582K Legacy Line With Axion Fan
Product Information
Product Name: 582K 04-07 LEGACYTM LINE WITH
AXION FANTM TECHNOLOGY SINGLE PACKAGE ROOFTOP GAS HEAT/ELECTRIC
COOLING UNITS
Edition Date: 5-23
Manufacturer: Bryant
Description: This product is a single package
rooftop gas heat/electric cooling unit that utilizes AXION FANTM
technology. It features a standard base unit with a cabinet and a
refrigerant system. The gas heat component meets the California Air
Quality Management NOx requirement of 40 nanograms/joule and
includes stainless steel heat exchangers. The unit comes with a
standard limited parts warranty.
Product Usage Instructions
To use the 582K 04-07 LEGACYTM LINE WITH AXION FANTM TECHNOLOGY
SINGLE PACKAGE ROOFTOP GAS HEAT/ELECTRIC COOLING UNITS, follow
these steps:
-
Ensure that the power supply to the unit is connected with the
correct voltage, phase, and frequency as specified in the
electrical data section of the user manual. -
Make sure the unit is properly installed on a certified roof
curb as per the certified roof curb details provided in the user
manual. -
Before operating the unit, familiarize yourself with the
performance data provided in the manual. Note the unit operating
weight, exhaust fan motor size, curb weight, gross total capacity
for cooling and heating (gas), compressor power input, airflow,
external static pressure, indoor fan motor size, and other relevant
performance specifications. -
For cooling operation, set the desired cooling capacity based
on the gross sensible capacity and the required airflow. Ensure
that the external static pressure is within the specified
range. -
For heating operation, determine the heating capacity required
based on the total heating capacity and the desired airflow. Set
the appropriate stage for heating and ensure that the indoor fan
motor size and motor setting are compatible. -
Refer to the electrical data section to determine the maximum
circuit amps and overcurrent protection for the unit. -
If desired, consider utilizing factory-installed options such
as economizers with dry bulb or enthalpy sensing, barometric
relief, low leak air dampers, and controllers that meet specific
requirements. -
Always refer to the user manual for any troubleshooting or
maintenance procedures.
Note: The manufacturer reserves the right to change
specifications and designs without notice. Please refer to the
latest version of the user manual for the most up-to-date
information.
582K 04-07 LEGACYTM LINE WITH AXION FANTM TECHNOLOGY
SINGLE PACKAGE ROOFTOP GAS HEAT/ELECTRIC COOLING UNITS
— PERFORMANCE DATA — CERTIFIED DIMENSION PRINTS — CERTIFIED ROOF CURB DETAILS
Edition Date: 5-23
Printed in U.S.A.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Form: SUB582K-4-7-03 Rev. A Replaces: SUB582K-4-7-02
JOB NAME: BUYER: UNIT NUMBER: PERFORMANCE DATA CERTIFIED BY:
LOCATION: BUYER PO #: MODEL NUMBER:
Bryant#:
DESCRIPTION
582K units are single-packaged electric cooling, gas heating unit that are
pre-wired and pre-charged with Puron® (R-410A) HFC refrigerant. The units are
factory tested in both heating and cooling modes. Sizes 04-06 models use
single-stage cooling capacity control. Size 07 models use two-stage cooling
capacity control.
