bryant 361AAN Oil Fired Furnaces User Manual

June 13, 2024
bryant

361AAN Oil Fired Furnaces

Product Information

Product Name Oil-Fired Furnaces
Model Numbers 361AAN, 362AAN & 363AAP
Sizes 075 thru 210
Manufacturer Unknown
Product Type Oil Furnace
Installation Options Upflow, Horizontal Right, Horizontal Left
Heat Exchanger Warranty Limited Lifetime Warranty

Product Usage Instructions

The Oil-Fired Furnaces (Models 361AAN, 362AAN & 363AAP) are
designed to provide reliable and comfortable home heating. Follow
the instructions below for proper usage:

  1. Select the appropriate installation option: upflow, horizontal
    right, or horizontal left, based on your application
    requirements.

  2. Ensure proper ventilation for the flue, which exits the front
    of the furnace.

  3. Perform regular maintenance and cleaning of the secondary heat
    exchanger tubes. Cleanout ports are provided for easy access.

  4. Make sure the Beckett oil burner is equipped with an electronic
    primary relay for added reliability.

  5. Install the integrated fan timer control board with low-voltage
    terminal strip and 40-va transformer for easy air conditioning
    installation.

  6. Utilize the heavy-duty blower with PSC type and 3-speed motors.
    The direct-drive blowers eliminate belt adjustments in the field.
    The constant low-speed blower switch provides air circulation
    during off cycles for indoor air filtration.

  7. Maintain the durable prepainted steel casing for long-lasting
    attractiveness.

  8. Replace the filter regularly to ensure efficient operation.
    Filter and filter rack are provided with each furnace.

Please refer to the product specifications for more detailed
information on unit sizes, ratings, performance, electrical
requirements, and blower data.

OIL-FIRED FURNACES

361AAN, 362AAN & 363AAP
Sizes 075 thru 210

AN IND FETY

ATORY TESTI

EPENDENT LABOR
®
NG FOR PUBLIC SA

361AAN Upflow/Horizontal

ama

362AAN Low-Boy

363AAP Upflow/Horizontal (Large Capacity)

Search

Form No. PDS 361A.75.2

MODEL 361AAN UPFLOW-HORIZONTAL OIL FURNACE

A93211

The 361AAN Furnace is designed for top performance to provide years of reliable, comfortable home heating.
The 361AAN is an upflow/horizontal oil furnace that can be installed upflow, horizontal right, or horizontal left for greater application coverage. The flue exits the front of the furnace. The heat exchanger is backed by a Limited Lifetime Warranty.
FEATURES
INSTALLATION FLEXIBILITY–The 361AAN installs in upflow, horizontal right, or horizontal left positions for greater application coverage and installation flexibility.
HEAT EXCHANGER–The stainless steel primary and aluminized steel secondary heat exchangers are designed for outstanding reliability backed by a Limited Lifetime Warranty. The heat exchanger utilizes crimped seams instead of welds for corrosion resistance. All internal surfaces are accessible for any field maintenance without removing the heat exchanger.
CLEANOUT PORTS–Allow easy cleaning of secondary heat exchanger tubes without disassembly of the furnace or heat exchanger.
CONTROLS–The Beckett oil burner is equipped with an electronic primary relay for added reliability. Integrated fan timer control board with low-voltage terminal strip and 40-va transformer make air conditioning installation easy.
HEAVY DUTY BLOWER–Blower motors are PSC type and 3 speed. The directdrive blowers eliminate belt adjustments in the field. The constant low-speed blower switch provides air circulation during “off” cycles for indoor air filtration.
DURABLE CABINET–The casing is constructed of prepainted steel for years of attractiveness. Filter and filter rack are provided with each furnace.

SPECIFICATIONS

UNIT SIZE

RATINGS AND PERFORMANCE

Firing Rate

Input (Btuh)

Heating Capacity (Btuh)*

AFUE %*

ICS

Oil Pump Stages

Heating Temperature Rise °F

Recommended Heating Blower Speed

Cooling CFM @ 0.5-in. wc Static Pressure

Heating CFM @ 0.2-in. wc Static Pressure

ELECTRICAL

Unit Volts–Hertz–Phase

Operating Voltage Range

Rated Load Amps

Minimum Ampacity for Wire Sizing

Minimum Wire Size AWG

Maximum Wire Length (Ft)

Maximum Fuse Size (Amps)**

Control Transformer (24v)

External Control Power Available

Heating

Cooling

Burner Model (3450 RPM)

BLOWER DATA

Motor HP

Blower Wheel Size (In.)

