BERNER SLC07 Air Curtain Instruction Manual
- June 15, 2024
- BERNER
Table of Contents
SANITATION CERTIFIED Low Profile 7
AIR CURTAIN SERIES SLC07
COMMERCIAL Low Profile 8
AIR CURTAIN SERIES CLC08
SLC07 Air Curtain
Installation & Maintenance Instructions
WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK OR INJURY TO PERSONS,
OBSERVE THE FOLLOWING:
A. Read all instructions before installing or using this air curtain.
B. Use this unit only in the manner intended by the manufacturer and described
in this manual. Any other use not recommended by the manufacturer may cause
fire, electric shock, or injury to persons. If you have any questions, contact
the manufacturer.
C. Before servicing or cleaning unit, switch power off at service panel and
lock the service disconnecting means to prevent power from being switched on
accidentally. When the service disconnecting means cannot be locked, securely
fasten a prominent warning device, such as a tag, to the service panel.
D. Installation work and electrical wiring must be done by qualified person(s)
in accordance with all applicable national and local codes having
jurisdiction, including fire-rated construction. See page 3, ELECTRICAL
CONNECTIONS (NEC Code ANSI/NFPA No. 70).
E. When cutting or drilling into wall or ceiling, do not damage electrical
wiring and other hidden utilities.
F. To reduce the risk of fire, do not store or use gasoline or other flammable
vapors and liquids in the vicinity of the air curtain.
G. This air curtain is hot when in use. To avoid burns, do not let bare skin
touch hot surfaces. Keep combustible materials, such as furniture, pillows,
bedding, papers, clothes, etc. and curtains at least 1 inch from the top,
back, front, sides and at least 6 feet from the discharge of the air curtain.
H. Extreme caution is necessary when any air curtain is used by or near
children or invalids, and whenever the heater is left operating unattended.
I. Do not operate any air curtain after it malfunctions. Disconnect power at
the service panel and have the air curtain inspected by a reputable
electrician before reusing.
J. To disconnect the air curtain, turn controls to “off”, and turn off power
to the air curtain circuit at main disconnect panel.
K. Do not insert or allow foreign objects to enter any ventilation or
discharge opening as this may cause an electric shock or fire, or damage the
air curtain.
L. To prevent a possible fire, do not block the air intake or discharge of the
air curtain in any manner.
M. The air curtain has hot and arcing or sparking parts inside. Do not use it
in areas where gasoline, paint, or flammable vapors or liquids are used or
stored.
N. This heater may include an audible or visual alarm to warn that parts of
the heater are getting excessively hot. If the alarm sounds (or illuminates),
immediately turn the heater off and inspect for any objects on or adjacent to
the heater that may have blocked the airflow or otherwise caused high
temperatures to have occurred.
DO NOT OPERATE THE HEATER WITH THE ALARM SOUNDING (OR ILLUMINATING).
I. UNCRATING THE AIR CURTAIN UNIT Carefully examine the carton(s) for damage
before opening. If the carton is damaged, immediately notify the shipping
company. If the unit(s) were shipped on wooden skids, remove protective wood
and banding straps securing the carton(s) to the skid. Open the carton(s) and
remove all protective packaging. Remove the plastic cover housing by lifting
vertically. Remove and discard four (4) nuts and washers holding the
motor/blower section to the bottom of the carton. Remove motor/blower section
from the carton.
CAUTION: ONLY LIFT THE UNIT BY GRASPING INLET RINGS ON THE BLOWER HOUSING
WITHOUT TOUCHING BLOWER WHEELS. Immediately verify that the electrical rating
nameplate located on the cover matches electrical power supply available.
Retain the shipping carton(s) until the unit(s) are installed and properly
operating.
ACCESSORIES: If the unit(s) were ordered with optional electrical
accessories (door switch, control panel, etc.), the accessories may be found
in the carton containing the unit or in a separate carton(s) accompanying the
unit(s). Check all of the cartons/skids for accessories before discarding.
II. MOUNTING INSTRUCTIONS (General)
The Certified Low Profile 7/Commercial Low Profile 8 air curtain is designed
to be an effective barrier against cold drafts in the winter and hot air in
the summer, flying insects and airborne contaminants. To achieve optimum
protection, the unit should be mounted on the inside of the building, flush to
the wall and as close to the top of the door opening as possible. To ensure
peak performance, keep air stream free of obstructions. The air curtain will
not perform properly if negative air pressure exists in the building. Under
these conditions, a means for make-up air to the building must be provided so
that the air pressure on both sides of the opening is in balance.