FEATURES
Standard Base Unit
· Puron (R-410A) HFC refrigerant · 14.0 SEER and 15.2 IEER on 3-phase products
and 13.8
SEER2 on single-phase products · IEER of 15.0 · Meets or exceeds ASHRAE 90.1
energy efficiency levels · Rated in accordance with AHRI Standards 210/240 for
sizes 04-06 and 340/360 for size 07 · Designed in accordance with Underwriters
Laboratories
Std 1995 · Listed by UL and UL-Canada · Single-stage cooling capacity control
on 04 to 06 models,
two-stage on 07 models · Corrosive resistant composite sloping design; side or
cen-
ter drain condensate pan. Meets ASHRAE Standard 62 · Standard cooling
operating range from 40°F up to 115°F
(4°C up to 46°C). Field installable accessory extends the minimum down to
20°F (29°C) · Field convertible from vertical to horizontal airflow for slab
mounting — no special kits required · Two-inch disposable return air filters ·
Thru-the-bottom power and gas entry capability · Single point gas and electric
connections · 24-volt control circuit protected with resettable circuit
breaker · Direct Drive – Axion Fan technology indoor fan system uses vane
axial fan design and electronically commutated motor
Shall have inherent automatic-reset thermal overload protection
Shall require no fan/motor belts for operation, adjustments, and/or initial
fan speed setup
Shall be internally protected from electrical phase reversal and loss
Shall have slow ramp up to speed control capabilities to help reduce sound
and comfort issues
Shall be a slide-out design with two screw removal
On 07 size model with two stage cooling capacity control, the indoor fan
speed is automatically controlled to meet the code compliant 66% low fan speed
and 100% at full fan speed
· Totally enclosed condenser motors with permanently lubricated bearings
· Low-pressure and high-pressure switches
· Full perimeter base rail with built-in rigging adapters and fork truck slots
· Centralized terminal board facilitating simple safety circuit
troubleshooting and simplified control box arrangement
· New unit control board with intuitive quick fan speed adjustment
Cabinet
· Access panels with easy grip handles · Innovative, easy starting, no-strip
screw feature on unit
access panels · Pre-painted exterior panels and primer-coated interior
panels tested to 500 hours salt spray protection · Fully insulated cabinet ·
Tool-less filter access door
Refrigerant System
· AcutrolTM refrigerant metering system on 04 to 06 models, TXV on 07 models
· Liquid line filter drier · Scroll compressors with internal line-break
overload
protection (one-stage on 04 to 06 models, two-stage on 07 models) · Copper
tube, aluminum fin coils with optional corrosion resistant coils · Top cover
removable gage line plugs for reading refrigerant pressure with unit panels in
place
Gas Heat
· IGC solid-state gas heat exchanger control for on-board diagnostics, anti-
cycle protection, LED error code designation, burner control logic and energy
saving indoor fan motor delay
· Gas efficiencies up to 81% · Inducted draft combustion · Redundant gas
valve, with 2 stages of heating · Flame roll-out safety protector · Solid-
state electronic direct spark ignition system · Dedicated 3 to 5 ton “low NOx”
models available that
meet California Air Quality Management NOx requirement of 40 nanograms/joule.
Low NOx models include stainless steel heat exchangers.
Standard Limited Parts Warranty
· 15-year gas heat exchanger parts – Stainless Steel · 10-year gas heat
exchanger parts – Aluminized · 5-year compressor parts
2
PERFORMANCE DATA
Unit Operating Weight __ lb
Exhaust Fan Motor Size ____ HP
COOLING
Curb Weight __ lb
Gross Total Capacity __ Btuh HEATING (GAS)
at Condenser Air Temperature __ °F Heating Capacity:
Gross Sensible Capacity ___ Btuh Stage 1 ____ Btuh
Compressor Power Input ___ kW Stage 2 ____ Btuh
Indoor Entering: db __ °F / wb __ °F
Heating Capacity Total ___ Btuh
Airflow _ CFM External Static Pressure __ in. wg Stage 1 ____ kW
Indoor Fan Motor Size _____ HP
Stage 2 ____ kW
Indoor Fan Motor Setting Vdc Heating Capacity Total kW
ELECTRICAL DATA
Power Supply to Unit ____ Volts
Phase
Hz Maximum Circuit Amps
__ Maximum Overcurrent Protection
SUBMITTAL DATA
Job Name _ Architect
__ Engineer
_ Contractor
_____ Unit Designation
®
®
®
®
3
FACTORY-INSTALLED OPTIONS
Economizer with DRY BULB Sensing and Barometric Relief (04-06 sizes)
Low Leak Air Dampers —
Models with W7212 controller provide standard non-diagnostic control
(EconoMi$er® IV system).
Models with W7220 controller meet California Title 24 (Section 120.2), IECC,
and ASHRAE 90.1 for Fault Detection and Diagnostic (FDD) requirements
(EconoMi$er X system).
Models with RTU Open controller meet California Title 24 (Section 120.2),
IECC, and ASHRAE 90.1 for Fault Detection and Diagnostic (FDD) requirements
(EconoMi$er 2 system).
