MAGNUM ENERGY RD2212 RD Series Modified Sine Wave Inverter Chargers Owner’s Manual
- June 12, 2024
- MAGNUM ENERGY
Table of Contents
- RD2212 RD Series Modified Sine Wave Inverter Chargers
- Introduction
- Installation
- 2 AWG or smaller| #8 AWG (8.4 mm 2)
- 1 to #1/0 AWG| #6 AWG (13.3 mm2 )
- 2/0 or #3/0 AWG| #4 AWG (21.1 mm2 )
- Operation
- Maintenance and Troubleshooting
- Appendix A – Specifi cations and Optional Equipment
- Appendix B – Battery Information
- Limited Warranty
- How to Receive Repair Service
- Documents / Resources
RD Series
Modifi ed Sine Wave
Inverter/Chargers Owner’s
Manual
RD2212 RD Series Modified Sine Wave Inverter Chargers
Disclaimer of Liability
The use of this manual and the conditions or methods of installation,
operation, use, and maintenance of the RD Series Inverter/Charger is beyond
the control of Magnum Energy, Inc. Therefore, this company assumes no
responsibility and expressly disclaims any liability for loss, damage, or
expense whether direct, indirect, consequential, or incidental that may arise
out of or be in anyway connected with such installation, operation, use, or
maintenance.
Due to continuous improvements and product updates, the images shown in this
manual may not exactly match the unit purchased.
Restrictions on Use
The RD Series Inverter/Charger may only be used in life-support devices or
systems with the express written approval of Magnum Energy. Failure of the RD
Series Inverter/Charger can reasonably be expected to cause the failure of
that life-support device or system, or to affect the safety or effectiveness
of that device or system. If the RD Series Inverter/Charger fails, it is
reasonable to assume that the health of the user or other persons may be
endangered.
Copyright Notice
Copyright © 2004, 2010 by Magnum Energy, Inc. All rights reserved. Permission
to copy, distribute, and/or modify this document is prohibited without express
written permission by Magnum Energy, Inc.
Contact Information
Magnum Energy, Inc.
2211 West Casino Rd.
Everett, WA 98204
Phone: 425-353-8833
Fax: 425-353-8390
Record the unit’s model and serial number in case you need to provide this information in the future. It is much easier to record this information now, instead of trying to gather it after the unit has been installed.
Model:| Serial Number:
RD2212| P1
RD1824| El
RD2824| Fl
RD3924| G1
IMPORTANT SAFETY INSTRUCTIONS
- This manual contains important safety instructions that must be followed during the installation and operation of this product.
- All electrical work must be performed in accordance with local, state and federal electrical codes.
- Read all instructions and safety information contained in this manual before installing or using this product.
- This product is designed for indoor/compartment installation. It must not be exposed to rain, snow, moisture, or liquids of any type.
- Use insulated tools to reduce the chance of electrical shock or accidental short circuits.
- Remove all jewelry such as rings, watches, bracelets, etc., when installing or performing maintenance on the inverter.
- Always disconnect the batteries or energy source prior to installing or performing maintenance on the inverter.
- Live power may be present at more than one point since an inverter utilizes both batteries and AC.
- Always verify proper wiring prior to starting the inverter.
- There are no user-serviceable parts contained in this product.
- This unit is provided with integral protection against overloads.
- The input and output AC and DC circuits are isolated from the inverter chassis. The inverter system grounding is the responsibility of the installer in accordance with the NEC/CEC and local codes.
- Both AC and DC overcurrent protection must be provided as part of the installation.
- Use Class 1 wiring methods for fi eld-wiring connections to terminals of a Class 2 circuit.
- Use only copper wires with a minimum temperature rating of 90°C.
- Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling.
Safety Symbols
To reduce the risk of electrical shock, fi re, or other safety hazard, the
following safety symbols have been placed throughout this manual to indicate
dangerous and important safety instructions.
WARNING: This symbol indicates that failure to take a specifi ed action
could result in physical harm to the user.
CAUTION: This symbol indicates that failure to take a specifi ed action
could result in damage to the equipment.
Info: This symbol indicates information that emphasizes or supplements
important points of the main text.
Remedy: This symbol provides possible solutions for related issues.
