RMDT UNIRAC Code Compliant Construction Drawings For Project Installation Guide

June 13, 2024
UNIRAC

RMDT UNIRAC Code Compliant Construction Drawings For Project

RMDT-UNIRAC-Code-Compliant-Construction-Drawings-For-Project-
PRODUCT

GENERAL NOTES

  • If provided refer to construction drawings for project specific details.
  • Construction drawings have precedence over these installation guidelines.

TECHNICAL SPECIFICATIONS

  • Material Types: 16G ASTM A653 GR50 Steel
  • Coating(s): G235 Galvanization, G180 Galvanization,
  • G40 Galvinization + InterCoat® ChemGuard,
  • G60 Galvinization + InterCoat® ChemGuard or
  • G80 Galvinization + InterCoat® ChemGuard
  • Hardware: Stainless Steel
  • Bonding and Grounding: UL2703 Listed Continuous Bonding Path.

TOOLS REQUIRED OR RECOMMENDED FOR LAYOUT, ATTACHMENTS & INSTALLATION

  • Drill (Do Not Use An Impact Driver)
  • 7/16” Socket
  • Torque Wrench
  • Tape Measure
  • Chalk Reel
  • Optional Spacers (See Diagram – Page Right)

GENERAL HARDWARE

  • ¼-20 X 2 ½” Hex Head Bolt – Module Clamps
  • ¼-20 Stainless Steel U-Nuts

SAFETY

  • All applicable OSHA safety guidelines should be observed when working on a PV installation job site.
  • The installation and handling of PV solar modules, electrical installation and PV racking systems involves handling components with potentially sharp metal edges. Rules regarding the use of gloves and other personal protective equipment should be observed.

LAYOUT ASSISTANCE TOOL

RMDT-UNIRAC-Code-Compliant-Construction-Drawings-For-Project-
FIG-1RMDT-UNIRAC-Code-
Compliant-Construction-Drawings-For-Project-FIG-2

SYSTEM COMPONENTS

BALLAST BAY: The Ballast Bay is constructed of a high strength low alloy steel with a coating to protect against corrosion. This system has a modular design that allows for easy installation around roof obstructions and accommodates roof undulations. The Ballast Bays are designed to nest within each other to optimize shipping logistics. NOTE: Systems installed on PVC roofs require ballast bays with pre- installed Santoprene pads.

CLAMP & HARDWARE: The Module Clamp is made of Stainless Steel and can be used with module frame heights indicated on the clamp. The clamps are a portion of the UL2703 Listed system when installed according to this installation guide. A ¼-20 stainless steel bolt and u-nut are the associated hardware for installing clamps.

RIDGE BALLAST BLOCK: The Ridge ballast bay can fi t up to 5 standard 4”x8”x16” solid concrete cap blocks. Block weight can range from 26 – 38 lbs and shall meet ASTM C1491 requirements for freeze thaw durability. Verify your block weights before using the Unirac U-builder online design tool

VALLEY BALLAST BLOCK: The Valley ballast bay can fi t up to 2 standard 4”x8”x16” solid concrete cap blocks. Block weight can range from 26 – 38 lbs and shall meet ASTM C1491 requirements for freeze thaw durability. Verify your block weights before using the Unirac U-builder online design tool.

OPTIONAL WIRE MANAGEMENT: Custom Unirac wire clip along with mounting options for various off the shelf wire management clips.
NOTE: All conduit and wire ways should be grounded & bonded per the (NEC) National Electric Code.

OPTIONAL MICROINVERTER MOUNTING: Microinverter / Power optimizer bracket, see page 10 for additional instructions.

