TEM8A0B24V21DC Communicating 24 Volt Control Convertible Air Handlers User Manual
- June 13, 2024
- TEM
Table of Contents
- TEM8A0B24V21DC Communicating 24 Volt Control Convertible Air Handlers
- Product Information
- Product Usage Instructions
- SAFETY SECTION
- Features
- Installation Instructions
- Sequence of Operation
- Electrical — Low Voltage
- Performance and Electrical Data
- Minimum Airflow CFM
- Outline Drawing
- Heater Pressure Drop Table
- Coil Conversion Instructions
- Checkout Procedures
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
TEM8A0B24V21DC Communicating 24 Volt Control Convertible Air Handlers
Product Information
The TEM8 series air handler is a versatile unit designed for installation in various locations such as closets, utility rooms, alcoves, basements, crawlspaces, or attics. It is suitable for both air conditioning and heat pump applications. The series includes the following models: TEM8A0B24V21DC, TEM8A0B30V31DC, TEM8A0C36V31DC, TEM8A0C42V41DC, TEM8A0C48V41DC, and TEM8B0C60V51DA. Field installed electric resistance heaters are also available.
Product Usage Instructions
Installation: Only qualified personnel should install the equipment. Ensure the unit is placed in a suitable location as mentioned in the manual (closet, utility room, alcove, basement, crawlspace, or attic). Refer to the wiring diagram, parts list, and service information provided in the manual. Grounding of the unit is required and all grounding devices must be properly connected.
- Safety Precautions: Before servicing the equipment, disconnect all electric power, including remote disconnects. Follow proper lockout/tagout procedures to prevent accidental energization. When working with live electrical components, follow all electrical safety precautions. Be cautious of sharp edges on the equipment or sheet metal cuts.
- Service and Troubleshooting: Only qualified personnel should service the equipment. Refer to the service information pack provided with the unit. If further information or assistance is needed, contact your installing dealer or local distributor.
- Refrigerant Handling: When dealing with refrigerant, follow the necessary precautions. The system contains oil and refrigerant under high pressure. Before opening the system, recover the refrigerant to relieve pressure. Only use approved refrigerants and avoid using substitutes or additives.
SAFETY SECTION
Important: This document contains a wiring diagram, a parts list, and
service information. This is customer property and is to remain with this
unit. Please return to service information pack upon completion of work.
Important: These instructions do not cover all variations in systems nor
provide for every possible contingency to be met in connection with the
installation. Should further information be desired or particular problems
arise that are not covered sufficiently for the purchaser’s purposes, the
matter should be referred to your installing dealer or local distributor.
WARNING: HAZARDOUS VOLTAGE!
Failure to follow this Warning could result in property damage, severe
personal injury, or death. Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/tagout procedures to
ensure the power cannot be inadvertently energized.
CAUTION: GROUNDING REQUIRED!
Failure to inspect or use proper service tools may result in equipment damage
or personal injury. Reconnect all grounding devices. All parts of this product
that are capable of conducting electrical current are grounded. If grounding
wires, screws, straps, clips, nuts, or washers used to complete a path to the
ground are removed for service, they must be returned to their original
position and properly tastened
WARNING: LIVE ELECTRICAL COMPONENTS!
Failure to follow this warning could result in property damage, severe
personal injury, or death.
Follow all electrical safety precautions when exposed to live electrical
components. It may be necessary to work with live electrical components during
installation, testing, servicing, and troubleshooting of this product.
WARNING: PRESSURIZED REFRIGERANT!
- Failure to follow this Warning could result in personal injury
- System contains oil and refrigerant under high pressure. Recover refrigerant to relieve pressure before opening the system. Do no use nonapproved refrigerants or refrigerant substitutes or refrigerant additives.
CAUTION: SHARP EDGE HAZARD!
Failure to follow this Caution could result in property damage or personal
injury. Be careful of sharp edges on equipment or any cuts made on sheet metal
while installing or servicing.
CAUTION: HAZARDOUS VAPORS!
Failure to follow this caution could result in property damage or personal
injury. Equipment corrosion damage. To prevent shortening its service life,
the air handler should not be used during the finishing phases of construction
or remodeling. The low return air temperatures can lead to the formation of
condensate. Condensate in the presence of chlorides and fluorides from paint,
varnish, stains, adhesives, cleaning compounds, and cement creates a corrosive
condition which may cause rapid deterioration of the cabinet and internal
components
CAUTION: COIL IS PRESSURIZED!
- Coil is pressurized with approximately 8–12 psi dry air and factory checked for leaks.
- Carefully release the pressure by removing the rubber plug on the liquid line.
- If no pressure is released, check for leaks.
WARNING: SAFETY HAZARD!
This appliance is not to be used by persons (including children) with reduced
physical, sensory, or mental capabilities, or lack of experience and
knowledge, unless they have been given supervision or instruction
WARNING: SAFETY HAZARD!
Children should be supervised to ensure that they do not play with the
appliance
- This product can expose you to chemicals including lead, which are known to the State of
- California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov.
Important: Installation of this unit shall be made in accordance with the
National Electric Code, NFPA No. 90A and 90B, and any other local codes or
utilities requirements.
Important: Air handlers do not require repositioning of the coil or drain
pan for upflow or horizontal left applications. See the downflow and
horizontal right installation sections for application instructions.
Note: Air handlers have been evaluated in accordance with the Code of
Federal Regulations, Chapter XX, Part 3280 or the equivalent. “SUITABLE FOR
MOBILE HOME USE.”
Note: Condensation may occur on the surface of the air handler when
installed in an unconditioned space. When units are installed in unconditioned
spaces, verify that all electrical and refrigerant line penetrations on the
air handler are sealed completely.
Note: The manufacturer recommends installing ONLY A.H.R.I approved,
matched indoor and outdoor systems. Some of the benefits of installing
approved matched indoor and outdoor split systems are maximum efficiency,
optimum performance, and the best overall system reliability
Features
Standard Features
-
COMMUNICATING OR 24 VOLT CONTROL
-
MULTI-POSITION UPFLOW, DOWNFLOW, HORIZONTAL LEFT AND HORIZONTAL RIGHT
-
PAINTED FINISH ON GALVANIZED STEEL EXTERIOR WITH
FULLY INSULATED CABINET THAT MEETS R4.2 VALUE -
STURDY POLYCARBONATE DRAIN PANS
- The TEM air handler has factory installed drain pans and is shipped for upflow and horizontal left applications
-
208/230 VAC OPERATION
-
VARIABLE-SPEED DIRECT DRIVE BLOWER.
-
FACTORY INSTALLED R-410A THERMAL EXPANSION VALVE
-
ALL ALUMINUM COIL
-
BOTTOM RETURN
-
MEETS THE MINIMUM LEAKAGE REQUIREMENTS FOR THE
FLORIDA AND CALIFORNIA BUILDING CODES
Optional Accessories
- 4,5,8,10,15,20, and 25 KW SINGLE PHASE ELECTRIC HEATERS
- Circuit breakers available on single phase 4, 5, 8, 10, 15, 20, and 25 KW heaters
- Lugs available on single phase 4, 5, 8, and 10 KW heaters
- Lugs available on three phase 10 and 15 KW heaters
- SINGLE POINT POWER ENTRY KIT (for 15 and 20 KW heaters)
- SUPPLY DUCT FLANGE KIT
- DOWNFLOW SUB-BASE KITS – TAYBASE185, TAYBASE235, TAYBASE260
- SLIM FIT FILTER BOX KIT — BAYSF1185AAA, BAYSF1235AAA, BAYSF1265AAA
Installation Instructions
-
Unpacking
Carefully unpack the unit and inspect the contents for damage. If any damage is found at the time of delivery, proper notification and claims should be made with the carrier.
Check the rating plate to assure model number and voltage, plus any kits match with what you ordered. The manufacturer should be notified within 5 days of any discrepancy or parts shortage. -
Location
The air handler should be centrally located and may be installed in a closet, alcove, utility room, basement, crawl space or attic. Minimum clearances must be met.
