Honeywell Home RedLINK FocusPRO Thermostats Instruction Manual
- June 13, 2024
- Honeywell Home
Table of Contents
Honeywell Home RedLINK FocusPRO Thermostats
View all Honeywell home thermostat manual
Product Information
The product is a zoning system with IAQ (Indoor Air Quality) control. It includes different components such as zone panels, thermostats, adapters, dampers, and transformers. The system allows for controlling and monitoring the temperature and air quality in up to 4 zones.
Technical Reference Manual
The product manual provides detailed information on zoning with IAQ control
using RedLINK FocusPRO Thermostats, Prestige Thermostats, and RedLINK
VisionPRO Thermostats. It also includes wiring diagrams and parts lists for
different configurations.
Parts List
For a 4-zone system with IAQ control, the following parts are required
- HZ322K zone panel kit : Includes HZ322 zone panel, C7735A1000 discharge sensor, and AT140A1042 transformer
- YTHX9421R Prestige IAQ kit with Thermostat & EIM
- YTH6320R1023: Includes TH6320R1004 wireless programmable FocusPRO thermostat and THM4000R1000 adapter
- TH6320R1004: Wireless thermostat for zone 3 (not needed for a 2-zone system)
- Appropriate zone dampers and bypass damper for the application
Product Usage Instructions
Follow the steps below to use the product
- Install the zone panel kit (e.g., HZ322K or HZ432K) according to the provided wiring diagram.
- Connect the necessary components, including the discharge sensor and transformer.
- Install the YTHX9421R Prestige IAQ kit with Thermostat & EIM. Ensure that the subbase of each THX9421R5021 thermostat is wired to a 24-volt transformer, either the one powering the zone panel or a separate transformer.
- If using wireless thermostats (e.g., YTH6320R1023), ensure that the EIMs and adapters are at least 2 feet apart from each other.
- Connect the appropriate zone dampers and bypass damper for the application.
- Refer to the system-specific wiring diagram on page 10 to wire the EIM to the corresponding zone, depending on the equipment being controlled.
- Ensure that the supply and return sensors included in the YTHX9421 2.0 Prestige IAQ kits are not used in zoning applications.
- Note that the thermostats cannot be set for delta-T diagnostics when used in zoning applications.
- Complete the power and wireless setup as instructed in the manual.
For more detailed information, refer to the provided wiring diagrams and consult the product manual.
TECHNICAL REFERENCE MANUAL
ZONING WITH IAQ CONTROL
RedLINK FocusPRO Thermostats
2–3 Zones
- Stage Furnace + 1–2 Stage Cooling ……………………………………………………………………………….. Option A. Page 2
- Single Stage Heat Pump + Electric Heat Strips for Auxiliary Heat …………………………………… Option A. Page 2
- Stage Heat Pump + Electric Heat Strips for Auxiliary Heat ……………………………………………. Option B. Page 3
- Dual Fuel (1 of 2 Stage Heat Pump + 1 or 2 Stage Gas/Oil Furnace ……………………………….. Option C. Page 4
4 Zones
- Stage Furnace + 1–2 Stage Cooling ……………………………………………………………………………….. Option B. Page 2
- Single Stage Heat Pump + Electric Heat Strips for Auxiliary Heat …………………………………… Option B. Page 2
- 2 Stage Heat Pump + Electric Heat Strips for Auxiliary Heat …………………………………………….. Option B. Page 2
- Dual Fuel (1 of 2 Stage Heat Pump + 1 or 2 Stage Gas/Oil Furnace ……………………………….. Option C. Page 4
5–32 Zones
System Type
- Stage Furnace + 1–2 Stage Cooling ………………………………………………………………………………..Option D. Page 4
- Single Stage Heat Pump + Electric Heat Strips for Auxiliary Heat ……………………………………Option D. Page 4
- Stage Heat Pump + Electric Heat Strips for Auxiliary Heat ……………………………………………..Option D. Page 4
Dual Fuel (1 of 2 Stage Heat Pump + 1 or 2 Stage Gas/Oil Furnace ………………………………..Option D. Page 4
Prestige Thermostats for All Zones
2–3 Zones
System Type
- Stage Furnace + 1–2 Stage Cooling ……………………………………………………………………………….. Option E. Page 6
- Single Stage Heat Pump + Electric Heat Strips for Auxiliary Heat …………………………………… Option E. Page 6
- Stage Heat Pump + Electric Heat Strips for Auxiliary Heat ………………………………………………Option F. Page 6
- Dual Fuel (1 of 2 Stage Heat Pump + 1 or 2 Stage Gas/Oil Furnace ………………………………..Option G. Page 6
4 Zones
System Type
- Stage Furnace + 1–2 Stage Cooling …………………………………………………………………………………Option F. Page 6
- Single Stage Heat Pump + Electric Heat Strips for Auxiliary Heat …………………………………….Option F. Page 6
- Stage Heat Pump + Electric Heat Strips for Auxiliary Heat ………………………………………………Option F. Page 6
- Dual Fuel (1 of 2 Stage Heat Pump + 1 or 2 Stage Gas/Oil Furnace ………………………………..Option G. Page 6
RedLINK VisionPRO Thermostats
- RedLINK VisionPRO Thermostats …………………………………………………………………………………………………………….. Page 8
- Zoning without IAQ Control ……………………………………………………………………………………………………………………….. Page 9
- EIM to Zone Panel Wiring Diagrams ……………………………………………………………………………………………………….Page 10
REDLINK® ZONING OPTIONS IAQ CONTROL FROM ZONE 1 STAT
Option A: 2–3 Zones
Table 1. 1–2 Stage Furnace + 1–2 Stage Cooling or Single Stage Heat-Pump +
Electric Heat-Strips for Auxiliary Heat. No Dual Fuel.