PART NUMBER DATA

S.No. Part Number Part Description
1 310801 RMDT RIDGE BAY
2 310802 RMDT VALLEY BAY
3 310804 RMDT RIDGE BAY, PVC
4 310805 RMDT VALLEY BAY, PVC
5 310823 RMDT MIDCLAMP 46-50MM
6 310824 RMDT MIDCLAMP 41-45MM
7 310825 RMDT MIDCLAMP 36-40MM
8 310826 RMDT MIDCLAMP 32-35MM
9 310820 RM5/DT ENDCLAMP 30-40MM
10 310821 RM5/DT ENDCLAMP 41-45MM
11 310822 RM5/DT ENDCLAMP 46-50MM
12 310850 RM5/DT WIRE MGMT CLIP
13 310851 RM5 WD WIRE MGMT CLIP
14 310860 RM5/DT 1/4-20 CLIP U-NUT SS18-8
15 310882 RM5/DT H-ATTACHMENT KIT
16 008114M MLPE MOUNT ASSY
17 205000S ENPHASE ENGAGE CABLE CLIP
18 008002S GROUND WEEBLUG #1
19 008009P ILSCO LAY IN LUG (GBL4DBT)
20 310999 FLASHLOC RM KIT

LOCATE ARRAY & PLACE BAYS

RMDT-UNIRAC-Code-Compliant-Construction-Drawings-For-Project-
FIG-9

SNAP WEST PERIMETER CHALK LINE, THEN NORTH OR SOUTH PERIMETER CHALK LINE. As best practice, mark lines on perimeter chalk lines to locate center of bays
PLACE WEST PERIMETER BAYS FIRST, THEN NORTH OR SOUTH PERIMETER BAYS. If slip sheets are required, place per manufacturer recommendations.
NOTE: Custom spacers can be made to aid in the placement of bays on the roof. See page 1

FILL IN BAYS

INSTALL U-NUT It is recommended to install u-nuts prior to placing ballast blocks & modules on the bays.
NOTE: U-NUT – Single Use Only – Do not re-torque once fully seated
NOTE: If mechanical attachment is required, place prior to installation of modules.

PLACE ALL BALLAST: A maximum of 2 ballasts can be placed in valley bay, and up to 5 ballasts can be placed in the ridge. Site specific ballast calculations should be created for each individual project in accordance with the U-Builder design software. This system has been rated for the mechanical load provisions of UL2703. In addition, it has been designed and tested to comply with the more rigorous requirements of SEAOC PV1, PV2 and ASCE 7.

RMDT-UNIRAC-Code-Compliant-Construction-Drawings-For-Project-
FIG-12

VALLEY BALLAST BLOCK OPTIONS: RIDGE BALLAST BLOCK OPTIONS

RMDT-UNIRAC-Code-Compliant-Construction-Drawings-For-Project-
FIG-12

MODULE PLACEMENT & ATTACH CLAMPS

WESTERN EDGE MODULE PLACEMENT. Tabs on valley and ridge bay provide mechanical stop and aid in proper spacing at ridge. Rows of modules must be wired together at this time. See page 8 for wire management options.
NOTE: Modules may be placed on bays without immediate installation of clamps. Column Spacing: 1 inch maximum gap between modules / ¼ inch minimum gap between modules.

EAST OR WEST EDGE MODULE PLACEMENT. Rows of modules must be wired together at this time. See page 8 for wire management options.
NOTE: Clamps should be installed for each East/West pair of rows after wiring has been completed.
NOTE: Wiring, wire management, and electrical QC should be done as each row is built.

INSTALL CLAMPS
NOTE: U-NUT – Single Use Only – Do not re-torque once fully seated
NOTE: CLAMP AND BOLT – Single Use Only – Do not re-torque once fully seated TORQUE VALUE: 7FT-LBS to achieve UL2703 required clamp load

PROPER VALLEY BAY ORIENTATION AT EAST AND WEST PERIMETERS

  • Valley bays are designed to tuck up underneath the modules for east and west perimeters
  • Bent tabs on all mounting surfaces act as a mechanical stop for the modules

PROPER INTER-ROW SPACING

  • Inter row spacing at the valley is designed to provide an 8” space for walkways
  • Bent tabs on all mounting surfaces act as a mechanical stop for the modules

CLOSE UP MOUNTING AT RIDGE

  • Bent tabs on the mounting surfaces aid in setting the correct gap between modules at the ridge

PROPER MID CLAMP INSTALLATION

  • The top of the clamp is stamped for module frame height.
  • Clamp should be firmly held against module frame while being torqued.

PROBLEM – CLAMP NOT ORIENTED CORRECTLY

PROBLEM – NOT USING PROPER SIZE OF CLAMP FOR MODULE FRAME HEIGHT

  • Double check the stamping on clamp to use the correct leg of clamp for module frame height
  • The module height shall fall within the range shown on the top of the clamp

PROPER CLAMP INSTALLATION

  • Clamp is stamped for module frame height on each leg
  • Clamp should be firmly held against module frame while being torqued

PROBLEM – CLAMP NOT SEATED AGAINST MODULE DURING TORQUING

  • Clamp needs to be held securely against the module frame during torquing for proper installation

PROBLEM – NOT USING PROPER SIZE OF CLAMP FOR MODULE FRAME HEIGHT

  • Double check the stamping on clamp to use the correct leg of clamp for module frame height
  • The module height shall fall within the range shown on the top of the clamp
  • Excessive angle on clamp will inhibit required clamp load on module

MODULE INSTALLATION & WIRE MGNT

FILL IN ALL MODULES. Wire each row as modules are installed, and secure the modules in place after each east/west row pair is complete.

RMDT-UNIRAC-Code-Compliant-Construction-Drawings-For-Project-
FIG-26

WIRE MANAGEMENT: Unirac provides a custom clip for wire management.
Additional holes are included in the bay to accommodate other off the shelf wire management clips.

RMDT-UNIRAC-Code-Compliant-Construction-Drawings-For-Project-
FIG-27

WIRE MANAGEMENT OPTION 1: Wire and bundle all east facing modules, run east facing bundle down north perimeter (or south perimeter) and vice versa for all west facing modules

RMDT-UNIRAC-Code-Compliant-Construction-Drawings-For-Project-
FIG-28

WIRE MANAGEMENT OPTION 2: Wire and bundle all east facing modules, wire and bundle all west facing modules. Run bundles along north or south perimeter

RMDT-UNIRAC-Code-Compliant-Construction-Drawings-For-Project-
FIG-29

BALLAST BAY ROOF ATTACHMENT

STEP 1 – POSITION U-ANCHOR
Position U-Anchor under bay requiring attachment and install according to manufacturer installation instructions.
NOTE: Position attachment so that it is close to center of the bay as possible.

PLACE NUT AND WASHER: Include the nut and washer on the anchor stud prior to placing the stud through the strut.

STEP – 3 PLACE H-STRUT: Position H-strut sections on bay as pictured above. Align the cross-strut with the anchor’s stud. Connect side strut sections to cross strut using a strutnut, bolt, and washer as pictured.

STEP 4 – SECURE H-STRUT TO
U-ANCHOR: Place 3/8” washer and 3/8-16 serrated flange nut on anchor stud, serrations facing down and tighten to 30 ft-lb.
TORQUE VALUE: 30FT-LBS

MICROINVERTER INSTALL & WIRE MGMT

RMDT-UNIRAC-Code-Compliant-Construction-Drawings-For-Project-
FIG-34

PRE-INSTALL MICROINVERTERS: Install MLPE in a location on the module that will not interfere with ballast bays or grounding lugs. To use trunk cable most effi ciently, install MLPE components in the same locations on all modules in the same row. TORQUE VALUE: 20FT-LBS

GROUNDING LUG MOUNTING DETAILS AS REQUIRED BY CODE & ENGINEER OF RECORD: The Ilsco
lug has a green colored set screw for grounding indication purposes. One lug is recommended per continuous array, not to exceed 150ft X 150ft. Unirac ROOFMOUNT is intended to be used with PV modules that have a system voltage less than or equal to that allowable by the National Electric Code (NEC). It is the installer’s responsibility to check adherence to local codes.
NOTE: The installation must be conducted in accordance with the National Electric Code ANSI / NFPA 70.

Ground Lug Bolt Size Torque Value
Ilsco Lug SGB-4 1/4″-20 6.5 ft-lbs (75 in-lbs)
Ilsco Lug GBL-4 #10-32 2.9 ft-lbs (35 in-lbs)
Wiley 6.7 1/4″-20 10 ft-lbs (120 in-lbs)

NOTE: In order to prevent corrosion induced by dissimilar metals, it is important to verify that the bare copper wire does not come into contact with aluminum or galvanized steel. These materials must be kept separate.
Although conformance with UL2703 was demonstrated without the use of oxide inhibitor material, it is recommended by Ilsco to provide an optimized bonding solution for their lay-in lug.

