ESYLUX PD-FLAT 360/8 Industrial LED Lamp Instruction Manual

June 12, 2024
ESYLUX

PD-FLAT 360/8 Industrial LED Lamp
Instruction Manual

PD-FLAT 360/8 Industrial LED Lamp

Item no.| Product name| A
ø m| B
ø m| C
ø m| H
m| H max.
m| X
mm| X1
mm| Y1
mm| Y2
mm|
---|---|---|---|---|---|---|---|---|---|---|---
EP10423024| PD-FLAT 360/8 SW BMS DALI-2| 8| 5| 4| 3| 5| 77| 60| 24| 6|
EP10423031| PD-FLAT 360/8 RW BMS DALI-2| 8| 5| 4| 3| 5| 94| 60| 24| 6
EP10423055| PD-FLAT-L 360/8 RW BMS DALI-2| 8| 5| 4| 3| 5| 104| 60| 24| 6

SHORT INSTRUCTION

DANGER!
Risk of fatal injury from electric shock!

  • Installation must only by performed by an electrical installation technician or a trained electrician, taking country-specific regulations into account
  • Switch off the mains voltage prior to assembly/disassembly

Intended use

The ceiling-mounted presence detector is designed for indoor use and for integration in a DALI-2 bus system. The presence detector must have an unobstructed view of people in the room. Detection range at an installation height of 3 m: diagonal (A), frontal (B); presence area (C).
A DALI-2 bus system enables communication and supplies the power via a DALI-2-enabled application controller (based on the IEC 62386-101/-103 standard).

  • Certified in accordance with the DALI-2 standard
  • Only suitable for light control in connection with a DALI-2-enabledapplication controller
  • Integrated motion sensor and light sensor based on the IEC 62386-303/-304 standard
  • Supply voltage via the DALI-2 bus system
  • One non-floating input for connecting a push button based on the IEC 62386-301 standard
    **** Do not use external voltage!

Connection

Connect as shown in figure (1.1).

  1. Standard operation
  2. Standard operation with an additional push button connected; maximum cable length from the push button to the presence detector is 30 m.

The installation cable length between the DALI-2 bus power supply and the presence detector must not exceed 300 m.

Activation

The device is activated in line with the current version of the DALI-2 standard. Connect the DALI bus voltage. A warm-up phase of approx. 25 seconds is initiated.
The signals from the sensor LEDs indicate the following:
State 1 No DALI-2 short address assigned.  The blue sensor LED flashes.
State 2 DALI-2 short address already assigned. The blue and red sensor LEDs flash alternately.
The warm-up phase is complete when the green sensor LED flashes briefly three times.
The presence detector provides the application controller with the following instances in their entirety:
Instance no. 0 Push button input S1 (instance type 1) in accordance with IEC 62386-301
Instance no. 1 Motion sensor (instance type 3) in accordance with IEC 62386-303
Instance no. 2 Light sensor (instance type 4) in accordance with IEC 62386-304

Settings

The presence detector is parameterized and controlled only via the application controller. In addition to standard commands, the following settings (in the table below) can be modified via the entries in memory bank 2:

  • Sensor LED on/off and sensor LED brightness
  • Motion sensor sensitivity
  • Light sensor calibration

Technical data

Connection| 2.5 mm2 / 1.5 mm2|
---|---|---
Weight| PD-FLAT 360/8 SW BMS DALI-2
PD-FLAT 360/8 RW BMS DALI-2
PD-FLAT-L 360/8 RW BMS DALI-2| 68 g
73 g
80 g
Material| UV stabilised polycarbonate|
Relative humidity| 5 – 93%, non-condensing|
Colour| White, similar to RAL 9010|
Nominal voltage| 9.5 – 22.5 V ****|
Standby consumption| < 0.1 W|
Power consumption| DALI peak current level
DALI no-load current level| 12 mA
6 mA
Switch-on time| 600 ms|

Disposal/warranty

**** This device must not be disposed of as unsorted residual waste. Owners are required by law to correctly dispose of used devices. Contact your local town council for more information.
The ESYLUX manufacturer’s warranty can be found online at www.esylux.com.
Technical and design features may be subject to change.

Address| Description| Default value (factory setting)| Behavior during RESET| Memory type
---|---|---|---|---
Ox00| Address of the last accessible memory slot| 0x13| 0x13| ROM
Ox01| Indicator byte| 0x00| Ox00| ROM
0x02| Database lock byte. Lockable bytes in the database must be read only; the lock byte has a different value to 0x55.| Ox FF| Ox FF| RAM
0x03| Database layout/structure version| 0x01| Ox01| ROM
0x04| LED mode (LEDs activated; signalization of “suppressed motion detection” deactivated)| 0x03| No change| NVM
0x05| LED brightness (range: 5…100%)| 50| No change| NVM
0x06, Ox07| ALS indicator word| 0| No change| ROM
0x08, Ox09| ALS 0 — correction factor of 100 lux (range: 1…50)| 10| No change| NVM
OxOA, OxOB| ALS 0 — correction factor of 500 lux (range: 1…50)| 10| No change| NVM
OxOC, Ox0D| ALS 1— correction factor of 100 lux (range: 1…50)| 10| No change| NVM
OxOE, OxOF| ALS 1— correction factor of 500 lux (range: 1…50)| 10| No change| NVM
0x10| PIR sensitivity (range: 1…100, 254, 255)| [1…100]| No change| NVM
Ox11| PIR 1 sensitivity (range: 1…100, 254, 255)| 255| No change| ROM
0x12| PIR 2 sensitivity (range: 1…100, 254, 255)| 255| No change| ROM
0x13| PIR 3 sensitivity (range: 1…100, 254, 255)| 255| No change| ROM

ESYLUX GmbH | An der Strobeck 40
22926 Ahrens burg / Germany
info@esylux.com 
www.esylux.com
MA01946700 Technical data for specific products can be found at www.esylux.com/products