Parts list | Description | Quantity |
---|---|---|
1. HZ322K zone panel kit | Includes HZ322 zone panel, C7735A1000 discharge | |
sensor, and AT140A1042 transformer | 1 | |
2. YTHX9421R | Prestige IAQ kit with Thermostat & EIM. (Different kits can | |
also include accessories such as a RedLINK Internet gateway.) | 1 | |
3. YTH6320R1023 | Includes TH6320R1004 wireless programmable FocusPRO | |
thermostat and THM4000R1000 adapter | 1 | |
4. TH6320R1004 | Wireless thermostat for zone 3 _(not needed for 2 zone | |
system)_ | 0–1 | |
5. Appropriate zone dampers and by-pass damper for the application |
Option B: 2–4 Zones
Table 2. 1–3 Stage Furnace + 1–2 Stage Cooling, or 1–2 Stage Heat-Pump +
Electric Heat-Strips for Auxiliary Heat.
Parts list | Description | Quantity |
---|---|---|
1. HZ432K zone panel kit | Includes HZ432 zone panel, C7735A1000 discharge | |
sensor, and AT140A1042 transformer | 1 | |
2. YTHX9421R | Prestige IAQ kit with Thermostat & EIM. (Different kits can | |
also include accessories such as a RedLINK Internet gateway.) | 1 | |
3. YTH6320R1023 | Includes: TH6320R1004 wireless programmable FocusPRO | |
thermostat and THM4000R1000 adapter | 1 | |
4. TH6320R1004 | Wireless thermostats for zones 3 and 4 _(not needed for 2 | |
zone system)_ | 0–2 | |
5. Appropriate zone dampers and by-pass damper for the application |
Option C: 2–4 Zones
Table 3. Dual Fuel. 1–2 Stage Heat-Pump + 1–2 Stage Gas Furnace.
| |
---|---|---
Parts list| Description| Quantity
1. HZ432K zone panel kit| Includes: HZ432 zone panel, C7735A1000
discharge sensor, and AT140A1042| 1
2. YTHX9421R| Prestige IAQ kit with Thermostat & EIM. (Different kits can
also include accessories such| 1
3. YTH6320R1023| Includes: TH6320R1004 wireless programmable FocusPRO
thermostat and| 1
4. TH6320R1004| Wireless thermostats for zones 3 and 4 (not needed for 2
zone system)| 0–2
5. C7089R1013| Wireless outdoor sensor for dual fuel changeover| 1
See Fig. 1 below for basic wiring.
Fig. 1. Zoning with IAQ equipment.
- THE SUBBASE OF EACH THX9421R5021 THERMOSTAT NEEDS TO BE WIRED TO A 24 VOLT TRANSFORMER. THIS CAN EITHER BE THE TRANSFORMER THAT POWERS THE ZONE PANEL OR A SEPARATE TRANSFORMER.
- EIMS AND ADAPTORS NEED TO BE AT LEAST 2 FEET APART FROM EACH OTHER.
- THE SUPPLY AND RETURN SENSORS INCLUDED IN THE YTHX9421 2.0 PRESTIGE IAQ KITS ARE NOT USED IN ZONING APPLICATIONS. THE THERMOSTATS CANNOT BE SET FOR DELTA-T DIAGNOSTICS WHEN USED IN ZONING APPLICATIONS.