RMDT-UNIRAC-Code-Compliant-Construction-Drawings-For-Project-
FIG-36

BONDING & GROUNDING ELECTRICAL DIAGRAM

Note
In order to avoid the need for utilizing bonding jumpers during maintenance or module removal do not attach the groung lug to a:

  1. valley bay with less than two modules
  2. ridge bay with less than three modules

RMDT-UNIRAC-Code-Compliant-Construction-Drawings-For-Project-
FIG-37

TEMPORARY BONDING PROCEDURES

TEMPORARY GROUNDING & BONDING PROCEDURE: Periodic inspections should be conducted on the PV array to ensure there are not loose components, loose fasteners or corrosion. If any of the above items are found, the affected components are to be immediately replaced. NOTE

  • If a module must be removed or replaced, a temporary bonding jumper must be used to ensure safety of the personnel and PV system.
  • Removing a PV module from a system is not considered to be routine maintenance. This type of activity should only be performed by trained and qualifi ed installers. • In order to prevent corrosion induced by dissimilar metals, it is important to verify that the bare copper wire
    does not come into contact with aluminum or galvanized steel. These materials must be kept separate.

BONDING JUMPER REQUIRED: One example of a module removal that will require the use of a bonding jumper

APPROVED LUGS and Terminal Torque

ATTACH LUGS: Use approved lug(s) to install on adjacent bays where the module is being removed.

INSERT COPPER WIRE: Insert bare copper wire into each lug, providing a bonding jumper across the missing module location. Remove module & reverse the operation after maintenance is complete

BONDING JUMPER NOT REQUIRED , due to integrated bonding/grounding path throughout module frames/ bays around this location.
NOTE: CLAMP AND BOLT – Single Use Only – Use new clamps after any module replacements or system maintenance.

SYSTEM LEVEL FIRE CODE COMPLIANCE

SYSTEM LEVEL FIRE CLASSIFICATION: The system fire class rating is only valid when the installation is conducted in accordance with the assembly instructions contained in this manual. RM ROOFMOUNT has been classified to the system level fire portion of UL2703. It has achieved Class A performance for low sloped roofs when used in conjunction with type 1, 2, 29 and 30 module constructions. Please see the specific conditions below for mounting details required to maintain the Class A fire rating. Minimum and maximum roof slopes are restricted through the system design and layout rules. The fire classification rating is only valid on roof pitches less than 2:12 (slopes < 2 inches per foot, or 9.5 degrees).

NOTE: Type 1, 2, 29, and 30 information is generally located on back of modules or through manufacturers documentation. Some building codes and fire codes require minimum clearances around such installations, and the installer should check local building code requirements for compliance.

Module Type System level Fire Rating Mitigation
Type 1 Class A None Required / No Limitations
Type 2 Class A None Required / No Limitations
Type 29 Class A None Required / No Limitations
Type 30 Class A None Required / No Limitations

TYPE 1, 2, 29, and 30 CLASS A FIRE RATING MOUNTING ORIENTATION
Unirac RM Dual tilt has achieved Class A system level fire performance for type 1 and type 2 module constructions. There are no provisions necessary in order to meet Class A requirements for this product.

RMDT-UNIRAC-Code-Compliant-Construction-Drawings-For-Project-
FIG-42

MECHANICAL LOAD TEST

The Unirac RM system has been tested to the mechanical load provisions of UL2703 and covers the following basic parameter(s):

  • Test Loads = 1.5 x Design Loads
  • PV modules may have a reduced load rating, independent of the RM5 load rating. Please consult the PV module manufacturer’s installation guide for more information.

TESTED MODULES


Module Manufacturer

| ****

Model / Series

| ****

Area (sq ft)

| Standard Installation Configuration – No

Mid Bay

| Installed with Additional Bay at Modules North/South Center
---|---|---|---|---
Up Design Load (psf)| Down Design Load (psf)| Up Design Load (psf)| Down Design Load (psf)
Jinko| JKMxxxM-72HL4-V| 27.8| 17.24| 36.20| Not Tested| Not Tested
Canadian Solar| CS7N-xxxMB-AG| 33.4| 15.67| 14.85| 23.52| 33.33

NOTE
All installation configurations have achieved a minimum of 5psf design load in the downslope direction.

