amerec Pro-10.5 Electric Sauna Heater Instruction Manual
- June 13, 2024
- amerec
Table of Contents
- INSTALLATION AND OPERATING INSTRUCTIONS
- SECTION 1: GENERAL INFORMATION
- SECTION 2: MOUNTING OF SAUNA HEATER
- SECTION 3: PLACING OF ROCKS
- SECTION 4: ELECTRICAL HOOK-UP
- SECTION 5: TEMPERATURE SENSOR
- SECTION 6: HEATER SCREEN (GUARD RAIL)
- SECTION 7: CONTROL INSTALLATION & OPERATION
- SECTION 8: LIMIT CONTROL (RESET BUTTON)
- SECTION 9: HOW TO TAKE A SAUNA
- SECTION 10: WARNING PLACARDS
- SECTION 11: ROOM CONSTRUCTION
- SECTION 12: VENTILATION
- SECTION 13: MAINTENANCE
- SECTION 14: TROUBLESHOOTING
- DIAGRAM 12: SL2 Control Mounting
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
INSTALLATION AND OPERATING INSTRUCTIONS
Pro Heater 1105-XXX
or
Laava Heater 1105-XXX2
External Switch 1601-36
SL2-C (SaunaLogic 2) (1601-43 or -43-1)
CB Box
(1201-17-1 or 1201-17-3
Pro 10.5, 12.0, & 14.4 (Model # 1105-105, 1105-120 & 1105-140)
Laava 10.5, 12.0, & 14.4 (Model # 1105-1052, 1105-1202 & 1105-1402)
with SL2-C (SaunaLogic 2) Control (Model # 1601-43 or 1601-43-1)
And / Or External Switch (Type # 1601-36) & CB 17-1 (1201-17-1)
or CB 17-3 (1201-17-3)
Read all instructions carefully before installation. Please leave all instructions and warranty with the owner.
WARNING
Prolonged exposure to elevated temperatures is capable of inducing
hyperthermia. Hyperthermia occurs when the internal temperature of the body
reaches several degrees above the normal body temperature of 98.6°F. The
symptoms of hyperthermia include an increase in the normal temperature of the
body, dizziness, lethargy, drowsiness, and fainting. The effects of the
hyperthermia include failure to perceive heat, failure to recognize the need
to exit the room, unawareness of impending hazard, fetal damage in pregnant
women, physical inability to exit the room and unconsciousness.
WARNING
The use of alcohol, drugs, or medication is capable of greatly increasing the
risk of fatal hyperthermia.
SECTION 1: GENERAL INFORMATION
These heaters are ETL approved by Intertek for permanent installations. All wiring must be performed in accordance with the NEC and local codes. See Table 1 for wire and room size requirements.
These heaters are free standing, secured to the floor, with separate contractor box and low voltage control.
WARNING
Do not take a sauna if using alcohol, drugs or medications.
Pregnant women or persons with poor health should consult their physician before using any sauna.
Caution fire hazard: Do not use the sauna room for drying clothes, bathing suits, etc. Do not hang towels above heater or place any object other than the rocks supplied on the heater. If any darkening of the wall around the heater is noticed discontinue sauna use immediately.
Inspect sauna regularly for required maintenance to heater, control and benches. Replace wood surfaces which show any signs of deterioration.
The heater gets extremely hot during operation and should not be touched or burns may result.
Minors should be adequately supervised whenever near a hot or warming sauna.
SECTION 2: MOUNTING OF SAUNA HEATER
Carefully locate the heater according to the dimensions shown in Diagram 1. Level the heater with the provided feet.
SECTION 3: PLACING OF ROCKS
The rocks supplied with the heater have been chosen to provide the best heater performance. Use of any other type of rock may void the heaters warranty. Never operate the heater without rocks in place! Rinse the rocks with water before placing in the heater. Place the larger rocks at the bottom and the smallest at the top. Place the rocks loosely so that the air can circulate through the heater. Packing the rocks too tightly may cause the heater high limit switch to trip. The rocks must fully cover the heating elements. Attach the guard with the screws provided.