MODEL | Net Weight (Ibs) |
---|---|
SLCO7 Ambient | CLCO8 Ambient |
CLC08-1030 | —- |
SLC07-1036, CLC08-1036 | 35 |
SLC07-1042, CLC08-1042 | 38 |
SLC07-1048, CLC08-1048 | 42 |
SLC07-1060, CLC08-1060 | 49 |
SLC07-1072, CLC08-1072 | 56 |
SLC07-2084, CLC08-2084 | 76 |
SLC07-2096, CLC08-2096 | 84 |
SLC07-2108, CLC08-2108 | 91 |
SLC07-2120, CLC08-2120 | 98 |
TABLE 1 – Weight Chart
Before mounting the unit, check the supporting structure to verify that it
has sufficient load-carrying capacity to support the weight of the unit(s).
The mounting hardware (supplied by others) should be capable of supporting a
minimum of three (3) times the weight of the unit. See TABLE 1.
A. When determining the mounting location for the unit(s), make sure that
nothing interferes with the curtain of air developed when the discharge vanes
are directed from 0° to 20° toward the door opening. If the air stream strikes
any obstruction (the top edge of the doorway, a door opening device, etc.),
the effectiveness of the unit will be greatly reduced. See FIGURE 1.
B. For optimum performance, the bottom of the unit (discharge nozzle) should
be no more than 1” above the top of the door opening with the unit mounted
flush to the wall. If the unit must be mounted higher, it must be spaced out
from the wall 3/8” for every inch the unit is above the door opening. Any void
between the air curtain and the wall should be sealed along the full length of
the unit. See FIGURE 2.
C. Proceed to: Section III-WALL MOUNTING or Section IV-SUSPENDED
MOUNTING
WALL MOUNTING
A. Determine the location on the wall above the opening where the air curtain
will be mounted. This location should center the unit over the opening and
provide suitable mounting support. It is recommended to use at least four
locations that correspond to the outer corners of the wall mounting plate. See
FIGURE 3.
B. Prepare the wall as necessary for the wall mounting plate anchors (by
others).
C. Drill holes in the wall mounting plate to correspond to the locations on
the wall.
D. Anchor the wall mounting plate over the door opening with the mounting tabs
pointing upwards.
E. Raise the unit over the door (air nozzle facing down) and onto the mounting
plate. Tilt the unit upward, matching the holes in the frame with the tabs on
the mounting plate. See FIGURE 4.
F. Lower the unit into place allowing it to rest on the mounting plate. The
unit flange should rest above the mounting plate flange.
G. After the unit is securely seated to the mounting plate, install the
locking screws along the bottom flange. See FIGURE 4.
H. Proceed to Section V-ELECTRICAL CONNECTIONS IV. SUSPENDED MOUNTING (Ceiling
Suspension)
A. When the unit is top mounted, the wall mounting plate is designed to store
on the back of unit for future use.
B. Four (4) factory installed #10-24 threaded inserts are located on the top
of the unit for top suspension mounting. See FIGURE 5.
C. Determine the exact mounting location of the air curtain.
D. The top of the unit is provided with an electrical knockout for power
connection. Remove the wiring tray compartment cover. Remove the knockout and
attach necessary electrical hardware. Save the wiring diagram found inside of
wiring tray.
E. Attach #10-24 threaded rods, or other suitable hardware to the top mounted
threaded inserts.
F. Proceed to Section V-ELECTRICAL CONNECTIONS
ELECTRICAL CONNECTIONS
All electrical wiring and connections MUST be performed by qualified personnel
in accordance with the National Electrical Code ANSI/NFPA No. 70 (latest
edition) or, in Canada, the Canadian Electrical Code, Part 1-C.S.A. Standard
22.1 and local codes and regulations.
A. Check the electrical rating nameplate on the top of the air curtain for
supply voltage and current requirements.
A separate line voltage supply with a suitable branch circuit protection
device should be run directly from the main electrical panel to the air
curtain. A disconnect switch for each branch circuit is a required part of
this installation.
B. All field wiring must be copper with a minimum insulation of 60° C within
approved conduit. If any of the wire supplied with the air curtain must be
replaced, it must be replaced with copper wiring with a minimum insulation of
90°C.
C. Remove the wiring tray cover; on air curtains that are comprised of
modules, remove the wiring tray cover that is located closest to the
electrical rating nameplate (if it has not already been done). See FIGURE 6.
D. The top of the air curtain has two knockouts on each side of the air
curtain, allowing for a left hand or right hand power connection. Remove the
required knockout if it has not already been done and connect the power supply
to the air curtain. Connect all supply and control circuit wires according to
the wiring diagram provided.