COMPATIBLE MODULES

ELECTRICAL BONDING & GROUNDING TEST MODULES: This racking system may be used to ground and/or mount a PV module complying with UL1703 or UL61730 only when the specific module has been evaluated for grounding and/or mounting in compliance with the included instructions.
VERIFIED COMPATIBLE MODULES

Manufacture| Module Model / Series| | Manufacture| Module Model / Series| | Manufacture| Module Model / Series|
---|---|---|---|---|---|---|---|---
Aionrise| AION60G1, AION72G1| Canadian Solar (Cont.)| ELPS CS6(P/A)-MM CS7N- xxxMB-AG CS7L-xxxMB-AG| Hyundai Heavy Industries| MG, TG, RG, KG, MI, RI, KI, HI & TI Series HiA-SxxxHG, HiD-SxxxRG(BK), HiS-S400PI|
Aleo| P18 & P19

S18, S19, S59, & S79

|
Inxeption| mSolar 108BB HC Series (TXI10-xxx108BB) mSolar 144BB HC Series (TXS6-xxx144BB)|
Centrosolar America| C-Series & E-Series|



Aptos Solar

| DNA-120-MF10 DNA-120-(MF/BF)26 DNA-144-(MF/BF)26

DNA-108-(MF/BF)10-xxxW

DNA-120-(MF/BF)10-xxxW

|
ITEK| iT, iT-HE & iT-SE Series|
CertainTeed| CTxxxMxx-(01/02/03/04) CTxxxPxx-01|
Japan Solar| JPS-60 & JPS-72 Series|






JA Solar

| JAM54S31 xxx/MR JAP6-60, JAM6-60 JAP6-72, JAM6-72

JAM72D30MB, JAM78D10MB, JAM72S30 /MR

JAP6(k)-60-xxx/4BB, JAP60S##-xxx/ JAM6(k)-60-xxx/, JAM60S##-xxx/ JAP6(k)-72-xxx/4BB, JAP72S##-xxx/ JAM6(k)-72-xxx/,  JAM72S##-xxx/ i. ##: 01, 02, 03, 09, 10

ii. **: SC, PR, BP, HiT, IB, MW, MR

** = Backsheet, ## Cell technology

|
Eco Solargy| Orion 1000 & Apollo 1000|


Astronergy

| CHSM6610(P/M)/HV CHSM6612(P/M)/HV CHSM72(P/M)-HC CHSM72M(DG)/F-BH|
ET Solar| ETAC & ET Modules

ET-M672BHxxxTW, ET-M772BH520-550WW/WB

|
Flextronics| FXS|
AU Optronics| PM Series|
Freedom Forever| FF-MP-BBB-xxx, FF-MP1-BBB-xxx|
Auxin| AXN6M610T, AXN6P610T AXN6M612T, AXN6P612T|
FreeVolt| PVGraf|
GCL| GCL-P6 & GCL-M6 Series|



Axitec

| AC-xxx(M/P)/(60/72)(S/V) AC-xxxP/156-60S

AXIpremium X HC: AC-xxxMH/(120/144)(S/V) AXIblackpremium X HC: AC- xxxMH/(120/144)(SB/VB) AXIpremium XL HC: AC-xxxMH/120(S/V)

AXIblackpremium XL HC: AC-xxxMH/120(SB/VB)

|
Hansol| TD-AN3, TD-AN4, UD-AN1 & UB-AN1|








Jinko

| JKMxxx(P/PP)-60, JKMxxxPP-60(Plus) JKMxxxPP-60B, JKMxxxM-60 JKMxxxM-60(B/L/HL/BL/LV)

JKMxxxM-60-V, JKMxxxPP-60B-J4 JKMSxxxM-60

JK07(A/B)

JKMSxxx(P/PP)-60, JKMSxxxPP-60B-J4 JKMxxx(M/P/PP)-72, JKMxxx-72L-V JKMxxxM- 72L-V, JKMxxxM-72HL(4)-V JKMxxxM-72HLM-TV

