JRG LegioTherm 2T Hycleen Automation System Instruction Manual
- June 13, 2024
- JRG
Table of Contents
+GF+
Installation instructions, operating and maintenance instructions
Hycleen Automation System
JRG LegioTherm 2T
Electrically Operated Water Valve
JRG Code 9910.0xx
Components
- Controller / Actuator
- Light ring
- Controller fastening screw (Allen key)
- PT1000 temperature sensor
- Labels with serial number (removable)
- M12 socket for serial wiring (Master / valve)
- M8 socket for connecting external sensor
- Plug for PT1000
- Flow arrow
- Insulation
Function
The JRG LegioTherm 2T circulation valve is used wherever a controlled thermal
disinfection of a hot water system is required in addition to its function as
a Controller (such as in nursing homes, hospitals, etc.).
The JRG LegioTherm 2T circulation valve allows for two calibration
temperatures (normal operation / thermal disinfection).
The JRG LegioTherm 2T circulation valve regulates the flow rate by permanently
reading the water temperature with the help of an immersed temperature sensor.
The measured values are processed by the Controller. If a deviation from
nominal temperature is detected, the circulation valve regulates the flow rate
by opening or closing the valve until the set-point temperature is reached.
This is done by means of an actuator.
JRG LegioTherm 2T Circulation valve with controller, PN 10
- Temperature: max. 90°C
- Material: gunmetal, stainless steel, EPDM
- Factory setting: 57°C (adjustable 0 – 90°C) thermal disinfection 70°C (adjustable 60 – 90°C)
- Connection: male thread (for union connection with flat gasket)
DN (mm) | JRG Code | GF Code | Weight (kg) |
---|---|---|---|
15 | 9910.015 | 351 110 550 | 0.820 |
20 | 9910.020 | 351 110 590 | 1.050 |
25 | 9910.025 | 351 110 630 | 1.400 |
DN | d1 G | d2 G | d3 Rp |
b | h1 | h2 | º |
--- | --- | --- | --- |
(mm) | (inch) | (inch) | (inch) |
(mm) | (mm) | (mm) | (mm) |
15 | 3∕4 | 1∕2 | 1∕4 |
20 | 3∕4 | 1∕4 | |
25 | 1 1∕4 | 1 | 1∕4 |
Installation
Wiring Master and valves
The connection cables contain four wires, two for power supply and two for signal transmission. Both cable ends are equipped with the same female connectors and feature an anti-twist design. The M12 knurled coupling nuts provide a reliable grip even in harsh environments.
Note:
Unapproved components may cause malfunctions!
All components must be connected in series (one after the other, with each
other) .
A parallel or star-shaped wiring of the components leads to malfunctions in
the BUS communication. Components and cables must not be modified. Never
disconnect the cable from electricity under power.
Connecting the Master
Connect one of the plugs (11) of the connection cable to one of the two M12 sockets (12) on the Master and screw on the knurled coupling nut. Both connections of the Master can be used at the same time.
Connecting the valve
Connect the other plug (11) of the connection cable with one of the two M12
sockets (6) of the valve and secure with the knurled coupling nut. It does not
matter which M12 socket is used.
Connecting further valves:
Connect one of the plugs of the next connection cable to the second M12 socket
(6) on the valve and secure with knurled coupling nut, etc.
Note:
Risk of malfunctions due to faulty installation!
If the knurled coupling nut is not tightened properly, the plug connection may
get loose over time. This may lead to a loss of functionality!
Make sure that all knurled coupling nuts of the connection cables are
tightened!
Laying the cables:
The cables may be mounted directly on the circulation line or if need be on
the outside of the insulation. Use temperature-resistant cable ties (up to 90
°C).
Hycleen Automation power supply and communication cable
- Description: For serial connection of Hycleen Automation System components (master, controller), incl. 2xM12 plugs, ROHS
L Voltage | JRG | GF Weight | d | d1 |
---|---|---|---|---|
(m) | Code | Code | (kg) | (mm) |
1.5 | 36V | 9940.001 | 351 110 581 | 0.110 |
36V | 9940.005 | 351 110 582 | 0.300 | 14.5 |
10 | 36V | 9940.01 | 351 110 583 | 0.630 |
20 | 36V | 9940.02 | 351 110 584 | 1.240 |
50 | 36V | 9940.05 | 351 110 585 | 3.200 |
Hycleen Automation Coupling
- Description: Coupling between 2 Hycleen Automation power supply and communication cable
JRG
Code| Weight
(kg)| GF
Code| l
(mm)| h
(mm)
---|---|---|---|---
9941.000| 0.100| 351 110 586| 58| 14
Installing a Power box
For cable lengths over 300 m, a Power box (14) must be installed between two
connection cables.
Installing a JRG LegioTherm 2T
The JRG LegioTherm 2T can be mounted in any position. The valve must be
accessible for inspections and revisions. We recommend to install shut-off
valves JRG Code 8339 before and after the Controller. To prevent the JRG
LegioTherm 2T circulation valve from being flowed against the desired flow
direction, it is advisable to install suitable check valves. We recommend
using JRG LegioTherm insulation to reduce heat emission.
Note:
For revision purposes there must be a clearance of 3 cm between the Controller
and the nearest surface.
Note:
After installation, remove the label (5) with the valve serial number from the
valve and stick it to the installation diagram.
In doing so, the valve can be easily located later on. The serial number is
also displayed in the Master.
An individual designation can be additionally defined in the Master.
