LSC PowerPoint Power Distribution System User Manual

June 13, 2024
LSC

LSC logo

Power Point
Power Distribution System

LSC PowerPoint Power Distribution System

User Manual

Version 1.3
March 2023
LSC Control Systems ©
+61 3 9702 8000
[email protected]
www.lsccontrol.com.au

Disclaimer

LSC Control Systems Pty Ltd has a corporate policy of continuous improvement, covering areas such as product design and documentation. To achieve this goal, we undertake to release software updates for all products on a regular basis. In light of this policy, some detail contained in this manual may not match the exact operation of your product. Information contained in this manual is subject to change without notice.
In any event, LSC Control Systems Pty Ltd cannot be held liable for any direct, indirect, special, incidental, or consequential damages or loss whatsoever (including, without limitation, damages for loss of profits, business interruption, or other pecuniary loss) arising out of the use or the inability to use this product for its intended purpose as expressed by the manufacturer and in conjunction with this manual.
Servicing of this product is recommended to be carried out by LSC Control Systems Pty Ltd or its authorised service agents. No liability will be accepted whatsoever for any loss or damage caused by service, maintenance or repair by unauthorised personnel.
In addition, servicing by unauthorised personnel may void your warranty.
LSC Control Systems’ products must only be used for the purpose for which they were intended.
Whilst every care is taken in the preparation of this manual, LSC Control Systems takes no responsibility for any errors or omissions.

Copyright Notices
“LSC Control Systems” is a registered trademark. lsccontrol.com.au is owned and operated by LSC Control Systems Pty Ltd.
All Trademarks referred to in this manual are the registered names of their respective owners.
All rights reserved.

Contact Details
LSC Control Systems Pty Ltd
ABN 21 090 801 675
65-67 Discovery Road
Dandenong South, Victoria 3175 Australia
Tel: +61 3 9702 8000
email: [email protected]
web: www.lsccontrol.com.au

Introduction

1.1 Overview
PowerPoint is a simple to use power distribution unit with a 3 phase mains input (single phase input available) and either 6 or 12 single phase outputs depending upon the model.
Designed for applications wherever fixed or mobile power distribution is required, the PowerPoint distribution rack offers a 4-pole mains input isolator switch with Neutral Disconnect as standard and individual RCBO (RCD+MCB) per output channel. There are also 3 neon phase indicators to show power input to the rack.
Output circuit rating can be specified as either 10A, 16A or 25 Amps and back panel options include either Australian GPO, Socapex, Power Con or Hard Wired Terminals, depending upon the model.

1.2 Features
The PowerPoint Feature list includes:

  • A front panel mounted 4-pole mains input isolator switch with neutral disconnect as standard provides easy access for quick isolation for the PowerPoint
  • Three neon indicators show state of input phase power. Easily visible from a distance
  • Twelve 10A, twelve 16A or six 25A output circuits
  • Residual Current circuit Breaker with Overcurrent protection (RCBO) devices for each output circuit are used to combine protection against current overload and short circuits and protection against earth leakage currents. Essentially, they protect connected loads and prevent users from receiving a life threatening shock. Standard on all LSC power products
  • The PowerPoint is at home as a 19″ rackmount module in portable flight cases or touring frames or permanently installed in equipment racks. Versatility plus for any situation!
  • Three phase operation
  • Single phase operation possible
  • Utilizing the same proven mechanical chassis as LSC’s premier products such as the APS power distribution unit, GEN VI and RED3 dimmers, the PowerPoint is built to the same exacting standards ensuring great consistent performance when you need it, time after time.

Front Panel

LSC PowerPoint Power Distribution System - Front Panel

See section 4 for rear panel options.

Setting Up and Connecting

3.1 Safety
All electrical work must be carried out by suitably qualified persons.
3.2 Unpacking
Your PowerPoint is fully tested and inspected before leaving the factory. Upon delivery, inspect the PowerPoint for signs of damage. In the event of any damage, contact your LSC agent.
3.3 Mounting
The PowerPoint is designed for mounting in a standard 19 inch rack. It occupies 3RU (Rack Units) of space.
3.4 Connections
3.4.1 Input Power Supply
Always ensure that the Input Isolator is in the OFF position before connecting or disconnecting the input power.
PowerPoint must be fed from a suitable external circuit breaker.
The nominal input voltage is 220-240 Volts. 3-phase Star (380-415V). 50-60Hz.
Single phase operation is possible but input current must be limited to 63A in total.

3.4.2 Outputs and Phasing
Always ensure that the Output Load RCBO’s are in the OFF position before connecting or disconnecting any loads.
The individual outputs are fed from the following input power phases. This input phase numbering is also shown on the front panel below each output circuit breaker.

Input Phase Output Input Phase Output
1 1 1 7
2 2 2 8
3 3 3 9
1 4 1 10
2 5 2 11
3 6 3 12

Troubleshooting

Warning. No user controls or user serviceable parts are located inside the PowerPoint. Refer all servicing to suitably qualified personnel.
4.1 Maintenance
Check that all connector screw terminals (if fitted) are tight. This must be performed by a suitably qualified person.
4.2 Tripped Breakers
If a channel is not working check the RCBO (Residual Current circuit Breaker with Over current protection) for that channel. If the RCBO has tripped (OFF), firstly try to determine the cause of the breaker tripping. It could be a blown lamp or a circuit overload or a earth leakage fault. Rectify to problem (replace the lamp or reduce the load) then restore the RCBO by pushing it all the way down then lifting it up. If the RCBO continues to trip, refer the problem to a suitably qualified person.