JKMxxx(M/PP)-72-V, JKMxxxPP-72(Plus) JKMxxx(P/PP)-72B

JKMSxxx-72, JKMSxxx(P/PP)-72 JKMxxxM-7RL3-V

JKMxxxM-72HBL-V JKMxxxM-72HL4-TV

|
Hanwha SolarOne| HSL 60 & HSL 72|


Heliene

| 36M, 60M, 60P, 72M & 72P Series

144HC M6

144HC M10 SL Bifacial

|
Boviet| BVM6610 & BVM6612|
BYD| P6K Series, MHK| ****

HT-SAAE

| HT72-156(M/P), HT72-156P-C, HT72-156P(V)-C HT60-156M-C, HT60-156M(V)-C, HT72-166M HT72-18X|





Canadian Solar

| CS1(K/H/U/Y)-MS, CS3(U/K)-MB-AG CS3K-(MB/MS/P/PB), CS3L-(P/MS) CS3N-MS, CS3U-(MB/MS/P/PB/PB-AG) CS3W-(MB-AG/MS/P/P-PB-AG)

CS3Y-MB-AG, CS5A-M

CS6K-(M/MS/P), CS6P-(M/P) CS6R-MS, CS6U-(M/P)

CS6V-M, CS6W-(MB-AG/MS)

CS6X-P, CS7L-MB-AG

|
Hyperion Solar| HY-DH108P8(B), HY-DH108N8B HY-DH144P8|


Hyundai

| HiS-SxxxYH(BK) HiS-SxxxXG(BK) HiN-SxxxXG(BK)|
|
Kyocera| KD-F Series|
|

  • Unless otherwise noted, all modules listed above include all wattages and specific models within that series. Variable wattages are represented as “xxx”
  • Items in parenthesis are those that may or may not be present in a compatible module’s model ID
  • Slashes “/” between one or more items indicates that either of those items may be the one that is present in a module’s model ID

ELECTRICAL BONDING & GROUNDING TEST MODULES: This racking system may be used to ground and/or mount a PV module complying with UL1703 or UL61730 only when the specific module has been evaluated for grounding and/or mounting in compliance with the included instructions.

Manufacture| Module Model / Series| | Manufacture| Module Model / Series| | Manufacture| Module Model / Series|
---|---|---|---|---|---|---|---|---


LA Solar

| LSxxxHC LSxxxBL LSxxxHC| ****


Panasonic

| VBHNxxxSA(15/16) VBHNxxxKA(01/02) VBHNxxxSA17(G/E) & SA18(E) VBHNxxxKA(03/04)

EVPVxxx

EVPVxxx(H/K/PK/HK)

| ****





Q.Cells (Cont.)

| Q.PEAK DUO XL (G9/G9.2/G9.3) Q.PEAK DUO XL- G9.3/BFG

Q.PEAK DUO BLK-G10(+) Q.PEAK DUO G10+

Q.PEAK DUO (BLK) ML-G10(.a)(+) Q.PEAK DUO BLK G10+ /AC Q.PEAK DUO BLK ML-G10+ / t Q.PEAK DUO BLK ML-G10+ / TS

Q.PEAK DUO XL-(G10/G10.2/G10.3/G10.c/G10.d) Q.PEAK DUO XL-G11S

Q.PEAK DUO XL-(G11.2/G11.3) Q.PEAK DUO XL-G11.3/BFG Q.PEAK DUO XL-G10.3/BFG

Q.PEAK DUO XL-G10.d/BFG

|






LG Electronics

| LGxxx(E1C/E1K/N1C/N1K/N2T/N2W/S1C/S2W/Q1C/ Q1K)-A5 LGxxx(A1C/M1C/M1K/N1C/N1K/Q1C/Q1K/QAC/ QAK)-A6

LGxxxN2T-B5 LGxxxN1K-B6

LGxxx(N1C/N1K/N2T/N2W)-E6 LGxxxN2T-J5 LGxxx(N1K/N1W/N2T/N2W)-L5 LGxxx(M1C/N1C/Q1C/Q1K)-N5 LGxxx(N1C/N1K/N2W/Q1C/Q1K)-V5

