60
*Table 17. ()Q6SE / PPH2SE, Single Phase**
*MODEL ()Q6SE / PPH2SE, 3-PHASE, 208/230V & 460V**
208/230V| 460V
*MODEL ()Q6SE / PPH2SE| HEATER KW| SINGLE CIRCUIT| MULTIPLE
SUPPLY CIRCUIT OPTION| **
MODEL
| ****
HEATER KW
| SINGLE CIRCUIT
MCA| MOP| CIRCUIT A (COMPRESSOR, BLOWER & FAN)| ****
CIRCUIT B (HEATER ONLY)
| ****
MCA
| ****
MOP
MCA| MOP| MCA| MOP
X36C| 0| 19.6| 30| –| –| –| –| ****
X36D
| 0| 10.5| 15
9| 46.7| 50| –| –| –| –| 9| 24.6| 25
15| 64.7| 70| 19.6| 30| 45.2| 50| 15| 34| 35
X48C| 0| 25.6| 40| –| –| –| –| ****
X48D
| 0| 12.5| 15
9| 52.7| 60| –| –| –| –| 9| 26.6| 30
15| 70.7| 80| 25.6| 40| 45.2| 50| 15| 36.1| 40
X60C| 0| 28.2| 45| –| –| –| –| ****
X60D
| 0| 14.7| 20
9| 55.3| 60| –| –| –| –| 9| 28.8| 30
15| 73.4| 80| 28.2| 45| 45.2| 50| 15| 38.2| 40
NOTE : All circuitry has been changed due to routing the blower motor to the contactor.
*Table 18. ()Q6SE / PPH2SE, 3-Phase**
*MODEL ()Q7RE / PPH3RE, SINGLE PHASE, 208/230V**
*MODEL ()Q7RE / PPH3RE| HEATER KW| MCA| MOP| CIRCUIT A
(COMPRESSOR, BLOWER & FAN)| CIRCUIT B (HEATER ONLY)| CIRCUIT C
(HEATER ONLY)
MCA| MOP| MCA| MOP| MCA| MOP
024K| 0| 15.3| 20.0| –| –| –| –| –| –
5| 40.3| 45.0| –| –| –| –| –| –
8| 54.9| 60.0| 15.3| 20| 39.6| 40| –| –
10| 65.3| 70.0| 15.3| 20| 50| 60| –| –
030K| 0| 17.3| 25.0| –| –| –| –| –| –
5| 42.3| 45.0| –| –| –| –| –| –
8| 56.9| 60.0| 17.3| 25| 39.6| 40| –| –
10| 67.3| 70.0| 17.3| 25| 50| 60| –| –
15| 92.3| 100| 42.3| 45| 50| 60| –| –
036K| 0| 28.2| 45.0| –| –| –| –| –| –
5| 53.2| 60.0| –| –| –| –| –| –
8| 67.7| 70.0| 28.2| 45| 39.6| 40| –| –
10| 78.2| 80.0| 28.2| 45| 50| 60| –| –
15| 103.2| 110| 53.2| 60| 50| 60| –| –
042K| 0| 31.9| 50.0| –| –| –| –| –| –
5| 56.9| 70.0| –| –| –| –| –| –
8| 71.5| 80.0| 31.9| 50| 39.6| 40| –| –
10| 81.9| 90.0| 31.9| 50| 50| 60| –| –
15| 106.9| 110| 56.9| 70| 50| 60| –| –
20| 131.9| 150| –| –| –| –| –| –
20 (3 circuit)| –| –| 31.9| 50| 50| 60| 50| 60
048K**| 0| 37.3| 60.0| –| –| –| –| –| –
5| 62.3| 80.0| –| –| –| –| –| –
8| 76.9| 90.0| 37.3| 60| 39.6| 40| –| –
10| 87.3| 100.0| 37.3| 60| 50| 60| –| –
15| 112.3| 125| 62.3| 80| 50| 60| –| –
20| 137.3| 150| –| –| –| –| –| –
20 (3 circuit)| –| –| 37.3| 60| 50| 60| 50| 60
*Table 19. ()Q7RE / PPH3RE, Single Phase**
*MODEL ()Q7RF / PPH3RF, SINGLE PHASE, 208/230V**
*MODEL ()Q7RF / PPH3RF| ****HEATER KW| SINGLE CIRCUIT| MULTIPLE SUPPLY CIRCUIT OPTION**
MCA
| ****
MOP
| CIRCUIT A (COMPRESSOR, BLOWER & FAN)| CIRCUIT B (HEATER ONLY)|
CIRCUIT C (HEATER ONLY)
MCA| MOP| MCA| MOP| MCA| MOP
X24K| 0| 21.0| 30| –| –| –| –| –| –
5| 46.0| 50| –| –| –| –| –| –
8| 60.6| 70| 21.0| 30| 39.6| 40| –| –
10| 71.0| 80| 21.0| 30| 50.0| 60| –| –
15| 96.0| 100| 21.0| 30| 25.0| 30| 50.0| 60
**X36K| 0| 25.5| 40| –| –| –| –| –| –
5| 50.5| 60| –| –| –| –| –| –
8| 65.1| 70| 25.5| 40| 39.6| 40| –| –
10| 75.5| 80| 25.5| 40| 50.0| 60| –| –
15| 100.5| 110| 25.5| 40| 25.0| 30| 50.0| 60
****X48K| 0| 35.0| 50| –| –| –| –| –| –
5| 60.0| 70| 46.8| 70| 25.0| 30| –| –
8| 74.5| 80| 46.8| 70| 39.6| 40| –| –
10| 85.0| 90| 46.8| 70| 50.0| 60| –| –
15| 110.0| 110| 46.8| 70| 25.0| 30| 50.0| 60
20| 135.0| 150| 46.8| 70| 50.0| 60| 50.0| 60
X60K**| 0| 46.8| 70| –| –| –| –| –| –
5| 71.8| 90| 46.8| 70| 25.0| 30| –| –
8| 86.4| 100| 46.8| 70| 39.6| 40| –| –
10| 96.8| 110| 46.8| 70| 50.0| 60| –| –
15| 121.8| 125| 46.8| 70| 25.0| 30| 50.0| 60
20| 146.8| 150| 46.8| 70| 50.0| 60| 50.0| 60
*Table 20. ()Q7RF / PPH3RF, Single Phase**
*MODEL ()Q8SF / PPH3SF, SINGLE PHASE, 208/230V**
*MODEL ()Q8SF / PPH3SF**
| ****
HEATER (KW)
| SINGLE CIRCUIT| MULTIPLE SUPPLY CIRCUIT OPTION
MCA
| ****
MOP
| CIRCUIT A (COMPRESSOR, BLOWER & FAN)| ****
CIRCUIT B (HEATER ONLY)
| ****
CIRCUIT C (HEATER ONLY)
MCA| MOP| MCA| MOP| MCA| MOP
X24K| 0| 20.8| 30| –| –| –| –| –| –
5| 45.8| 50| 20.8| 30| 25| 30| –| –
8| 60.4| 70| 20.8| 30| 39.6| 40| –| –
10| 70.8| 80| 20.8| 30| 50| 60| –| –
15| 95.8| 100| 20.8| 30| 75| 80| –| –
15 (3 circuit)| 95.8| 100| 20.8| 30| 50| 60| 25.0| 30
X36K
| 0| 26.7| 40| –| –| –| –| –| –
5| 51.7| 60| 26.7| 40| 25| 30| –| –
8| 66.3| 70| 26.7| 40| 39.6| 40| –| –
10| 76.7| 80| 26.7| 40| 50| 60| –| –
15| 101.7| 110| 26.7| 40| 75| 80| –| –
15 (3 circuit)| 101.7| 110| 26.7| 40| 50| 60| 25.0| 30
X48K| 0| 36.8| 50| –| –| –| –| –| –
5| 61.8| 70| 36.8| 50| 25.0| 30| –| –
8| 76.4| 80| 36.8| 50| 39.6| 40| –| –
10| 86.8| 90| 36.8| 50| 50.0| 60| –| –
15| 111.8| 125| 36.8| 50| 75.0| 80| –| –
15 (3 circuit)| 111.8| 125| 36.8| 50| 50.0| 60| 25.0| 30
*Table 21. ()Q8SF / PPH3SF, Single Phase**
*Model ()P94RD, SINGLE PHASE, 208/230V**
Model Number| Heater kW| Single Circuit| Multiple Circuit
Option
Circuit A (Compressor, Blower, & Fan)| Circuit B (Heater Only)
MCA| MOP| MCA| MOP| MCA| MOP
()P94RD-018K| 0| 14.3| 20| –| –| –| –
5| 29.8| 30| –| –| –| –
8| 44.3| 45| –| –| –| –
10| 54.8| 60| –| –| –| –
15| 79.8| 80| 54.8| 60| 25| 25
()P94RD-024K| 0| 16.3| 25| –| –| –| –
5| 29.8| 30| –| –| –| –
8| 44.3| 45| –| –| –| –
10| 54.8| 60| –| –| –| –
15| 79.8| 80| 54.8| 60| 25| 25