Economizer with ENTHALPY Sensing and Barometric Relief (04-06 sizes)
Low Leak Air Dampers —
Models with W7212 controller provide standard non-diagnostic control
(EconoMi$er® IV system).
Models with W7220 controller meet California Title 24 (Section 120.2), IECC,
and ASHRAE 90.1 for Fault Detection and Diagnostic (FDD) requirements
(EconoMi$er X system).
Models with RTU Open controller meet California Title 24 (Section 120.2),
IECC, and ASHRAE 90.1 for Fault Detection and Diagnostic (FDD) requirements
(EconoMi$er 2 system).
Economizer with DRY BULB Sensing and Barometric Relief (04-07 sizes)
ULTRA LOW LEAK Air Dampers —
Models with W7220 controller meet California Energy Commission Title 24-2016
prescriptive section 140.4 (damper leakage, etc.), and mandatory section
120.2.i for Fault Detection and Diagnostic controls. Economizers meet ASHRAE
90.1-2016 damper leakage requirements as stated in section 6.5.1.1.4 and Table
6.4.3.4.3, and meet 2016 Fault Detection and Diagnosis requirements in section
6.4.3.12. For outside air, return, and relief air damper leakage requirements
economizers meet IECC 2012 section C402.4.5.2 and IECC 2015 sections
C403.2.4.3 and C403.3.3.5 and IECC 2015 section C403.2.4.7 for Fault Detection
and Diagnostic requirements. NOTE: IECC 2015 section C403.2.4.7.1 requires
differential return air sensor, which must be ordered separately. Outside air,
return air, and relief air (volume) dampers are AMCA rated — plus 5 year
limited parts warranty (EconoMi$er X system).
Models with RTU Open meet California Energy Commission Title 24-2016
prescriptive section 140.4 (damper leakage, etc.) and mandatory section
120.2.i for Fault Detection and Diagnostic requirements. Economizers meet
ASHRAE 90.1-
2016 damper leakage requirements as stated in section 6.5.1.1.4 and Table
6.4.3.4.3, and meet 2016 Fault Detection and Diagnosis requirements in section
6.4.3.12. Economizers meet IECC 2012 section C402.4.5.2 and IECC 2015 sections
C403.2.4.3 and C403.3.3.5 for outside air, return air, and relief air damper
leakage requirements and IECC 2015 section C403.2.4.7 for Fault Detection and
Diagnostic requirements. NOTE: IECC 2015 section C403.2.4.7.1 requires
differential return air sensor, which must be ordered separately. Outside air,
return air, and relief air (volume) dampers are AMCA rated — plus 5 year
limited parts warranty (EconoMi$er 2 system).
Economizer with ENTHALPY Sensing and Baromet-
ric Relief (04-07 sizes)
ULTRA LOW LEAK Air Dampers —
Models with W7220 controller meet California Energy Commission Title 24-2016
prescriptive section 140.4 (damper leakage, etc.), and mandatory section
120.2.i for Fault Detection and Diagnostic controls. Economizers meet ASHRAE
90.1-2016 damper leakage requirements as stated in section 6.5.1.1.4 and Table
6.4.3.4.3, and meet 2016 Fault Detection and Diagnosis requirements in section
6.4.3.12. For outside air, return, and relief air damper leakage requirements
economizers meet IECC 2012 section C402.4.5.2 and IECC 2015 sections
C403.2.4.3 and C403.3.3.5 and IECC 2015 section C403.2.4.7 for Fault Detection
and Diagnostic requirements. NOTE: IECC 2015 section C403.2.4.7.1 requires
differential return air sensor, which must be ordered separately. Outside air,
return air, and relief air (volume) dampers are AMCA rated — plus 5 year
limited parts warranty (EconoMi$er X system).
Models with RTU Open meet California Energy Commission Title 24-2016
prescriptive section 140.4 (damper leakage, etc.) and mandatory section
120.2.i for Fault Detection and Diagnostic requirements. Economizers meet
ASHRAE 90.12016 damper leakage requirements as stated in section 6.5.1.1.4 and
Table 6.4.3.4.3, and meet 2016 Fault Detection and Diagnosis requirements in
section 6.4.3.12. Economizers meet IECC 2012 section C402.4.5.2 and IECC 2015
sections C403.2.4.3 and C403.3.3.5 for outside air, return air, and relief air
damper leakage requirements and IECC 2015 section C403.2.4.7 for Fault
Detection and Diagnostic requirements. NOTE: IECC 2015 section C403.2.4.7.1
requires differential return air sensor, which must be ordered separately.