SAVE THESE INSTRUCTIONS
IMPORTANT BATTERY SAFETY INSTRUCTIONS
- Be very careful when working around batteries, they can produce extremely high currents if short-circuited. Read the battery supplier’s precautions before installing the inverter and batteries.
- Wear eye protection such as safety glasses when working with batteries.
- Remove all jewelry such as rings, watches, bracelets, etc., when installing or performing maintenance on the inverter.
- Never work alone. Always have someone near you when working around batteries.
- Use proper lifting techniques when working with batteries.
- Never use old or untested batteries. Check each battery’s label for age, type, and date code to ensure all batteries are identical.
- Batteries are sensitive to changes in temperature. Always install batteries in a stable environment.
- Install batteries in a well ventilated area. Batteries can produce explosive gases. For compartment or enclosure installations, always vent batteries to the outside.
- Provide at least one inch (2.5 cm) of air space between batteries to provide optimum cooling.
- Never smoke in the vicinity of batteries.
- To prevent a spark at the battery and reduce the chance of explosion, always connect the cables to the batteries fi rst. Then connect the cables to the inverter.
- Use insulated tools at all times.
- Always verify proper polarity and voltage before connecting the batteries to the inverter.
- To reduce the chance of fi re or explosion, do not short-circuit the batteries.
- In the event of accidental exposure to battery acid, wash thoroughly with soap and water. In the event of exposure to the eyes, fl ood them for at least 15 minutes with running water and seek immediate medical attention.
- Recycle old batteries.
SAVE THESE INSTRUCTIONS
Introduction
1.0 Introduction
Congratulations on your purchase of the RD Series inverter/charger from Magnum
Energy. The RD Series is a modifi ed sine wave inverter designed especially for
renewable energy use. Powerful, yet simple to operate, this inverter/charger
will provide you with the years of trouble-free performance you have come to
expect from Magnum Energy, all backed by our limited 2 year warranty.
Installation is easy. Simply connect the inverter’s output to your
distribution circuits or electrical panel, connect your utility power cable
(AC) to the inverter’s easy-to-reach terminal block, connect the batteries,
and then switch it on for power.
Use the optional accessories listed below to control and monitor many other
Magnum devices.
The RD Series inverter/charger includes the following:
- 1800, 2200, 2800, or 3900 watt models in a small footprint – less weight and area needed for installation (shelf, bulkhead, or upside-down mounting)
- Modifi ed Sine Wave output
- Automatic Power Factor Corrected (PFC) multi-stage battery charging
- RS485 standard communication protocol
- Remote and Network ports (easy connection for optional accessories)
- ON/OFF inverter-mounted switch with LED indicator
- 30 Amp per leg/input (can connect two inputs together to allow 60 Amp pass-thru)
- Large AC access and terminal block [wire size: 10 to 6 AWG (5.3 to 13.3 mm
- DC terminal covers with 360 degree connection
- Field-serviceable for qualifi ed personnel – tested repair kits available
- ETL listed to UL STD 1741, 1st edition for safety
- Automatic battery temperature compensation (using battery temperature sensor) – for optimum charging even during extreme temperature changes
- Overcurrent, over-temperature, and high/low battery voltage protection
The following accessories are also available for use with the RD Series inverter/charger:
- ME-RC50 (Basic Remote Control) – easy to read LCD display panel that enables standard inverter and accessories set up, control, and troubleshooting.
- ME-ARC50 (Advanced Remote Control) – easy to read LCD display panel that enables advance inverter and accessories set up, control, and troubleshooting.
- ME-AGS-N (Automatic Generator Start Module – Network version) – automatically starts/stops your generator.
- ME-BMK (Battery Monitor Kit – with Shunt) – provides precise DC voltage/current measurements and provides information on your battery’s State of Charge (SOC) condition.
- ME-CB (Conduit Box) – provides 1/2” – 2” knockouts for connecting AC and DC conduit runs to the inverter.
- ME-SBC (Smart Battery Combiner) – monitors and keeps a second battery charged using a portion of the current that is charging a main battery.
- MMP (Mini Magnum Panel) – combines all of the major components required for a renewable energy system into a single, easy to install pre-wired enclosure.