Specifications and Output Options

Model 12 x 10A 12 x 16A 6 x 25A
Protection 10A Residual Current Breaker (RCBO) per
output channel 16A Residual Current Breaker (RCBO) per
output channel 25A Residual Current Breaker (RCBO) per

output channel
30mA Earth leakage trip current per channel Front panel mounted neon power indicator per phase Mains power input protected by 4-pole mains isolator switch with neutral disconnect
| ” PWP12116/32A
model supplied with 3- phase 32A MCB in lieu
of 4-pole mains isolator

  • PWP12/16/40A model supplied with 3-phase 40A MCB in lieu of 4-pole mains isolator|
    Power| Nominal 100-240V AC
    3-phase star TN-S with fully rated earth, 50-60Hz
    Operating ange typically 90-260V AC 45-65Hz
    Auto voltage and frequency adjustment Hardwired models supplied with rear panel mounted 5 cage clamp style terminals
    Supplied with 1.2m long H07 rubber 5 core x 6mm2 cable with 32A 5-pin 3-phase plug fitted (export models supplied with no plug)| Supplied with 1.2m long H07 rubber 5 core x 10mm2 cable no connector supplied (export models supplied with no plug)
    PWP12/16/32A model supplied with 3-phase
    1.2m H07 5 core x 6mm2 rubber cable fitted with 32A 3-phase plug.
    PWP12/16/40A model supplied with 3-phase
    1.2m H07 5 core x 6mm2 rubber cable
    fitted with 40A 3-phase plug| Supplied with 1.2m long H07 rubber 5 core
    x 6mm2 cable with 40A 5-pin 3-phase plug
    fitted (export models supplied with no plug)
    Mechanicals| 483mm (w) x 132mm (h) x 300mm (d)
    3RU x 191* rackmount
    Weight: 11kg
    Corrosion-resistant, powder-coated steel chassis with rear-screened polycarbonate labels
    Peace of
    mind| CE (European) and RCM (Australian) approved, two-year warranty, designed and manufactured in Australia by LSC, an Australian owned
    company with over 40 years’ experience in developing world first products
    Outputs| 12 x 3-pin 10 Amp Australian sockets| 12 x 3-pin 20 Amp
    Australian sockets.
    32A MCB (Main Circuit Breaker)| 6 paired 3-pin
    20Amp/15Amp
    Australian sockets
    ---|---|---|---
    | 12Ch x 10A
    Hardwired terminals| 12 x 3-pin 20 Amp
    Australian sockets.
    40A MCB (Main Circuit Breaker)| 6Ch x 25A
    Hardwired terminals
    | 2 x 16-pin Wieland sockets| |
    | 2 x 19-pin Socapex sockets| |
    | 12 x Power CON sockets| |

5.2 Wieland Pinouts

LSC PowerPoint Power Distribution System - Wieland
Pinouts

WARNING. Several wiring standards exist for the pin outs of Wieland multipin sockets. If in doubt, a suitably qualified person should check that your Wieland cables are wired to the same standard as your Power point..
Note: Earth connection is via the clips on the side of the socket insert.
5.3 Socapex Pinouts

Connector #1 Function Connector #2 Function
Pin 1 Chan 1 Active Pin 1 Chan 7 Active
Pin 2 Chan 1 Neutral Pin 2 Chan 7 Neutral
Pin 3 Chan 2 Active Pin 3 Chan 8 Active
Pin 4 Chan 2 Neutral Pin 4 Chan 8 Neutral
Pin 5 Chan 3 Active Pin 5 Chan 9 Active
Pin 6 Chan 3 Neutral Pin 6 Chan 9 Neutral
Pin 7 Chan 4 Active Pin 7 Chan 10 Active
Pin 8 Chan 4 Neutral Pin 8 Chan 10 Neutral
Pin 9 Chan 5 Active Pin 9 Chan 11 Active
Pin 10 Chan 5 Neutral Pin 10 Chan 11 Neutral
Pin 11 Chan 6 Active Pin 11 Chan 12 Active
Pin 12 Chan 6 Neutral Pin 12 Chan 12 Neutral
Pin 13 Earth Pin 13 Earth
Pin 14 Earth Pin 14 Earth
Pin 15 Earth Pin 15 Earth
Pin 16 Earth Pin 16 Earth
Pin 17 Earth Pin 17 Earth
Pin 18 Earth Pin 18 Earth
Pin 19 Earth Pin 19 Earth

Compliance Statements

The Power Point from LSC Control Systems Pty Ltd meets all required CE (European), RCM (Australian) and UKCA (United Kingdom) standards.

**** CENELEC (European Committee for Electrotechnical Standardization).
Australian RCM (Regulatory Compliance Mark).

UK Conformity Assessed.
WEEE (Waste Electrical and Electronic Equipment).
**** The WEEE symbol indicates that the product should not be discarded as unsorted waste but must be sent to separate collection facilities for recovery and recycling.

For more information about how to recycle your LSC product, contact the dealer where you
purchased the product or contact LSC via email at [email protected]

You can also take any old electrical equipment to participating civic amenity sites (often known as ‘household waste recycling centers’) run by local councils. You can locate your closest participating recycling centre using the following links.

LSC logo

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

LSC User Manuals

Related Manuals