Outside air, return air, and relief air (volume) dampers are AMCA rated — plus
5 year limited parts warranty (EconoMi$er 2 system).
4
FACTORY-INSTALLED OPTIONS (cont)
Standard Base Unit
RTU Open multi-protocol controller communicates to BACnetTM1, Modbus®1,
LonWorks®1, and Johnson N2 protocols.
Through the base connectors for gas and electric conduit/piping
Stainless steel gas heat exchanger (includes tubes, vestibule plate and
collector box)
Perfect HumidityTM adaptive dehumidification system (This option should also
include low ambient controls)2
Two-position motorized outdoor air damper (04-06 sizes)
Non-fused disconnect Powered 115-volt convenience outlet2 Non-powered 115-volt
convenience outlet
High static evaporator fan motor Return air smoke detector Supply air smoke
detector CO2 sensor Condenser hail guard – louvered style2 Special coating
protection for evaporator and condenser
coils2 Hinged access doors Condensate overflow switch
Optional Warranties
Complete unit parts only, up to 5 years Complete unit parts and labor, up to 5
years
Many other optional warranties are available. See the Commercial Start-Up and
Optional Extended Warranty Price pages for further information.
1. Third-party trademarks and logos are the property of their respective
owners.
2. Not available on single-phase models.
5
FIELD-INSTALLED ACCESSORIES
NOTE: 582K 07 models use two-speed indoor fan logic, the W7212 controller is
designed for single-speed motor control. See Application Tip “BY-
ROOFTOP-18-01” for further guidance when using this unit.
Economizer with DRY BULB Sensing and Barometric Relief
Low Leak Air Dampers —
Models with W7212 controller provide standard non-diagnostic control.
EconoMi$er® IV.
Models with W7220 controller meet California Title 24 (Section 120.2), IECC,
and ASHRAE 90.1 for Fault Detection and Diagnostic (FDD) requirements
(EconoMi$er X system).
Models with RTU Open controller meet California Title 24 (Section 120.2),
IECC, and ASHRAE 90.1 for Fault Detection and Diagnostic (FDD) requirements
(EconoMi$er 2 system).
Economizer with ENTHALPY Sensing and Barometric Relief
Low Leak Air Dampers —
Models with W7212 controller provide standard non-diagnostic control.
EconoMi$er IV.
Models with W7220 controller meet California Title 24 (Section 120.2), IECC,
and ASHRAE 90.1 for Fault Detection and Diagnostic (FDD) requirements
(EconoMi$er X system).
Models with RTU Open controller meet California Title 24 (Section 120.2),
IECC, and ASHRAE 90.1 for Fault Detection and Diagnostic (FDD) requirements
(EconoMi$er 2 system).
Economizer with DRY BULB Sensing and Barometric Relief
ULTRA LOW LEAK Air Dampers —
Models with W7220 controller meet California Energy Commission Title 24-2016
prescriptive section 140.4 (damper leakage, etc.), and mandatory section
120.2.i for Fault Detection and Diagnostic controls. Economizers meet ASHRAE
90.1-2016 damper leakage requirements as stated in section 6.5.1.1.4 and Table
6.4.3.4.3, and meet 2016 Fault Detection and Diagnosis requirements in section
6.4.3.12. For outside air, return, and relief air damper leakage requirements
economizers meet IECC 2012 section C402.4.5.2 and IECC 2015 sections
C403.2.4.3 and C403.3.3.5 and IECC 2015 section C403.2.4.7 for Fault Detection
and Diagnostic requirements. NOTE: IECC 2015 section C403.2.4.7.1 requires
differential return air sensor, which must be ordered separately. Outside air,
return air, and relief air (volume) dampers are AMCA rated.