Blower Motor Speed and Type

Filter Quantity and Size

036075

036105

048125

060155

0.50 72,000 55,000
80.0
Low 1255
850

0.76 105,000
85,000 80.7
Medium 1365 1425

1 55–85

0.90 125,000 100,000
81.5
Medium 1745 1645

1.12 154,000 125,000
80.3
High 1935 2170

12.55 14 14 26 15

12.55 14 14 26 15

115–60–1 104–127
40va 35va 35va Beckett AFG

15.65 18 12 32 20

16.15 19 12 30 20

1/3

1/3

1/2

3/4

10 x 9

10 x 9

12 x 9

12 x 12

1075 PSC Direct

(1) 20-1/8 x 25 x 1

(1) 20-1/8 x 30 x 1

  • Capacity and AFUE in accordance with U.S. Government DOE test procedures. Permissible limits of the voltage range at which the unit will operate satisfactorily. Length shown is measured 1 way along wire path between unit and service panel for maximum 2% voltage drop. ** Time-delay fuse is recommended. ICS–Isolated Combustion System

–2–

Search

DIMENSIONS–MODEL 361AAN

M

SIDE RETURN AIR DUCT

F
A D

E B

ALTERNATE OIL INLET THROUGH SLOTS

KNOCK-OUT BOTH SIDES FOR SIDE FLUE

B

1

12 1/16

E

SIDE RETURN AIR DUCT
L

CLEANOUT PORTS
C

4 3 1/16

2

21 9/16 13 9/16

2 9/16
H

OIL INLET 7/8-IN. DIA (2 PLACES) BOTH SIDES

ELECTRICAL CONNECTIONS (TOP) 1/2-IN. DIA BOTH SIDES (BOTTOM) 7/8-IN. DIA BOTH SIDES

G 1

J

11 15/16

K

1

END RETURN

AIR DUCT

N

P

DIMENSIONS (In.)

UNIT SIZE

UNIT DIMENSIONS

DUCT SUPPLY FLUE SIDE RETURN

SHIP. WIDTH DEPTH HEIGHT OPENING DIAMETER OPENING*

WT (Lb) A

B

C

D

E

F

G

H

END (BOTTOM) RETURN OPENING

J

K

SIDE RETURN DUCT SIZE

L

M

036075 215

22 30-1/2 48

20

17

6

15 25-1/4 20-1/8 17-1/16 18-1/4 25-1/4

036105 228

22 30-1/2 48

20

17

6

15 25-1/4 20-1/8 17-1/16 18-1/4 25-1/4

048125 254

22 35-1/2 48

20

22

6

15 30-1/4 20-1/8 22-1/16 18-1/4 30-1/4

060155 265

22 35-1/2 48

20

22

6

15 30-1/4 20-1/8 22-1/16 18-1/4 30-1/4

  • Filter rack provides transition from duct size to opening size. Duct sizes are ID dimensions for slipping over filter rack. Outlet of heat exchanger and elbow shipped with furnace is 6 in. Flue pipe may be reduced to 5-in. diameter for vent sizing.

A96306

END (BOTTOM) RETURN DUCT
SIZE

N

P

20-1/4 25-1/4

20-1/4 25-1/4

20-1/4 30-1/4

20-1/4 30-1/4

MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS (In.)

UNIT APPLICATION SIDES–Furnace
Supply Plenum and Warm-Air Duct Within 6 ft of Furnace BACK TOP– Furnace Casing or Plenum
Horizontal Warm-Air Duct Within 6 ft of Furnace BOTTOM FLUE PIPE– Horizontally or Below Pipe
Vertically Above Pipe FRONT

UPFLOW 0 1 0 2 2 0* 4 8 8

  • Floor may be combustible.