- WIRING FROM EIM TO CORRESPONDING ZONE DEPENDS ON EQUIPMENT CONTROLLED. SEE PAGE 10 FOR SYSTEM SPECIFIC WIRING.
Option D: More Than 4 Zones (Cannot use THM4000R Wireless Adapter)
Table 4. 1–3 Stage Furnace + 1–2 Stage Cooling, Heat-Pump with 1–2 Compressor Stages + Auxiliary Heat, or 1–2 Stage Heat-Pump + 1–2 Stage Gas Furnace (Dual Fuel).
See Fig. 2 below for basic wiring.
Fig. 2. More than 4 zones with Prestige on zone 1 and RedLINK FocusPRO for other zones.
- EIMS AND ADAPTORS NEED TO BE AT LEAST 2 FEET APART FROM EACH OTHER.
- THE SUPPLY AND RETURN SENSORS INCLUDED IN THE YTHX9421 2.0 PRESTIGE IAQ KITS ARE NOT USED IN ZONING APPLICATIONS. THE THERMOSTATS CANNOT BE SET FOR DELTA-T DIAGNOSTICS WHEN USED IN ZONING APPLICATIONS.
- WIRING FROM EIM TO CORRESPONDING ZONE DEPENDS ON EQUIPMENT CONTROLLED. SEE PAGE 10 FOR SYSTEM SPECIFIC WIRING.
- THE PRESTIGE EIM IS TYPICALLY WIRED TO ZONE 1. THIS DIAGRAM SHOWS IT GOING TO ZONE 4 TO SIMPLIFY THE LAYOUT OF THE DIAGRAM.
NO IAQ EQUIPMENT OR ECONOMIZER CONTROL
For any of the 2-4 zone applications listed in this document that do not need
to control a Humidifier, Dehumidifier, Ventilator, economizer, or Remote
Indoor Sensor, you can eliminate the THM5421R1021. You can either enroll the
Prestige IAQ thermostat to the THM4000R1000 wireless adapter that is included
in the YTH6320R1023 kit or use another TH6320R1004 thermostat for zone 1 in
place of the Prestige IAQ. When a TAZ-4H is used for systems over 4 zones, you
cannot use a THM4000R1000.
See Fig. 3 below for basic wiring. Fig. 3. No IAQ Equipment.
- EIMS AND ADAPTORS NEED TO BE AT LEAST 2 FEET APART FROM EACH OTHER.
- THE SUPPLY AND RETURN SENSORS INCLUDED IN THE YTHX9421 2.0 PRESTIGE IAQ KITS ARE NOT USED IN ZONING APPLICATIONS. THE THERMOSTATS CANNOT BE SET FOR DELTA-T DIAGNOSTICS WHEN USED IN ZONING APPLICATIONS.
- PRESTIGE IAQ THERMOSTATS USED WITH A THM4000R ADAPTOR AND THM6000R GATEWAY LOSE THE 2.0 FUNCTIONALITY ONLINE. THIS MEANS YOU WILL BE ABLE TO OVERRIDE THE SET POINT BUT CANNOT PROGRAM THEM OR CONTROL THE FAN SETTING VIA APP. ALSO THEY CANNOT BE USED IN A DEMAND RESPONSE UTILITY PROGRAM. ALSO, YOU CANNOT USE THOSE THERMOSTATS WITH AN R EM1000R1003 EXIT/ENTRY CONTROL OR WSK 24 REMOTE SETBACK.
REDLINK® ZONING OPTIONS
ALL PRESTIGE THERMOSTATS WITHOUT IAQ CONTROL
- Option E: 2–3 Zones (If C7189R or C7189U Indoor Sensors are Used, Cannot Use THM4000R. Need separate EIM for Each Stat).
Table 5. 1–2 Stage Furnace + 1–2 Stage Cooling or Single Stage Heat-Pump + Electric Heat-Strips for Auxiliary Heat. Not Dual Fuel.
Parts list | Description | Quantity |
---|---|---|
1. HZ322K zone panel kit | Includes: HZ322 zone panel, C7735A1000 | |
discharge sensor, and AT140A1042 transformer | 1 | |
2. YTHX9421R | Prestige IAQ kit with Thermostat & EIM for IAQ zone (usually |
zone 1). Different kits can also include accessories such as a RedLINK
Internet gateway| 1
3. THX9421R5021| Prestige without EIM for zones 2–3| 1–2
4. THM4000R1000| Wireless adapter for zone 2–3 Prestige IAQ thermostats not
controlling IAQ equipment or using an indoor sensor| 1
5. Appropriate zone dampers and by-pass damper for the application|
Option F: 2–4 Zones (If C7189R or C7189U Indoor Sensors are Used, Cannot Use THM4000R. Need Separate EIM for Each Stat).
Table 6. 1–3 Stage Furnace + 1–2 Stage Cooling, or 1–2 Stage Heat- Pump + Electric Heat-Strips for Auxiliary Heat.
Parts list | Description | Quantity |
---|---|---|
1. HZ432K zone panel kit | Includes: HZ432 zone panel, C7735A1000 | |
discharge sensor, and AT140A1042 transformer | 1 | |
2. YTHX9421R | Prestige IAQ kit with Thermostat & EIM for IAQ zone (usually |
zone 1). Different kits can also include accessories such as a RedLINK
Internet gateway| 1
3. THX9421R5021| Prestige without EIM for zones 2–4| 1–3
4. THM4000R1000| Wireless adapter for zone 2–4 Prestige IAQ thermostats not
controlling IAQ equipment or using an indoor sensor| 1
5. Appropriate zone dampers and by-pass damper for the application.|
- Option G: 2–4 Zones (If C7189R or C7189U Indoor Sensors are Used, Cannot Use THM4000R. Need Separate EIM for Each Stat).
Table 7. Dual Fuel. 1–2 Stage Heat-Pump + 1–2 Stage Gas Furnace.
Parts list | Description | Quantity |
---|---|---|
1. HZ432K zone panel kit. | Includes: HZ432 zone panel, C7735A1000 discharge | |
sensor, and AT140A1042 transformer | 1 | |
2. YTHX9421R | Prestige IAQ kit with Thermostat & EIM for IAQ zone (usually |
zone 1). Different kits can also include accessories such as a RedLINK
Internet gateway| 1
3. THX9421R5021| Prestige without EIM for zones 2–4| 1–3
4. THM4000R1000| Wireless adapter for zone 2-4 Prestige IAQ thermostats not
controlling IAQ equipment or using an indoor sensor| 1
5. C7089R1013| Wireless outdoor sensor| 1
6. Appropriate zone dampers and by-pass damper for the application|
See Fig. 4 below for basic wiring.
- THE SUBBASE OF EACH THX9421R5021 THERMOSTAT NEEDS TO BE WIRED TO A 24 VOLT TRANSFORMER. THIS CAN EITHER BE THE TRANSFORMER THAT POWERS THE ZONE PANEL OR A SEPARATE TRANSFORMER.
- EIMS AND ADAPTORS NEED TO BE AT LEAST 2 FEET APART FROM EACH OTHER.
- THE SUPPLY AND RETURN SENSORS INCLUDED IN THE YTHX9421 2.0 PRESTIGE IAQ KITS ARE NOT USED IN ZONING APPLICATIONS. THE THERMOSTATS CANNOT BE SET FOR DELTA-T DIAGNOSTICS WHEN USED IN ZONING APPLICATIONS.
- PRESTIGE IAQ THERMOSTATS USED WITH A THM4000R ADAPTOR AND THM6000R GATEWAY LOSE THE 2.0 FUNCTIONALITY ONLINE. THIS MEANS YOU WILL BE ABLE TO OVERRIDE THE SET POINT BUT CANNOT PROGRAM THEM OR CONTROL THE FAN SETTING VIA APP. ALSO THEY CANNOT BE USED IN A DEMAND RESPONSE UTILITY PROGRAM. ALSO YOU CANNOT USE THOSE THERMOSTATS WITH AN REM1000R1003 EXIT/ENTRY CONTROL OR WSK 24 REMOTE SETBACK.
- WIRING FROM EIM TO CORRESPONDING ZONE DEPENDS ON THE EQUIPMENT CONTROLLED. SEE PAGE 10 FOR SYSTEM SPECIFIC WIRING.
Fig. 4. Zoning with IAQ equipment (humidifier, dehumidifier, or ventilator).
Option H : More Than 4 zones (Cannot Use THM4000R Wireless Adapter)
Table 8. 1–3 Stage Furnace + 1–2 Stage Cooling, Heat-Pump with 1–2 Compressor Stages + Auxiliary Heat, or 1–2 Stage Heat-Pump + 1–2 Stage Gas Furnace (Dual Fuel).
RedLINK VisionPRO instead of Prestige
For any of the A–F applications listed, you could replace the Prestige IAQ
thermostats with TH8321R1001 RedLINK VisionPRO models. When the RedLINK
VisionPRO models are used, you can link to the THM5421R1021 or THM4000R1000
(same as Prestige) or wire directly from the thermostat sub-base to the zone
connection on the zone panel if wires are available.