()P94RD-030K| 0| 18.7| 25| –| –| –|
5| 29.8| 30| –| –| |
8| 44.3| 45| –| –| –| –
10| 54.8| 60| –| –| –| –
15| 79.8| 80| 54.8| 60| 25| 25
()P94RD-036K| 0| 25.5| 40| –| –| –| –
5| 29.8| 40| –| –| –| –
8| 44.3| 45| –| –| –| –
10| 54.8| 60| –| –| –| –
15| 79.8| 80| 54.8| 60| 25| 25
()P94RD-042K| 0| 30.1| 45| –| –| –| –
5| 31.8| 45| –| –| –| –
8| 46.3| 50| –| –| –| –
10| 56.8| 60| –| –| –| –
15| 81.8| 90| 56.8| 60| 25| 25
20| 106.8| 110| 56.8| 60| 50| 50
()P94RD-048K| 0| 38.2| 60| –| –| –| –
5| 38.2| 60| –| –| –| –
8| 46.3| 60| –| –| –| –
10| 56.8| 60| 38.2| 60| 50| 50
15| 81.8| 90| 56.8| 60| 25| 25
20| 106.8| 110| 56.8| 60| 50| 50
*()P94RD-060K**| 0| 41.4| 60| –| –| –| –
5| 41.4| 60| –| –| –| –
8| 48.3| 60| 41.4| 60| 39.6| 40
10| 58.8| 60| 41.4| 60| 50| 50
15| 83.8| 90| 58.8| 60| 25| 25
20| 108.8| 110| 58.8| 60| 50| 50
*Table 22. ()P94RD, Single Phase**
*Model ()Q94RD, SINGLE PHASE, 208/230V**
Model Number
| ****
Heater kW
| ****
Single Circuit
| Multiple Circuit Option
Circuit A (Compressor, Blower, & Fan)| Circuit B (Heater Only)|
Circuit C (Heater Only)
MCA| MOP| MCA| MOP| MCA| MOP| MCA| MOP
*()Q94RD-024K**
| 0| 16.2| 25| –| –| –| –| –| –
5| 41.2| 45| –| –| –| –| –| –
8| 55.7| 60| –| –| –| –| –| –
10| 66.2| 70| 16.2| 25| 50.0| 50| –| –
15| 91.2| 100| 41.2| 45| 50.0| 50| –| –
*()Q94RD-030K**
| 0| 18.7| 30| –| –| –| | –| –
5| 43.7| 50| –| –| | | –| –
8| 58.3| 60| 18.7| 30| 39.6| 40| –| –
10| 68.7| 70| 18.7| 30| 50.0| 50| –| –
15| 93.7| 100| 43.7| 50| 50.0| 50| –| –
*()Q94RD-036K**
| 0| 24.6| 40| –| –| –| –| –| –
5| 49.6| 60| –| –| –| –| –| –
8| 64.2| 70| 24.6| 40| 39.6| 40| –| –
10| 74.6| 80| 24.6| 40| 50.0| 50| –| –
15| 99.6| 100| 49.6| 60| 50.0| 50| –| –
*()Q94RD-042K**
| 0| 29.3| 45| –| –| –| –| –| –
5| 54.3| 60| –| –| –| –| –| –
8| 68.9| 70| 29.3| 45| 39.6| 40| –| –
10| 79.3| 80| 29.3| 45| 50.0| 50| –| –
15| 104.3| 110| 54.3| 60| 50.0| 50| –| –
20| 129.3| 150| 29.3| 45| 50.0| 50| 50.0| 50
*()Q94RD-048K**
| 0| 31.4| 50| –| –| –| –| –| –
5| 56.4| 70| 31.4| 50| 25.0| 25| –| –
8| 70.9| 80| 31.4| 50| 39.6| 40| –| –
10| 81.4| 90| 31.4| 50| 50.0| 50| –| –
15| 106.4| 110| 31.4| 50| 25.0| 25| 50.0| 50
20| 131.4| 150| 31.4| 50| 50.0| 50| 50.0| 50
*()Q94RD-060K**
| 0| 44.5| 70| –| –| –| –| –| –
5| 69.5| 90| 44.5| 70| 25.0| 25| –| –
8| 84.0| 100| 44.5| 70| 39.6| 40| –| –
10| 94.5| 110| 44.5| 70| 50.0| 50| –| –
15| 119.5| 125| 44.5| 70| 25.0| 25| 50.0| 50
20| 144.5| 150| 44.5| 70| 50.0| 50| 50.0| 50
*Table 23. ()Q94RD, Single Phase**
*Model ()Q104SD, SINGLE PHASE, 208/230V**
Model Number
| ****
Heater kW
| ****
Single Circuit
| Multiple Supply Circuit Option
Circuit A (Compressor, Blower & Fan)| Circuit B (Heater Only)|
Circuit C (Heater Only)
MCA| MOP| MCA| MOP| MCA| MOP| MCA| MOP
*()Q104SD- X24K**| 0| 16.2| 25| –| –| –| –| –| –
5| 41.2| 45| –| –| –| –| –| –
8| 55.7| 60| –| –| –| –| –| –
10| 66.2| 70| 16.2| 25| 50.0| 50| –| –
15| 91.2| 100| 41.2| 45| 50.0| 50| –| –
*()Q104SD- X30K**
| 0| 18.7| 30| –| –| –| | –| –
5| 43.7| 50| –| –| | | –| –
8| 58.3| 60| 18.7| 30| 39.6| 40| –| –
10| 68.7| 70| 18.7| 30| 50.0| 50| –| –
15| 93.7| 100| 43.7| 50| 50.0| 50| –| –
(*)Q104SD- X36K*| 0| 24.6| 40| –| –| –| –| –| –
5| 49.6| 60| –| –| –| –| –| –
8| 64.2| 70| 24.6| 40| 39.6| 40| –| –
10| 74.6| 80| 24.6| 40| 50.0| 50| –| –
15| 99.6| 100| 49.6| 60| 50.0| 50| –| –
)Q104SD- X42K**| 0| 29.3| 45| –| –| –| –| –| –
5| 54.3| 60| –| –| –| –| –| –
8| 68.9| 70| 29.3| 45| 39.6| 40| –| –
10| 79.3| 80| 29.3| 45| 50.0| 50| –| –
15| 104.3| 110| 54.3| 60| 50.0| 50| –| –
20| 129.3| 150| 29.3| 45| 50.0| 50| 50.0| 50
*()Q104SD- X48K**
| 0| 31.4| 50| –| –| –| –| –| –
5| 56.4| 70| 31.4| 50| 25.0| 25| –| –
8| 70.9| 80| 31.4| 50| 39.6| 40| –| –
10| 81.4| 90| 31.4| 50| 50.0| 50| –| –
15| 106.4| 110| 31.4| 50| 25.0| 25| 50.0| 50
20| 131.4| 150| 31.4| 50| 50.0| 50| 50.0| 50
*()Q104SD- X60K**| 0| 44.5| 70| –| –| –| –| –| –
5| 69.5| 90| 44.5| 70| 25.0| 25| –| –
8| 84.0| 100| 44.5| 70| 39.6| 40| –| –
10| 94.5| 110| 44.5| 70| 50.0| 50| –| –
15| 119.5| 125| 44.5| 70| 25.0| 25| 50.0| 50
20| 144.5| 150| 44.5| 70| 50.0| 50| 50.0| 50
*Table 24. ()Q104SD, Single Phase**
AIRFLOW DATA
*MODEL ()P7RE / PPA3RE, SINGLE PHASE**
MODEL NUMBER| BLOWER SETTING| EXTERNAL STATIC PRESSURE DROP –
INCHES WATER COLUMN
0.1| 0.2| 0.3| 0.4| 0.5| 0.6| 0.7| 0.8
CFM| HEAT RISE| CFM| HEAT RISE| CFM| HEAT RISE|
CFM| HEAT RISE| CFM| HEAT RISE| CFM| HEAT RISE|
CFM| HEAT RISE| CFM| HEAT RISE
018K
| Tap T1| 609| 52| 541| 58| 522| 61| 450| 70| 390| 81| 333| 95| –| –| –| –
Tap T2*| 729| 43| 690| 46| 651| 49| 599| 53| 542| 58| 475| 67| 421| 75| 357|
88
Tap T3| 859| 37| 813| 39| 768| 41| 724| 44| 673| 47| 609| 52| 555| 57| 497| 64
Tap T4| 1123| 28| 1100| 29| 1065| 30| 1023| 31| 978| 32| 929| 34| 877| 36|
820| 39
Tap T5| 1359| 23| 1320| 24| 1302| 24| 1280| 25| 1243| 25| 1205| 26| 1162| 27|
1112| 28
****024K| Tap T1| 950| 33| 823| 38| 881| 36| 832| 38| 788| 40| 722| 44|
655| 48| 593| 53
Tap T2| 1123| 28| 1100| 29| 1065| 30| 1023| 31| 978| 32| 929| 34| 877| 36|
820| 39
Tap T3| 1189| 27| 1158| 27| 1141| 28| 1084| 29| 1047| 30| 1009| 31| 959| 33|
906| 35
Tap T4| 1291| 24| 1246| 25| 1236| 26| 1195| 26| 1161| 27| 1120| 28| 1075| 29|
1031| 31
Tap T5| 1359| 23| 1320| 24| 1302| 24| 1280| 25| 1243| 25| 1205| 26| 1162| 27|
1112| 28
030K| Tap T1| 965| 33| 910| 35| 870| 36| 800| 39| 720| 44| 665| 48| 615|
51| 560| 56
Tap T2| 1100| 29| 1050| 30| 1010| 31| 955| 33| 890| 35| 830| 38| 750| 42|
700| 45
Tap T3| 1160| 27| 1120| 28| 1080| 29| 1030| 31| 980| 32| 930| 34| 880| 36|
800| 39
Tap T4| 1440| 22| 1400| 23| 1360| 23| 1320| 24| 1280| 25| 1220| 26| 1180| 27|
1120| 28
Tap T5| 1560| 20| 1530| 21| 1490| 21| 1440| 22| 1400| 23| 1360| 23| 1310| 24|
1270| 25
****036K| Tap T1| 1215| 26| 1175| 27| 1130| 28| 1075| 29| 1020| 31|
970| 33| 900| 35| 840| 38
Tap T2| 1313| 24| 1277| 25| 1236| 26| 1190| 27| 1153| 27| 1104| 29| 1051| 30|
992| 32
Tap T3| 1460| 22| 1415| 22| 1385| 23| 1335| 24| 1275| 25| 1225| 26| 1170| 27|
1120| 28
Tap T4*| 1502| 21| 1466| 22| 1437| 22| 1388| 23| 1345| 23| 1305| 24| 1251| 25|
1204| 26
Tap T5| 1565| 20| 1525| 21| 1490| 21| 1450| 22| 1410| 22| 1370| 23| 1315| 24|
1270| 25
042K
| Tap T1| 1375| 23| 1345| 23| 1310| 24| 1275| 25| 1240| 25| 1205| 26| 1160|
27| 1120| 28
Tap T2| 1470| 21| 1435| 22| 1400| 23| 1370| 23| 1335| 24| 1300| 24| 1260|
25| 1215| 26
Tap T3| 1600| 20| 1570| 20| 1535| 21| 1505| 21| 1470| 21| 1440| 22| 1400| 23|
1355| 23
Tap T4| 1715| 18| 1680| 19| 1650| 19| 1620| 20| 1585| 20| 1545| 20| 1505| 21|
1470| 21
Tap T5| 1895| 17| 1865| 17| 1830| 17| 1795| 18| 1760| 18| 1730| 18| 1695| 19|
1655| 19
048K| Tap T1| 1375| 23| 1345| 23| 1310| 24| 1275| 25| 1240| 25| 1205|
26| 1160| 27| 1120| 28
Tap T2| 1470| 21| 1435| 22| 1400| 23| 1370| 23| 1335| 24| 1300| 24| 1260|
25| 1215| 26
Tap T3| 1600| 20| 1570| 20| 1535| 21| 1505| 21| 1470| 21| 1440| 22| 1400| 23|
1355| 23
Tap T4| 1715| 18| 1680| 19| 1650| 19| 1620| 20| 1585| 20| 1545| 20| 1505| 21|
1470| 21
Tap T5| 1895| 17| 1865| 17| 1830| 17| 1795| 18| 1760| 18| 1730| 18| 1695| 19|
1655| 19
X60K
| Tap T1*| 1390| 23| 1350| 23| 1310| 24| 1270| 25| 1240| 25| 1205| 26| 1160|
27| 1120| 28
Tap T2| 1540| 21| 1510| 21| 1480| 21| 1440| 22| 1410| 22| 1380| 23| 1340| 24|
1310| 24
Tap T3| 1700| 19| 1670| 19| 1630| 19| 1600| 20| 1580| 20| 1540| 21| 1510| 21|
1480| 21
Tap T4| 1770| 18| 1740| 18| 1700| 19| 1660| 19| 1640| 19| 1600| 20| 1580| 20|
1540| 21
Tap T5| 2080| 15| 2030| 16| 2020| 16| 1970| 16| 1940| 16| 1910| 17| 1870| 17|
1840| 17
NOTES
Temperature rises shaded gray are for reference only. These conditions are not
recommended. * Denotes factory set cooling speed.
Denotes factory set electric heating speed.
*Table 25. ()P7RE / PPA3RE, Single Phase**
*MODEL ()P7RF / PPA3RF, SINGLE PHASE**
MODEL NUMBER
| ****
BLOWER SETTING
| EXTERNAL STATIC PRESSURE DROP – INCHES WATER COLUMN
0.1| 0.2| 0.3| 0.4| 0.5| 0.6| 0.7| 0.8
CFM| HEAT RISE| CFM| HEAT RISE| CFM| HEAT RISE|
CFM| HEAT RISE| CFM| HEAT RISE| CFM| HEAT RISE|
CFM| HEAT RISE| CFM| HEAT RISE
X24K| Tap T1| 467| 68| 443| 71| 417| 76| 343| 92| 272| 116| –| –| –| –|
–| –
Tap T2| 872| 36| 828| 38| 795| 40| 740| 43| 689| 46| 628| 50| 580| 54| 534|
59
Tap T3| 1115| 28| 1079| 29| 1043| 30| 1006| 31| 964| 33| 916| 34| 866| 36|
819| 39
Tap T4| 1244| 25| 1207| 26| 1173| 27| 1136| 28| 1102| 29| 1064| 30| 1011| 31|
965| 33
Tap T5| 1496| 21| 1465| 22| 1437| 22| 1407| 22| 1370| 23| 1331| 24| 1295| 24|
1257| 25
X36K| Tap T1*| 900| 35| 865| 37| 818| 39| 767| 41| 696| 45| 646| 49|
592| 53| 547| 58
Tap T2*| 1131| 28| 1096| 29| 1058| 30| 1021| 31| 968| 33| 916| 34| 858| 37|
792| 40
Tap T3| 1344| 24| 1313| 24| 1270| 25| 1231| 26| 1197| 26| 1156| 27| 1106|
29| 1046| 30
Tap T4| 1507| 21| 1475| 21| 1441| 22| 1401| 23| 1362| 23| 1326| 24| 1281| 25|
1230| 26
Tap T5| 1602| 20| 1570| 20| 1533| 21| 1501| 21| 1463| 22| 1418| 22| 1383| 23|
1336| 24
X48| Tap T1| 1062| 30| 1023| 31| 985| 32| 956| 33| 921| 34| 860| 37|
813| 39| 766| 41
Tap T2| 1079| 29| 1039| 30| 1006| 31| 969| 33| 927| 34| 870| 36| 842| 38|
777| 41
Tap T3| 1398| 23| 1356| 23| 1317| 24| 1277| 25| 1238| 26| 1200| 26| 1160| 27|
1115| 28
Tap T4| 1654| 19| 1623| 19| 1572| 20| 1542| 20| 1509| 21| 1468| 22| 1428|
22| 1394| 23
Tap T5| 1982| 16| 1955| 16| 1921| 16| 1881| 17| 1851| 17| 1812| 17| 1782| 18|
1741| 18
X60*| Tap T1| 1079| 29| 1039| 30| 1006| 31| 969| 33| 927| 34| 870| 36|
842| 38| 777| 41
Tap T2*| 1238| 26| 1216| 26| 1181| 27| 1135| 28| 1099| 29| 1057| 30| 1023| 31|
964| 33
Tap T3| 1610| 20| 1582| 20| 1551| 20| 1514| 21| 1475| 21| 1449| 22| 1412| 22|
1372| 23
Tap T4**| 1827| 17| 1794| 18| 1773| 18| 1741| 18| 1694| 19| 1657| 19| 1624|
19| 1583| 20
Tap T5| 2059| 15| 2026| 16| 1998| 16| 1960| 16| 1933| 16| 1901| 17| 1856| 17|
1827| 17
NOTES
- Temperature rises shaded gray are for reference only. These conditions are not recommended. * Denotes factory set Low COOL speed.
- Denotes factory set High COOL speed.
- Denotes factory set electric HEAT speed.