SECTION 4: ELECTRICAL HOOK-UP
Electrical installation must be made by a licensed electrician in accordance with the National Electrical Code and local regulations.
This heater is intended for use with CB 17 Box and the SL2-C Control only. Use of any other control will void the warranty and safety listing. The control must be installed in a dry location outside the sauna room.
The model CB 17-3 contactor is required for use with 3 phase heaters, the model CB 17-1 contactor is required for use with single phase heaters. To determine the correct wire size, refer to Table 1. Use copper supply wire only, suitable for minimum 90 degrees C. The heater must be grounded! See the heater diagrams for proper connections. The location must be selected to allow installation of the thermostat’s temperature sensor shown in Diagram 1. (30 foot sensor wire supplied.)
Contactor Box should located outside the sauna room. It should be surface mounted with 4 screws to a wall. Refer to Diagram 1 for details.
SECTION 5: TEMPERATURE SENSOR
Route the sensor wire from the contactor box to the sensor location on the ceiling It may be necessary to drill holes to string the wire through the studs or ceiling joists. Route wire harness into contactor box and connect CN 4 connector. Ensure low voltage wiring and high voltage wiring is separated by a minimum of 4″or an electrical barrier.
With a flat tip screwdriver, unsnap sensor cover from sensor. Mount sensor on the ceiling according to Diagrams 1, 2, 3, & 4.
SECTION 6: HEATER SCREEN (GUARD RAIL)
Install a wooden heater guard to prevent the sauna bather from accidentally touching the sauna heater. Install the heater guard rail with the height clearances and dimensions shown in Diagram 1.
WARNING
Fire sprinkler systems used inside any sauna room should be properly rated for sauna room temperatures.
Do not pour chlorinated pool or spa water on heater. Excessive water use on heater may cause damage and void warranty.
Do not install a shower in sauna room.
Electric Shock Hazard – High voltage exists within this equipment. There are no user serviceable parts in this equipment. All installation and service to this equipment should be performed by qualified licensed personnel in accordance with local and national codes.
Do not construct sauna room so as to restrict air flow through the bottom of the heater.
Packing the rocks too tightly may cause the heater high limit switch to trip.
DIAGRAM 1
-
Sensor Mounted On Ceiling
-
Pro Heater Size
20″W x 22″D x 28″H -
Leveling Feet
Pro Heater
Model # 1105-XXX
- High Limit Control Reset
- Sensor Mounted On Ceiling
- ¾ x 4″ wooden rail
- 1×1″ wooden post
CAUTION: Avoid fire, Do Not Place Combustible Material on sauna heater
OBSERVING MINIMUM DISTANCES IS REQUIRED TO REDUCE THE RISK OF FIRE
-
Sensor Mounted On Ceiling
-
Laava Heater Size
21″W x 24″D x 28″H -
Leveling Feet
Laava Heater
Model 1105-XXX2
- High Limit Control Reset
- Sensor Mounted On Ceiling
- ¾ x 4″ wooden rail
- 1×1″ wooden post
DIAGRAM 2
- Sensor is mounted on the ceiling. See Diagram 1 for detailed location.
- Locate CB 17-1 or 17-3 contactor box outside the sauna room. (See Note 1)
- Locate the control outside the sauna room in commercial applications.
- Power input to contactor box.
- High Limit Location
Note 1: The contactor box may be mounted anywhere outside the sauna room. A location should be selected so the front cover is accessible for service and the noise of the contactor pulling in will not be a nuisance.
Provide a service loop into the sauna room to the proposed heater location.
Contactor Box 17
Dimensions
4 Mounting Screws
All wiring for sauna system or accessories should be routed inside the walls or away from the high temperature air from the sauna heater.
High Limit Reset
TABLE 1
- Total amp draw of combined circuits and accessory circuits.
