BlauHoff BLH-5KW Battery LFP Battery User Manual
- June 4, 2024
- BlauHoff
Table of Contents
BLH-5KW/BLH-10KW/BLH-15KW/BLH-20KW/BLH-25KW/BLH-30KW
User Manual
BLH-5KW Battery LFP Battery
Dear customer,
This is your BlauHoff BLH-5KW Battery LFP battery for the home energy storage
system. We provide safe, well-designed, and high-performance standard LFP
battery packs for you. The battery pack is compact, easy to install, free of
maintenance, and used as the building block of energy storage systems by
assembling in parallel. It is widely applied in home applications, small
commercial and industrial energy storage systems as well as Telecom stations.
This manual contains all the information necessary to install, use and
maintain the LFP battery. We kindly ask you to read this manual carefully
before using the product.
This manual is meant for the installer and the user of the LFP battery. Only
trained and qualified staff may install and perform maintenance on the LFP
battery.
The boundaries of its use, as described in this manual should be kept in mind.
The LFP battery may not be used in medical or in aviation-related
applications. The LFP battery may not be used for any purposes other than
described in this manual. Using the LFP battery for any other purpose will be
considered improper use and will void the warranty of the product. BlauHoff
cannot be held responsible for any damage caused by improper, incorrect, or
unwise use of the product. Read and understand this manual completely
before using the product. During the use of the product, user safety should
always be ensured, so installers, users, service personnel, and third parties
can safely use the LFP battery.
This is the original manual, keep it in a safe location! Please consult
info@blauhoff.com for the latest version of all
manuals.
Before Using
Read and understand the following instructions:
Warning
- This equipment may only be installed, operated, and maintained by trained and qualified staff.
- The local safety regulations and relevant operating procedures must be observed during the installation, operation, and maintenance of the equipment, otherwise, the equipment may be damaged. The safety precautions mentioned in the manual are only intended to supplement local safety regulations.
Caution
- Do not dispose of batteries in a fire. The batteries may explode.
- Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.
- A battery can present a risk of electric shock and burns by high short-circuit current.
- Failed batteries can reach temperatures that exceed the burn thresholds for touchable surfaces. The following precautions should be observed when working on batteries: a) disconnect the charging source before connecting or disconnecting battery terminals;b) do not wear any metal objects including watches and rings;c) do not lay tools or metal parts on top of batteries; and in addition, when the battery maintenance cannot be performed by an ordinary person, the following appliesd) use tools with insulated handles;e) wear rubber gloves and boots;
If determine it the battery is other intentionally or in between by grounded contact with any part of a grounded battery can result in electric shock and burns by high short-circuit current. the risk of such hazards can be reduced if the ground is removed during installation and maintenance by a skilled person.
- before moving or reconnecting the running system. the power must be off and the system should be shut down, otherwise, there will be a risk of electric shock.
- Do not expose the Li-ion battery to the heat of the fire in case of fire, place using a dry powder fire extinguisher.
- Do not dismantle any part of the system without contacting bytes or bytes authorized technical engineer. system failure caused by such will not be covered by the warranty.
Danger
- Keep the Li-ion battery away from water, dust, and contamination, otherwise, it may cause an explosion or other dangers and may even lead to personal injury.
- Do not short-circuit the Li-ion battery.
- Observe the plus (+) and minus (-) marks on the Li-ion battery and equipment and ensure correct use. Do not reverse-connect the Li-ion battery.
- Do not dismantle, crush, puncture, open, or shred the Li-ion battery.
- Before moving or reconnecting the running system, the power must be off and the system should be shut down, otherwise, there will be risk of electric shock.
- Do not expose the Li-ion battery to heat or fire. In case of fire, please use the dry powder fire extinguisher.
- Do not dismantle any part of the system without contacting PYTES or PYTES authorized technical engineers. System failure caused by such will not be covered by the warranty.