AIR DELIVERY–CFM (Without Filters)

HORIZONTAL 2 1 0 2 3 0* 4 8 24

UNIT SIZE 036075
036105
048125
060155

BLOWER MOTOR
HP 1/3 PSC
1/3 PSC
1/2 PSC
3/4 PSC

SPEED High
Medium Low High
Medium Low High
Medium Low High
Medium Low

0.1 1530 1240
870 1635 1470 1280 1965 1695 1340 2240 2000 1535

0.2 1475 1200
850 1560 1425 1245 1915 1645 1330 2170 1965 1495

0.3 1410 1150
830 1500 1365 1205 1865 1615 1320 2085 1890 1450

EXTERNAL STATIC PRESSURE IN. WC

0.4

0.5

0.6

0.7

1340

1255

1170

1075

1110

1065

1000

920

805

765

720

660

1425

1365

1260

1165

1290

1220

1140

1030

1145

1085

1010

935

1805

1745

1665

1590

1565

1530

1465

1410

1290

1270

1215

1180

1980

1935

1820

1750

1795

1755

1690

1625

1420

1365

1330

1275

–3–

0.8 970 830 590 1040 935 835 1515 1335 1125 1665 1555 1205

0.9 855 705 480 945 825 710 1445 1255 1045 1590 1480 1125

1.0 705 555 360 785 695 590 1345 1165 990 1510 1375 1035

Search

MODEL 362AAN LOW-BOY OIL FURNACE

A96358

The 362AAN Furnace is designed for top performance to provide years of reliable, comfortable home heating.
The 362AAN is a Low-Boy style oil furnace that can be installed in limited overhead areas for greater application coverage. The heat exchanger is backed by a Limited Lifetime Warranty.
FEATURES
LOW-BOY CABINET STYLE–The 362AAN allows easy installation in low overhead areas such as crawlspaces and sub-basements.
HEAT EXCHANGER–The stainless steel primary and aluminized steel secondary heat exchangers are designed for outstanding reliability backed by a Limited Lifetime Warranty. The heat exchanger utilizes crimped seams instead of welds for corrosion resistance. All internal surfaces are accessible for any field maintenance without removing the heat exchanger.
CLEANOUT PORTS–Allow easy cleaning of secondary heat exchanger tubes without disassembly of the furnace or heat exchanger.
CONTROLS–The Beckett oil burner is equipped with an electronic primary relay for added reliability. Integrated fan timer control board with low-voltage terminal strip and 40-va transformer make air conditioning installation easy.
HEAVY DUTY BLOWER–Blower motors are PSC type and 3 speed. The directdrive blowers eliminate belt adjustments in the field. The constant low-speed blower switch provides air circulation during “off” cycles for indoor air filtration.
DURABLE CABINET–The casing is constructed of prepainted steel for years of attractiveness. Filter provided with each furnace.

UNIT SIZE

RATINGS AND PERFORMANCE

Firing Rate

Input (Btuh)

Heating Capacity (Btuh)*

AFUE %*

ICS

Oil Pump Stages

Heating Temperature Rise °F

Recommended Heating Blower Speed

Cooling CFM @ 0.5-in. wc Static Pressure

Heating CFM @ 0.2-in. wc Static Pressure

ELECTRICAL

Unit Volts–Hertz–Phase

Operating Voltage Range

Rated Load Amps

Minimum Ampacity for Wire Sizing

Minimum Wire Size AWG

Maximum Wire Length (Ft)

Maximum Fuse Size (Amps)**

Control Transformer (24v)

External Control Power Available

Heating

Cooling

Burner Model (3450 RPM)

BLOWER DATA

Motor HP

Blower Wheel Size (In.)

Blower Motor Speed and Type

Filter Quantity and Size

036105 0.76
105,000 85,000
80.3
Medium 1550 1335
12.55 14 14 26 15
1/3 12 x 9

048125
0.90 125,000 100,000
82.5 1
55–85 Medium
1630 1675
115–60–1 104–127
15.65 18 12 32 20
40va 35va 35va Beckett AFG
1/2 12 x 9 1075 PSC Direct (1) 21-1/4 x 21-1/4 x 1

  • Capacity and AFUE in accordance with U.S. Government DOE test procedures. Permissible limits of the voltage range at which the unit will operate satisfactorily. Length shown is measured 1 way along wire path between unit and service panel for maximum 2% voltage drop. ** Time-delay fuse is recommended. ICS–Isolated Combustion System

060155 1.12
154,000 125,000
81.0
High 1800 1960
16.15 19 12 30 20
3/4 12 x 12

–4–

Search

DIMENSIONS–MODEL 362AAN
G
CLEAN-OUT PORTS
B

SUPPLY DUCT

RETURN DUCT

A D

12 1/16

E

3

H

1

ELECTRICAL CONNECTIONS
C

INSULATION PARTITION PANEL
FILTER

OIL INLET

INSULATION INTERMEDIATE PANEL

1
F

A96309

DIMENSIONS (In.)

UNIT DIMENSIONS

UNIT SIZE

SHIP. WT (Lb)

WIDTH A

DEPTH B

HEIGHT C

DUCT SUPPLY OPENING

D

E

036105

248

22

52

33

20

17-1/4

048125

269

22

57

33

20

22-1/4

060155

278

22

57

33

20

22-1/4

*Flue pipe may be reduced to 5-in. diameter on 105 and 125 sizes for vent sizing.

FLUE DIAMETER
F 6 6 6*

RETURN DUCT

G

H

20

18

20

18

20

18

MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS (In.)

UNIT APPLICATION SIDES–Furnace
Supply Plenum and Warm-Air Duct Within 6 ft of Furnace BACK TOP– Furnace Casing or Plenum
Horizontal Warm-Air Duct Within 6 ft of Furnace BOTTOM FLUE PIPE– Horizontally or Below Pipe
Vertically Above Pipe FRONT

LOW-BOY 0 1 0 2 2 0* 4 8 8

  • Floor may be combustible.

UNIT SIZE 036105
048125
060155

BLOWER MOTOR
HP 1/3 PSC
1/2 PSC
3/4 PSC

SPEED High
Medium Low High
Medium Low High
Medium Low

0.1 1795 1365
995 1905 1750 1390 2025 1885 1555

AIR DELIVERY–CFM (Without Filters)

0.2 1735 1335
965 1845 1675 1350 1960 1825 1490

0.3 1675 1305
945 1770 1620 1305 1905 1760 1445

EXTERNAL STATIC PRESSURE IN. WC

0.4

0.5

0.6

0.7

1605

1550

1485

1425

1275

1255

1215

1155

925

900

870

825

1695

1630

1565

1490

1560

1500

1440

1370

1260

1220

1180

1120

1850

1800

1655

1575

1705

1640

1565

1500

1410

1350

1280

1230

0.8 1350 1105
775 1425 1305 1060 1500 1430 1155

0.9 1275 1050
725 1325 1235
985 1415 1350 1085

1.0 1220
985 670 1220 1130 880 1315 1265 1005

–5–

Search

MODEL 363AAP UPFLOW/HORIZONTAL OIL FURNACE

A93213

The 363AAP Furnace is designed for top performance to provide years of reliable, comfortable home heating. This furnace is also designed to meet the need for large residential and light commercial markets.
The 363AAP is a large capacity upflow/horizontal oil furnace that can be installed upflow, horizontal right, or horizontal left for greater application coverage. The flue exits the rear of the furnace. The heat exchanger is backed by a Limited Lifetime Warranty.
FEATURES
INSTALLATION FLEXIBILITY–The 363AAP installs in either upflow, horizontal right, or horizontal left orientation for greater application coverage and installation flexibility.
HEAT EXCHANGER–The stainless steel primary and aluminized steel secondary heat exchangers are designed for outstanding reliability backed by a Limited Lifetime Warranty. The heat exchanger utilizes crimped seams instead of welds for corrosion resistance. All internal surfaces are accessible for any field maintenance without removing the heat exchanger.
CONTROLS–The Beckett oil burner is equipped with an electronic primary relay for added reliability. Integrated fan timer control board with low-voltage terminal strip and 40-va transformer make air conditioning installation easy.
HEAVY DUTY BLOWER–Blower motors are PSC type and 3 speed. The directdrive blowers eliminate belt adjustments in the field. The constant low-speed blower switch provides air circulation during “off” cycles for indoor air filtration.
DURABLE CABINET–The casing is constructed of prepainted steel for years of attractiveness. Filter and frame are provided with each furnace.

UNIT SIZE

RATINGS AND PERFORMANCE

Firing Rate

Input (Btuh)

Heating Capacity (Btuh)*

AFUE %*

ICS

Oil Pump Stages

Heating Temp Rise °F

Recommended Heating Blower Speed

Cooling CFM @ 0.5-in. wc Static Pressure

Heating CFM @ 0.2-in. wc Static Pressure

ELECTRICAL

Unit Volts–Hertz–Phase

Operating Voltage Range

Rated Load Amps

Minimum Ampacity for Wire Sizing

Minimum Wire Size AWG

Maximum Wire Length (Ft)

Maximum Fuse Size (Amps)**

Control Transformer (24v)

External Control Power Available

Heating

Cooling

Burner Model (3450 RPM)

BLOWER DATA

Motor HP

Blower Wheel Size (In.)