Flushing
Before installing the JRG LegioTherm 2T circulation valve, all pipes have to
be flushed thoroughly.
Gaskets
Only AFM 34 gaskets are to be used. AFM 34 gaskets must not be oiled or
greased.
Soldering
When using soldered joints, the JRG LegioTherm 2T valve must not be installed
during soldering (possible damage due to overheating) .
Specifications
Material:
Casing: | Gunmetal |
---|---|
Follower / spring / seat: | Stainless steel |
Valve cone: | Gunmetal |
Function | The device is responsible for the equal and consistent distribution |
of water flows and temperatures across the building. Furthermore, it is
essential to reduce energy consumption and increase comfort.
Gaskets:| EPDM
Feature of automatic action:| Type 1 action
Pollution degree:| 2
Use:| Medium drinking water
Dimensions:| DN 15/20/25
Standards:| Meets DVGWVP 554
(2003.04)
Water temperature:| 1 – 90 °C
Control accuracy:| < ± 1 °C
Maximum operating temperature:| 90°C
Maximum operating pressure:| 10 bar
Ambient temperature:| 5 – 45 °C
Temp. limits of the mounting surface| T45
Winding insulation:| Class F
Nb. Of Automatic cycles A for each cycles automatic action| 6000
Power supply:| 36 V DC
Actuator:| Minimum stroke 5 mm
Duty cycle:| 1 min ON/1min OFF
Operating voltage:| 24 V DC
Power consumption open/close:| 6 W
IP code (degree of protection):| IP 44
BLE Working Frequency| 2402~2480MHz
BLE Maximum Power| 2.2dBm
Supply Connection| M12 socket
Light ring legend:
If a valve is connected to the circuit, the light ring lights up. The
frequency or light colour provide the following visual information:
Purple | constant | valvesetat leakage rate (lowest flow rate) |
---|---|---|
flashes | valve not set at leakage rate (highest flow rate) | |
Yellow | constant | initialization / valve update (software) |
Blue | flashes | bluetooth connection with smartphone / tablet |
Orange | flashes | communication error |
Maintenance
The JRG LegioTherm 2T valve is largely maintenance-free.
Customer service hotline: +41 61 975 23
77,tkd.jrg.ps@georgfischer.com
Inspections
The sealing points on the JRG LegioTherm valve are to be checked once a year.
Disposal
System parts of the JRG LegioTherm 2T valve can be disposed of in accordance
with local regulations.
Remarks:
– This device complies with part 15 of the FCC Rules. Operation is subject to
the following two conditions : (1) This device may not cause harmful
interference, and (2) this device must accept any interference, including
interference that may cause undesired operation
– Please note that changes or modifications not expressly approved by the
party responsible for compliance could would void the user’s authority to
operate the equipment.
– Note: This equipment has been tested and found to comply with the limits
for a Class B digital device, pursuant to part 15 of the FCC Rules. These
limits are to provide reasonable protection against harmful interference in a
residential installation. This
equipment generates uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause harmful
interference to radio communications. However, there is no guarantee that
interference will not occur in a particular installation. If this equipment
does cause harmful interference to radio or television reception, which can be
determined by turning equipment off and on, the user is encouraged to try to
correct the interference by one or more of following measures:
- Reorient or relocate the receiving antenna.
- Increase separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for Help.
– This device contains licence-exempt transmitter(s)/receiver(s) that comply
with Innovation, Science and Economic Development Canada’s licence exempt
RSS(s).
Operation is subject to the following two conditions: (1) This device may not
cause interference; and (2) This device must accept any interference,
including interference that may cause undesired operation of the device.
EC DECLARATION OF CONFORMITY
CE Declaration of Incorporation for Council Radio Equipment Directive 2014/53/
Manufacturer:
Georg Fischer JRG AG, Hauptstrasse 130, 4450 Sissach/Switzerland Person
authorized to compile technical documentation: Arnaud Andreolli Georg Fischer
JRG, Product Manager, Hauptstrasse 130, 4450 Sissach/Switzerland UK
UK Importer:
GEORG FISCHER Ltd Paradise Way, Coventry CV2 2ST, United Kingdom
JRG LegioTherm 2T circulation valve with temperature sensor and actuator for Installation in a hot water / cold water circulation JRG Code 9910.0XX is conform to the requirements of Council Radio Equipment Directive 2014/53/EU, as far as the scope of delivery allows. We further declare that the special technical documentation has been compiled in accordance with Directive 2014/53/EU. We shall forward this, if requested, to the competent authorities via the before mentioned authorized person.
Commissioning is prohibited until it has been established that the entire
machine, into which the aforementioned incomplete machine is to be
incorporated, meets the provisions of Council Radio Equipment Directive
2014/53/EU based on the following standards,
EN 61000-3-2:2019+A1, EN 61000-3-3, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4
EN 61000-4-5, EN 61000-4-6, IEC6100-4-8, EN 61000-11
EN 55032:2015 class B, EN 61000 -6-3:2021
EN 60730-1:2016+A1+A2, EN 300 328 V2.2.2:2019, EN 301 489-1 V2.2.3:2019, EN
301 48917
V3.2.4:2020, EN 62479:2012
Georg Fischer JRG AG Name: David Harsch
Position: R&D Manager
Georg Fischer JRG AG
Hauptstrasse 130, CH-4450 Sissach
Phone +41 (0)61 975 22 22, Fax +41 (0)61 975 22 00
info.jrg.ps。georgfischer.com
www.gfps.com