See Fig. 5 below for basic wiring.
- THE SUBBASE OF EACH THX9421R5021 THERMOSTAT NEEDS TO BE WIRED TO A 24 VOLT TRANSFORMER. THIS CAN EITHER BE THE TRANSFORMER THAT POWERS THE ZONE PANEL OR A SEPARATE TRANSFORMER.
- EIMS NEED TO BE AT LEAST 2 FEET APART FROM EACH OTHER.
- THE SUPPLY AND RETURN SENSORS INCLUDED IN THE YTHX9421 2.0 PRESTIGE IAQ KITS ARE NOT USED IN ZONING APPLICATIONS. THE THERMOSTATS CANNOT BE SET FOR DELTA-T DIAGNOSTICS WHEN USED IN ZONING APPLICATIONS.
- WIRING FROM EIM TO CORRESPONDING ZONE DEPENDS ON EQUIPMENT CONTROLLED. SEE PAGE 10 FOR SYSTEM SPECIFIC WIRING.
Fig. 5. More than 4 zones with all Prestige.
No IAQ Equipment
Any of the above listed 2-4 zone applications that do not need to control a
Humidifier, Dehumidifier, Ventilator, Economizer or Remote Indoor Sensor can
eliminate the THM5421R1021. You can enroll all Prestige IAQ or RedLINK
VisionPRO thermostats to the THM4000R1000 wireless adapter. When a TAZ-4H is
used for systems over 4 zone you cannot use a THM4000R1000.
See Fig. 6 below for basic wiring.
- THE SUBBASE OF EACH THX9421R5021 THERMOSTAT NEEDS TO BE WIRED TO A 24 VOLT TRANSFORMER. THIS CAN EITHER BE THE TRANSFORMER THAT POWERS THE ZONE PANEL OR A SEPARATE TRANSFORMER.
- EIMS AND ADAPTORS NEED TO BE AT LEAST 2 FEET APART FROM EACH OTHER.
- THE SUPPLY AND RETURN SENSORS INCLUDED IN THE YTHX9421 2.0 PRESTIGE IAQ KITS ARE NOT USED IN ZONING APPLICATIONS. THE THERMOSTATS CANNOT BE SET FOR DELTA-T DIAGNOSTICS WHEN USED IN ZONING APPLICATIONS.
- PRESTIGE IAQ THERMOSTATS USED WITH A THM4000R ADAPTOR AND THM6000R GATEWAY LOSE THE 2.0 FUNCTIONALITY ONLINE. THIS MEANS YOU WILL BE ABLE TO OVERRIDE THE SET POINT BUT CANNOT PROGRAM THEM OR CONTROL THE FAN SETTING VIA APP. ALSO THEY CANNOT BE USED IN A DEMAND RESPONSE UTILITY PROGRAM. ALSO YOU CANNOT USE THOSE THERMOSTATS WITH AN REM1000R1003
- EXIT/ENTRY CONTROL OR WSK 24 REMOTE SETBACK.
Fig. 6. No IAQ equipment or remote indoor sensor.
EIM to Zone Panel Wiring Diagrams
- LEAVE R, Rc, Rh JUMPERS INSTALLED.
- DOTTED LINES FOR MULTI-STAGE ONLY.
Fig. 7. Gas furnace and AC.
- LEAVE R, Rc, Rh JUMPERS INSTALLED.
- ADD A JUMPER FROM W1/E TO W2 AT ZONE PANEL.
Fig. 8. Heat pump with 1-stage compressor and electric strips.
- LEAVE R, Rc, Rh JUMPERS INSTALLED.
- ADD A JUMPER FROM W1/E TO W3 AT ZONE PANEL.
Fig. 9. Heat pump with 2-stage compressor and electric strips.
- LEAVE R, RC, RH JUMPERS INSTALLED.
- DOTTED LINES FOR DOTTED LINES FOR 2-STAGE COMPRESSOR ONLY.
Fig. 10. Dual fuel heat pump.
To Learn More
For more information regarding zoning, contact
800-468-1502, or for technical
literature go to customer.resideo.com
Resideo Technologies, Inc.
- 1985 Douglas Drive North, Golden Valley, MN 55422 1-800-468-1502
- 33-00642—03 SA Rev. 05-23 | Printed in United States
- www.resideo.com
© 2023 Resideo Technologies, Inc. All rights reserved.
The Honeywell Home trademark is used under license from Honeywell
International, Inc. This product is manufactured by Resideo Technologies, Inc.
and its affiliates.
Honeywell Home RedLINK FocusPRO Thermostats User Manual
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>