Blower Motor Speed and Type

Filter Quantity and Size

060210
1.50 210,000 170,000
81.2 2
70–100 Medium
2145 2125
115–60–1 104–127
16.15 19 12 30 20
40va 35va 35va Beckett AFG
3/4 12 x 12 1075 PSC Direct (1) 24-1/2 x 38-1/4 x 1

  • Capacity and AFUE in accordance with U.S. Government DOE test procedures. Permissible limits of the voltage range at which the unit will operate satisfactorily. Length shown is measured 1 way along wire path between unit and service panel for maximum 2% voltage drop. ** Time-delay fuse is recommended. ICS–Isolated Combustion System

–6–

Search

DIMENSIONS–MODEL 363AAP

CLEANOUT PORTS

CLEANOUT PORTS

M

E

B
ALTERNATE OIL INLET THROUGH SLOTS

A D
SIDE RETURN AIR DUCT
L CONTROL BOX J
N

1

12 1/16

C

B E

REAR VIEW FLUE DIAMETER F

CLEANOUT PORTS
OIL INLET 3/8 IN. DIA (2 PLCS) BOTH SIDES ELECTRICAL CONNECTIONS (TOP) 1/2 IN. DIA BOTH SIDES (BOTTOM) 7/8 IN. DIA BOTH SIDES

H

11 15/16

K

END

RETURN AIR DUCT

P

G 1
2

A96336

DIMENSIONS (In.)

UNIT SIZE

SHIP WT (Lb)

UNIT DIMENSIONS

DUCT SUPPLY FLUE SIDE RETURN

WIDTH DEPTH HEIGHT OPENING DIAMETER OPENING*

A

B

C

D

E

F

G

H

060210 385

26 42-1/2 54-3/4 24

29

7

17-3/4 37-1/4

*Filter rack provides transition from duct to opening size. Duct sizes are ID dimensions for slipping over filter rack.

END (BOTTOM) RETURN OPENING

J

K

24-1/8 29-1/16

SIDE RETURN DUCT SIZE

L

M

20-1/4 38-1/4

END (BOTTOM) RETURN
DUCT SIZE

N

P

24-1/4 38-1/4

MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS (In.)

UNIT APPLICATION SIDES–Furnace
Supply Plenum and Warm-Air Duct Within 6 ft of Furnace BACK TOP– Furnace Casing or Plenum
Horizontal Warm-Air Duct Within 6 ft of Furnace BOTTOM FLUE PIPE– Horizontally or Below Pipe
Vertically Above Pipe FRONT

  • Floor may be combustible.

UPFLOW 2 1 2 2 2 0* 9 9 24

HORIZONTAL 2 1 2 2 3 0* 9 9 24

UNIT SIZE
060210

BLOWER MOTOR
HP
3/4 PSC

SPEED High
Medium Low

0.1 2485 2195 1640

AIR DELIVERY–CFM (Without Filters)

0.2 2395 2125 1590

0.3 2305 2060 1540

EXTERNAL STATIC PRESSURE IN. WC

0.4

0.5

0.6

0.7

2250

2145

2075

1975

1990

1915

1860

1785

1515

1460

1410

1350

0.8 1885 1700 1275

0.9 1780 1620 1190

1.0 1675 1525 1075

–7–

Search

SERVICE TRAINING

Packaged Service Training programs are an excellent way to increase your

knowledge of the equipment discussed in this manual, including:

· Unit Familiarization

· Maintenance

· Installation Overview

· Operating Sequence

A large selection of product, theory, and skills programs is available, using popular

video-based formats and materials. All include video and/or slides, plus companion

book.

Classroom Service Training plus “hands-on” the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting, fewer callbacks. Course descriptions and schedules are in our catalog.

CALL FOR FREE CATALOG 1-800-962-9212

[ ] Packaged Service Training [ ] Classroom Service Training

A94328

© 1997 Bryant Heating & Cooling Systems, 7310 W. Morris St., Indpls., IN 46231

–8–

Search

SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: PDS 361A.75.1B
PRINTED IN U.S.A. Catalog No. 5236-100 8-97

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>