Models with RTU Open meet California Energy Commission Title 24-2016
prescriptive section 140.4 (damper leakage, etc.) and mandatory section
120.2.i for Fault Detection and Diagnostic requirements. Economizers meet
ASHRAE 90.12013 / 2016 damper leakage requirements as stat-
ed in section 6.5.1.1.4 and Table 6.4.3.4.3, and meet 2016 Fault Detection and
Diagnosis requirements in section 6.4.3.12. Economizers meet IECC 2012 section
C402.4.5.2 and IECC 2015 sections C403.2.4.3 and C403.3.3.5 for outside air,
return air, and relief air damper leakage requirements and IECC 2015 section
C403.2.4.7 for Fault Detection and Diagnostic requirements. NOTE: IECC 2015
section C403.2.4.7.1 requires differential return air sensor, which must be
ordered separately. Outside air, return air, and relief air (volume) dampers
are AMCA rated — plus 5 year limited parts warranty. EconoMi$er 2.
Economizer with ENTHALPY Sensing and Baromet-
ric Relief
ULTRA LOW LEAK Air Dampers —
Models with W7220 controller meet California Energy Commission Title 24-2016
prescriptive section 140.4 (damper leakage, etc.), and mandatory section
120.2.i for Fault Detection and Diagnostic controls. Economizers meet ASHRAE
90.1-2016 damper leakage requirements as stated in section 6.5.1.1.4 and Table
6.4.3.4.3, and meet 2016 Fault Detection and Diagnosis requirements in section
6.4.3.12. For outside air, return, and relief air damper leakage requirements
economizers meet IECC 2012 section C402.4.5.2 and IECC 2015 sections
C403.2.4.3 and C403.3.3.5 and IECC 2015 section C403.2.4.7 for Fault Detection
and Diagnostic requirements. NOTE: IECC 2015 section C403.2.4.7.1 requires
differential return air sensor, which must be ordered separately. Outside air,
return air, and relief air (volume) dampers are AMCA rated.
Models with RTU Open meet California Energy Commission Title 24-2016
prescriptive section 140.4 (damper leakage, etc.) and mandatory section
120.2.i for Fault Detection and Diagnostic requirements. Economizers meet
ASHRAE 90.12016 damper leakage requirements as stated in section 6.5.1.1.4 and
Table 6.4.3.4.3, and meet 2016 Fault Detection and Diagnosis requirements in
section 6.4.3.12. Economizers meet IECC 2012 section C402.4.5.2 and IECC 2015
sections C403.2.4.3 and C403.3.3.5 for outside air, return air, and relief air
damper leakage requirements and IECC 2015 section C403.2.4.7 for Fault
Detection and Diagnostic requirements. NOTE: IECC 2015 section C403.2.4.7.1
requires differential return air sensor, which must be ordered separately.
Outside air, return air, and relief air (volume) dampers are AMCA rated — plus
5 year limited parts warranty. EconoMi$er 2.
6
FIELD-INSTALLED ACCESSORIES (cont)
NOTE: 582K 07 models use two-speed indoor fan logic, the two-position damper
and manual dampers are designed for single-speed motor control. See
Application Tip “BY-ROOFTOP-18-01″ for further guidance when using this unit.
Power exhaust — prop fan design Two-position motorized outdoor air damper
Manual outside air damper 25% Manual outside air damper 50% Roof curb — 14
inch (356 mm) tall Roof curb — 24 inch (610 mm) tall Thru-the-bottom
connections, electrical only Thru-the-bottom connections, electrical and gas
Condenser hail guard, louvered style Flue shield Flue discharge deflector
Liquid propane (LP) conversion kit High altitude conversion kit Phase monitor
(loss of phase/phase reversal) Winter start kit, down to 25°F (4°C)
Fan/Filter status switch Low ambient head pressure controller, down to
20°F (29°C)
Time Guard II compressor anti-cycle protection Thermostats and sensors
NOTE: Size 07 model has two-stage cooling thermostat; use appropriate
thermostat. Condensate overflow switch Non-powered 115-volt (20 amp)
convenience outlet Side access hinged filter door kit Horn/Strobe annunciator
Economizer Sensors
Single dry bulb control Differential dry bulb control Single enthalpy control
Differential enthalpy control CO2 — wall mounted CO2 — duct mounted CO2 — unit
mounted
7
8
CERTIFIED DIMENSION PRINT
Fig. 1 — 582K**04-07 Dimensional Drawing
9
CERTIFIED DIMENSION PRINT
Fig. 1 — 582K**04-07 Dimensional Drawing (cont)
10
CERTIFIED DIMENSIONS PRINT
Fig. 1 — 582K**04-07 Dimensional Drawing (cont)
ROOF CURB ACCESSORY # CRRFCURB001A01
CRRFCURB002A01
A
14″ [356] 24″ [610]
ROOF CURB DETIALS
NOTES:
