DVP 271 Ground Fault Detection Module Installation Guide
GET STARTED
The 271 is a ground fault detection module that detects ground faults without harming the control panel. The module connects to a zone and the earth ground to determine if there is a fault. Refer to the panel installation guide for more information about zone programming.
What’s Included
▶ One 271 Ground Fault Detection Module
▶ 3 Nylon Standoffs
▶ 2 Nylon Washers
▶ 2 Nylon Cup Washers
▶ 1 Ferrite Core
What You’ll Need
▶ #2 Phillips screwdriver
*Connect to the positive terminal of any available zone between 1 and 8
Figure 1: PCB Features
INSTALLATION
Preparing for Installation
- Unscrew the panel from the enclosure and remove the panel
- Place the included nylon cup washer between the enclosure standoffs and the Place the flat nylon washer on the screw to secure the panel. This provides ground isolation from the enclosure.
- Screw the panel PCB back into
Figure 2: Washer and Panel Installation
Mount the Module
The module can be mounted in a DMP enclosure using the standard 3-hole mounting pattern. Refer to Figure 2 as needed during installation.
- Hold the plastic standoffs against the inside of the enclosure side
- Insert the included Phillips head screws from outside of the enclosure into the standoffs. Tighten the screws.
- Carefully snap the module onto the
F igure 3: Standoff and Module Installation
Wire the Module
Caution: Disconnect all power from the panel before wiring the module. Failure to do so may result in equipment damage or injury. Observe polarity when making power connections.
Use 18 to 22 gauge wire when wiring the module.
- Use a wire to connect the module’s 12V negative to terminal 10 on the Use another wire to connect the module’s 12V positive to terminal 7 on the panel.
- Connect the module to the earth ground (if available) using 14 gauge wire or Additional options are a cold water pipe, ground rod, or building ground. Gas pipes or sprinkler pipes should not be used. Do not connect to an electrical ground, server rack or telephone company ground.
- Connect the module’s OUT to the positive terminal of any available zone between 1 and Do not attach a resistor to the zone, there is a resistor built into the 271.
Note: The module monitors all busses on the panel through the on-board zone connection.
Wire the Ferrite Core
Refer to Figure 4 as needed during installation.
- Unplug the keypad harness from the panel keypad bus
- Open the ferrite
- Loop the keypad harness wires around the core and
Reconnect the keypad harness to the panel keypad bus header.
Program the Panel
Refer to the panel programming guide for full programming information.
After completing each of the following steps, press CMD to advance to the
next prompt.
- Reset the At a keypad, enter 6653 (PROG) to access the PROGRAMMER menu.
- In STATUS LIST , navigate to SUPERVISORY ZONES and select keypads to display the ground fault
- At ZONE INFORMATION , enter the zone
- At UNUSED , name the zone GROUND FAULT.
- At ZONE TYPE , select SUPERVISORY (SV).
- Press CMD until STOP Press a top row select key or area to save programming.
ADDITIONAL INFORMATION
Module Operation
When a ground fault is detected, the panel will enter into a trouble condition and annunciate at the keypad programmed in the Status list. The trouble condition will continue until a valid user code is entered at the keypad. In addition, ground fault conditions on the zone will light the corresponding GND FAULT red LED.
Compatibility
▶ XR Series Panels
SPECIFICATIONS
Primary Power | 12 VDC from panel |
---|---|
Current Draw | |
Idle | 8.8 mA |
Operating | 12.8 mA |
CERTIFICATIONS
Underwriters Laboratory (UL) Listed
ANSI/UL 864 | Fire Protective Signaling |
---|