Specifications
Table 1-1 Battery Pack Specifications
Battery Model | BLH-5KW |
---|---|
Chemistry | LFP |
Nominal Voltage | 51.2V |
Voltage Range | 47.5V-57.6V |
Nominal Capacity | 100Ah |
Nominal Energy | 5.12kWh |
Unit Dimension | L440mm W620mm H117mm(2.6U) |
Unit Weight | 51kg |
Standard Charge/Discharge Current | 50A |
Maximum Charge/Discharge Current | 50A |
Peak Current | 102A@15s |
Round-Trip Efficiency | ≥95% |
Communication Protocol | RS232, RS485, CAN |
Cycle Life | ≥6000cycles@0.5C/0.5C, 25℃ |
Calendar Life | ≥10 years |
Operating Temperature | Charge: 0℃~ 45℃, Discharge: -10℃~50℃ |
Certificates | UL1973, IEC62619 / UN38.3 |
Storage Temperature | Within 1month: -20~55°C 1-3months: -20~35°C |
3-12months: 20~25°C
1.1 Product standard configuration
Items | Quantity | Specifications | Pictures |
---|---|---|---|
BLH-5KW | **** 1pcs | 51.2V/100Ah LFP pack; including BMS, three |
interfaces (CAN/RS-485/RS232), 2 Link ports, LED power indicator and insulated coating metal case.| ****
Power Cable| **** 1set| Connect battery to battery; 0.2m; Positive and negative|
Communicate Cable| **** 1pcs| Connect battery to battery; 0.2m; CAN or RS485 communicate|
Earthing cable| 1pcs| 1m|
1.2 BMS function
Protection and Alarm | Management and Monitor |
---|---|
Charge/Discharge End | Cell Balance |
Charge over Voltage | Intelligent Charge Model |
Charge/Discharge Over Current | Charge/Discharge current Limit |
High/Low Temperature | Capacity Retention Calculate |
Short Circuit | Administrator Monitor |
Power Cable Reverse | Operation Recordes |
Interface and protection functions
2.1 Battery front panel schenatic
2.2 Components
No. | Name | Label | Functions description |
---|---|---|---|
1 | Ground | **** | Grounding |
2 | **** Power button | **** POWER | Power button. When |
switched to “ON”, the system can be activated by the “SW” key or external
power supply; when switched to “OFF”, the system is off.
**3| ** Soft start switch| **** SW| Press and hold this
button for 1 second while the switch key is “ON” to enter Start or Sleep mode
**4| ** DIP switch| ADD| Select the match manufacturer, see
the match list(appendix A)
**5| ** Running lights| RUN| Green lights. The lights flash
when Standby. The lights are constantly on when charging.
| | | The lights flash when discharging.
---|---|---|---
Alarm indicator| ALM| Red light. The lights flash when Alarm. The
lights are constantly on when protected.
Capacity indicator| CHARGE| A total of 6 green lights showing
battery capacity, each representing 16.7% of SOC.
**6| External CAN communication port| ** CAN| Communication
with external devices
**7| External RS-485 communication port| ** RS485|
Communication with external devices
**8| ** Cascade terminal| **** Link Port| Used
for master-slave cascade communication. Connected with a standard direct-
connected network cable, the master is connected to PORT1, and the slave is
connected to PORT0.
**9| Input and output interface (negative)| “-“| ** Negative input
and output interface
**10**| Input and output interface (positive)| “+“| Positive input and
output interface
Waging: 6.7,8,9.10 is DVC-A circuit, they shall not be connected to DVC-B/C circuit when installed, or hazard shock will occur.
Operating Environment
- Battery operating environment requirements:
- Operating Temperature: -10 ℃~55℃
- Relative Humidity: 20%-80%, no condensation
- Altitude: <4000m
- Site environment requirements: Keep away from heat source, avoid direct sunlight, no corrosive gas, no explosive gas, no insulating gas, no insulating conductive dust.
- Installed in cabinet which shall not be opened without a tool or
- install in a restricted access area.
Packaging, transportation, storage requirements
4.1 Transportation
Always check all applicable local, national, and international regulations
before transporting an LFP battery.
During the transportation, protected the battery from severe vibration, shock,
or squeezing during transportation, as well as prevents sun and rain.
During the loading and unloading process, the battery should be handled
lightly and protected against falling, rolling, and heavy pressure.
4.2 Storage
Follow the storage instructions in this manual to optimize the lifespan of the
LFP battery during storage. If these instructions are not followed and the LFP
battery has no charge remaining when it is checked, consider it to be damaged.
Do not attempt to recharge or use it. Replace it with a new LFP battery.
See previous storage temperature conditions. The self-discharge of the LFP
battery is 1-2% per month. Keep the battery SOC to 40%-60% during storage.
Disconnect the LFP battery from all loads and, if present, the charging
device. Store the battery in a cool and dry place without direct sunshine.