*Table 26. ()P7RF / PPA3RF, Single Phase**
MODEL P8SE / PPA3SE, SINGLE PHASE
MODEL NUMBER
| ****
BLOWER SETTING
| EXTERNAL STATIC PRESSURE DROP – INCHES WATER COLUMN
0.1| 0.2| 0.3| 0.4| 0.5| 0.6| 0.7| 0.8
CFM| HEAT RISE| CFM| HEAT RISE| CFM| HEAT RISE|
CFM| HEAT RISE| CFM| HEAT RISE| CFM| HEAT RISE|
CFM| HEAT RISE| CFM| HEAT RISE
X36| Tap T1| 1091| 29| 1031| 31| 995| 32| 929| 34| 871| 36| 774| 41|
704| 45| 629| 50
Tap T2| 1296| 24| 1244| 25| 1169| 27| 1153| 27| 1089| 29| 1030| 31| 961| 33|
863| 37
Tap T3*| 1525| 21| 1499| 21| 1448| 22| 1391| 23| 1338| 24| 1264| 25| 1221| 26|
1159| 27
Tap T4| 1641| 19| 1590| 20| 1543| 20| 1489| 21| 1444| 22| 1386| 23| 1345| 23|
1285| 25
Tap T5| 1791| 18| 1740| 18| 1659| 19| 1610| 20| 1555| 20| 1521| 21| 1467| 22|
1414| 22
X48| Tap T1*| 1264| 25| 1183| 27| 1126| 28| 1051| 30| 954| 33| 848| 37|
774| 41| 716| 44
Tap T2| 1462| 22| 1397| 23| 1322| 24| 1240| 25| 1181| 27| 1133| 28| 1006| 31|
888| 36
Tap T3| 1776| 18| 1717| 18| 1654| 19| 1573| 20| 1533| 21| 1484| 21| 1422| 22|
1369| 23
Tap T4| 2127| 15| 2037| 16| 2008| 16| 1957| 16| 1865| 17| 1801| 18| 1743| 18|
1690| 19
Tap T5| 2419| 13| 2355| 13| 2311| 14| 2267| 14| 2194| 14| 2150| 15| 2085| 15|
2027| 16
X60| Tap T1| 1209| 26| 1145| 28| 1106| 29| 1020| 31| 928| 34| 843| 37|
776| 41| 709| 45
Tap T2| 1629| 19| 1550| 20| 1479| 21| 1435| 22| 1369| 23| 1300| 24| 1244| 25|
1139| 28
Tap T3*| 1847| 17| 1800| 18| 1718| 18| 1668| 19| 1611| 20| 1556| 20| 1497| 21|
1449| 22
Tap T4| 2128| 15| 2059| 15| 1992| 16| 1961| 16| 1887| 17| 1828| 17| 1779| 18|
1718| 18
Tap T5| 2500| 13| 2444| 13| 2417| 13| 2345| 13| 2285| 14| 2228| 14| 2172| 15|
2109| 15
NOTES
Denotes factory set cooling speed.
Denotes factory set electric heating speed.Calculations made based on 10kW/H,
Airflow performance with Dry Coil.
*Table 27. ()P8SE / PPA3SE, Single Phase**
MODEL P8SE / PPA3SE, 3-PHASE
MODEL NUMBER
| ****
BLOWER SETTING
| EXTERNAL STATIC PRESSURE DROP – INCHES WATER COLUMN
0.1| 0.2| 0.3| 0.4| 0.5| 0.6| 0.7| 0.8
CFM| TEMP RISE| CFM| TEMP RISE| CFM| TEMP RISE|
CFM| TEMP RISE| CFM| TEMP RISE| CFM| TEMP RISE|
CFM| TEMP RISE| CFM| TEMP RISE
**X36D| Tap 1| 1124| 25| 1040| 27| 981| 29| 908| 31| 824| 35| 750|
38| 687| 41| 623| 46
Tap 2*| 1320| 22| 1266| 22| 1210| 23| 1159| 25| 1100| 26| 1029| 28| 945| 30|
884| 32
Tap 3| 1542| 18| 1479| 19| 1443| 20| 1386| 21| 1329| 21| 1283| 22| 1234| 23|
1182| 24
Tap 4| 1642| 17| 1594| 18| 1533| 19| 1492| 19| 1441| 20| 1396| 20| 1340| 21|
1300| 22
Tap 5| 1750| 16| 1694| 17| 1642| 17| 1600| 18| 1560| 18| 1510| 19| 1467| 19|
1421| 20
X48D
| Tap 1*| 1279| 22| 1214| 23| 1134| 25| 1078| 26| 1034| 27| 944| 30| 855|
33| 800| 36
Tap 2| 1510| 19| 1452| 20| 1399| 20| 1338| 21| 1294| 22| 1236| 23| 1174| 24|
1059| 27
Tap 3| 1760| 16| 1711| 17| 1641| 17| 1597| 18| 1545| 18| 1488| 19| 1435| 20|
1386| 21
Tap 4| 1949| 15| 1912| 15| 1858| 15| 1789| 16| 1748| 16| 1701| 17| 1646| 17|
1603| 18
Tap 5| 2242| 13| 2153| 13| 2110| 13| 2063| 14| 2016| 14| 1965| 14| 1922| 15|
1870| 15
X60D| Tap 1*| 1228| 23| 1150| 25| 1074| 26| 1014| 28| 956| 30| 867| 33|
769| 37| 705| 40
Tap 2| 1670| 17| 1617| 18| 1551| 18| 1497| 19| 1458| 20| 1417| 20| 1342| 21|
1303| 22
Tap 3| 1926| 15| 1891| 15| 1850| 15| 1783| 16| 1741| 16| 1680| 17| 1634| 17|
1579| 18
Tap 4| 2087| 14| 2029| 14| 1981| 14| 1939| 15| 1885| 15| 1834| 16| 1780| 16|
1721| 17
Tap 5| 2278| 12| 2233| 13| 2193| 13| 2141| 13| 2098| 14| 2046| 14| 2001| 14|
1943| 15
X36C
| Tap 1*| 1126| 25| 1065| 27| 1024| 28| 940| 30| 853| 33| 768| 37| 702| 41|
637| 45
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
Tap 2| 1315| 22| 1268| 22| 1206| 24| 1144| 25| 1076| 26| 987| 29| 907| 31|
839| 34
Tap 3| 1492| 19| 1438| 20| 1386| 21| 1337| 21| 1287| 22| 1230| 23| 1171| 24|
1062| 27
Tap 4| 1587| 18| 1534| 19| 1494| 19| 1439| 20| 1388| 20| 1338| 21| 1280| 22|
1216| 23
Tap 5| 1684| 17| 1638| 17| 1591| 18| 1541| 18| 1492| 19| 1444| 20| 1390| 20|
1336| 21
X48C
| Tap 1*| 1238| 23| 1170| 24| 1108| 26| 1051| 27| 986| 29| 890| 32| 817| 35|
755| 38
Tap 2| 1403| 20| 1351| 21| 1301| 22| 1232| 23| 1175| 24| 1125| 25| 997| 29|
955| 30
Tap 3| 1772| 16| 1727| 16| 1670| 17| 1621| 18| 1568| 18| 1509| 19| 1463| 19|
1399| 20
Tap 4| 1968| 14| 1926| 15| 1873| 15| 1823| 16| 1774| 16| 1717| 17| 1665| 17|
1619| 18
Tap 5| 2242| 13| 2183| 13| 243| 117| 2098| 14| 2044| 14| 1995| 14| 1953| 15|
1907| 15
X60C| Tap 1*| 1161| 24| 1116| 25| 1084| 26| 1031| 28| 954| 30| 895| 32|
834| 34| 779| 37
Tap 2| 1553| 18| 1521| 19| 1474| 19| 1437| 20| 1379| 21| 1335| 21| 1276| 22|
1183| 24
Tap 3| 1862| 15| 1818| 16| 1766| 16| 1731| 16| 1678| 17| 1635| 17| 1599| 18|
1539| 18
Tap 4| 2009| 14| 1973| 14| 1923| 15| 1887| 15| 1838| 15| 1796| 16| 1752| 16|
1703| 17
Tap 5| 2288| 12| 2246| 13| 2210| 13| 2170| 13| 2132| 13| 2094| 14| 2050| 14|
2014| 14
NOTES
- Airflow performance is with a dry coil.
- Denotes factory set cooling speed.
- Denotes factory set electric heating speed. Calculations made based on 9kW/H.