The unit should be installed in a level position to ensure proper condensation drainage. Up to an additional 1/4” rise over the width or depth of the unit is allowed to create additional sloping towards the drain. Unit must be positioned between level and ¼” rise, sloping toward the drain connections. When the unit is installed in a closet or utility room, the room should be large enough, and have an opening to allow replacement of the unit. All servicing is done from the front and a clearance of 21″ is needed for service unless the closet door aligns with the front of the air handler.
If you are installing the unit in an unconditioned space such as an attic or crawl space, you must ensure that the area provides sufficient air circulation to prevent moisture collection on the cabinet during high dew point conditions. A drain pan must be installed under the entire unit when it is installed in or above a finished ceiling or in an unconditioned space. -
Duct Work
The duct work should be installed in accordance with the NFPA No. 90A “Installation of Air Conditioning and Ventilating systems” and No. 90B “Residential Type Warm Air Heating and Air Conditioning Installation.”
The ductwork should be insulated in accordance with the applicable requirements for the particular installation as required by HUD, FHA, VA the applicable building code, local utility or other governing body. -
Condensate Drain
The unit is supplied with primary and auxiliary condensate drains that have 3/4″ NPT connections. The primary drain must be trapped outside the unit and piped in accordance with applicable building codes.
The figure shows the operation of a properly designed trap under normal operating conditions when the blower is running and the condensate is draining. Note the difference in height of the water column must at least equal the normal negative static pressure existing during operation between the cooling coil and blower. It is advisable to have the difference in water column height somewhat greater than the normal maximum operating static to allow for greater static caused by dirty filters or for the bounce of the water column on start up.-
Proper operation of condensate trap under normal operating conditions.
-
“A” height of water column equals negative static pressure existing in system. “C” dimension should at least equal two times the maximum negative static pressure that can occur in system.
Do not reduce the drain line size less than the connection size on the drain pan. Condensate should be piped to an open drain or to the outside. All drains must pitch downward away from the unit a minimum of 1/4″ per foot of line to ensure proper drainage -
Important: If cleanout Tee is used, stand pipe must be sealed/capped.
-
Important: If a vent Tee is used, it must be downstream from the trap. Insulate the primary drain line to prevent sweating where dew point temperatures may be met. (Insulation is optional depending on climate and application needs.)
-
-
Refrigerant Piping
Refrigerant piping external to the unit shall be sized in accordance with the instructions of the manufacturer of the outdoor equipment. -
Metering Device
All units are shipped and installed with an internally-checked, non-bleed TXV designed for air conditioning or heat pump operation. Some outdoor models may require a start assist kit. See outdoor unit for more information. -
Blower
This unit is supplied with a variable speed motor with a direct drive blower wheel which can obtain various air flows. The unit is shipped with factory set cooling and heating air flows. Performance tables are available for additional airflow settings. Disconnect all power to the unit before making any adjustments to the airflow settings. Be sure to check the air flow and the temperature drop across the evaporator coil to ensure sufficient air flow. -
Airflow Adjustment
Note: A CDA tool may be plugged into the TEM8
Refrigerant piping external to the unit shall be sized in accordance with the instructions of the manufacturer of the outdoor equipment.
Table 3. Delay Options
The blower delay profile is to be configured for heating and cooling modes of operation. There are 4 blower off delay options
Option 1| 90 seconds at 100% air flow
Option 2| No delay
Option 3| 180 seconds at 50% air flow
Option 4| Enhanced Mode
Wiring
- Consult all schematic and pictorial wiring diagrams of this unit and the outdoor equipment to determine compatibility of wiring connections and to determine specific requirements.
- All field wiring to the air handler should be installed in accordance with the latest edition of the National
Electric Code NFPA No. 70 and any local codes. Check rating plates on unit for rated volts, minimum circuit ampacity and maximum over current protection. Supply circuit power wiring must be 75 degree C (167 degree F) minimum copper conductors only. Copper supply wires shall be sized to the National Electric Code or local code requirements, whichever is more stringent.
The unit is shipped wired for 230/240 Volt AC 60 HZ 1 Phase Operation. If the unit is to be operated at 208 VAC 60HZ, follow the instructions on the indoor unit wiring diagram to change the low voltage transformer to 208 VAC operation (Ensure unit is properly grounded).
Class 2 low voltage control wiring should not be run in conduit with power
wiring and must be separated from power wiring unless class 1 wire with proper
voltage rating is used.
Low voltage control wiring should be 18 Awg, color coded (105 degree C
minimum). For lengths longer than 100ft., 16 Awg wire should be used. Make
certain that separation of control wiring and power wiring has been
maintained.
Air Filter
To protect the coil, blower and other internal parts from excessive dirt and
dust an air filter must be installed before air enters the evaporator coil. A
remote filter must be installed. Consult the filter manufacturer for proper
sizing and maximum velocity requirements.
Important: Air filters shall meet the test requirements in UL 900.
Operational and Checkout Procedures
To obtain proper performance, all units must be operated and charge
adjustments made in accordance with procedures found in the Service Facts
document of the outdoor unit. After installation has been completed, it is
recommended that the entire system be checked against the checkout list
located at the back of this document. See “Checkout Procedures,” p. 27.
Maintenance
The system air filter(s) should be inspected, cleaned or replaced at least
monthly. Make certain that the access panels are replaced and secured properly
before placing the unit back in operation. This product is designed for
dependable service; however, periodic maintenance should be scheduled and
conducted by trained professional service personnel. This service should be
conducted at least annually and should include testing and inspection of
electrical and refrigerant components, flushing of condensate drain, and
repriming of condensate trap. The heat transfer surface should be cleaned. The
blower motor is permanently lubricated for normal operating conditions.
Sequence of Operation
Abbreviations
- AFC = Airflow Control
Note: Use variable speed outdoor Sequence of
Operation in conjunction with the TEM8
Sequence of Operation.
The installing and servicing technician should have an understanding of the sequence of operation to be able to properly setup and diagnose functions of the air handler.
See unit, electric heat, and field wiring diagrams for additional information
Continuous Fan
Important: If the indoor air exceeds 60% relative humidity or simply feels uncomfortably humid, it is recommended that the indoor fan only be used in the AUTO mode.
- When a fan request is received from the thermostat, the AFC sends a command to the serial communicating blower motor to run. Airflow can be adjusted through the thermostat.
- Humidity Control – When enabled at the thermostat, this feature will disable any blower off delays and disable continuous fan mode when the humidity is above the dehumidification setpoint. This will help prevent coil condensation from being evaporated back into the air stream.
Cooling Mode
- When a request for 1st stage cooling is received, the AFC sends a command to the serial communicating blower motor to run at 1st stage cooling airflow. (Delay profiles from the thermostat may change blower motor timing and actual airflow demand)
- When a request for 2nd stage cooling is received, the AFC sends a command to the serial communicating blower motor to run at 100 % cooling airflow.
- When a request for cooling is removed, the AFC will turn off the blower motor after any user selected fan-off delays have expired.
Note: Delay profiles from the thermostat may change blower motor timing and actual airflow demand
Heat pump (compressor only)
- When a request for 1st stage heat is received, the AFC sends a command to the serial communicating blower motor to run at 1st stage heating airflow.
- Humidifier contacts close on demand from thermostat.
- When a request for 2nd stage mechanical heat is received, the AFC sends a command to the serial communicating blower motor to run at 100 % heating airflow.
- When a request for heat pump is removed, the AFC will turn off the blower motor after any user selected fan-off delays have expired.
Note: Delay profiles from the thermostat may change blower motor timing and actual airflow deman
Electric Heat
- When a request for electric heat is received, the AFC will energize the on board 24 volt relays per the amount of heat requested from the thermostat and the size of the heater installed.
- The AFC sends a command to the serial communicating blower motor to run proper airflow and close the blower interlock relay on the EHC.
Defrost
- The OD unit will initiate defrost and send a message to the AFC.
