LSC PowerPoint Power Distribution System User Manual
- June 13, 2024
- LSC
Table of Contents
Power Point
Power Distribution System
User Manual
Version 1.3
March 2023
LSC Control Systems ©
+61 3 9702 8000
info@lsccontrol.com.au
www.lsccontrol.com.au
Disclaimer
LSC Control Systems Pty Ltd has a corporate policy of continuous improvement,
covering areas such as product design and documentation. To achieve this goal,
we undertake to release software updates for all products on a regular basis.
In light of this policy, some detail contained in this manual may not match
the exact operation of your product. Information contained in this manual is
subject to change without notice.
In any event, LSC Control Systems Pty Ltd cannot be held liable for any
direct, indirect, special, incidental, or consequential damages or loss
whatsoever (including, without limitation, damages for loss of profits,
business interruption, or other pecuniary loss) arising out of the use or the
inability to use this product for its intended purpose as expressed by the
manufacturer and in conjunction with this manual.
Servicing of this product is recommended to be carried out by LSC Control
Systems Pty Ltd or its authorised service agents. No liability will be
accepted whatsoever for any loss or damage caused by service, maintenance or
repair by unauthorised personnel.
In addition, servicing by unauthorised personnel may void your warranty.
LSC Control Systems’ products must only be used for the purpose for which they
were intended.
Whilst every care is taken in the preparation of this manual, LSC Control
Systems takes no responsibility for any errors or omissions.
Copyright Notices
“LSC Control Systems” is a registered trademark.
lsccontrol.com.au is owned and operated by LSC
Control Systems Pty Ltd.
All Trademarks referred to in this manual are the registered names of their
respective owners.
All rights reserved.
Contact Details
LSC Control Systems Pty Ltd
ABN 21 090 801 675
65-67 Discovery Road
Dandenong South, Victoria 3175 Australia
Tel: +61 3 9702 8000
email: info@lsccontrol.com.au
web: www.lsccontrol.com.au
Introduction
1.1 Overview
PowerPoint is a simple to use power distribution unit with a 3 phase mains
input (single phase input available) and either 6 or 12 single phase outputs
depending upon the model.
Designed for applications wherever fixed or mobile power distribution is
required, the PowerPoint distribution rack offers a 4-pole mains input
isolator switch with Neutral Disconnect as standard and individual RCBO
(RCD+MCB) per output channel. There are also 3 neon phase indicators to show
power input to the rack.
Output circuit rating can be specified as either 10A, 16A or 25 Amps and back
panel options include either Australian GPO, Socapex, Power Con or Hard Wired
Terminals, depending upon the model.
1.2 Features
The PowerPoint Feature list includes:
- A front panel mounted 4-pole mains input isolator switch with neutral disconnect as standard provides easy access for quick isolation for the PowerPoint
- Three neon indicators show state of input phase power. Easily visible from a distance
- Twelve 10A, twelve 16A or six 25A output circuits
- Residual Current circuit Breaker with Overcurrent protection (RCBO) devices for each output circuit are used to combine protection against current overload and short circuits and protection against earth leakage currents. Essentially, they protect connected loads and prevent users from receiving a life threatening shock. Standard on all LSC power products
- The PowerPoint is at home as a 19″ rackmount module in portable flight cases or touring frames or permanently installed in equipment racks. Versatility plus for any situation!
- Three phase operation
- Single phase operation possible
- Utilizing the same proven mechanical chassis as LSC’s premier products such as the APS power distribution unit, GEN VI and RED3 dimmers, the PowerPoint is built to the same exacting standards ensuring great consistent performance when you need it, time after time.
Front Panel
See section 4 for rear panel options.
Setting Up and Connecting
3.1 Safety
All electrical work must be carried out by suitably qualified persons.
3.2 Unpacking
Your PowerPoint is fully tested and inspected before leaving the factory. Upon
delivery, inspect the PowerPoint for signs of damage. In the event of any
damage, contact your LSC agent.
3.3 Mounting
The PowerPoint is designed for mounting in a standard 19 inch rack. It
occupies 3RU (Rack Units) of space.
3.4 Connections
3.4.1 Input Power Supply
Always ensure that the Input Isolator is in the OFF position before connecting
or disconnecting the input power.
PowerPoint must be fed from a suitable external circuit breaker.
The nominal input voltage is 220-240 Volts. 3-phase Star (380-415V). 50-60Hz.
Single phase operation is possible but input current must be limited to 63A in
total.
3.4.2 Outputs and Phasing
Always ensure that the Output Load RCBO’s are in the OFF position before
connecting or disconnecting any loads.
The individual outputs are fed from the following input power phases. This
input phase numbering is also shown on the front panel below each output
circuit breaker.
Input Phase | Output | Input Phase | Output |
---|---|---|---|
1 | 1 | 1 | 7 |
2 | 2 | 2 | 8 |
3 | 3 | 3 | 9 |
1 | 4 | 1 | 10 |
2 | 5 | 2 | 11 |
3 | 6 | 3 | 12 |
Troubleshooting
Warning. No user controls or user serviceable parts are located inside the
PowerPoint. Refer all servicing to suitably qualified personnel.
4.1 Maintenance
Check that all connector screw terminals (if fitted) are tight. This must be
performed by a suitably qualified person.
4.2 Tripped Breakers
If a channel is not working check the RCBO (Residual Current circuit Breaker
with Over current protection) for that channel. If the RCBO has tripped (OFF),
firstly try to determine the cause of the breaker tripping. It could be a
blown lamp or a circuit overload or a earth leakage fault. Rectify to problem
(replace the lamp or reduce the load) then restore the RCBO by pushing it all
the way down then lifting it up. If the RCBO continues to trip, refer the
problem to a suitably qualified person.
