Unisenza Plus – Receiver
Unisenza Plus – Receiver
Installation and user manual
Release | Date |
---|---|
First release | Aug-23 |
SAFETY WARNINGS
Pictograms used in this manual
To make reading clearer and more enjoyable, three types of symbols have been
used in this manual to convey to the reader the meaning or importance of the
information provided:
Hazard signs. Triangular framed shape. Indicate prescriptions relating to present or possible dangers.
Prohibition signs. Circular, barred frame. Indicate prescriptions relating to actions that must be avoided.
Mandatory signs. Full circle. Indicate information that is important to read and comply with.
Purpose of the manual
The purpose of this manual is to guide the qualified installer the
installation, maintenance and proper and safe use of the equipment.
For this reason, it is mandatory for all personnel involved in the installation, maintenance and use of the equipment to read this manual.
Contact the Manufacturer if any points are unclear or difficult to understand.
This manual contains information regarding:
- Technical specifications of the equipment;
- Installation and connection instructions.
Intended use
The Receiver can be used for the wireless control of boiler, pump or zone
valves in a HVAC system. It provides two channels relay on/off output and an
OpenTherm interface, and can be paired with Unisenza PLUS Thermostat and
Unisenza PLUS Electronic Thermostatic Head in the product platform to support
multiple applications.
Its features are:
- Two channels on/off control with volt-free relay output @230V 5A resistive, 3A inductive.
- Local switches for the manual override of the wireless controls on each channel.
- Build-in OpenTherm Controller function with an OT/+ interface auto detection.
- Support pairing with Unisenza PLUS Thermostat and Unisenza PLUS Electronic
Thermostatic Head for room temperature control or boiler interlock.
- Over the air firmware update capability.
- Powered by 230V AC supply.
Safety regulations
Before proceeding with any installation or use, it is necessary to thoroughly
inspect the product. Make sure that all the information contained in this
manual correspond exactly to the purchased equipment. In the event that
differences are identified, it is necessary to contact the Manufacturer in
order to obtain the assistance and specific technical information necessary to
operate.
Read this manual carefully before the installation, use and maintenance of the product and keep it for any further future consultation by the various operators.
All installation, assembly, electrical connections to the mains and ordinary/ extraordinary maintenance must be performed only by qualified personnel or technicians complying with the legal requirements.
Installation, use or maintenance other than those specified in the manual may
cause damage, injury or death, invalidate the warranty and relieve the
Manufacturer of all liability.
Disconnect the equipment from the mains before installing or maintaining it.
Do not install the equipment outdoors. The product has been designed to be
installed indoors, protected from bad weather, in places where the temperature
is between 0 and +50 °C.
At the end of the installation it is necessary to instruct the user in the
correct use of the equipment.
TECHNICAL DATA
Output interface | Relay On/Off or OpenTherm (OT/+) protocol specification v4.1 |
---|---|
Switch rating (Volt-free output) | Main: 230V/50Hz, 5A resistive, 3A inductive |
Aux: 230V/50Hz, 5A resistive, 3A inductive
Firmware update| Over the air firmware update capability
Wireless Communication| ZigBee 3.0, 2.4GHz
Power Supply| 230Vac 50Hz
Operating Environment| Indoor, residential & commercial
Operating Temperature| 0°C – 50°C
Storage Temperature| -10°C – 60°C
Operating/Storage Humidity| <90% RH, non-condensing
Dimensions| 144.6(W) x 99.8(D) x 34.5(H) mm
Ingress Protection Rating| IP30
Regulation| CE, UKCA
Environmental Requirement| RoHS compliance
The Unisenza Plus Receiver complies with the following European directives:
- RED directive 2014/53/EU
- ROHS directive 2011/65/EU
- REACH (EC 1907/2006)
The Unisenza Plus Receiver complies with the relevant UK Statutory Instruments:
- Electrical Equipment (Safety) Regulations 2016
- Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment Regulations 2012 (SI 2012/3032)
- REACH ETC. (Amendment etc.) Regulations 2020 – SVHC
DIMENSIONS
PACK CONTENTS
a. Unisenza
Plus Receiver
b. Fixing screw
c. Fisher for plate fixing
OVERVIEW
- Slide switch for Main output
- LED for Slide switch for Main output
- LED for Slide switch for Aux output
- Slide switch for Aux output
- Pair button
- Reset button
LED functions
LED Status at Main / Aux| Description On/Off System| Description
OpenTherm(OT/+) System
---|---|---
Solid Red| Relay Off| OpenTherm Boiler Off
Solid Green| Relay On| OpenTherm (OT/+) On
Solid Orange| Factory reset| Factory reset
Flash Red 1 time then repeat| Pairing mode| Pairing mode
Flash Red 3 times then repeat| Joining to the gateway| Joining to the gateway
Main LED Flash Red or Green 3 times then repeat during normal operations| Lost
link with gateway| Lost link with gateway
Flash Red 4 times then repeat (when slide switch position is at Auto)| Lost
link with all paired ther- mostats or E-TRV| Lost link with all paired thermo-
stats or E-TRV
Terminals Description
| Terminal| Function
---|---|---
230V 50-60Hz (AC Input)| L| Incoming Mains – Live
| Earth
N| Incoming Mains – Neutral
Main (Volt free Output)| NO| Main relay, Normally Open Contact
COM| Main relay, Common Contact
NC| Main relay, Normally Close Contact
AUX (Volt free Output)| NC| Auxiliary relay, Normally Close Contact
NO| Auxiliary relay, Normally Open Contact
COM| Auxiliary relay, Common Contact
OpenTherm Interface| A-B| Wire to OpenTherm Boiler
APPLICATIONS
Heating only (On/Off or OpenTherm boiler) or Heat/Cool (2-pipe system)
-
The receiver provides single output control when paired with Unisenza Plus Thermostat or Unisenza PLUS Electronic Thermostatic Head.