Keep the battery away from corrosive substances, inflammable and explosive
material as well as hazardous gases. For long-term storage (> 6 months),
charge the LFP battery to more than 80% of its rated capacity before storage.
The battery needs to be recharged every 6 months to more than 80% of the rated
capacity.
Installation and configuration
5.1 Installation preparation
5.1.1 Safety Requirements
Only those who have been trained in the power system and have a good knowledge
of the power system are allowed to install the device. Always observe local
safety regulations and the safety requirements listed below during the
installation process.
Before installing or removing the device, make sure that the power system is
not powered and that the battery device is turned off. Distribution cabling
should be reasonable and with protective measures to avoid being touched
during operation.
5.1.2 Checking the operating environment
The operating environment should meet the requirements described in Chapter 3,
“Operating Environment”. Otherwise, it needs to be adjusted and re-examined.
5.1.3 Tools
The tools that may be used are shown in Table 5-1.
Table 5-1 Tools
Tools
Screwdriver (Slotted, Phillips)| Multimeter
Wrench| clip-on ammeter
Diagonal pliers| Insulating tape
Thermometer| Pliers
Anti-static wrist ring| Clip Pliers
---|---
Tapes| Strippers
5.1.4 Technical preparation
Electrical interface settings:
If the battery is connected to the user device directly, please check:
- Whether the DC charging interface of the energy storage inverter meets the charging voltage and current requirements in Table 1-1 Battery Pack Specifications.
- Whether the power of the electrical equipment matches the parameters listed in “Table 1-1 Battery Pack Specifications”;
Security check:
Fire-fighting equipment such as portable dry powder fire extinguishers should be available near the equipment. Do not place dangerous materials such as flammable or explosive ones near the battery.
5.2 Unpacking
- When the battery arrives at the installation site, it must be loaded and unloaded properly and prevented from direct sunshine and rain. Before installation, check if there is any component missing according to the packing list attached in the packing box and check whether the box appearance is intact;
- Carefully handling during the unpacking. Protect the insulated coating on the case surface;
- Check the LFP battery for damage after unpacking. If there is any damage, contact BlauHoff or your reseller.
5.3 The preparatory work
- Make sure the POWER buttons of all batteries are OFF.
- Ensure the charging voltage of power supply equipment is DC57.5±0.1V;
- All power supply should be off.
5.4 Installation
5.4.1 Install the battery
The BLH-5KW can be installed either vertically or horizontally. In this
chapter, it’s mainly instructions for horizontal installation such as
installation in a 19-inch cabinet. Vertical installation is similar. All
equipment must be placed steadily during installation.
5.4.2 Connect Ground cable
Unscrew the screw at the grounding hole on the front panel of the battery,
wrap the ground cable around the screw, and tighten it with a screwdriver.
Connect the other end of the ground cable to a reliable ground point.
External Bi-polar over current protection devices and Bi-polar external
isolator shall be equipped
The minimum diameter must be >10awg
Note: The grounding resistance should be less than 0.1Ω.
5.4.3 Connecting the power cable
Before connecting the power cable, connect and disconnect the cable to
identify the positive and negative terminal, then make a mark respectively.
After the cable is connected, measure whether there is a short-circut or
reverse connection.
Select the correct line based on your load by referencing to the table below
AWG | Area | Standard Current | Max. current |
---|---|---|---|
(kcmil) | (mm²) | ( A ) | ( A ) |
5 | 33.1 | 16.8 | 66.2 |
6 | 26.3 | 13.3 | 52.5 |
7 | 20.8 | 10.5 | 41.6 |
8 | 16.5 | 8.37 | 33 |
9 | 13.1 | 6.63 | 26.2 |
10 | 10.4 | 5.26 | 20.8 |
- Single battery:
- Connect the positive and negative poles of the battery to the positive and negative terminal of the DC port of the energy storage inverter (or the junction box) with a red and black cable respectively.
- Multiple batteries (Max number 8):
The connection between batteries, as well as between the battery and ESS inverter are in parallel. First, connect the two positive terminals of adjacent batteries with the red cable; and the two negative terminals of adjacent batteries with the black cable; then connect the positive and negative terminal of the battery with the positive terminal of the DC port of the energy storage inverter (or the junction box) with a red and black cable respectively;
The capacity can be increased by connecting the batteries in parallel, but due to the limitations of BMS and power cable we supply, only two batteries can be connected in parallel and a bus bar should be used for connecting them together.
Warning : Batteries connected in series are forbidden, high voltage would lead to hazard shock.
2. Power cable connection instructions of Multi-Rack:
Collect the positive and negative power cables respectively by the bus bar or
junction box, then connect two racks in parallel. The length, thickness,
material, and resistance of the cables connected in parallel must be the same.
Note: When the cable is inserted into the positive and negative terminals
of the battery and “Click”, the cable is firmly connected. Before pulling out
the cable, press the small button next to the terminal. When multiple
batteries are connected in parallel, in order to reduce the influence of the
circular current, the overall positive and negative output cables can be
connected from different batteries.
Figure 5-1 Schematic diagram of battery connection
Note: The battery must be placed in a locked cabinet or room, a 5cm
cooling gap is reserved when installing the battery, and each layer of the
battery cabinet should have a load capacity of more than 100kg.
5.4.4 Connecting communication cables
Single battery: Choose port to be inserted according to the communication
protocol (RS485/CAN/RS232) between the battery and ESS inverter, then insert
the communication cables to the port;
Multiple batteries: The host and the slave communicate in cascade mode: one is
the host and the rest are the slaves. Please refer to the following picture
for the cascade connection. User need to inset communication cables to
relevant link ports between batteries and be aware that:
- The host Link Port 0 must be kept free;
- The end slave Link Port 1 must be kept free;
Note: The system may not be able to communicate if not follow the instruction.
Table 5-3 LED indications
Battery status| Protection / Alarm / Normal| RUN| ALM| Capacity LED|
Descriptions
---|---|---|---|---|---
| | | | | | |
Shut down| | OFF| OFF| OFF| OFF| OFF| OFF| OFF| OFF| All off
Power-on| Normal| ON| ON| ON| ON| ON| ON| ON| ON| All light on one second at
same time.
Standby| Normal| Flash 1| OFF| OFF| OFF| OFF| OFF| OFF| OFF| Indication
standby
Alarm| OFF| Flash 3| OFF| OFF| OFF| OFF| OFF| OFF| Battery low voltage
Charging| Normal| Light| OFF| Base on capacity|
Alarm| Light| Flash 3
Protection| OFF| Light| OFF| OFF| OFF| OFF| OFF| OFF| Stop charging, protect
start
Discharge| Normal| Flash 3| Flash 3| Base on capacity|
Alarm| Flash 3| Flash 3|
Protection| OFF| Light| OFF| OFF| OFF| OFF| OFF| OFF| Stop discharge, protect
start
Note: The flashing instructions, flash 1-0.25s light/3.75s off; flash
2-0.5s light/0.5s off; flash 3-0.5s light/1.5s off.
—End of installation-
Communication
There are RS-232C, RS485, and CAN communication ports on the battery. The
battery status can be obtained and the battery internal parameters can be
modified via a host computer.
CAN
CAN communication Terminal (RJ45 port) follow CAN protocol, to output
batteries information.
RS485
RS485 Communication Terminal:(RJ45 port) follow RS485 protocol, to output
batteries information.
RS232
RS232 Communication Terminal:(RJ45 port) follow RS232 protocol, to upgrade the
software and communicate with your PC.
Link Port 0,1
Link Port0,1 Communication Terminal:(RJ45 port) follow CAN/RS485 protocol, to
communicate between multiple parallel batteries.
6.1 RS232 port
Default baud rate of RS-232C ports: 115200bps.
Table 6-1 RS232 Connector Pin Assignments
Pin number | RS-232C port |
---|---|
1 | GND |
2 | TXD |
3 | RXD |
4 | GND |
6.2 RS485 port and CAN port.
Default baud rate of RS-485 port: 9600bps
Default baud rate of CAN port: 500K
Table 6-2 RS485 and CAN Connector Pin Assignments
Pin number | Serial | CAN |
---|---|---|
1 | RS485B | — |
2 | RS485A | GND |
3 | GND | — |
4 | — | CANH |
5 | — | CANL |
6 | GND | — |
7 | RS485A | — |
8 | RS485B | — |
Troubleshooting
Please refer to the troubleshooting methods mentioned below. Please read the
“Table 5 -3 LED indication” of this manual before troubleshooting to prevent
false operations. For example, it doesn’t indicate the battery is faulty if
the ALM alarm red light on the front panel is blinking or constantly on. When
there is an “alarm” indication, it usually works well and needs no
troubleshooting. When there is “protection” indication, the battery will work
normally automatically after “protection” status is released.
Warning: Do not repair the battery if no authorization from BlauHoff!
7.1 Unable to start
Problem | Troubleshooting Steps | Solution |
---|
Press the POWER button to the “ON” state and press the SW button for 1 second,
but the LED indicator doesn’t
respond or all the LEDs are off after 1S.| 1. Confirm that the POWER button
remains in the “ON”
state;
2. Charge the battery correctly and observe if the battery can
be charged properly.| 1. If the battery enters charging mode, the
battery can return to normal after charging.
2. If not, please contact the local reseller or BlauHoff.
7.2 Unable to charge
Problem | Troubleshooting Steps | Solution |
---|---|---|
The battery cannot be charged properly when the battery is not fully charged. |
1. Confirm that the battery is turned on;
2. Check the power cord. Confirm that the power cables are correctly
connected and the charging circuit is correct;
3. Check the battery indicator LED to see if the battery is under the
“Protection” state. If so, unplug the battery power cord, find the cause of
the protection, and fix the problem, then restart the battery;
4. Check if the charging voltage meets the battery charging requirements. If
not, adjust the power supply voltage to the
proper range.| If the battery still does not charge properly
after following the above steps, please
contact the local reseller or BlauHoff.
7.3 Unable to discharge
Problem | Troubleshooting Steps | Solution |
---|---|---|
The battery cannot be discharged a propertly. | 1. Confirm that the battery is |
turned on;
2. Check the power cables to ensure that they are properly connected.
3. Unplug the battery power cable and measure the battery power output
voltage. If the battery voltage is too low, charge it immediately.
4. Check the battery indicator LED to see if the battery is in “Protection”
state. If so, unplug the battery power cables, find the cause of the
protection, and fix the problem, then restart the battery;| If the battery
still does not discharge properly after
following the above steps, please contact the local
reseller or BlauHoff.
7.4 ALM indicator is always on
When the ALM indicator is constantly red and the other indicators are off, the battery is in the “Protection” state. When the condition-triggered protection is released, the battery will automatically return to normal operation. There are a few issues requiring immediate measures.
Problem | Troubleshooting Steps | Solution |
---|---|---|
The ALM indicator is constantly red and all other indicators are off. | 1. |
Check the power cables to ensure that they are properly connected.
2. Check whether the charging voltage,
charging/discharging current, battery/cell voltage, and temperature meet the
relevant protection conditions, and release the “protection” state to ensure
that the voltage, current, and temperature are within the normal working
range.| If the battery protection state cannot be released,
or the ALM indicator is constantly on when
the battery is properly charged after it is restarted, please contact your
local reseller or BlauHoff.
7.5 Battery designation
EXAMPLE 1 –ICP200/1 50/150/[7S]E/0+50/75 would designate a battery composed of
7S connected prismatic Li-ion secondary cells, with a cobalt-based positive
electrode. Its cell maximum thickness is between 199 mm and 200mm, its cell
maximum width is between 149 mm and 150 mm, and its cell overall height is
between 149 mm and 150 mm. It is designed for a low discharge rate over a long
period. Its low-temperature grade is 0°C. Its high-temperature grade is +50
°C. Its capacity after 500 cycles to rated capacity is between 75 % and 79 %.
EXAMPLE 2 —NR54/222[4P3S]H/-20+50/80 would designate a battery composed of 4P-
3S connected cylindrical Li-ion secondary cells, with a nickel-based positive
electrode. Its cell maximum diameter is between 53mm and 54 mm, and its cell
overall height is between 221 mm and 222 mm. It is designed for a high
discharge rate. Its low-temperature grade is -20 °C. Its high-temperature
grade is +50 C. Its capacity after 500 cycles to rated capacity is between 80
% and 84%.
Warranty Card
Battery model| Inverter bronemods4|
Battery quantity| inverter quantity|
Battery using lime I| Inverter using time|
PV ways power i| on-grid/off-grid|
Problem description (including fauk tine, weather. condition. inverter error
code, etc.)
Photos of battery wiring
Photos of Inverter wiring and panels
The right of interpretation belongs to BlauHoff.
V 2.0
May 27, 2022