LGxxxN3K-V6

|
Peimar| SGxxxM (FB/BF), SMxxxM|
Phono Solar| PSxxxM4(H)-24/TH|
Phono Solar Tech.| Standard Modules|
Prism Solar| P72 Series, P72X-xxx|











Q.Cells

| Q.PRO L-G2, Q.PEAK (BLK) (G3/G3.1)

Q. PLUS/PRO G3, Q.PLUS BFR G3.1, Q.PRO/PLUS G4 Q.PLUS/PEAK/PRO – L G4.x

B.LINE PLUS/PRO – L G4.x

Q.PRO BFR G4x, Q.PEAK (BLK) G4.1 (TAA/MAX) Q.PLUS BFR G4.1(TAA/MAX)

B.LINE (PLUS/PRO) BFR G4.1 Q.PLUS L-G4.2/TAA

Q.PRO EC-G4.4 Q.PEAK DUO (BLK) G5

Q.PEAK DUO L-(G5/G5.1/G5.2/G5.3) B.LINE PEAK DUO L-(G5/G5.1/G5.2/G5.3) Q.PEAK DUO (BLK)-G6+

Q.PEAK DUO BLK-G6+/TS Q.PEAK DUO L-(G6/6.2/6.3) Q.PEAK DUO (G7/G7.2) Q.PEAK DUO (BLK)-G7

Q.PEAK DUO L-(G7/G7.1/G7.2/G7.3/G7.7) B.LINE PEAK DUO (G7/G7.2)

B.LINE PEAK DUO L-(G7/G7.1/G7.2/G7.3) Q.PEAK DUO (BLK) G8(+)

Q.PEAK DUO L-(G8/G8.1/G8.2/G8.3/G8.3 BFG)

Q.PEAK DUO (BLK) ML G9(+)

|






REC

| PEAK & ECO

RECxxxAA (BLK/Pure/Pure-R) RECxxxNP (N-PEAK)

RECxxxNP2 (Black) RECxxxNP3 Black RECxxxPE, RECxxxPE72 RECxxxTP RECxxxTP2(BLK2) RECxxxTP2S(B)(XV)

RECxxxTP3M (Black)

RECxxxTP4 (Black)

|


LONGi

| LR6-60, LR6-60(BK/PE/PB/PH/HPB/HIB/HPH/HIH) LR6-72, LR6-72(BK/HV/PE/PB/PH/HPH/HIH)

LR4-60(HPB/HIB/HPH/HIH)

LR4-72(HPH/HIH)

|
Maxeon| SPR-MAX3-xxx-COM|
Meyer Burger| Meyer Burger Black, Meyer Burger White Meyer Burger Glass|
Mission Solar Energy| MSE MONO & MSE PERC MSExxx(SR8T/SR8K/SR9S/SX5T/SX5K/SX6W)|
Mitrex| Mxxx-L3H, Mxxx-I3H| Renesola| 60 Cell Modules & Vitrus2|
Mitsubishi| MJE & MLE Series| Risen| RSM60-6, RSM72-6, RSM144-6 RSM110-8-xxxBMDG|
Neo Solar Power Co.| D6M Series|
SEG Solar| SEG-xxx-BMD-HV SEG-xxx-BMD-TB|
NE Solar| NESE xxx-72MHB-M10 NESE xxx-60MH-M6|
S-Energy| SN72, SN60 Series|
| |

  • Unless otherwise noted, all modules listed above include all wattages and specific models within that series. Variable wattages are represented as “xxx”
  • Items in parenthesis are those that may or may not be present in a compatible module’s model ID
  • Slashes “/” between one or more items indicates that either of those items may be the one that is present in a module’s model ID

ELECTRICAL BONDING & GROUNDING TEST MODULES: This racking system may be used to ground and/or mount a PV module complying with UL1703 or UL61730 only when the specific module has been evaluated for grounding and/or mounting in compliance with the included instructions.