1. ROOFCURB ACCESSORY IS SHIPPED DISASSEMBLED.
2. INSULATED PANELS: 25.4 [1″] THK. POLYURETHANE FOAM, 44.5 [1-3/4] # DENSITY.
3. DIMENSIONS IN [ ] ARE IN MILLIMETERS.
4. ROOFCURB: 18 GAGE STEEL.
5. ATTACH DUCTWORK TO CURB. (FLANGES OF DUCT REST ON CURB).
6. SERVICE CLEARANCE 4 FEET ON EACH SIDE.
DIRECTION OF AIR FLOW.
8. CONNECTOR PACKAGE CRBTMPWR001A01 IS FOR THRU-THE-CURB GAS TYPE
PACKAGE CRBTMPWR003A01 IS FOR THRU-THE-BOTTOM TYPE GAS CONNECTIONS.
CONNECTOR PKG. ACC. GAS CONNECTION TYPE GAS FITTING
CRBTMPWR001A01
THRU THE CURB
3/4″ [19] NPT
CRBTMPWR003A01
THRU THE BOTTOM
1/2″ [12.7] NPT
1-3/4″ [44.5]
POWER WIRING FITTING
CONTROL WIRING ACCESSORY CONVENIENCE
FITTING
OUTLET WIRING CONNECTOR
3/4″ [19] NPT
1/2″ [12.7] NPT
1/2″ [12.7] NPT
5.42″ [137.7] 21.74″ [552.2]
4.96″ [126.0]
15.19″ [385.8]
3.00″ [76.2]
14.00″ [355.6] 1.75″ [44.5]
4 9/16″ [115.5]
1/4″ [7.0]
11.96″ [303.8]
70.87″ [1800.2]
1/3/4″[44.5] 21.84″ [554.7] SUPPLY AIR OPENING
RETURN AIR OPENING
E
16.03″ [407.2]
E
32.19″ [817.6]
20.41″ [518.3] 40.69″ [1033.5]
3.00″ [76.2] 13.78” [350.0]
VIEW “B”
CORNER DETAIL
GASKET (SUPPLIED WITH CURB)
DUCT (FIELD SUPPLIED)
“A”
1.00″ [25.4]
11 3/4″[298.5] WIDE INSULATED DECK PANELS
1-3/4″ [44.4] SECTION E-E
SCALE 0.250
8 9/16″[217.5] WIDE INSULATED DECK PANEL
GAS SERVICE PLATE THRU THE CURB DRILL HOLE 2″ [50.8] @ ASSEMBLY (IF REQUIRED)
(SEE NOTE #8)
1′ 4-13/16″ [427] INSIDE
SUPPLY AIR
UNIT
7/16″ [11]
NAIL (FIELD SUPPLIED) TYPICAL (4) SIDES
COUNTER FLASHING (FIELD SUPPLIED)
“A”
ROOFING FELT (FIELD SUPPLIED)
CANT STRIP (FIELD SUPPLIED)
ROOFING MATERIAL (FIELD SUPPLIED)
3′-1 3/16″ [944.6] SEE VIEW “B”
RETURN AIR
1-3/4″ [44.5]
2-3/8″ [61]
SEE NOTE #2
5′ 7-3/8″ [1711.3]
1-3/4″ [44.4]
11
SUPPLY AIR
RETURN AIR
RIGID INSULATION (FIELD SUPPLIED)
Fig. 2 — 582K**04-07 Roof Curb Accessory Details
48TC400427
© 2023 Carrier
Edition Date: 5-23
Printed in U.S.A.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Pg 12
Form: SUB582K-4-7-03 Rev. A Replaces: SUB582K-4-7-02