Single phase heaters are supplied power from two circuits which must be grouped and marked per NEC.
Note:** System needs a separate 120 volt circuit to power the contactor box.
DIAGRAM 3
- Back of sensor
- Insert screwdriver tip here to unsnap sensor cover from sensor.
DIAGRAM 4
- Mount the sensor on ceiling. See Diagram 1 for location.
DIAGRAM 5
WIRING DIAGRAM: CONTROL AND HEATER MODELS
Pro/Laava 10.5, 12.0, & 14.4 with CB 17-1 and SL2-C (1601-43)
-
1 Phase Wiring Diagram
-
Power From Breaker Box
-
Circuit 1 Heater Power
-
Circuit 2 Heater Power
-
To CB 18-1 Box (Optional)
-
Input 120 Volt Circuit
-
CB 17-1
(Model # 1201-17-1) -
Power Supply
-
CN 1 Control (RJ 11)
-
CN 8 Light (Optional)
-
CN 10 Door Switch
-
CN 5 High Limit
-
CN 4 Sensor
-
CN 7 BlueTooth (Optional)
-
Primary Heater
-
Heater High Limit Wire
-
High Limit
-
208V or 240V
1-phase -
Heater Models
1105-105
1105-1052
1105-120
1105-1202
1105-140
1105-1402 -
HEATER JUNCTION BOX
-
Heater Input
– – – – – Field Wiring
27 Oct 2020
| 24-0012| 354 SKLE 32 A
---|---|---
WIRING DIAGRAM: CONTROL AND HEATER MODELS
Pro/Laava 10.5, 12.0, & 14.4 with CB 17-3 and SL2-C (1601-43)
-
3 Phase Wiring Diagram
-
Power From Breaker Box
-
Circuit 1 Heater Power
-
To CB 18-3 Box (Optional)
-
Input 120 Volt Circuit
-
CB 17-3
(Model # 1201-17-3) -
Power Supply
-
CN 1 Control (RJ 11)
-
CN 8 Light (Optional)
-
CN 10 Door Switch
-
CN 5 High Limit
-
CN 4 Sensor
-
CN 7 BlueTooth (Optional)
-
Primary Heater
-
Heater High Limit Wire
-
High Limit
-
208V or 240V
1-phase -
Heater Models
1105-105
1105-1052
1105-120
1105-1202
1105-140
1105-1402 -
HEATER JUNCTION BOX
-
Heater Input
– – – – – Field Wiring
27 Oct 2020
| 24-0013| 354 SKLE 32 A
---|---|---
DIAGRAM 6: SL2-C OPENING COVER
Tip to Remove Cover:
Press down on the top edge of the glass and then put the screw driver in the
notch below.
This allows the bottom tabs to release easier.
DIAGRAM 7: SL2-C MOUNTING
SECTION 7: CONTROL INSTALLATION & OPERATION
INSTALLATION ROUGH IN The SL2-C (1601-43) control must be mounted outside the sauna room in a dry environment. See Diagram 12 for control opening.
To mount the control cut an opening 2-3/4 ” wide by 4-3/4″ tall. Route the control wire from CB Box to the control. Note: Use the factory supplied cable only! Do not staple through or otherwise damage the cable!
Remove glass from touch screen, (See Diagram 6) using flat blade screwdriver (See Diagram 5, 6, and 12) and attach the two plastic “wings” with the screws provided. The wings will rotate during installation and secure the box in the wall. (See Diagram 7) Connect the control cable to the back of the circuit board with the RJ 11 cable and secure the control to the wall by 2 mounting screws provided.
Connect the other end of the control cable through the electrical access hole on the bottom of the control box and connect it to CN1
OPERATING INSTRUCTIONS FOR TRADITIONAL SAUNA HEATER
Press the SL2-C icon once. The default settings for the temperature is 194°F, the bath time is 60 minutes(1601-43). These settings are adjustable (as described below) from 119° to 194°. Length of sauna can be set from 0 to 60 minutes. The time delay before start can be up to 24 hours. Any changes are remembered by the heater for your next bath. Should the heater power be lost then restored, the settings will return to their default values.
SETTING THE DURATION AND TEMPERATURE
Press the icon for time “+” or “2 icon on the SL2-C to increase or decrease time for desired setting. The maximum of time is 60 minutes.
Note: SL2-C24 (1601-43-1) Can operate for 24 hours in a commercial application where there is attendance on duty.
Press the icon and then press “+” or “-” icon on the SL2 to increase or decrease temperature for desired setting. The maximum temperature is 194°F (90°C).
- Power
- Increase
- Delay
- Temperature
- Heat Time
- Lights
- Decrease
- BlueTooth
Note: Typical bathing temperature is 150F to 165F displayed on the control.
PRE-SET DELAYED START Press the icon and delay time will appear in the display and will toggle between “dlay” the amount of time remaining. The maximum of time is 24 hours. If no delay is desired, press button to toggle off the function.
LIGHTING OPERATION (Optional) SL2 is capable of operating ONLY a Lighting package purchased with the system. Press the icon to cycle through lighting options. Press and hold the icon for 3 seconds to turn off the light from during any color. Light will automatically turn off after 10 minutes the sauna cycle is completed.
Color sequence — White — Red — Green — Blue — Yellow — Aqua — Purple — Rotation of Colors – Off
Choose the color of choice and then set lighting brightness. The brightness will be on display for 3 seconds. Press the ” +” or “-” button to increase or decrease the light setting. The setting options are 25, 50, 75, and 100% light output.
BLUETOOTH OPERATION (Optional) SL2 is capable of operating ONLY a Bluetooth package purchased with the system. Press the icon to turn on or off to the system.
EXTERNAL SWITCH (1601-36) is a momentary, illuminated switch provides simple ON/OFF function to your SL2-C Control. In a commercial environment, it is recommended that the main Sauna Control be located either in a utility closet or at the Attendant’s desk so the sauna time and temperature functions can be secured from the general public. This optional external switch will provide the sauna bather with the ability to turn the sauna ON or OFF only.
When the momentary switch is activated, the power icon will illuminate in blue and activate the sauna session that has been programmed on the SL2-C. Pressing the switch when it is illuminated will remove power to the sauna heater and end the bathing session.
This switch cannot function as a control. It has to be connected to the system with another control.
WARNING
Do not locate benches over heater. Refer to Diagram 1 for minimum clearance of ceiling above heater is required.
Minimum clearance from heater to wooden surfaces (benches, side walls, heater fence etc.) is required. Refer to Diagram 1 for specific information.
Use only copper wire of the size and type indicated in the Heater Specification Chart and the temperature rating indicated on the heater junction box.
All heaters and controls must be grounded per NEC to prevent electrical shock in case of unit failure.
Electrical outlets or receptacle must not be installed in a sauna room.
A guardrail or fence is required around the heater to prevent burns from accidental contact.
SECTION 8: LIMIT CONTROL (RESET BUTTON)
The sauna heater has a built-in High Limit control, which automatically turns off the heater if the temperature inside in the sauna room rises to an abnormally high level.
To restart the heater, let the heater cool and the timer run down to zero (off), then push the reset button (wire) on the bottom of the heater, See Diagram 2. If the High Limit continually shuts off the heater, refer to Section 14 for Troubleshooting.
SECTION 9: HOW TO TAKE A SAUNA
- When taking a sauna, allow time to relax completely.
- Remove clothing and jewelry…if required, wear a towel loosely.
- After 10 minutes or when perspiration begins, leave sauna and relax in dressing area…follow with a cool shower.
- Cooling time should equal time spent in sauna. Enter sauna room again and stay 5 or 10 minutes.
- Repeat the cycle 2 or 3 times; end with a brisk shower…rinse in cool water.
- Dress when completely dry and perspiration has stopped.