- Electric or hydronic heat will be energized to help temper the air.
Unit Test Mode
Unit Test Mode will exit if any demand is given to the unit.
To enter Unit Test Mode:
- Set System Switch on comfort control to Off.
- Scroll down to the Unit Test selection and push the “Enter” button
Sequence of Unit Test Mode (OD unit is not energized during the Unit Test Mode
- AFC energizes the blower at 50% and then continues to ramp until it reaches 100% cooling airflow.
- Humidifier contacts close when the blower starts.
- AFC energizes the W relays in 10 second intervals. The blower remains at 100% air flow.
- All relays de-energize and the blower shuts off five seconds after the last bank of heat is energized.
Note: If an error occurs during the Unit Test Mode, the Fault LED will flash a code and continue the test.
Electrical — Low Voltage
Table 4. Low Voltage Maximum Wire Length
The Low Voltage Maximum Wire Length table defines the size and combined total maximum length of the low voltage wiring from the outdoor unit, to the indoor unit, and to the thermostat.
Note: The use of color coded low voltage wire is recommended to simplify connections between the outdoor unit, the control, and the indoor unit.
Control Wire — Communicating
WIRE SIZE| MAX. WIRE LENGTH
18 AWG| 500 FT. Combineed
Control Wire — 24 Volt
WIRE SIZE| MAX. WIRE LENGTH
18 AWG| 100 FT. Combineed
Humidifier and External Switch
Table 6. Low Voltage Hook-up Instructions
Communicating Controls Wiring Diagram
Wiring D806011P02revA
Performance and Electrical Data
TEM8A0B24V21DC AIRFLOW PERFORMANCE CONSTANT CFM MODE / CONSTANT TORQUE MODE
OUTDOOR MULTIPLIER (TONS)| COOLING AIRFLOW SETTING| AIRFLOW POWER| EXTERNAL STATIC PRESSURE (Constant CFM / Constant
Torque)
| HEATING AIRFLOW SETTING| AIRFLOW POWER| EXTERNAL STATIC PRESSURE
0.1| 0.3| 0.5| 0.7| 0.9| 0.1| 0.3| 0.5| 0.7| 0.9
1.5 tons
| 290
CFM/ton
| CFM
Watts
| 430 / 538
50 / 39
| 430 / 415
75 / 48
| 430 / 264
95 / 43
| 430 / NA
110 / NA
| 430 / NA
145 / NA
| 290
CFM/ton
| CFM
Watts
| 434
34
| 419
64
| 419
96
| 403
130
| 384
167
350
CFM/ton
| CFM
Watts
| 520 / 620
60 / 53
| 520 / 514
90 / 64
| 520 / 398
120 / 61
| 520 / NA
135 / NA
| 510 / NA
175 / NA
| 350
CFM/ton
| CFM
Watts
| 521
44
| 512
77
| 514
112
| 500
153
| 485
196
400
CFM/ton
| CFM
Watts
| 590 / 688
75 / 67
| 590 / 593
105 / 80
| 590 / 493
140 / 80
| 590 / NA
160 / NA
| 590 / NA
205 / NA
| 400
CFM/ton
| CFM
Watts
| 595
56
| 589
91
| 595
127
| 584
173
| 573
222
450
CFM/ton
| CFM
Watts
| 670 / 758
85 / 85
| 670 / 671
125 / 100
| 660 / 581
160 / 102
| 660 / NA
190 / NA
| 660 / NA
235 / NA
| 450
CFM/ton
| CFM
Watts
| 668
71
| 667
107
| 675
145
| 668
196
| 660
250
2 tons
| 290
CFM/ton
| CFM
Watts
| 570 / 670
60 / 63
| 570 / 573
90 / 76
| 570 / 469
125 / 75
| 570 / NA
165 / NA
| 568 / NA
215 / NA
| 290
CFM/ton
| CFM
Watts
| 575
53
| 569
87
| 573
123
| 561
167
| 549
215
350
CFM/ton
| CFM
Watts
| 690 / 781
85 / 91
| 690 / 696
120 / 107
| 690 / 609
160 / 110
| 690 / 518
210 / 98
| 680 / NA
259 / NA
| 350
CFM/ton
| CFM
Watts
| 693
76
| 693
113
| 702
152
| 696
204
| 689
259
400
CFM/ton
| CFM
Watts
| 790 / 875
110 / 122
| 790 / 798
150 / 140
| 790 / 720
195 / 145
| 780 / 639
250 / 137
| 780 / 555
301 / 115
| 400
CFM/ton
| CFM
Watts
| 791
103
| 795
143
| 805
184
| 803
240
| 798
301
450
CFM/ton
| CFM
Watts
| 890 / 971
145 / 161
| 890 / 899
185 / 181
| 880 / 827
235 / 189
| 880 / 754
295 / 184
| 880 / 680
347 / 184
| 450
CFM/ton
| CFM
Watts
| 889
138
| 895
181
| 902
226
| 899
284
| 891
347
2.5 tons †
| 290
CFM/ton
| CFM
Watts
| 720 / 823
90 / 104
| 720 / 741
140 / 120
| 710 / 659
170 / 124
| 710 / 573
220 / 115
| 710 / 481
260 / 91
| 290
CFM/ton
| CFM
Watts
| 717
82
| 718
120
| 728
159
| 723
212
| 717
269
350
CFM/ton
| CFM
Watts
| 870 / 963
140 / 157
| 860 / 892
182 / 177
| 873 / 819
235 / 185
| 860 / 746
280 / 180
| 850 / 671
330 / 161
| 350
CFM/ton
| CFM
Watts
| 865
128
| 871
170
| 879
214
| 876
272
| 869
335
390 †
CFM/ton
| CFM
Watts
| 958 / 1075
147 / 170
| 975 / 1000
203 / 195
| 946 / 878
269 / 211
| 871 / 711
342 / 197
| 802 / 617
403 / 189
| 390 †
CFM/ton
| CFM
Watts
| 958
138
| 979
192
| 957
257
| 878
336
| 822
406
400
CFM/ton
| CFM
Watts
| 980 / 1100
157 / 181
| 993 / 1019
213 / 205
| 958 / 889
280 / 219
| 875 / 714
357 / 205
| 801 / 616
418 / 196
| 400
CFM/ton
| CFM
Watts
| 980
146
| 998
202
| 969
268
| 882
351
| 821
422
450
CFM/ton
| CFM
Watts
| 980 / 1100
157 / 181
| 993 / 1019
213 / 205
| 958 / 889
280 / 219
| 875 / 714
357 / 205
| 801 / 616
418 / 196
| 450
CFM/ton
| CFM
Watts
| 980
146
| 998
202
| 969
268
| 882
351
| 821
422
• † Factory Setting
• Status LED will blink once per 100 CFM requested. In torque mode, actual airflow may be lower.
• To prevent water blow-off, the max airflow demand allowable is 1000 CFM. If an outdoor multiplier and cooling airflow setting should result in a demand higher than 1000, the AFC will default the demand back to 1000.
| • Torque mode will reduce airflow when static is above approximately 0.3″ water column.
• All heating modes default to Constant CFM.
• In communicating mode, default CFM/Ton is 400.