Specifications and Output Options
Model | 12 x 10A | 12 x 16A | 6 x 25A |
---|---|---|---|
Protection | 10A Residual Current Breaker (RCBO) per | ||
output channel | 16A Residual Current Breaker (RCBO) per | ||
output channel | 25A Residual Current Breaker (RCBO) per |
output channel
30mA Earth leakage trip current per channel Front panel mounted neon power
indicator per phase Mains power input protected by 4-pole mains isolator
switch with neutral disconnect
| ” PWP12116/32A
model supplied with 3- phase 32A MCB in lieu
of 4-pole mains isolator
- PWP12/16/40A model supplied with 3-phase 40A MCB in lieu of 4-pole mains isolator|
Power| Nominal 100-240V AC
3-phase star TN-S with fully rated earth, 50-60Hz
Operating ange typically 90-260V AC 45-65Hz
Auto voltage and frequency adjustment Hardwired models supplied with rear panel mounted 5 cage clamp style terminals
Supplied with 1.2m long H07 rubber 5 core x 6mm2 cable with 32A 5-pin 3-phase plug fitted (export models supplied with no plug)| Supplied with 1.2m long H07 rubber 5 core x 10mm2 cable no connector supplied (export models supplied with no plug)
PWP12/16/32A model supplied with 3-phase
1.2m H07 5 core x 6mm2 rubber cable fitted with 32A 3-phase plug.
PWP12/16/40A model supplied with 3-phase
1.2m H07 5 core x 6mm2 rubber cable
fitted with 40A 3-phase plug| Supplied with 1.2m long H07 rubber 5 core
x 6mm2 cable with 40A 5-pin 3-phase plug
fitted (export models supplied with no plug)
Mechanicals| 483mm (w) x 132mm (h) x 300mm (d)
3RU x 191* rackmount
Weight: 11kg
Corrosion-resistant, powder-coated steel chassis with rear-screened polycarbonate labels
Peace of
mind| CE (European) and RCM (Australian) approved, two-year warranty, designed and manufactured in Australia by LSC, an Australian owned
company with over 40 years’ experience in developing world first products
Outputs| 12 x 3-pin 10 Amp Australian sockets| 12 x 3-pin 20 Amp
Australian sockets.
32A MCB (Main Circuit Breaker)| 6 paired 3-pin
20Amp/15Amp
Australian sockets
---|---|---|---
| 12Ch x 10A
Hardwired terminals| 12 x 3-pin 20 Amp
Australian sockets.
40A MCB (Main Circuit Breaker)| 6Ch x 25A
Hardwired terminals
| 2 x 16-pin Wieland sockets| |
| 2 x 19-pin Socapex sockets| |
| 12 x Power CON sockets| |
5.2 Wieland Pinouts
WARNING. Several wiring standards exist for the pin outs of Wieland
multipin sockets. If in doubt, a suitably qualified person should check that
your Wieland cables are wired to the same standard as your Power point..
Note: Earth connection is via the clips on the side of the socket insert.
5.3 Socapex Pinouts
Connector #1 | Function | Connector #2 | Function |
---|---|---|---|
Pin 1 | Chan 1 Active | Pin 1 | Chan 7 Active |
Pin 2 | Chan 1 Neutral | Pin 2 | Chan 7 Neutral |
Pin 3 | Chan 2 Active | Pin 3 | Chan 8 Active |
Pin 4 | Chan 2 Neutral | Pin 4 | Chan 8 Neutral |
Pin 5 | Chan 3 Active | Pin 5 | Chan 9 Active |
Pin 6 | Chan 3 Neutral | Pin 6 | Chan 9 Neutral |
Pin 7 | Chan 4 Active | Pin 7 | Chan 10 Active |
Pin 8 | Chan 4 Neutral | Pin 8 | Chan 10 Neutral |
Pin 9 | Chan 5 Active | Pin 9 | Chan 11 Active |
Pin 10 | Chan 5 Neutral | Pin 10 | Chan 11 Neutral |
Pin 11 | Chan 6 Active | Pin 11 | Chan 12 Active |
Pin 12 | Chan 6 Neutral | Pin 12 | Chan 12 Neutral |
Pin 13 | Earth | Pin 13 | Earth |
Pin 14 | Earth | Pin 14 | Earth |
Pin 15 | Earth | Pin 15 | Earth |
Pin 16 | Earth | Pin 16 | Earth |
Pin 17 | Earth | Pin 17 | Earth |
Pin 18 | Earth | Pin 18 | Earth |
Pin 19 | Earth | Pin 19 | Earth |
Compliance Statements
The Power Point from LSC Control Systems Pty Ltd meets all required CE (European), RCM (Australian) and UKCA (United Kingdom) standards.
**** CENELEC (European Committee for Electrotechnical Standardization).
Australian RCM (Regulatory Compliance Mark).
UK Conformity Assessed.
WEEE (Waste Electrical and Electronic Equipment).
**** The WEEE symbol indicates that the product should not be discarded as
unsorted waste but must be sent to separate collection facilities for recovery
and recycling.
For more information about how to recycle your LSC product, contact the dealer
where you
purchased the product or contact LSC via email at
info@lsccontrol.com.au
You can also take any old electrical equipment to participating civic amenity sites (often known as ‘household waste recycling centers’) run by local councils. You can locate your closest participating recycling centre using the following links.
- AUSTRALIA http://www.dropzone.org.au.
- NEW ZEALAND http://ewaste.org.nz/welcome/main
- NORTH AMERICA http://1800recycling.com
- UK www.recycle-more.co.uk.
References
- RecycleNation – Search. Find. Recycle.
- RecycleNation – Search. Find. Recycle.
- LSC
- LSC
- LSC
- LSC
- Everything you need to know to Recycle More
- Everything you need to know to Recycle More
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>