Manufacture| Module Model / Series| | Manufacture| Module Model / Series| | Manufacture| Module Model / Series|
---|---|---|---|---|---|---|---|---

Seraphim

| SEG-(6PA/6PB/6MA/6MA-HV/6MB/E01/E11) SRP-(6QA/6QB)

SRP-xxx-6MB-HV, SRP-320-375-BMB-HV, SRP-xxx-BMC-HV, SRP-390-415-BMA-HV,

SRP-390-405-BMD-HV

|

SunPower

| X-Series 72 & E-Series 72

X-Series 96 & E-Series 96 P-Series, Sig Black

SPR E20 435 COM (G4 Frame)

Axxx-BLK-G-AC, SPR-Mxxx-H-AC

|

VSUN

| VSUNxxx-60M-BB, VSUNxxx-72MH VSUN400-415-144BMH

VSUN4xx-144BMH-DG VSUN5xx-144BMH-DG VSUNxxx-108M-BB VSUNxxx-120M-BB VSUNxxx- 120BMH VSUNxxx-132BMH

VSUNxxx-108BMH

|

Sharp

| ND-24CQCJ, ND-25CQCS ND-Q235F4, ND-F4Q300 NU-SA, NU-SC| SunTech| STP XXX, STPXXXS – B60/Wnhb|

Talesun

| TP572, TP596, TP654, TP660

TP672, Hipor M, Smart TD6I72M, TP7G54M(H)

|

Silfab

| SLA-M/P, SLG-M/P

SILxxx(BG/BK/BL/HC/HC+/HL/HM/HN/ML/NL/NT/ NX/NU)

|
Waaree| Arka Series WSMDi|
Tesla| TxxxS, TxxxH|
Winaico| WST & WSP Series|

Trina

| PA05, PD05, DD05

DD06, DE06, DE09.05, DE09C.07

PD14, PE14, DD14, DE14, DE15, DE15V(II) DEG15HC.20(II), DEG15MC.20(II), DEG15VC.20(II) DE18M(II), DEG18MC.20(II)

DE19, DEG19C.20

|
Solar4America| S4Axxx-108MH10BB, S4Axxx-72MH5BB|

Yingli

| YGE 60 Cell

YGE 60 Cell Series 2

YLM 60

YLM 72 YLM-VG

|
SolarEver USA| SE-16683-xxxM-120N SE-18291-xxxM-108N|

Solaria

| PowerXTxxxR-PD/BD/AC PowerXTxxxC

PowerXT-xxxR-PM (AC)

PowerX-400R

|
Yotta Energy| YSM-B450-1|

Universal Solar

| UNI4xx-144BMH-DG UNI5xx-144BMH-DG UNIxxx-108M-BB UNIxxx-120M-BB UNIxxx- 120MH|

ZNShine Solar

| ZXM6-72 Series, ZXM6-NH144 ZXM6-NHLDD144-XXX/M

ZXM7-SH108 Series

|
SolarTech| STU HJT & STU PERC|
SolarWorld| Sunmodule Protect/Plus|
|

Sonali

| SS-M-360 to 390 Series SS-M-390 to 400 Series SS-M-440 to 460 Series

SS-M-430 to 460 BiFacial Series

|
Upsolar| UP-Mxxx|

URE

| D7KH8A, D7M(H7A/H8A) FAKxxx(C8G/E8G), FAMxxxE7G-BB FAMxxxE8G(-BB), FBKxxxM8G|
Sun Edison/ Flextronics| F-Series / FLEX FXS, R-Series / FLEX FXS|
URECO| F6MxxxE7G-BB FBMxxxMFG-BB|
Suniva| Optimus Series, MV Series|

Vikram

| Eldorado, Solivo & Somera PREXOS VSMDHT.60.AAA.05 PREXOS VSMDHT.72.AAA.05|
Sunmac Solar| M754SH-BB Series|
|

  • Unless otherwise noted, all modules listed above include all wattages and specific models within that series. Variable wattages are represented as “xxx”
  • Items in parenthesis are those that may or may not be present in a compatible module’s model ID
  • Slashes “/” between one or more items indicates that either of those items may be the one that is present in a module’s model ID

UNIRAC welcomes input concerning the accuracy and user-friendliness of this publication. Please write to publications@unirac.com.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals