CRANE FLUID SYSTEMS ACT992TH Thermic Actuator Instruction Manual

June 13, 2024
CRANE FLUID SYSTEMS

FLUID SYSTEMS
OUR GENIUS IS VALVES
INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS
ACT992TH THERMIC ACTUATOR

OVERVIEW

The ACT992TH provides on/off control.
They are small and light making them a good choice for confined spaces.
The ACT992TH is compatible with normally closed zone valves including D102B, D103B and D104B.

FEATURES

  • Low and line voltage models available
  • Easy to assemble to valves with M30x1.5 connecting thread
  • Compact design, ideal for installation in confined spaces
  • Can be mounted after valve body is installed
  • Highly visible actuator stroke indicator
  • IP44 rated in vertical position

MOUNTING INSTRUCTIONS

The connecting thread on the valve and actuator is M30 x 1.5. When mounting the actuator, follow these instructions:

  • Hand tighten only. Do not over tighten. When mounting the actuator on the valve, only hand tighten the brass threaded coupling. Using a wrench to tighten the coupling will damage the actuator, cause it to fail, and will void the warranty. Position the actuator on the valve before tightening by hand.
  • Never grab the actuator and forcibly turn it.

To reposition the actuator on the valve, loosen the coupling, reposition the actuator and then retighten the brass coupling by hand.

  •  Sufficient clearance must be allowed for actuator removal.
  • Check to be sure the actuator spindle is in its full retracted position as received.
  • Do not connect the power supply before mounting the actuator on the valve.

Mounting the actuator onto the valve sets the valve to its normally open position.

WIRING INSTRUCTIONS

When servicing make sure that:

  • the electric supply to the actuator is switched off to avoid possible damage to the equipment, personal injury or shock
  • the line power supply is in accordance with the power supply specified on the actuator
  • all wiring conforms to local codes and is carried out by authorized personnel only
  • you do not touch or attempt to connect or disconnect wires when electric power is on
  • you do not open or attempt to repair, contact the Crane Technical Department.

WIRING DIAGRAM

ACTUATOR TIMING

CRANE FLUID SYSTEMS ACT992TH Thermic Actuator - ACTUATOR
TIMING

Actuator| Voltage| Valve Opening| Valve closing (after 5’ power on)| Valve closing (after 30’ power on)
---|---|---|---|---
Dead zone (s)| Total time (s)| Dead zone (s)| Total time (s)| Dead zone (s)| Total time (s)
0JG93496B| 24V| 150| 400| 180| 390| 150| 400
0JG93497C| 230V| 80| 230| 180| 390| 150| 400

To visit our Video Library go to: www.youtube.com/user/CraneBSU
CRANE HOUSE, EPSILON TERRACE,
WEST ROAD, IPSWICH,
SUFFOLK IP3 9FJ
TELEPHONE: +44 (0)1473 277300
FAX: +44 (0)1473 277301
UK SALES ENQUIRES: enquiries@cranefs.com
TECHNICAL ENQUIRES: tech-enquiries@crane-ltd.co.uk
TELEPHONE: +44 (0)1473 277400
MIDDLE EAST & NORTH AFRICA
SALES OFFICE,
BUILDING 4, OFFICE 901,
THE GALLERIES, PO BOX 17415,
DOWNTOWN JEBEL ALI
DUBAI, UAE
TELEPHONE: +971 4816 5800
EXPORT SALES ENQUIRES: mena-enquiries@cranefs.com
www.cranefs.com
• Designed and manufactured under quality management systems in accordance with BS EN ISO 9001.
Every effort has been made to ensure that the information contained in this publication is accurate at the time of publishing.
Crane Ltd assumes no responsibility or liability for typographical errors or omissions or for any misinterpretation of the information within the publication and reserves the right to change without notice.

BUILDING SERVICES & UTILITIES
www.cranebsu.com
CFS_ACT992TH1122
IOM
v1

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals