window aster **WSK 320 Fire Pressure with Acoustic Signal Instruction Manual
**
Technical data / Dan
Min cable dimension: 0.5mm 2
Max cable dimension: 1.0mm Max permissible cable length when using 4x2x0.8: up
to 200m
IP rating: IP 40 Teknik data
Connection
1-3 Input: 24-30V, max 20mA
4-5: GND 0V
6-8 output: max 30V, max 50mA
9: NC
Mounting
WSK 320 is to be mounted inside on a wall through the holes in the back plate. Please follow national guidelines regarding distance between the WSK and floor level.
Connection table between WSK 220 and WSK 320
LED & Ikon der LEDs
OK and green LED When the green LED to the left of the OK icon is constantly on, everything is OK
and yellow LED
If the yellow LED to the left of the exclamation mark icon is on, there is a
system error. Refer to the smoke
panel manual for error descriptions
Red LED
If the red LED above the trigger button is on, the system has been tripped.
Green and yellow LED
If the green LED is constantly on, the yellow LED flash alternately, and the break glass unit is alarming, it is a maintenance indication. Refer to the smoke panel manual for maintenance indication
Signal / Acoustic signal
Constant acoustic signa: fault or alarm Repeated acoustic signal: service
timer, see the instruction manual for the smoke panel