*Table 28. ()P8SE / PPA3SE, 3-Phase**
*MODEL ()Q6SE SINGLE PHASE**
UNIT MODEL| BLOWER SETTING| EXTERNAL STATIC PRESSURE DROP –
INCHES WATER COLUMN
0.1| 0.2| 0.3| 0.4| 0.5| 0.6| 0.7| 0.8
CFM| TEMP RISE| CFM| TEMP RISE| CFM| TEMP RISE|
CFM| TEMP RISE| CFM| TEMP RISE| CFM| TEMP RISE|
CFM| TEMP RISE| CFM| TEMP RISE
X24| Tap T1| 823| 38| 784| 40| 712| 44| 646| 49| 580| 54| 510| 62| 436|
72| –| –
Tap T2| 969| 33| 924| 34| 866| 36| 800| 39| 717| 44| 652| 48| 591| 53| 522| 61
Tap T3*| 1068| 30| 1010| 31| 947| 33| 906| 35| 814| 39| 743| 43| 674| 47| 617|
51
Tap T4| 1188| 27| 1142| 28| 1068| 30| 1022| 31| 954| 33| 861| 37| 803| 39|
763| 41
Tap T5| 1330| 24| 1274| 25| 1221| 26| 1164| 27| 1105| 29| 1044| 30| 957| 33|
881| 36
X30| Tap T1| 890| 35| 832| 38| 766| 41| 687| 46| 624| 51| 576| 55| 502|
63| 419| 75
Tap T2| 969| 33| 924| 34| 866| 36| 800| 39| 717| 44| 652| 48| 591| 53| 522|
61
Tap T3| 1188| 27| 1142| 28| 1068| 30| 1022| 31| 954| 33| 861| 37| 803| 39|
763| 41
Tap T4| 1382| 23| 1334| 24| 1273| 25| 1220| 26| 1164| 27| 1097| 29| 1020| 31|
947| 33
Tap T5| 1640| 19| 1604| 20| 1547| 20| 1490| 21| 1437| 22| 1381| 23| 1324| 24|
1249| 25
X36| Tap T1| 1137| 28| 1075| 29| 1012| 31| 950| 33| 863| 37| 770| 41|
694| 46| 619| 51
Tap T2| 1242| 25| 1187| 27| 1128| 28| 1057| 30| 993| 32| 921| 34| 827| 38|
754| 42
Tap T3| 1418| 22| 1370| 23| 1308| 24| 1251| 25| 1204| 26| 1123| 28| 1064| 30|
974| 32
Tap T4| 1567| 20| 1515| 21| 1459| 22| 1397| 23| 1338| 24| 1272| 25| 1184| 27|
1107| 29
Tap T5| 1700| 19| 1658| 19| 1596| 20| 1534| 21| 1481| 21| 1421| 22| 1358| 23|
1279| 25
X42| Tap T1| 1257| 25| 1199| 26| 1133| 28| 1070| 30| 982| 32| 906| 35|
830| 38| 761| 42
Tap T2| 1374| 23| 1332| 24| 1270| 25| 1220| 26| 1153| 27| 1077| 29| 972| 33|
901| 35
Tap T3*| 1574| 20| 1520| 21| 1470| 21| 1418| 22| 1356| 23| 1295| 24| 1214| 26|
1095| 29
Tap T4| 1733| 18| 1678| 19| 1637| 19| 1575| 20| 1528| 21| 1467| 22| 1408| 22|
1334| 24
Tap T5| 1848| 17| 1795| 18| 1741| 18| 1708| 18| 1641| 19| 1593| 20| 1541| 21|
1477| 21
X48| Tap T1| 952| 33| 901| 35| 864| 37| 728| 43| 672| 47| 583| 54| 508|
62| –| –
Tap T2*| 1646| 19| 1593| 20| 1520| 21| 1476| 21| 1417| 22| 1349| 23| 1265|
25| 1198| 26
Tap T3| 1764| 18| 1705| 19| 1626| 19| 1570| 20| 1525| 21| 1451| 22| 1403| 23|
1304| 24
Tap T4| 1962| 16| 1916| 16| 1838| 17| 1787| 18| 1720| 18| 1670| 19| 1595| 20|
1537| 21
Tap T5| 2391| 13| 2334| 14| 2301| 14| 2242| 14| 2180| 14| 2132| 15| 2074| 15|
2017| 16
X60| Tap T1| 1088| 29| 1032| 31| 958| 33| 878| 36| 789| 40| 715| 44|
641| 49| 570| 55
Tap T2*| 1764| 18| 1705| 19| 1626| 19| 1570| 20| 1525| 21| 1451| 22| 1403|
23| 1304| 24
Tap T3| 1962| 16| 1916| 16| 1838| 17| 1787| 18| 1720| 18| 1670| 19| 1595| 20|
1537| 21
Tap T4| 2106| 15| 2059| 15| 2000| 16| 1944| 16| 1878| 17| 1828| 17| 1751| 18|
1689| 19
Tap T5| 2391| 13| 2334| 14| 2301| 14| 2242| 14| 2180| 14| 2132| 15| 2074| 15|
2017| 16
NOTES
Denotes factory set cooling speed.
Denotes factory set electric heating speed.
Heat Rise calculated based on 10kW of electric heat.
*Table 29. ()Q6SE Single Phase**
*MODEL ()Q7RE / PPH3RE, SINGLE PHASE**
MODEL NUMBER| BLOWER SETTING| HEAT RISE DATA (BASED ON NOMINAL
10KW ELECTRIC HEAT KIT)
EXTERNAL STATIC PRESSURE DROP – INCHES WATER COLUMN
0.1| 0.2| 0.3| 0.4| 0.5| 0.6| 0.7| 0.8
CFM| HEAT RISE| CFM| HEAT RISE| CFM| HEAT RISE|
CFM| HEAT RISE| CFM| HEAT RISE| CFM| HEAT RISE|
CFM| HEAT RISE| CFM| HEAT RISE
**024K| Tap T1*| 930| 34| 875| 36| 818| 39| 761| 42| 704| 45| 645| 49|
585| 54| 525| 60
Tap T2| 1158| 27| 1119| 28| 1076| 29| 1028| 31| 977| 32| 921| 34| 861| 37|
796| 40
Tap T3| 1308| 24| 1271| 25| 1230| 26| 1185| 27| 1136| 28| 1084| 29| 1027|
31| 967| 33
Tap T4| 1440| 22| 1406| 22| 1368| 23| 1326| 24| 1281| 25| 1232| 26| 1179| 27|
1122| 28
Tap T5| 1622| 19| 1587| 20| 1550| 20| 1510| 21| 1467| 22| 1422| 22| 1373| 23|
1323| 24
030K*| Tap T1| 930| 34| 875| 36| 818| 39| 761| 42| 704| 45| 645| 49| 585|
54| 525| 60
Tap T2| 1158| 27| 1119| 28| 1076| 29| 1028| 31| 977| 32| 921| 34| 861| 37|
796| 40
Tap T3| 1308| 24| 1271| 25| 1230| 26| 1185| 27| 1136| 28| 1084| 29| 1027|
31| 967| 33
Tap T4| 1440| 22| 1406| 22| 1368| 23| 1326| 24| 1281| 25| 1232| 26| 1179| 27|
1122| 28
Tap T5| 1622| 19| 1587| 20| 1550| 20| 1510| 21| 1467| 22| 1422| 22| 1373| 23|
1323| 24
036K| Tap T1| 1158| 27| 1119| 28| 1076| 29| 1028| 31| 977| 32| 921| 34|
861| 37| 796| 40
Tap T2| 1308| 24| 1271| 25| 1230| 26| 1185| 27| 1136| 28| 1084| 29| 1027| 31|
967| 33
Tap T3| 1266| 25| 1332| 24| 1291| 24| 1245| 25| 1192| 27| 1132| 28| 1067| 30|
995| 32
Tap T4| 1518| 21| 1481| 21| 1442| 22| 1400| 23| 1355| 23| 1307| 24| 1256|
25| 1202| 26
Tap T5| 1686| 19| 1644| 19| 1601| 20| 1556| 20| 1509| 21| 1460| 22| 1410| 22|
1358| 23
042K| Tap T1| 1339| 24| 1297| 24| 1254| 25| 1210| 26| 1166| 27| 1121|
28| 1075| 29| 1029| 31
Tap T2| 1459| 22| 1422| 22| 1383| 23| 1342| 24| 1300| 24| 1256| 25| 1211|
26| 1164| 27
Tap T3| 1569| 20| 1530| 21| 1491| 21| 1451| 22| 1410| 22| 1368| 23| 1625| 19|
1282| 25
Tap T4| 1709| 18| 1674| 19| 1638| 19| 1601| 20| 1562| 20| 1521| 21| 1479| 21|
1436| 22
Tap T5| 1820| 17| 1785| 18| 1748| 18| 1710| 18| 1671| 19| 1630| 19| 1589| 20|
1545| 20
048K| Tap T1*| 1418| 22| 1385| 23| 1351| 23| 1316| 24| 1279| 25| 1242|
25| 1203| 26| 1163| 27
Tap T2| 1530| 21| 1500| 21| 1467| 22| 1433| 22| 1396| 23| 1358| 23| 1318| 24|
1275| 25
Tap T3| 1679| 19| 1645| 19| 1611| 20| 1576| 20| 1541| 21| 1505| 21| 1469| 22|
1432| 22
Tap T4| 1787| 18| 1757| 18| 1726| 18| 1693| 19| 1658| 19| 1621| 19| 1582| 20|
1542| 20
Tap T5| 2006| 16| 1973| 16| 1939| 16| 1905| 17| 1870| 17| 1834| 17| 1798| 18|
1761| 18
060K| Tap T1*| 1214| 26| 1142| 28| 1067| 30| 997| 32| 905| 35| 794| 40|
700| 45| 742| 43
Tap T2| 1713| 18| 1625| 19| 1547| 20| 1451| 22| 1360| 23| 1261| 25| 1165| 27|
1028| 31
Tap T3| 2153| 15| 2063| 15| 1983| 16| 1884| 17| 1799| 18| 1700| 19| 1604| 20|
1482| 21
Tap T4| 2359| 13| 2250| 14| 2159| 15| 2053| 15| 1935| 16| 1839| 17| 1710| 18|
1576| 20
Tap T5| 2457| 13| 2355| 13| 2265| 14| 2166| 15| 2068| 15| 1956| 16| 1837| 17|
1726| 18
*Table 30. ()Q7RE / PPH3RE, Single Phase**
*MODEL ()Q7RF / PPH3RF, SINGLE PHASE**
MODEL NUMBER| ****
BLOWER SETTING
| EXTERNAL STATIC PRESSURE DROP – INCHES WATER COLUMN
0.1| 0.2| 0.3| 0.4| 0.5| 0.6| 0.7| 0.8
CFM| HEAT RISE| CFM| HEAT RISE| CFM| HEAT RISE|
CFM| HEAT RISE| CFM| HEAT RISE| CFM| HEAT RISE|
CFM| HEAT RISE| CFM| HEAT RISE
X24K| Tap T1| 686| 46| 651| 49| 621| 51| 589| 54| 530| 60| 477| –| 431|
–| 382| –
Tap T2| 926| 34| 884| 36| 861| 37| 827| 38| 785| 40| 734| 43| 676| 47| 622|
51
Tap T3| 1184| 27| 1161| 27| 1134| 28| 1109| 28| 1075| 29| 1041| 30| 1002|
32| 962| 33
Tap T4| 1383| 23| 1360| 23| 1330| 24| 1303| 24| 1277| 25| 1246| 25| 1215| 26|
1137| 28
Tap T5| 1537| 21| 1510| 21| 1487| 21| 1459| 22| 1437| 22| 1412| 22| 1382| 23|
1350| 23
X36K| Tap T1*| 1004| 31| 972| 33| 938| 34| 897| 35| 845| 37| 779| 41|
739| 43| 668| 47
Tap T2*| 1167| 27| 1132| 28| 1100| 29| 1061| 30| 1020| 31| 979| 32| 921| 34|
851| 37
Tap T3| 1355| 23| 1320| 24| 1282| 25| 1247| 25| 1209| 26| 1168| 27| 1121|
28| 1066| 30
Tap T4| 1510| 21| 1477| 21| 1441| 22| 1403| 23| 1366| 23| 1330| 24| 1288| 25|
1243| 25
Tap T5| 1648| 19| 1614| 20| 1578| 20| 1544| 20| 1512| 21| 1473| 21| 1434| 22|
1393| 23
X48| Tap T1| 1108| 29| 1063| 30| 1031| 31| 987| 32| 939| 34| 894| 35|
850| 37| 808| 39
Tap T2| 1108| 29| 1063| 30| 1031| 31| 987| 32| 939| 34| 894| 35| 850| 37|
808| 39
Tap T3| 1666| 19| 1629| 19| 1587| 20| 1572| 20| 1542| 20| 1507| 21| 1477|
21| 1431| 22
Tap T4| 1884| 17| 1824| 17| 1795| 18| 1762| 18| 1730| 18| 1707| 19| 1671| 19|
1634| 19
Tap T5| 1979| 16| 1948| 16| 1925| 16| 1892| 17| 1861| 17| 1834| 17| 1804| 18|
1766| 18
X60*| Tap T1| 923| 34| 875| 36| 799| 40| 735| 43| 677| 47| 623| 51|
579| 55| 543| 58
Tap T2*| 1335| 24| 1295| 24| 1259| 25| 1214| 26| 1183| 27| 1144| 28| 1117| 28|
1063| 30
Tap T3| 1754| 18| 1721| 18| 1684| 19| 1660| 19| 1634| 19| 1597| 20| 1568| 20|
1541| 21
Tap T4**| 2045| 15| 2022| 16| 1983| 16| 1950| 16| 1921| 16| 1894| 17| 1869|
17| 1826| 17
Tap T5| 2253| 14| 2218| 14| 2187| 14| 2153| 15| 2117| 15| 2091| 15| 2057| 15|
2021| 16
NOTES
- Temperature rises shaded gray are for reference only. These conditions are not recommended. * Denotes factory set Low COOL speed.
Denotes factory set High COOL speed.
Denotes factory set electric HEAT speed.
*Table 31. ()Q7RF / PPH3RF, Single Phase**
*MODEL ()Q8SF / PPH3SF, SINGLE PHASE**
MODEL NUMBER| SWITCH SETTINGS
0 = OFF, 1 = ON
| COOLING OR HEATING AIRFLOW (CFM)
0.1| 0.2| 0.3| 0.4| 0.5| 0.6| 0.7| 0.8
1/5| 2/6| 3/7| 4/8| CFM| TEMP RISE|
CFM| TEMP RISE| CFM| TEMP RISE| CFM| TEMP
RISE| CFM| TEMP RISE| CFM| TEMP RISE|
CFM| TEMP RISE| CFM| TEMP RISE
X24K| 0| 0| 0| 0| 840| 38| 745| 42| 655| 48| 590| 54| 520| 61| 430| 73|
345| 92| 320| 99
1| 0| 0| 0| 920| 34| 850| 37| 780| 41| 695| 45| 615| 51| 540| 59| 465| 68|
420| 75
0| 1| 0| 0| 1025| 31| 960| 33| 890| 35| 800| 39| 710| 44| 645| 49| 575| 55| 535| 59
1| 1| 0| 0| 1110| 28| 1050| 30| 990| 32| 900| 35| 805| 39| 745| 42| 685| 46|
610| 52
0| 0| 1| 0| 1165| 27| 1120| 28| 1070| 30| 975| 32| 875| 36| 815| 39| 750| 42|
715| 44
1| 0| 1| 0| 1235| 26| 1190| 27| 1140| 28| 1070| 30| 995| 32| 905| 35| 820| 39|
800| 39
0| 1| 1| 0| 1335| 24| 1285| 25| 1235| 26| 1170| 27| 1110| 28| 1010| 31| 910|
35| 850| 37
1| 1| 1| 0| 1400| 23| 1355| 23| 1310| 24| 1250| 25| 1185| 27| 1090| 29| 990|
32| 925| 34
0| 0| 0| 1| 1455| 22| 1410| 22| 1360| 23| 1295| 24| 1235| 26| 1140| 28| 1045|
30| 985| 32
1| 0| 0| 1| 1515| 21| 1465| 22| 1420| 22| 1355| 23| 1290| 24| 1215| 26| 1145|
28| 1055| 30
0| 1| 0| 1| 1590| 20| 1540| 21| 1490| 21| 1440| 22| 1390| 23| 1325| 24| 1260|
25| 1160| 27
1| 1| 0| 1| 1640| 19| 1593| 20| 1545| 20| 1500| 21| 1450| 22| 1385| 23| 1320|
24| 1220| 26
0| 0| 1| 1| 1690| 19| 1645| 19| 1600| 20| 1550| 20| 1500| 21| 1440| 22| 1375|
23| 1280| 25
1| 0| 1| 1| 1740| 18| 1695| 19| 1645| 19| 1600| 20| 1555| 20| 1495| 21| 1435|
22| 1360| 23
0| 1| 1| 1| 1805| 18| 1760| 18| 1710| 18| 1665| 19| 1615| 20| 1555| 20| 1500|
21| 1440| 22
1| 1| 1| 1| 1850| 17| 1800| 18| 1755| 18| 1705| 19| 1660| 19| 1610| 20| 1555|
20| 1495| 21
X36K| 0| 0| 0| 0| 700| 45| 625| 51| 545| 58| 475| 67| 400| 79| 370| 85|
343| 92| –| –
1| 0| 0| 0| 824| 38| 760| 42| 695| 45| 620| 51| 550| 57| 500| 63| 450| 70|
395| 80
0| 1| 0| 0| 1005| 31| 935| 34| 860| 37| 790| 40| 720| 44| 660| 48| 605| 52|
510| 62
1| 1| 0| 0| 1130| 28| 1055| 30| 975| 32| 905| 35| 835| 38| 775| 41| 710| 44|
605| 52
0| 0| 1| 0| 1285| 25| 1230| 26| 1175| 27| 1090| 29| 1000| 32| 955| 33| 910|
35| 755| 42
1| 0| 1| 0| 1420| 22| 1400| 23| 1375| 23| 1335| 24| 1295| 24| 1270| 25| 1250| 25| 900| 35
0| 1| 1| 0| 1540| 21| 1480| 21| 1420| 22| 1370| 23| 1320| 24| 1250| 25| 1180|
27| 1025| 31
1| 1| 1| 0| 1635| 19| 1585| 20| 1530| 21| 1470| 21| 1410| 22| 1350| 23| 1290|
24| 1130| 28
0| 0| 0| 1| 1750| 18| 1695| 19| 1640| 19| 1580| 20| 1520| 21| 1460| 22| 1405|
22| 1270| 25
1| 0| 0| 1| 1855| 17| 1805| 18| 1755| 18| 1700| 19| 1645| 19| 1595| 20| 1540|
21| 1400| 23
0| 1| 0| 1| 1955| 16| 1910| 17| 1860| 17| 1800| 18| 1745| 18| 1695| 19| 1640|
19| 1515| 21
1| 1| 0| 1| 2020| 16| 1973| 16| 1925| 16| 1870| 17| 1815| 17| 1770| 18| 1720|
18| 1615| 20
0| 0| 1| 1| 2100| 15| 2055| 15| 2010| 16| 1960| 16| 1905| 17| 1860| 17| 1810|
17| 1705| 19
1| 0| 1| 1| 2175| 15| 2125| 15| 2075| 15| 2025| 16| 1975| 16| 1920| 16| 1865|
17| 1760| 18
0| 1| 1| 1| 2270| 14| 2205| 14| 2140| 15| 2085| 15| 2030| 16| 1985| 16| 1945|
16| 1835| 17
1| 1| 1| 1| 2320| 14| 2265| 14| 2210| 14| 2160| 15| 2110| 15| 2060| 15| 2015|
16| 1915| 16
X48K| 0| 0| 0| 0| 900| 35| 775| 41| 645| 49| 520| 61| 400| 79| –| –| –|
–| –| –
1| 0| 0| 0| 1010| 31| 895| 35| 785| 40| 670| 47| 555| 57| –| –| –| –| –| –
0| 1| 0| 0| 1135| 28| 1055| 30| 975| 32| 860| 37| 745| 42| 675| 47| 605| 52|
515| 61
1| 1| 0| 0| 1280| 25| 1184| 27| 1090| 29| 1000| 32| 910| 35| 830| 38| 750| 42|
610| 52
*0| 0| 1| 0| 1395| 23| 1325| 24| 1250| 25| 1160| 27| 1065| 30| 1000| 32| 935|
34| 780| 41
1| 0| 1| 0| 1525| 21| 1445| 22| 1365| 23| 1290| 24| 1215| 26| 1130| 28| 1045|
30| 915| 35
0| 1| 1| 0| 1630| 19| 1555| 20| 1480| 21| 1420| 22| 1360| 23| 1290| 24| 1215|
26| 1085| 29
1| 1| 1| 0| 1725| 18| 1665| 19| 1605| 20| 1535| 21| 1470| 21| 1400| 23| 1330| 24| 1180| 27
0| 0| 0| 1| 1825| 17| 1765| 18| 1710| 18| 1650| 19| 1595| 20| 1535| 21| 1470|
21| 1345| 23
1| 0| 0| 1| 1880| 17| 1830| 17| 1780| 18| 1725| 18| 1670| 19| 1615| 20| 1555|
20| 1440| 22
0| 1| 0| 1| 1975| 16| 1920| 16| 1865| 17| 1820| 17| 1770| 18| 1725| 18| 1680|
19| 1560| 20
1| 1| 0| 1| 2065| 15| 2005| 16| 1940| 16| 1895| 17| 1845| 17| 1790| 18| 1740|
18| 1635| 19
0| 0| 1| 1| 2120| 15| 2070| 15| 2025| 16| 1970| 16| 1915| 16| 1875| 17| 1830|
17| 1730| 18
1| 0| 1| 1| 2210| 14| 2155| 15| 2095| 15| 2040| 15| 1985| 16| 1945| 16| 1905|
17| 1805| 18
0| 1| 1| 1| 2230| 14| 2190| 14| 2150| 15| 2100| 15| 2045| 15| 2000| 16| 1950|
16| 1860| 17
1| 1| 1| 1| 2355| 13| 2290| 14| 2220| 14| 2185| 14| 2145| 15| 2100| 15| 2050|
15| 1955| 16
NOTES
Compressor high and low heating and cooling airflows are the Same. Compressor
low heating and cooling airflows are approximate 70% of high values. * Denotes
factory set cooling speed.
Denotes factory set electric heating speed.
Emergency heat has only high speed settings.
Heat rise calculated based on 10kW of electric heat.
*Table 32. ()Q8SF / PPH3SF, Single Phase**
*Model ()Q94RD, SINGLE PHASE, 208/230V Airflow Data**
MODEL NUMBER
| ****
BLOWER SETTING
| EXTERNAL STATIC PRESSURE DROP – INCHES OF WATER COLUMN
0.1| 0.2| 0.3| 0.4| 0.5| 0.6| 0.7| 0.8
CFM| Rise| CFM| Rise| CFM| Rise| CFM|
Rise| CFM| Rise| CFM| Rise| CFM| Rise|
CFM| Rise
(*)Q94RD- 024K| Tap T1| 1009| 31| 951| 33| 910| 35| 856| 37| 797|
40| 725| 44| 660| 48| 605| 52
Tap T2**| 1146| 28| 1102| 29| 1049| 30| 1004| 31| 955| 33| 898| 35| 829|
38| 761| 42
Tap T3*| 1,198| 26| 1,154| 27| 1,107| 29| 1,059| 30| 1,010| 31| 959| 33|
895| 35| 827| 38
Tap T4| 1,290| 24| 1,242| 25| 1,197| 26| 1,150| 27| 1,102| 29| 1,049|
30| 1,003| 31| 939| 34
Tap T5| 1,425| 22| 1,383| 23| 1,334| 24| 1,287| 25| 1,246| 25| 1,194|
26| 1,149| 27| 1,092| 29
*)Q94RD- 030K| Tap T1| 1009| 31| 951| 33| 910| 35| 856| 37| 797|
40| 725| 44| 660| 48| 605| 52
Tap T2**| 1,146| 28| 1,102| 29| 1,049| 30| 1,004| 31| 955| 33| 898| 35|
829| 38| 761| 42
Tap T3| 1,290| 24| 1,242| 25| 1,197| 26| 1,150| 27| 1,102| 29| 1,049|
30| 1,003| 31| 939| 34
Tap T4*| 1,397| 23| 1,353| 23| 1,306| 24| 1,262| 25| 1,213| 26| 1,168|
27| 1,120| 28| 1,060| 30
Tap T5| 1,546| 20| 1,505| 21| 1,467| 22| 1,417| 22| 1,366| 23| 1,320|
24| 1,272| 25| 1,223| 26
**(*)Q94RD- 036K| Tap T1| 1146| 28| 1107| 29| 1056| 30| 1004| 31|
960| 33| 910| 35| 842| 38| 782| 40
Tap T2**| 1269| 25| 1,232| 26| 1197| 26| 1146| 28| 1098| 29| 1056| 30|
993| 32| 932| 34
Tap T3| 1400| 23| 1,363| 23| 1316| 24| 1276| 25| 1229| 26| 1,191| 27|
1,142| 28| 1087| 29
Tap T4*| 1485| 21| 1,445| 22| 1404| 23| 1366| 23| 1325| 24| 1,282| 25|
1,236| 26| 1,184| 27
Tap T5| 1612| 20| 1,571| 20| 1530| 21| 1492| 21| 1453| 22| 1,409| 22|
1,364| 23| 1,322| 24
*()Q94RD- 042K| Tap T1| 1,512| 21| 1,459| 22| 1,443| 22| 1,400| 23|
1,367| 23| 1,335| 24| 1,298| 24| 1,271| 25
Tap T2**| 1,627| 19| 1,596| 20| 1,558| 20| 1,534| 21| 1,503| 21| 1,467|
22| 1,433| 22| 1,400| 23
Tap T3| 1,734| 18| 1,700| 19| 1,670| 19| 1,642| 19| 1,606| 20| 1,575|
20| 1,543| 20| 1,509| 21
Tap T4| 1,840| 17| 1,813| 17| 1,780| 18| 1,750| 18| 1,716| 18| 1,685|
19| 1,650| 19| 1,613| 20
Tap T5| 1,942| 16| 1,920| 16| 1,884| 17| 1,853| 17| 1,821| 17| 1,787|
18| 1,752| 18| 1,713| 18
()Q94RD- 048K| Tap T1| 1,474| 21| 1,417| 22| 1,379| 23| 1,344| 24|
1,304| 24| 1,266| 25| 1,230| 26| 1,184| 27
Tap T2**| 1,590| 20| 1,559| 20| 1,519| 21| 1,467| 22| 1,439| 22| 1,396|
23| 1,360| 23| 1,320| 24
Tap T3| 1,749| 18| 1,711| 18| 1,665| 19| 1,633| 19| 1,589| 20| 1,551|
20| 1,514| 21| 1,476| 21
Tap T4| 1,913| 17| 1,873| 17| 1,835| 17| 1,802| 18| 1,760| 18| 1,718|
18| 1,688| 19| 1,643| 19
Tap T5| 2,097| 15| 2,052| 15| 2,016| 16| 1,980| 16| 1,939| 16| 1,894|
17| 1,856| 17| 1,814| 17
()Q94RD- 060K| Tap T1| 1,455| 22| 1,412| 22| 1,362| 23| 1,323| 24|
1,277| 25| 1,238| 26| 1,188| 27| 1,160| 27
Tap T2**| 1,668| 19| 1,627| 19| 1,599| 20| 1,558| 20| 1,521| 21| 1,478|
21| 1,444| 22| 1,405| 22
Tap T3| 1,854| 17| 1,809| 17| 1,783| 18| 1,745| 18| 1,707| 19| 1,667|
19| 1,629| 19| 1,593| 20
**Tap T4*| 2,008| 16| 1,976| 16| 1,939| 16| 1,904| 17| 1,875| 17| 1,833|
17| 1,801| 18| 1,760| 18
Tap T5**| 2,174| 15| 2,133| 15| 2,101| 15| 2,066| 15| 2,038| 16| 2,002|
16| 1,969| 16| 1,932| 16
- Denotes factory set cooling speed.
- Denotes factory set electric heating speed.
- Heat rise calculated based on 10kW of electric heat using formula (kW x 3413) / 1.08 / CFM
- Temperature rises in tables are approximate. Actual temperature rises may vary.
- Shaded areas are not approved for proper electric heat operation above 40º F rise. (For reference only)
- Deduct approximately 3% from airflow shown for 208V applications.
*Table 33. ()Q94RD, Single Phase**
*Model ()Q104SD, SINGLE PHASE, 208/230V Airflow Data**
MODEL NUM- BER| ****
BLOWER SETTING
| EXTERNAL STATIC PRESSURE DROP – INCHES OF WATER COLUMN
0.1| 0.2| 0.3| 0.4| 0.5| 0.6| 0.7| 0.8
CFM| Rise| CFM| Rise| CFM| Rise| CFM|
Rise| CFM| Rise| CFM| Rise| CFM| Rise|
CFM| Rise
(*)Q104SD- X24K| Tap T1| 825| 38.4| 785| 40.3| 710| 44.4| 645|
48.9| 580| 54.5| 510| 62.0| 435| 72.5| –| –
Tap T2| 970| 32.6| 925| 34.2| 865| 36.5| 800| 39.5| 715| 44.1| 650|
48.5| 590| 53.5| 520| 60.5
Tap T3 **| 1070| 29.6| 1010| 31.3| 9456| 33.4| 905| 34.9| 815| 38.8|
745| 42.5| 675| 46.9| 615| 51.2
Tap T4 *| 1190| 26.6| 1140| 27.7| 1070| 29.6| 1020| 30.9| 955| 33.1|
860| 36.7| 805| 39.3| 765| 41.4
Tap T5| 1330| 23.8| 1275| 24.8| 1220| 25.9| 1165| 27.1| 1105| 28.6|
1045| 30.3| 955| 33.0| 880| 35.9
(*)Q104SD- X30K| Tap T1| 890| 35.5| 830| 38.0| 765| 41.3| 685|
46.0| 625| 50.6| 575| 54.9| 500| 62.9| 420| 75.4
Tap T2| 970| 32.6| 925| 34.2| 865| 36.5| 800| 39.5| 715| 44.1| 650|
48.5| 590| 53.5| 520| 60.5
Tap T3 **| 1190| 26.6| 1140| 27.7| 1070| 29.6| 1020| 30.9| 955| 33.1|
860| 36.7| 805| 39.3| 765| 41.4
Tap T4 *| 1380| 22.9| 1335| 23.7| 1275| 24.8| 1220| 25.9| 1165| 27.1|
1095| 28.8| 1020| 31.0| 945| 33.4
Tap T5| 1640| 19.3| 1605| 19.7| 1545| 20.4| 1490| 21.2| 1435| 22.0|
1380| 22.9| 1325| 23.9| 1250| 25.3
*)Q104SD- X36K| Tap T1| 1135| 27.8| 1075| 29.4| 1010| 31.2| 950|
33.3| 865| 36.6| 770| 41.0| 695| 45.5| 620| 51.0
Tap T2 **| 1240| 25.4| 1185| 26.6| 1130| 28.0| 1055| 29.9| 995| 31.8|
920| 34.3| 825| 38.2| 755| 41.9
Tap T3| 1420| 22.3| 1370| 23.1| 1310| 24.2| 1250| 25.3| 1205| 26.2|
1125| 28.1| 1065| 29.7| 975| 32.4
Tap T4 *| 1630| 19.4| 1590| 19.9| 1530| 20.7| 1465| 21.6| 1410| 22.4|
1345| 23.5| 1270| 24.9| 1195| 26.4
Tap T5| 1700| 18.6| 1660| 19.1| 1595| 19.8| 1535| 20.6| 1480| 21.3|
1420| 22.2| 1360| 23.3| 1280| 24.7
(*)Q104SD- X42K| Tap T1 **| 1260| 25.1| 1200| 26.4| 1135| 27.9|
1070| 29.5| 980| 32.2| 905| 34.9| 830| 38.1| 760| 41.5
Tap T2| 1375| 23.0| 1330| 23.7| 1270| 24.9| 1220| 25.9| 1155| 27.4|
1075| 29.3| 970| 32.5| 900| 35.1
Tap T3| 1575| 20.1| 1520| 20.8| 1470| 21.5| 1420| 22.3| 1355| 23.3|
1295| 24.4| 1215| 26.0| 1095| 28.9
Tap T4 *| 1655| 19.1| 1600| 19.8| 1555| 20.3| 1500| 21.1| 1445| 21.9|
1380| 22.9| 1315| 24.0| 1215| 26.0
Tap T5| 1850| 17.1| 1795| 17.6| 1740| 18.2| 1710| 18.5| 1640| 19.3|
1595| 19.8| 1540| 20.5| 1475| 21.4
(*)Q104SD- X48K| Tap T1| 950| 33.2| 900| 35.1| 865| 36.6| 730|
43.4| 670| 47.0| 585| 54.2| 510| 62.2| –| –
Tap T2 **| 1645| 19.2| 1595| 19.8| 1520| 20.8| 1475| 21.4| 1415| 22.3|
1350| 23.4| 1265| 25.0| 1200| 26.4
Tap T3| 1765| 17.9| 1705| 18.5| 1625| 19.4| 1570| 20.1| 1525| 20.7|
1450| 21.8| 1405| 22.5| 1305| 24.2
Tap T4 *| 1995| 15.8| 1945| 16.2| 1875| 16.8| 1790| 17.6| 1725| 18.3|
1660| 19.0| 1610| 19.6| 1550| 20.4
Tap T5| 2390| 13.2| 2335| 13.5| 2300| 13.7| 2240| 14.1| 2180| 14.5|
2130| 14.8| 2075| 15.2| 2015| 15.7
(*)Q104SD- X60K| Tap T1| 1090| 29.0| 1030| 30.6| 960| 33.0| 880|
36.0| 790| 40.0| 715| 44.2| 640| 49.3| 570| 55.4
Tap T2 **| 1765| 17.9| 1705| 18.5| 1625| 19.4| 1570| 20.1| 1525| 20.7|
1450| 21.8| 1405| 22.5| 1305| 24.2
Tap T3| 2000| 15.8| 1945| 16.2| 1890| 16.7| 1835| 17.2| 1785| 17.7|
1735| 18.2| 1690| 18.7| 1635| 19.3
Tap T4 *| 2235| 14.1| 2180| 14.5| 2125| 14.9| 2075| 15.2| 2035| 15.5|
1985| 15.9| 1940| 16.3| 1895| 16.7
Tap T5| 2390| 13.2| 2335| 13.5| 2300| 13.7| 2240| 14.1| 2180| 14.5|
2130| 14.8| 2075| 15.2| 2015| 15.7
- Denotes factory set cooling speed.
- Denotes factory set electric heating speed.
- Heat rise calculated based on 10kW of electric heat using formula (kW x 3413) / 1.08 / CFM
- Temperature rises in tables are approximate. Actual temperature rises may vary.
- Shaded areas are not approved for proper electric heat operation above 40F rise. (For reference only)
- Deduct approximately 3% from airflow shown for 208V applications.
*Table 34. ()Q104SD, Single Phase**
NOTES
- Circuit breakers are not wired to heater kit by the factory, see Installation Instructions for wiring procedure.
- If any of the original wire supplied with this unit must be replaced, it must be replaced with wiring material of the same gauge size and temperature rating. The installation of this heater kit may require a change in the blower speed tap connection. See Installation Instructions for details.
- Use copper conductors with a minimum temperature rating of 60 C for supply connections.
LEGEND: FIELD WIRING
- LOW VOLTAGE
- HIGH VOLTAGE
Figure 8. Single Phase, 15 KW, 2 Circuit, HP
INSTALLER : PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WITH THE HOMEOWNER
Specifications & illustrations subject to change without notice or incurring obligations (09/22). O’Fallon, MO, © Nortek Global HVAC LLC 2022. All Rights Reserved.
10459790
(Replaces 10439260)
Read User Manual Online (PDF format)