NOTE: For Electrically Heated air curtain(s) provided with the optional
remote thermostat: mount and wire the thermostat according to instructions and
wiring diagram. VI. MECHANICAL CONNECTIONS
A. ELECTRICALLY HEATED MODELS
The heater circuit may be controlled by a combination of a remote thermostat
and the fan/off/fan & heat rockers itch. Overheating protection is provided by
auto reset thermal cutouts built into the heater coil assembly (see the wiring
diagram, located in wiring tray).
B. STEAM OR HOT WATER HEATED MODELS
Piping should be done in accordance with local codes, regulations and standard
practices. Connect the building system supply and return to the ¾” MPT nipples
on the heating coil. See FIGURE 7.
OPERATING INSTRUCTIONS
A. GENERAL OPERATION
- The air curtain can be directly operated by using the rocker switches located on the bottom of the unit. The air curtain may also be automatically operated by a combination of the rocker switches and a remote door switch and/or thermostat (See the wiring diagram).
- Rocker switch positions are labeled on the air curtain cabinet.
- Unheated units have one rocker switch that turns the unit on or off. The other rocker switch selects fan speed.
- Heated units have one rocker switch that determines whether the unit is off, energizes only the fans, or energizes both the fans and the method of heat. The other rocker switch selects fan speed.
B. AIR STREAM SPLIT ADJUSTMENT
- With the air curtain operating and the door in its full open position, check to see that nothing is obstructing the air flow at the discharge nozzle vanes.
- Find the air stream split location. Hold a handkerchief, by its corners, approximately 12” above the floor. Gently move the handkerchief back and forth in the doorway. Make sure the air is being directed to both the inside and the outside. The split location is indicated where the handkerchief is vertical with minimal or no fluttering. See FIGURE 8.
- Adjust the discharge nozzle vanes so the split location is approximately 3” outside the doorway. This is accomplished by first de-energizing the unit.
Remove the cover housing, loosen the nozzle vane locking screws and adjust vanes.
MAINTENANCE AND CLEANING
CAUTION: ELECTRIC SHOCK HAZARD Disconnect power whenever servicing air
curtain unit. More than one disconnect may be required to de-energize air
curtain unit.
Keep your air curtain operating at peak efficiency by cleaning the blower
wheels, motor(s) and intake grille. Buildup of dust on the blower wheels can
cause vibration, noise and excessive wear on the motor bearings. The frequency
of cleaning will depend on the environment in which the unit is operating.
Dirty, dusty or greasy environments could require a cleaning schedule of once
every two months. If the environment is not that dirty, the unit(s) should be
scheduled for cleaning a minimum of once every (6) months. To access the
interior of the unit:
A. Disconnect the power to the unit.
B. Remove the intake grille by removing all Philips head screws around edge.
See FIGURE 9.
C. Vacuum and scrape (if necessary) to remove the buildup of dirt and debris.
The motor(s) are permanently lubricated and require no additional lubrication.
Reinstall the cover and intake grille.
D. Reconnect the power, and turn on after cleaning. CAUTION: STAND CLEAR OF
THE UNIT OR WEAR SAFETY GOGGLES AS LOOSE DEBRIS MAY BE PRESENT AND MAY EXIT
THROUGH THE NOZZLE.
SERVICE
CAUTION: ELECTRIC SHOCK HAZARD Disconnect power whenever servicing air
curtain unit. More than one disconnect may be required to de-energize unit.
Any service performed on the Certified Low Profile7/Commercial Low Profile 8
air curtain MUST be done by qualified personnel.
Berner air curtains require very little servicing. All parts are easily
accessible for periodic inspection and maintenance. Units should be cleaned at
least twice a year. Your particular application (the amount of dirt and dust
in the air) and location of the unit(s) will determine how often your unit(s)
will need to be cleaned and serviced. All motors have permanently lubricated,
sealed, sleeve bearings and require no maintenance.
A. FAN AND MOTOR REMOVAL
- Disconnect power to the unit.
- Remove the intake grille by removing all phillips head screws around edge. See FIGURE 9.
- Unplug motor harness from motor and remove necessary wiring.
- Using a 1 /8” Allen wrench, loosen each set screw attaching fan(s) to motor
- While holding the motor in place, loosen and remove the motor clips.
- Slide the fans toward the motor so that the ball bearings on the outer fan shaft are exposed.
- Slowly roll the motor out of the motor mount cradle forward and down. The hubs of the fans are flexible enough to allow the motor to move before the fans’ outer ball bearings pull out of the unit. 8. Reinstall in reverse order of removal.
TROUBLESHOOTING
SYMPTOMS CAUSE REMEDY | CAUSE | REMEDY |
---|---|---|
NO AIR | •Electrical Power supply line open (no power) |
•Fuse blown/circuit breaker tripped
•Motor overload tripped
•Failed switch| •Check power source, check method of control is in “ON”
position
•Replace fuse(s)/reset breaker
•Internally protected motor – should reset automatically after cool-down, if
not, replace motor.
•Replace switch
MOTOR RUNNING/FANS ARE NOT ROTATING WHEN DOOR IS OPEN
•Broken fan hub
•Shaft rotating inside fan
•Broken / Loose coupling| • Replace fan
•Tighten set screws/tighten fan on shaft
•Replace / Tighten coupling
ELECTRICAL CONTROLS NOT FUNCTIONING
•Selector switch is in “OFF” position
•Door limit switch not operating| •Repair or replace limit switch
MINIMUM AIR| •Air directional discharge vanes misadjusted
•Inadequate intake clearance
•Blower motor operates below speed
•Fan rubbing against housing
•Fan wheels clogged with dirt| • Adjust vanes to proper position; see
installation instructions
•Move air curtain or remove obstruction Provide adequate space for air curtain
•Improper voltage
•Free fan from housing
•Clean and vacuum fan wheels
AIR IS NOT HITTING FLOOR| •Air stream too weak
•Air steam hits obstruction
•Negative pressure| •Adjust nozzle to proper position, adjust motor speed; see
installation instructions
•Remove obstruction or reposition air curtain (move out 3/8″ for every 1″ up
from the door)
•Relieve negative pressure by providing makeup air
UNEVEN AIR| •Shaft rotating inside fan| •Tighten set screws/Replace fan
EXCESSIVE AIR MOVEMENT AT DOORWAY| •Nozzle not angled out far enough
•Air movement too cold
•Pushing air outside building
SEE: AIR IS NOT HITTING FLOOR| •Adjust nozzle angle to outside
•Add auxiliary heat to overcome wind chill
•Adjust nozzle angle towards door threshold
WARRANTY
Berners International (“The Company”) warrants all new equipment to be free of
defects in workmanship and material for a period of five years (5 years) on
unheated models and two years (2 years) on heated models from the original
date of shipment, provided the equipment has been properly cared for,
installed and operated in accordance with the limits specified on the
nameplate and The Company’s instructions. All warranted parts will be replaced
at no charge for a period of six months from date the parts were shipped.
The Company will correct by repair or replacement, at its option and expense,
any proven defects in said apparatus, subject to the above conditions,
provided that immediate written notice of such defects is given to The
Company. The warranty does not include any labor incurred for the removal or
installation of defective part(s). The Company reserves the right to inspect,
or have inspected by a qualified representative, any apparatus at the place of
installation before authorizing repair or replacement. Repair or replacement
will be made F.O.B. factory with any applicable transportation charges to be
borne by the customer. Merchandise not of The Company’s manufacture supplied
in piece, or in component assemblies, is not covered by the above warranty,
but The Company will give the customer the benefit of any adjustment as made
with the Manufacturer. This warranty is void if the apparatus has been
tampered with in any way or shows evidence of misuse.
The Company will not assume any expense or liability for repairs made outside
its factory without proper written consent from its service manager, nor for
any transportation charges on apparatus returned to the factory without
written authorization by The Company.
Nothing in the above warranty provisions, however, shall impose any liability
or obligation of any type, nature or description upon Berner International if
Berner has not received payment in full for the apparatus in question.
THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF
INCLUDING THE IMPLIED WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR
PURPOSE. LIMITATION OF DAMAGES
Notwithstanding anything to the contrary above, customer’s exclusive remedy
for any and all losses or damages resulting from the sale of The Company’s
equipment under this agreement, including but not limited to, any allegations
of breach of warranty, breach of contract, negligence or strict liability,
shall be limited, at The Company’s option, to either the return of the
purchase price or the replacement of the particular equipment for which a
claim is made and proved. In no event shall The Company be liable for any
special, consequential, incidental or indirect losses or damages from the sale
of The Company’s equipment under this agreement.
SERIAL NUMBER……..
MODEL NUMBER………….
DATE PURCHASED………………….
BERNER INTERNATIONAL
New Castle, Pennsylvania
724-658-3551 •
1-800-245-4455 •
www.Berner.com
Berners reserves the right to alter specifications without prior notice.
© Copyright 2022 Berners International M
MADE IN U.S.A.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>