-
If there is no OpenTherm (OT/+) connection, the control output will go through the On/Off relay.
The Aux Relay will be in-sync with the Main relay for the interlock of additional equipment such as the circulation pump -
If the unit detects an OpenTherm (OT/+) connection, the control will be taken over by the integrated OpenTherm controller automatically. It can be paired with the Unisenza Plus Thermostat and work together as an OT master unit.
Central Heating plus Domestic Hot Water (S-plan or Y-plan)
- The receiver provides two output controls. Main Relay controls Central Heating, and Aux Relay controls Domestic Hot Water.
- It is paired with a thermostat supporting both heating and DHW function, such as the Unisenza Plus Thermostat .
Heat/Cool Independent system (4-pipe system)
- The receiver provides two output controls. Main Relay controls Heating, and Aux Relay controls Cooling.
- It is paired with a thermostat with heat/cool manual changeover functions, such as the Unisenza Plus Thermostat.
Dual Zone Controls
- The receiver provides two on/off output controls. Main Relay controls Zone 1 and Aux Relay controls Zone 2.
- It is paired with two zone thermostats with each controlling the heating or cooling in the zone individually.
- Pairing with multiple Unisenza Plus Thermostats or Unisenza PLUS Electronic Thermostatic Heads for boiler interlock is supported for Zone 1 only.
- A maximum of 16 devices including Unisenza Plus Thermostat and Unisenza PLUS Electronic Thermostatic Head can be paired with the Unisenza Plus Receiver.
DOWNLOAD THE APP
The management of the Unisenza Plus Receiver is also possible through a
dedicated APP that allows its configuration and the management of the devices
you will pair.
In order to download the APP, you need to connect to the STORE of your device
used for configuration and install the Unisenza Plus.
Or, again using the device, you can directly access the installation page
using the following QR codes, again depending on the operating system.
NAMEPLATE
On the side of the Unisenza Plus Receiver there is a sticker (A) which
indicates the device data.
QR code availability for future feature.
INSTALLATION
Recommendations for a correct installation
Wall installation
Disconnect the equipment from the mains before installing or maintaining it.
All installation, assembly, electrical connections to the mains and ordinary/extraordinary maintenance must be performed only by qualified personnel or technicians complying with the legal requirements, using personal protective equipment, in compliance with the regulations in force in the country the equipment is to be used in and the laws on safety in the workplace.
For installation requirements, it is possible to route the electric cables in the lower part of the device, using the appropriate holes and the relative cable gland.
Unisenza Plus Receiver should be mounted on a suitable location that is both
accessible for the connection of mains and control wiring, and allows good
reception of the RF signal from the Unisenza Plus Gateway.
The Unisenza Plus Receiver needs a 230V AC mains supply to operate and should
be fused appropriately (5A max.).
System Type Selection with DIP switch and wiring diagrams
Disconnect the equipment from the mains before installing or maintaining it.
All electrical connections must be performed only by qualified personnel or technicians complying with the legal requirements, using personal protective equipment, in compliance with the regulations in force in the country the equipment is to be used in and the laws on safety in the workplace.
Different system type and application can be selected by using the DIP switch located at the back of the front panel.
Default setting of DIP-1 to DIP-4 is at On position.
After the change of DIP switches, the new setting will become effective after a Factory Reset by pressing and holding the PAIR button for 10 seconds, the Main/Aux LEDs will light up orange.
Application 1 | Output Controls |
---|---|
Main relay | Aux relay |
Heating only
(On/Off or OpenTherm)| Heat| Sync with Main| OT/+ (when connected)|
Volt-free Combi boiler Control| OpenTherm boiler Control
---|---
|
Application 2| Output Controls
---|---
Main relay| Aux relay| OpenTherm| DIP Switch
Heat/Cool 2-pipe system| Heat/Cool| Sync with Main| –|
Heat/Cool 2-pipe Zone Valve Control
Application 3 | Output Controls |
---|---|
Main relay | Aux relay |
Heat/Cool 4-pipe system | Heat |
Heat/Cool 4-pipe Zone Valves Control
Application 4 | Output Controls |
---|---|
Main relay | Aux relay |
Central Heating plus Domestic Hot Water
– Supports S-Plan and Y-Plan wiring| Heat| Domestic Hot Water| –|
Application 5 | Output Controls |
---|---|
Main relay | Aux relay |
Dual Zone Controls | Zone 1 Heat/Cool |
USE
Pairing to Unisenza Plus Gateway
With APP
Without APP
Pairing with other Unisenza Plus device (optional)
After the Unisenza Plus Receiver has joined a Unisenza Plus network, it can be
paired with a Unisenza Plus Electronic Thermostatic Head or Unisenza Plus
Thermostat.
Pair device using App
Pair device without using App
For pairing with the 2nd zone thermostat in a Dual zone control application, set the Main Switch to the right (OFF) Positon.
Switch placement
Both the main switch and the auxiliary switch of the Unisenza Plus Receiver
have three positions to which a command is assigned.
Move the switch to the desired position with your finger according to your
needs.
Main slide switch| Position| Action On/Off System| Action
OpenTherm (OT/+) System
---|---|---|---
| AUTO| Relay output is controlled via ZigBee communications| OpenTherm
(OT/+) Control Setpoint
| ON| Relay output is always on| OpenTherm (OT/+) max CH water Setpoint
| OFF| Relay output is always off| OpenTherm (OT/+) boiler off (heat demand
disabled)
Aux slide switch| Position| Action On/Off System| Action
OpenTherm (OT/+) System
---|---|---|---
| AUTO| Relay output is controlled via ZigBee communications| No function
| ON| Relay output is always on| No function
| OFF| Relay output is always off| No function
MAINTENANCE
Power Cycle Reset
For any reason the Unisenza Plus Receiver does not response or needs a
restart, press RESET button to restart.
Factory reset
Warning: this process restores the device to factory settings and disconnects
it from the Gateway it was associated with.
Cleaning
MANUAL DOWNLOAD AND UPDATES
Due to the requirement for continuous improvement, we constantly update the
user manuals of our systems.
We therefore invite you to periodically check whether the manual in your
possession is always the latest written version.
To do this, you can connect to the following internet address:
https://www.purmogroup.com/support
or by scan the QR code displayed below.
DISPOSAL AT THE END OF LIFE
Pursuant to art. 13 of Decree-Law No. 49 of 2014 “Implementation of the
WEEE Directive 2012/19/EU on waste electrical and electronic equipment”.
**** The mark of the crossed-out bin with a bar specifies that the product
was placed on the market after 13 August 2005 and that at the end of its
useful life it must not be collected with other waste but must be disposed of
separately.
All the appliances are made of recyclable metal materials (stainless steel,
iron, aluminium, galvanized sheet metal, copper, etc.) in a percentage greater
than 90% by weight. Make the equipment unusable for disposal by removing the
power cable and any compartment or cavity closing device (if any). It is
necessary to pay attention to the management of this product at the end of its
life by reducing any negative impacts on the environment and improving the
efficiency of the use of resources, applying the principles of “polluter
pays”, prevention, preparation for reuse, recycling and recovery. Please note
that the illegal or incorrect disposal of the product entails the application
of the penalties provided for by current legislation.
Information on disposal in Italy
In Italy WEEE equipment must be delivered to:
collection centres (also called waste separation areas or platforms) the
Dealer where you buy new equipment, who is required to accept it free of
charge (“one on one” collection).
Information on disposal in European Union countries
The EU WEEE equipment directive has been adopted differently by each country,
therefore if you want to dispose of this equipment we suggest you contact the
local authorities or the dealer to ask for the correct method of disposal.
A PURMO GROUP BRAND
Bulevardi 46
P.O. Box 115
FI-00121 Helsinki
Finland
www.purmogroup.com
Every care has been taken in the creation of this document. No part of this
document
may be reproduced without the express written consent of Purmo Group. Purmo
Group
accepts no responsibility for any inaccuracies or consequences arising from
the use or
misuse of the information contained herein.