• Cooling airflow values are with wet coil, no filter
OUTDOOR
MULTIPLIER (TONS)
| COOLING AIRFLOW SETTING| AIRFLOW POWER| EXTERNAL STATIC PRESSURE (Constant
CFM / Constant Torque)| HEATING AIRFLOW SETTING| AIRFLOW POWER| EXTERNAL
STATIC PRESSURE
---|---|---|---|---|---|---
0.1| 0.3| 0.5| 0.7| 0.9| 0.1| 0.3| 0.5| 0.7| 0.9
1.5 tons
| 290
CFM/ton
| CFM
Watts
| 430 / 538
50 / 39
| 430 / 415
75 / 48
| 430 / 264
95 / 43
| 430 / NA
110 / NA
| 430 / NA
145 / NA
| 290
CFM/ton
| CFM
Watts
| 434
34
| 419
64
| 419
96
| 403
130
| 384
167
350
CFM/ton
| CFM
Watts
| 520 / 620
60 / 53
| 520 / 514
90 / 64
| 520 / 398
120 / 61
| 520 / NA
135 / NA
| 510 / NA
175 / NA
| 350
CFM/ton
| CFM
Watts
| 521
44
| 512
77
| 514
112
| 500
153
| 485
196
400
CFM/ton
| CFM
Watts
| 590 / 688
75 / 67
| 590 / 593
105 / 80
| 590 / 493
140 / 80
| 590 / NA
160 / NA
| 590 / NA
205 / NA
| 400
CFM/ton
| CFM
Watts
| 595
56
| 589
91
| 595
127
| 584
173
| 573
222
450
CFM/ton
| CFM
Watts
| 670 / 758
85 / 85
| 670 / 671
125 / 100
| 660 / 581
160 / 102
| 660 / NA
190 / NA
| 660 / NA
235 / NA
| 450
CFM/ton
| CFM
Watts
| 668
71
| 667
107
| 675
145
| 668
196
| 660
250
2 tons
| 290
CFM/ton
| CFM
Watts
| 570 / 670
60 / 63
| 570 / 573
90 / 76
| 570 / 469
125 / 75
| 570 / NA
165 / NA
| 568 / NA
215 / NA
| 290
CFM/ton
| CFM
Watts
| 575
53
| 569
87
| 573
123
| 561
167
| 549
215
350
CFM/ton
| CFM
Watts
| 690 / 781
85 / 91
| 690 / 696
120 / 107
| 690 / 609
160 / 110
| 690 / 518
210 / 98
| 680 / NA
259 / NA
| 350
CFM/ton
| CFM
Watts
| 693
76
| 693
113
| 702
152
| 696
204
| 689
259
400
CFM/ton
| CFM
Watts
| 790 / 875
110 / 122
| 790 / 798
150 / 140
| 790 / 720
195 / 145
| 780 / 639
250 / 137
| 780 / 555
301 / 115
| 400
CFM/ton
| CFM
Watts
| 791
103
| 795
143
| 805
184
| 803
240
| 798
301
450
CFM/ton
| CFM
Watts
| 890 / 971
145 / 161
| 890 / 899
185 / 181
| 880 / 827
235 / 189
| 880 / 754
295 / 184
| 880 / 680
347 / 184
| 450
CFM/ton
| CFM
Watts
| 889
138
| 895
181
| 902
226
| 899
284
| 891
347
2.5 tons
| 290
CFM/ton
| CFM
Watts
| 720 / 823
90 / 104
| 720 / 741
140 / 120
| 710 / 659
170 / 124
| 710 / 573
220 / 115
| 710 / 481
260 / 91
| 290
CFM/ton
| CFM
Watts
| 717
82
| 718
120
| 728
159
| 723
212
| 717
269
350
CFM/ton
| CFM
Watts
| 870 / 963
140 / 157
| 860 / 892
182 / 177
| 873 / 819
235 / 185
| 860 / 746
280 / 180
| 850 / 671
330 / 161
| 350
CFM/ton
| CFM
Watts
| 865
128
| 871
170
| 879
214
| 876
272
| 869
335
390
CFM/ton
| CFM
Watts
| 969 / 1087
143 / 166
| 985 / 1011
198 / 191
| 993 / 921
262 / 205
| 992 / 809
329 / 189
| 1000 / 770
399 / 187
| 390
CFM/ton
| CFM
Watts
| 969
134
| 989
188
| 1004
250
| 999
323
| 1026
402
400
CFM/ton
| CFM
Watts
| 993 / 1114
152 / 176
| 1008 / 1035
208 / 200
| 1017 / 943
273 / 214
| 1015 / 828
341 / 196
| 1022 / 787
413 / 194
| 400
CFM/ton
| CFM
Watts
| 993
142
| 1013
197
| 1028
261
| 1023
335
| 1049
416
450
CFM/ton
| CFM
Watts
| 993 / 1114
152 / 176
| 1008 / 1035
208 / 200
| 1017 / 943
273 / 214
| 1015 / 828
341 / 196
| 1022 / 787
413 / 194
| 450
CFM/ton
| CFM
Watts
| 993
142
| 1013
197
| 1028
261
| 1023
335
| 1049
416
3 tons †
| 290
CFM/ton
| CFM
Watts
| 868 / 974
111 / 128
| 884 / 907
163 / 156
| 891 / 826
220 / 173
| 893 / 729
281 / 162
| 894 / 688
345 / 162
| 290
CFM/ton
| CFM
Watts
| 868
103
| 888
154
| 901
211
| 900
277
| 917
347
350
CFM/ton
| CFM
Watts
| 993 / 1114
152 / 176
| 1008 / 1035
208 / 200
| 1017 / 943
273 / 214
| 1015 / 828
341 / 196
| 1022 / 787
413 / 194
| 350
CFM/ton
| CFM
Watts
| 993
142
| 1013
197
| 1028
261
| 1023
335
| 1049
416
390 †
CFM/ton
| CFM
Watts
| 993 / 1114
152 / 176
| 1008 / 1035
208 / 200
| 1017 / 943
273 / 214
| 1015 / 828
341 / 196
| 1022 / 787
413 / 194
| 390 †
CFM/ton
| CFM
Watts
| 993
142
| 1013
197
| 1028
261
| 1023
335
| 1049
416
400
CFM/ton
| CFM
Watts
| 993 / 1114
152 / 176
| 1008 / 1035
208 / 200
| 1017 / 943
273 / 214
| 1015 / 828
341 / 196
| 1022 / 787
413 / 194
| 400
CFM/ton
| CFM
Watts
| 993
142
| 1013
197
| 1028
261
| 1023
335
| 1049
416
450
CFM/ton
| CFM
Watts
| 993 / 1114
152 / 176
| 1008 / 1035
208 / 200
| 1017 / 943
273 / 214
| 1015 / 828
341 / 196
| 1022 / 787
413 / 194
| 450
CFM/ton
| CFM
Watts
| 993
142
| 1013
197
| 1028
261
| 1023
335
| 1049
416
• † Factory Setting
• Status LED will blink once per 100 CFM requested. In torque mode, actual airflow may be lower.
• To prevent water blow-off, the max airflow demand allowable is 1000 CFM. If an outdoor
multiplier and cooling airflow setting should result in a demand higher than 1000, the AFC will default the demand back to 1000.
| • Torque mode will reduce airflow when static is above approximately 0.3″ water column.
• All heating modes default to Constant CFM.
• In communicating mode, default CFM/Ton is 400.
• Cooling airflow values are with wet coil, no filter
OUTDOOR
MULTIPLIER (TONS)
| COOLING AIRFLOW SETTING| AIRFLOW POWER| EXTERNAL STATIC PRESSURE (Constant
CFM / Constant Torque)| HEATING AIRFLOW SETTING| AIRFLOW POWER| EXTERNAL
STATIC PRESSURE
---|---|---|---|---|---|---
0.1| 0.3| 0.5| 0.7| 0.9| 0.1| 0.3| 0.5| 0.7| 0.9
1.5 tons
| 290
CFM/ton
| CFM
Watts
| 430 / 538
50 / 39
| 430 / 415
75 / 48
| 430 / 264
95 / 43
| 430 / NA
110 / NA
| 430 / NA
145 / NA
| 290
CFM/ton
| CFM
Watts
| 434
34
| 419
64
| 419
96
| 403
130
| 384
167
350
CFM/ton
| CFM
Watts
| 520 / 620
60 / 53
| 520 / 514
90 / 64
| 520 / 398
120 / 61
| 520 / NA
135 / NA
| 510 / NA
175 / NA
| 350
CFM/ton
| CFM
Watts
| 521
44
| 512
77
| 514
112
| 500
153
| 485
196
400
CFM/ton
| CFM
Watts
| 590 / 688
75 / 67
| 590 / 593
105 / 80
| 590 / 493
140 / 80
| 590 / NA
160 / NA
| 590 / NA
205 / NA
| 400
CFM/ton
| CFM
Watts
| 595
56
| 589
91
| 595
127
| 584
173
| 573
222
450
CFM/ton
| CFM
Watts
| 670 / 758
85 / 85
| 670 / 671
125 / 100
| 660 / 581
160 / 102
| 660 / NA
190 / NA
| 660 / NA
235 / NA
| 450
CFM/ton
| CFM
Watts
| 668
71
| 667
107
| 675
145
| 668
196
| 660
250
2 tons
| 290
CFM/ton
| CFM
Watts
| 570 / 670
60 / 63
| 570 / 573
90 / 76
| 570 / 469
125 / 75
| 570 / NA
165 / NA
| 568 / NA
215 / NA
| 290
CFM/ton
| CFM
Watts
| 575
53
| 569
87
| 573
123
| 561
167
| 549
215
350
CFM/ton
| CFM
Watts
| 690 / 781
85 / 91
| 690 / 696
120 / 107
| 690 / 609
160 / 110
| 690 / 518
210 / 98
| 680 / NA
259 / NA
| 350
CFM/ton
| CFM
Watts
| 693
76
| 693
113
| 702
152
| 696
204
| 689
259
400
CFM/ton
| CFM
Watts
| 790 / 875
110 / 122
| 790 / 798
150 / 140
| 790 / 720
195 / 145
| 780 / 639
250 / 137
| 780 / 555
301 / 115
| 400
CFM/ton
| CFM
Watts
| 791
103
| 795
143
| 805
184
| 803
240
| 798
301
450
CFM/ton
| CFM
Watts
| 890 / 971
145 / 161
| 890 / 899
185 / 181
| 880 / 827
235 / 189
| 880 / 754
295 / 184
| 880 / 680
347 / 184
| 450
CFM/ton
| CFM
Watts
| 889
138
| 895
181
| 902
226
| 899
284
| 891
347
2.5 tons
| 290
CFM/ton
| CFM
Watts
| 720 / 823
90 / 104
| 720 / 741
140 / 120
| 710 / 659
170 / 124
| 710 / 573
220 / 115
| 710 / 481
260 / 91
| 290
CFM/ton
| CFM
Watts
| 717
82
| 718
120
| 728
159
| 723
212
| 717
269
350
CFM/ton
| CFM
Watts
| 870 / 963
140 / 157
| 860 / 892
182 / 177
| 873 / 819
235 / 185
| 860 / 746
280 / 180
| 850 / 671
330 / 161
| 350
CFM/ton
| CFM
Watts
| 865
128
| 871
170
| 879
214
| 876
272
| 869
335
390
CFM/ton
| CFM
Watts
| 969 / 1087
143 / 166
| 985 / 1011
198 / 191
| 993 / 921
262 / 205
| 992 / 809
329 / 189
| 1000 / 770
399 / 187
| 390
CFM/ton
| CFM
Watts
| 969
134
| 989
188
| 1004
250
| 999
323
| 1026
402
400
CFM/ton
| CFM
Watts
| 993 / 1114
152 / 176
| 1008 / 1035
208 / 200
| 1017 / 943
273 / 214
| 1015 / 828
341 / 196
| 1022 / 787
413 / 194
| 400
CFM/ton
| CFM
Watts
| 993
142
| 1013
197
| 1028
261
| 1023
335
| 1049
416
450
CFM/ton
| CFM
Watts
| 993 / 1114
152 / 176
| 1008 / 1035
208 / 200
| 1017 / 943
273 / 214
| 1015 / 828
341 / 196
| 1022 / 787
413 / 194
| 450
CFM/ton
| CFM
Watts
| 993
142
| 1013
197
| 1028
261
| 1023
335
| 1049
416
3 tons †
| 290
CFM/ton
| CFM
Watts
| 868 / 974
111 / 128
| 884 / 907
163 / 156
| 891 / 826
220 / 173
| 893 / 729
281 / 162
| 894 / 688
345 / 162
| 290
CFM/ton
| CFM
Watts
| 868
103
| 888
154
| 901
211
| 900
277
| 917
347
350
CFM/ton
| CFM
Watts
| 993 / 1114
152 / 176
| 1008 / 1035
208 / 200
| 1017 / 943
273 / 214
| 1015 / 828
341 / 196
| 1022 / 787
413 / 194
| 350
CFM/ton
| CFM
Watts
| 993
142
| 1013
197
| 1028
261
| 1023
335
| 1049
416
390 †
CFM/ton
| CFM
Watts
| 993 / 1114
152 / 176
| 1008 / 1035
208 / 200
| 1017 / 943
273 / 214
| 1015 / 828
341 / 196
| 1022 / 787
413 / 194
| 390 †
CFM/ton
| CFM
Watts
| 993
142
| 1013
197
| 1028
261
| 1023
335
| 1049
416
400
CFM/ton
| CFM
Watts
| 993 / 1114
152 / 176
| 1008 / 1035
208 / 200
| 1017 / 943
273 / 214
| 1015 / 828
341 / 196
| 1022 / 787
413 / 194
| 400
CFM/ton
| CFM
Watts
| 993
142
| 1013
197
| 1028
261
| 1023
335
| 1049
416
450
CFM/ton
| CFM
Watts
| 993 / 1114
152 / 176
| 1008 / 1035
208 / 200
| 1017 / 943
273 / 214
| 1015 / 828
341 / 196
| 1022 / 787
413 / 194
| 450
CFM/ton
| CFM
Watts
| 993
142
| 1013
197
| 1028
261
| 1023
335
| 1049
416
• † Factory Setting
• Status LED will blink once per 100 CFM requested. In torque mode, actual airflow may be lower.
• To prevent water blow-off, the max airflow demand allowable is 1000 CFM. If an outdoor
multiplier and cooling airflow setting should result in a demand higher than 1000, the AFC will default the demand back to 1000.
| • Torque mode will reduce airflow when static is above approximately 0.3″ water column.
• All heating modes default to Constant CFM.
• In communicating mode, default CFM/Ton is 400.