- Some sauna bathers enjoy the soothing effect of steam by splashing water on the heated sauna rocks. Use only one dipper full (approx. ½ cup) at a time and take care to keep clear of the steam as it rises off the rocks.
- Do not smoke, exercise or drink alcoholic beverages in the sauna room.
- Do not pour chlorinated pool or spa water on the heater or corrosion damage may result.
SECTION 10: WARNING PLACARDS
Two metal placards are included in the Installation Instruction Envelope
packaged with every Sauna Heater. The CAUTION placard must be attached to the
interior wall of the sauna room directly above the heater where it is visible
to the bather.
The WARNING placard must be attached to the door of the sauna room.
SECTION 11: ROOM CONSTRUCTION
- For safety and reliability, the following rules must be addressed.
- No permanent locking or latch system is to be used on the sauna door.
- Acceptable door fittings are: magnetic catches, friction catches, spring or gravity loaded closures.
- The door must always open outwards.
- No shower may be installed in a sauna room.
- No electrical receptacle shall be installed inside the sauna room.
- The enclosed WARNING: Reduce the risk of overheating … warning plate must be mounted on or alongside the door outside the sauna room at about eye level.
- The enclosed CAUTION: Reduce the risk of fire … caution plate must be mounted on the interior wall above the heater.
- The heater should not be operated without its container properly filled with rocks and the rock guard in place.
- If an intercom speaker is installed, it should be away from the heater and as close to the floor as possible.
- Fire sprinkler systems installed inside any sauna room should be properly rated for sauna room temperatures.
- Always mount the heater according to these installation instructions.
- Minimum of R12 insulation in 16″ on center 2×4 stud walls.
- Recommended minimum flooring thickness of 5/8″
Shower
Sauna (10 – 15 min.)
Shower or swim
Rest (10 – 15 min.)
Relax with juice or water
You liked it?
Do it once again and you will feel great.
DIAGRAM 8
TYPICAL PRE-CUT WALL CONSTRUCTION
- 2×4″ framing
- 1/2″ wallboard
- fiberglass insulation
- foil vapor barrier
- T&G soft wood
SECTION 12: VENTILATION
VENTILATION Ventilation shall be provided in a sauna, the air should be changed about 6 times an hour. This can be achieved by making a vent opening (fresh air inlet) in the sauna wall directly below the heater. The air outlet must be lower than the upper benches, as far as possible from the heater and about two feet higher than the fresh air inlet vent, See Diagram 9.
The minimum opening should be determined using one of the following formulas:
For R < 31, V ≥9.4
For R ≥ 31, V ≥ 0.3R
R = the floor area of the room in square feet
V = the minimum vent size in square inches
DIAGRAM 9
- Air Outlet Vent
- Air Inlet Vent
The “CAUTION” and “WARNING” placards must be mounted in accordance with Section 10.
WARNING
REDUCE THE RISK OF OVERHEATING
- Exit immediately if uncomfortable, dizzy, or sleepy. Staying too long in a sauna is capable of causing overheating.
- Supervise children at all times.
- Check with a doctor before use if pregnant, in poor health, or under medical care.
- Breathing heated air in conjunction with consumption of alcohol, drugs: or medication is capable of causing unconsciousness.
CAUTION
REDUCE THE RISK OF FIRE
Do Not Place Combustible Material On The Heater At Any Time.
For safety purpose sauna door must open out and not lock.
Never use a wood stain, seal or preservative on the inside of your sauna room.
Light fixtures get very hot during operation. Locate light fixture where it will not be a burn hazard.
DIAGRAM 10: ROOM TEMPERATURES
- Ceiling
- Head Height
- Upper Bench
- Bench Support
- Lower Bench
- Floor
Non-Typical Ceiling Height
Notes:
Temperatures vary in a sauna room by height and distance from heater.
Ventilation will help reduce it but will not eliminate temperature variations.
The hottest part of the room is always at the ceiling directly above the sauna heater and should not exceed 194°F (90°C).