• Cooling airflow values are with wet coil, no filter
OUTDOOR
MULTIPLIER (TONS)
| COOLING AIRFLOW SETTING| AIRFLOW POWER| EXTERNAL STATIC PRESSURE (Constant
CFM / Constant Torque)| HEATING AIRFLOW SETTING| AIRFLOW POWER| EXTERNAL
STATIC PRESSURE
---|---|---|---|---|---|---
0.1| 0.3| 0.5| 0.7| 0.9| 0.1| 0.3| 0.5| 0.7| 0.9
1.5 tons
| 290
CFM/ton
| CFM
Watts
| 430 / 538
50 / 39
| 430 / 415
75 / 48
| 430 / 264
95 / 43
| 430 / NA
110 / NA
| 430 / NA
145 / NA
| 290
CFM/ton
| CFM
Watts
| 434
34
| 419
64
| 419
96
| 403
130
| 384
167
350
CFM/ton
| CFM
Watts
| 520 / 620
60 / 53
| 520 / 514
90 / 64
| 520 / 398
120 / 61
| 520 / NA
135 / NA
| 510 / NA
175 / NA
| 350
CFM/ton
| CFM
Watts
| 521
44
| 512
77
| 514
112
| 500
153
| 485
196
400
CFM/ton
| CFM
Watts
| 590 / 688
75 / 67
| 590 / 593
105 / 80
| 590 / 493
140 / 80
| 590 / NA
160 / NA
| 590 / NA
205 / NA
| 400
CFM/ton
| CFM
Watts
| 595
56
| 589
91
| 595
127
| 584
173
| 573
222
450
CFM/ton
| CFM
Watts
| 670 / 758
85 / 85
| 670 / 671
125 / 100
| 660 / 581
160 / 102
| 660 / NA
190 / NA
| 660 / NA
235 / NA
| 450
CFM/ton
| CFM
Watts
| 668
71
| 667
107
| 675
145
| 668
196
| 660
250
2 tons
| 290
CFM/ton
| CFM
Watts
| 570 / 670
60 / 63
| 570 / 573
90 / 76
| 570 / 469
125 / 75
| 570 / NA
165 / NA
| 568 / NA
215 / NA
| 290
CFM/ton
| CFM
Watts
| 575
53
| 569
87
| 573
123
| 561
167
| 549
215
350
CFM/ton
| CFM
Watts
| 690 / 781
85 / 91
| 690 / 696
120 / 107
| 690 / 609
160 / 110
| 690 / 518
210 / 98
| 680 / NA
259 / NA
| 350
CFM/ton
| CFM
Watts
| 693
76
| 693
113
| 702
152
| 696
204
| 689
259
400
CFM/ton
| CFM
Watts
| 790 / 875
110 / 122
| 790 / 798
150 / 140
| 790 / 720
195 / 145
| 780 / 639
250 / 137
| 780 / 555
301 / 115
| 400
CFM/ton
| CFM
Watts
| 791
103
| 795
143
| 805
184
| 803
240
| 798
301
450
CFM/ton
| CFM
Watts
| 890 / 971
145 / 161
| 890 / 899
185 / 181
| 880 / 827
235 / 189
| 880 / 754
295 / 184
| 880 / 680
347 / 184
| 450
CFM/ton
| CFM
Watts
| 889
138
| 895
181
| 902
226
| 899
284
| 891
347
2.5 tons
| 290
CFM/ton
| CFM
Watts
| 720 / 823
90 / 104
| 720 / 741
140 / 120
| 710 / 659
170 / 124
| 710 / 573
220 / 115
| 710 / 481
260 / 91
| 290
CFM/ton
| CFM
Watts
| 717
82
| 718
120
| 728
159
| 723
212
| 717
269
350
CFM/ton
| CFM
Watts
| 870 / 963
140 / 157
| 860 / 892
182 / 177
| 873 / 819
235 / 185
| 860 / 746
280 / 180
| 850 / 671
330 / 161
| 350
CFM/ton
| CFM
Watts
| 865
128
| 871
170
| 879
214
| 876
272
| 869
335
390
CFM/ton
| CFM
Watts
| 969 / 1087
143 / 166
| 985 / 1011
198 / 191
| 993 / 921
262 / 205
| 992 / 809
329 / 189
| 1000 / 770
399 / 187
| 390
CFM/ton
| CFM
Watts
| 969
134
| 989
188
| 1004
250
| 999
323
| 1026
402
400
CFM/ton
| CFM
Watts
| 993 / 1114
152 / 176
| 1008 / 1035
208 / 200
| 1017 / 943
273 / 214
| 1015 / 828
341 / 196
| 1022 / 787
413 / 194
| 400
CFM/ton
| CFM
Watts
| 993
142
| 1013
197
| 1028
261
| 1023
335
| 1049
416
450
CFM/ton
| CFM
Watts
| 993 / 1114
152 / 176
| 1008 / 1035
208 / 200
| 1017 / 943
273 / 214
| 1015 / 828
341 / 196
| 1022 / 787
413 / 194
| 450
CFM/ton
| CFM
Watts
| 993
142
| 1013
197
| 1028
261
| 1023
335
| 1049
416
3 tons †
| 290
CFM/ton
| CFM
Watts
| 868 / 974
111 / 128
| 884 / 907
163 / 156
| 891 / 826
220 / 173
| 893 / 729
281 / 162
| 894 / 688
345 / 162
| 290
CFM/ton
| CFM
Watts
| 868
103
| 888
154
| 901
211
| 900
277
| 917
347
350
CFM/ton
| CFM
Watts
| 993 / 1114
152 / 176
| 1008 / 1035
208 / 200
| 1017 / 943
273 / 214
| 1015 / 828
341 / 196
| 1022 / 787
413 / 194
| 350
CFM/ton
| CFM
Watts
| 993
142
| 1013
197
| 1028
261
| 1023
335
| 1049
416
390 †
CFM/ton
| CFM
Watts
| 993 / 1114
152 / 176
| 1008 / 1035
208 / 200
| 1017 / 943
273 / 214
| 1015 / 828
341 / 196
| 1022 / 787
413 / 194
| 390 †
CFM/ton
| CFM
Watts
| 993
142
| 1013
197
| 1028
261
| 1023
335
| 1049
416
400
CFM/ton
| CFM
Watts
| 993 / 1114
152 / 176
| 1008 / 1035
208 / 200
| 1017 / 943
273 / 214
| 1015 / 828
341 / 196
| 1022 / 787
413 / 194
| 400
CFM/ton
| CFM
Watts
| 993
142
| 1013
197
| 1028
261
| 1023
335
| 1049
416
450
CFM/ton
| CFM
Watts
| 993 / 1114
152 / 176
| 1008 / 1035
208 / 200
| 1017 / 943
273 / 214
| 1015 / 828
341 / 196
| 1022 / 787
413 / 194
| 450
CFM/ton
| CFM
Watts
| 993
142
| 1013
197
| 1028
261
| 1023
335
| 1049
416
• † Factory Setting
• Status LED will blink once per 100 CFM requested. In torque mode, actual airflow may be lower.
• To prevent water blow-off, the max airflow demand allowable is 1000 CFM. If an outdoor
multiplier and cooling airflow setting should result in a demand higher than 1000, the AFC will default the demand back to 1000.
| • Torque mode will reduce airflow when static is above approximately 0.3″ water column.
• All heating modes default to Constant CFM.
• In communicating mode, default CFM/Ton is 400.
• Cooling airflow values are with wet coil, no filter
Note: Heater size needs to be set in Configuration Menu.
Table 7. Electrical Data
TEM8A0B24V21DC HEATER DATA
Heater Model No.
| No. of Circuits/ Phases| 240 Volt| 208 Volt
Capacity| Heater Amps per Circuit| Minimum Circuit Ampacity| Maximum Overload
Protection| Capacity| Heater Amps per Circuit| Minimum Circuit Ampacity|
Maximum Overload Protection
kW| BTUH| kW| BTUH
No Heater| | | | 2.8 | 4| 15| | | 2.8 | 4| 15
BAYHTR1504BRK BAYHTR1504LUG| 1/1| 3.84| 13100| 16.0| 24| 25| 2.88| 9800| 13.8|
21| 25
BAYHTR1505BRK BAYHTR1505LUG| 1/1| 4.80| 16400| 20.0| 29| 30| 3.60| 12300|
17.3| 25| 25
BAYHTR1508BRK BAYHTR1508LUG| 1/1| 7.68| 26200| 32.0| 44| 45| 5.76| 19700|
27.7| 38| 40
BAYHTR1510BRK BAYHTR1510LUG| 1/1| 9.60| 32800| 40.0| 54| 60| 7.20| 24600|
34.6| 47| 50
BAYHTR1517BRK
Circuit 1 (a)
| ****
2/1
| 9.60| 32800| 40.0| 54| 60| 7.20| 24600| 34.6| 47| 50
BAYHTR1517BRK
Circuit 2
| 4.80| 16400| 20.0| 25| 25| 3.60| 12300| 17.3| 22| 25
BAYHTR3510LUG| 1/3| 9.60| 32800| 23.1| 32| 35| 7.20| 24600| 20.0| 28| 30
BAYHTR3517LUG| 1/3| 14.40| 49100| 34.6| 46| 50| 10.80| 36900| 30.0| 41| 45
- = Motor Amps
(a) MCA and MOP for circuit 1 contains the motor amps
Table 8. Electrical Data
TEM8A0B30V31DC HEATER DATA
Heater Model No.
| No. of Circuits/ Phases| 240 Volt| 208 Volt
Capacity| Heater Amps per Circuit| Minimum Circuit Ampacity| Maximum Overload
Protection| Capacity| Heater Amps per Circuit| Minimum Circuit Ampacity|
Maximum Overload Protection
kW| BTUH| kW| BTUH
No Heater| | | | 3.9 | 5| 15| | | 3.9 | 5| 15
BAYHTR1504BRK BAYHTR1504LUG| 1/1| 3.84| 13100| 16.0| 25| 25| 2.88| 9800| 13.8|
22| 25
BAYHTR1505BRK BAYHTR1505LUG| 1/1| 4.80| 16400| 20.0| 30| 30| 3.60| 12300|
17.3| 27| 30
BAYHTR1508BRK BAYHTR1508LUG| 1/1| 7.68| 26200| 32.0| 45| 45| 5.76| 19700|
27.7| 39| 40
BAYHTR1510BRK BAYHTR1510LUG| 1/1| 9.60| 32800| 40.0| 55| 60| 7.20| 24600|
34.6| 48| 50
BAYHTR1517BRK
Circuit 1 (a)
| ****
2/1
| 9.60| 32800| 40.0| 55| 60| 7.20| 24600| 34.6| 48| 50
BAYHTR1517BRK
Circuit 2
| 4.80| 16400| 20.0| 25| 25| 3.60| 12300| 17.3| 22| 25
BAYHTR3510LUG| 1/3| 9.60| 32800| 23.1| 33| 35| 7.20| 24600| 20.0| 29| 30
BAYHTR3517LUG| 1/3| 14.40| 49100| 34.6| 48| 50| 10.80| 36900| 30.0| 42| 45
- = Motor Amps
(a) MCA and MOP for circuit 1 contains the motor amps
Table 9. Electrical Dat
TEM8A0C36V31DC, TEM8A0C42V41DC HEATER DATA
Heater Model No.
| No. of Circuits/ Phases| 240 Volt| 208 Volt
Capacity| Heater Amps per Circuit| Minimum Circuit Ampacity| Maximum Overload
Protection| Capacity| Heater Amps per Circuit| Minimum Circuit Ampacity|
Maximum Overload Protection
kW| BTUH| kW| BTUH
No Heater| | | | 3.9 | 5| 15| | | 3.9 | 5| 15
BAYHTR1504BRK BAYHTR1504LUG| 1/1| 3.84| 13100| 16.0| 25| 25| 2.88| 9800| 13.8|
22| 25
BAYHTR1505BRK BAYHTR1505LUG| 1/1| 4.80| 16400| 20.0| 30| 30| 3.60| 12300|
17.3| 27| 30
TEM8A0C36V31DC, TEM8A0C42V41DC HEATER DATA
BAYHTR1508BRK BAYHTR1508LUG| 1/1| 7.68| 26200| 32.0| 45| 45| 5.76| 19700|
27.7| 39| 40
BAYHTR1510BRK BAYHTR1510LUG| 1/1| 9.60| 32800| 40.0| 55| 60| 7.20| 24600|
34.6| 48| 50
BAYHTR1517BRK
Circuit 1 (a)
| ****
2/1
| 9.60| 32800| 40.0| 55| 60| 7.20| 24600| 34.6| 48| 50
BAYHTR1517BRK
Circuit 2
| 4.80| 16400| 20.0| 25| 25| 3.60| 12300| 17.3| 22| 25
BAYHTR1523BRK
Circuit 1 (a)
| ****
2/1
| 9.60| 32800| 40.0| 55| 60| 7.20| 24600| 34.6| 48| 50
BAYHTR1523BRK
Circuit 2
| 9.60| 32800| 40.0| 50| 50| 7.20| 24600| 34.6| 43| 45
BAYHTR3510LUG| 1/3| 9.60| 32800| 23.1| 33| 35| 7.20| 24600| 20.0| 29| 30
BAYHTR3517LUG| 1/3| 14.40| 49100| 34.6| 48| 50| 10.80| 36900| 30.0| 42| 45
- = Motor Amps
(a) MCA and MOP for circuit 1 contains the motor amps
Table 10. Electrical Data
TEM8A0C48V41DC, TEM8B0C60V51DA HEATER DATA
Heater Model No.
| No. of Circuits/ Phases| 240 Volt| 208 Volt
Capacity| Heater Amps per Circuit| Minimum Circuit Ampacity| Maximum Overload
Protection| Capacity| Heater Amps per Circuit| Minimum Circuit Ampacity|
Maximum Overload Protection
kW| BTUH| kW| BTUH
No Heater| | | | 5.7 | 7| 15| | | 5.7 | 7| 15
BAYHTR1504BRK BAYHTR1504LUG| 1/1| 3.84| 13100| 16.0| 27| 30| 2.88| 9800| 13.8|
24| 25
BAYHTR1505BRK BAYHTR1505LUG| 1/1| 4.80| 16400| 20.0| 32| 35| 3.60| 12300|
17.3| 29| 30
BAYHTR1508BRK BAYHTR1508LUG| 1/1| 7.68| 26200| 32.0| 47| 50| 5.76| 19700|
27.7| 42| 45
BAYHTR1510BRK BAYHTR1510LUG| 1/1| 9.60| 32800| 40.0| 57| 60| 7.20| 24600|
34.6| 50| 50
BAYHTR1517BRK
Circuit 1 (a)
| ****
2/1
| 9.60| 32800| 40.0| 57| 60| 7.20| 24600| 34.6| 50| 50
BAYHTR1517BRK
Circuit 2
| 4.80| 16400| 20.0| 25| 25| 3.60| 12300| 17.3| 22| 25
BAYHTR1523BRK
Circuit 1 (a)
| ****
2/1
| 9.60| 32800| 40.0| 57| 60| 7.20| 24600| 34.6| 50| 50
BAYHTR1523BRK
Circuit 2
| 9.60| 32800| 40.0| 50| 50| 7.20| 24600| 34.6| 43| 45
BAYHTR1525BRK
Circuit 1 (a)
| ****
4/1
| 6.00| 20500| 25.0| 38| 40| 4.50| 15400| 21.6| 34| 35
BAYHTR1525BRK
Circuit 2
| 6.00| 20500| 25.0| 31| 35| 4.50| 15400| 21.6| 27| 30
BAYHTR1525BRK
Circuit 3
| 6.00| 20500| 25.0| 31| 35| 4.50| 15400| 21.6| 27| 30
BAYHTR1525BRK
Circuit 4
| 6.00| 20500| 25.0| 31| 35| 4.50| 15400| 21.6| 27| 30
BAYHTR3510LUG| 1/3| 9.60| 32800| 23.1| 35| 35| 7.20| 24600| 20.0| 31| 35
BAYHTR3517LUG| 1/3| 14.40| 49100| 34.6| 50| 50| 10.80| 36900| 30.0| 44| 45
- = Motor Amps
Minimum Airflow CFM
TEM8A0B24V21DC, TEM8A0B30V31DC
Heater| Minimum Heater Airflow CFM
| With Heat Pump| Without Heat Pump
BAYHTR1504BRK, BAYHTR1504LUG, BAYHTR1505BRK, BAYHTR1505LUG
| ****
650
| ****
600
BAYHTR1508BRK, BAYHTR1508LUG| 850| 700
BAYHTR1510BRK, BAYHTR1510LUG| 850| 700
BAYHTR1517BRK| 1000| 850
BAYHTR3510LUG| 850| 700
BAYHTR3517LUG| 1000| 850
TEM8A0C36V31DC, TEM8A0C42V41DC
Heater| Minimum Heater Airflow CFM
| With Heat Pump| Without Heat Pump
BAYHTR1504BRK, BAYHTR1504LUG, BAYHTR1505BRK, BAYHTR1505LUG| 675| 675
BAYHTR1508BRK, BAYHTR1508LUG| 950| 900
BAYHTR1510BRK, BAYHTR1510LUG| 950| 900
BAYHTR1517BRK| 950| 900
BAYHTR3510LUG| 950| 900
BAYHTR3517LUG| 1050| 950
BAYHTR1523BRK| 1500| 1300
TEM8A0C48V41DC, TEM8B0C60V51DA
Heater| Minimum Heater Airflow CFM
| With Heat Pump| Without Heat Pump
BAYHTR1504BRK, BAYHTR1504LUG, BAYHTR1505BRK, BAYHTR1505LUG| 900| 800
BAYHTR1508BRK, BAYHTR1508LUG| 1200| 1000
BAYHTR1510BRK, BAYHTR1510LUG| 1350| 1000
BAYHTR1517BRK| 1400| 1100
BAYHTR3510LUG| 1200| 1000
BAYHTR3517LUG| 1400| 1100
BAYHTR1523BRK| 1430| 1300
BAYHTR1525BRK| 1850| 1600
Outline Drawing
PRODUCT DIMENSIONS
Air Handler Model| A| B| C| D| E| F| H| Flow Control| Gas Line Braze
TEM8A0B24, 30| 46.77| 18.50| 16.50| 16.75| 4.68| 7.33| 20.09| TXV| 3/4
TEM8A0C36, 42| 51.27| 23.50| 21.50| 21.75| 7.01| 9.66| 24.59| TXV| 7/8
TEM8A0C48/ TEM8B0C60| 57.40| 23.50| 21.50| 21.75| 4.68| 9.66| 27.19| TXV| 7/8
All dimensions are in inches
Heater Pressure Drop Table
Airflow CFM
| Number of Racks| | Heater Racks
---|---|---|---
1| 2| 3| 4| Heater Model| No. of Racks
Air Pressure Drop — Inches W.G.| BAYHTR1504| 1
1800| 0.02| 0.04| 0.06| 0.14| BAYHTR1505| 1
1700| 0.02| 0.04| 0.06| 0.14| BAYHTR1508| 2
1600| 0.02| 0.04| 0.06| 0.13| BAYHTR1510| 2
1500| 0.02| 0.04| 0.06| 0.12| BAYHTR3510| 3
1400| 0.02| 0.04| 0.06| 0.12| BAYHTR1517| 3
1300| 0.02| 0.04| 0.05| 0.11| BAYHTR1523| 4
1200| 0.01| 0.04| 0.05| 0.10| BAYHTR3517| 3
1100| 0.01| 0.03| 0.05| 0.09| BAYHTR1525| 4
1000| 0.01| 0.03| 0.04| 0.09| |
900| 0.01| 0.03| 0.04| 0.08| |
800| 0.01| 0.03| | | |
700| 0.01| 0.02| | | |
600| 0.01| 0.02| | | |
Subcooling Adjustment
System Matched with:| Indoor Unit Model No.|
Outdoor Model No.| Subcooling
---|---|---|---
15 SEER HP — 3 ton| TEM8A0C36V31| 4TWR5036G1000A| 14 Degrees
| TEM8A0C42V41| 4A6H5036G1000A|
All other matches must be charged per the nameplate charging instructions
Subcooling Adjustment for TEM8A0C48V41 & TEM8B0C60V51
Sub-Cooling Charge Specification For AHRI Rated Performance
OD Equipment| Up Flow / Horizontal| Down Flow
AC UNIT| OD Name Plate| OD Name Plate
HP UNIT ≤ 3.5 Tons| OD Name Plate| OD Name Plate
+ 4 Degrees
HP UNIT = 4 and 5 Tons| OD Name Plate| OD Name Plate
Coil Conversion Instructions
Downflow
Follow the conversion steps when installing the air handler in downflow
configuration.
-
Remove the front panels panel from the air handler.
The coil and line set panel do not need to be separated. -
Remove the fasteners on both sides of the coil.
-
Remove the two screws holding the center horizontal bracket and rotate out of place. Retain parts.
-
Slide the coil assembly out. Remove and discard the horizontal drain pan.
-
On both sides of the cabinet, remove the screws that hold the coil support brackets and retain for later use. Seal the holes to prevent air leakage.
-
Rotate and lift the two coil support brackets to remove from front slots in cabinet.
-
Rotate the unit into the downflow orientation.
-
Pre-drill two clearance holes in the cabinet at dimples located below the location the screws were removed for the coil support brackets. There is one hole per side. See location of holes.
-
Replace the center horizontal bracket removed in Step 3. Use the screws retained from Step 3 to attach.
-
Place coil support brackets into the lower set of slots and rotate into place. Push downward to lock into place.
-
Secure each bracket with a screw that were previously removed.
-
Slide the coil assembly back into the air handler cabinet as shown.
-
Remove the appropriate knock out for the condensate piping.
-
Replace all panels.
Horizontal Right
Follow the conversion steps when installing the air handler in horizontal
right configuration.
-
Remove the front panels from the air handler. The coil and line set panel do not need to be separated.
-
Remove the fasteners on both sides of the coil. Retain the coil retaining brackets and screws.
-
Remove the two screws holding the center horizontal bracket and rotate out of place. Retain parts.
-
Make note of the horizontal drain pan orientation (up/down).
-
Slide the coil assembly out.
Important: For Horizontal Right applications, ON SOME MODELS the top panel assembly of the coil must be rotated for proper condensate management. -
On the right side of the top baffle, position a flathead tip underneath the top baffle flange and pivot the screwdriver downward to release the front tab as shown below.
-
Repeat for right rear tab to release top baffle assembly from coil
-
Rotate 180 degrees and snap all four corner tabs to lock in place.
-
Remove left side water diverter brackets and screws and reinstall on the right side.
Important: The coil slabs are different and the mount hole locations will vary. See the illustrations on the following pages that correspond to the unit tonnage to see the correct mounting position of the water diverter bracket.
Important: The water diverter brackets are not symmetrical and will vary by tonnage Coil Conversion Instructions -
Relocate the horizontal drain pan from the left side of the coil to the right side.
-
Remove the drain pan support bracket. Do not discard. Remove the two drain plugs from the front of the drain pan and insert them in the drains at the rear of the drain pan.
Important: When reinstalling coil in Step 13, it is important that the coil corner locks in place under the tab in the side bracket to support the coil weight horizontally. -
Reinstall the drain pan support bracket. The bracket should be located between the two drain plugs as shown
-
Slide the coil assembly back into the air handler cabinet.
Important: Make sure that the coil corner locks in place under the tab in the side left bracket to support the coil weight in the horizontal right position. -
Replace the center horizontal bracket using screws removed earlier in Step 3.
-
Replace the two coil retaining brackets removed in a previous step.
-
Replace all panels.
Checkout Procedures
The final phase of the installation is the system Checkout Procedures. The following list represents the most common items covered in a Checkout Procedure. Confirm all requirements in this document have been met.
- All wiring connections are tight and properly secured.
- Voltage and running current are within limits.
- All refrigerant lines (internal and external to equipment) are isolated, secure, and not in direct contact with each other or structure.
- All braze connections have been checked for leaks. A vacuum of 350 microns provides confirmation that the refrigeration system is leak free and dry.
- Final unit inspection to confirm factory tubing has not shifted during shipment. Adjust tubing if necessary so tubes do not rub against each other or any component when unit runs.
- Ductwork is sealed and insulated.
- All drain lines are clear with joints properly sealed. Pour water into drain pan to confirm proper drainage. Provide enough water to ensure drain trap is primed.
- For TEM8 models, set the heater size in the Configuration Menu.
- Supply registers and return grilles are open, unobstructed, and air filter is installed.
- Indoor blower and outdoor fan are operating smoothly and without obstruction.
- Indoor blower motor set on correct speed setting to deliver required CFM.
- Cover panels are in place and properly tightened.
- For gas heating systems, manifold pressure has been checked and all gas line connections are tight and leak free.
- For gas heating systems, flue gas is properly vented.
- System functions safely and properly in all modes.
- Owner has been instructed on use of system and given manual
About Trane and American Standard Heating and Air Conditioning
Trane and American Standard create comfortable, energy efficient indoor
environments for residential applications. For more information, please visit
www.trane.com or
www.americanstandardair.com.
The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices
18-GF09D1-1J-EN 07 Oct 2022
Supersedes 18-GF09D1-1H-EN (July 2022)
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>