Air temperature will be 15°F to 25°F lower on the opposite side of the room from the heater close to the ceiling.
The temperatures in the elevated view are general numbers. Each sauna room is different due to construction variations and ventilation.
Typical Ceiling Height
SECTION 13: MAINTENANCE
Inspect sauna room at the end of each day the room to ensure the control and system is off.
The sauna, like a bathroom, should be kept clean and odor free. Towels or mats should always be used on benches and floor as perspiration otherwise penetrates the soft wood.
Air out the sauna often by keeping the door and vents open when the sauna is not in use. Saunas that are in daily use should be washed down at least once a week to keep them clean and the air fresh. Duckboard should be removed from the sauna, the sauna floor mopped and dried in a conventional manner, and the duckboard thoroughly scrubbed and dried before returning to the sauna room. The sauna heater should be wiped down occasionally with a damp cloth to remove lint and dust. The rocks should be removed once a year for cleaning and small or crumbled rocks replaced.
To clean and remove perspiration stains, use soap or detergent in warm water,
best applied with a scrub brush.
Badly soiled surfaces may require sanding. Sand paper wrapped around a wooden
block works well.
Benches and supporting structure must be inspected annually for potential deterioration due to age, dry rot or abuse. Any boards with signs of deteriorations should be replaced immediately to avoid possible injury.
SECTION 14: TROUBLESHOOTING
If control displays “Pre-Heat’ it means there is no sensor connected to the CB Box or the room temperature is below 10°F. Refer to Section 5 for sensor installation information. Note: the system will heat for 5 minutes and then turn off and error “No Sensor” if a sensor is not connected to CN 4.
If control displays “HL” it means the high limit is open. Refer to Section 9 for high limit information how to reset the device. If the heater continues to have the high limit issue, check placement of sensor for correct location.
If the control displays “Door Open” check to see if the there is a connector on CN 10.
System wont start to heat, ensure the system is not in the delay mode. If “dLAY” is flashing in the display window, the system is in the delay mode.
If control acts erratically or buttons turn on and off by itself during startup. Turn power off at the 120 Volt circuit breaker for control power, place the glass on the control and turn power back on the system. The control will automatically reset the sensitivity of the capacitive switches. Turn power back on and test.
CAUTION: Use only a contactor approved for 250,000 endurance Cylces
For troubleshooting or service questions call 1-888-780-4427 and ask to speak with service. Prior to calling, please have the Model and Type number available. You may also email us at techsupport@tyloheloinc.com
This page is left blank intentionally.
DIAGRAM 12: SL2 Control Mounting
Recessed Mounting For the SL2-C Control
The recessed mounting box allows the control to mount with its surface
almost even to the wall surface. Print this page to “Actual” Size on Printer
Options. (This will ensure the size of the opening is correct). Cut out the
middle of this page on the dotted lines. The hole will be the size of the
mounting box. Insert the mounting box in the hole of this page to ensure it is
the correct size.
Trace the paper cut out on the wall. Cut a hole in the wall to match the inner dotted line for the mounting box. Run the control cable out of the wall through the hole in the mounting box. Ensure the hole is just big enough to mount the box. Push the mounting box into the hole and turn the mounting screws to pull the tab tight against the inside of the wall. Ensure the box is level and the correct end is UP (there is an arrow on the wall side of the box pointing up).
Connect the Control coupler to the control cable then feed the cables and connector through the hole in the box and into the wall. Test the Control before mounting it into the wall.
Hang the top of the control glass on the top of the recessed box and press the bottom of glass to snap on to box.
-
Level Line
-
Print Page as “Actual” Size
Cut on Dotted Line and remove this part of page
Trace This Inner Opening on the Wall
Solid Line represents the outline of the housing lip. -
Print page to “Actual Size”; do not select “Fit” to page on printer Page Sizing.
72-0139 05-05-2021 7013549 314 SKLE 84 A
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>