1.1 Features and Benefi ts
The RD Series inverter/charger is designed to allow easy access to wiring,
circuit breakers, and controls. Its die cast baseplate with one-piece aluminum
cover ensures maximum durability with minimum weight, as well as cooler more
effi cient operation.
The front of the RD Series is equipped with the following features (see
Figures 1-1 and 1-2):
-
Power ON/OFF Switch – a momentary pushbutton switch that alternately turns the inverter On or Off.
-
Status LED Indicator – this green LED illuminates to provide information on the inverter or charger operation.
-
Stack/Accessories Connection Port (red label) – a RJ11 port that accepts the optional Remote Switch Adapters (RSAs) which enable remote on/off switch operation.
Info: The stacking feature is NOT available with the RD Series. -
Network Connection Port (green label) – a RJ11 port that accepts optional network capable accessories (e.g., Auto Gen Start or Battery Monitor).
-
Remote Connection Port (blue label) – a RJ11 port that allows the optional remote controls (ME-RC50 or ME-ARC50) to be connected.
-
BTS Connection Port (yellow label) – RJ11 port that accepts the remote Battery Temperature Sensor (BTS) accessory.
-
DC Equipment Ground Terminal – this connection is used to tie the exposed chassis of the inverter to the DC grounding system. This terminal accepts CU/AL conductors from #14 to #2 AWG (2.1 to 33.6 mm 2 ).
-
AC Input/Output Connections – two 3/4” knockouts provided with cable-clamp strain reliefs to allow and hold the AC input and output fi eld wiring.
-
Intake Air Vents – ventilation openings to pull in air to help keep the inverter cool for peak performance.
-
Positive DC Terminal – provides 360 degree connection point for the positive (+) cable from the battery bank; provided with a Kep or Flange nut on a 5/16-18 bolt (5/8” usable length) to hold the battery cable to the DC terminal.
-
Negative DC Terminal – provides 360 degree connection point for the negative (-) cable from the battery bank; provided with a Kep or Flange nut on a 5/16-18 bolt (5/8” usable length) to hold the battery cable to the DC terminal.
-
Mounting Flange – used to secure the inverter to a shelf or wall. The left side of the RD Series is equipped with the following features (see Figure 1-3):
-
Exhaust Air Vent – ventilation openings that allow heated air to be removed by the internal cooling fan.
-
Model/Serial Number Label – includes model/serial number information, date of manufacture, and inverter and charger specifi cations. See the RD Specifi cations in Appendix A for more information and the different models that are available.
-
AC Access Cover – provides access to the internal AC wiring terminal block. This terminal block is used to hardwire all inverter AC input and output wiring connections. Remove the two screws to access the AC wiring terminal block.
-
Input Circuit Breaker – this circuit breaker protects the unit’s internal charger wiring and pass-thru relay while in Standby Mode. This circuit breaker will pop out when it opens. Press in to reset. This input circuit breaker is not branch-circuit rated, therefore, branch-circuit rated breakers must be installed in the inverter’s input wiring.
CAUTION: The inverter’s internal AC transfer relay is rated for 30 amps per leg. The pass-thru current must be no greater than 30 amps per leg or damage to the relays may occur.
1.2 How an
Inverter/Charger Works
An inverter takes direct current (DC) from your batteries and turns it into
alternating current (AC).
It also takes alternating current (when connected to a generator or to utility
power) and transforms it into direct current to charge your batteries. These
two modes of operation associated with this inverter/charger are referred to
in this document as:
-
Inverter Mode:
When the inverter is properly connected to batteries and turned on, the direct current(DC) from the batteries is transformed into a modifi ed sine wave alternating current (AC). This AC is similar to the voltage provided by a utility for your home, and is used to power the AC electrical appliances (i.e., AC loads) connected to the inverter’s output. -
Standby Mode:
When an external source of AC power (e.g., utility power or generator) is connected and qualifi ed on the inverter’s AC input, it operates in the Standby Mode. In the Standby Mode, the unit operates as a Battery Charger to convert the incoming AC power into DC power to recharge the batteries; and at the same time, automatically closes an internal AC Transfer Relay to pass the incoming AC power directly to the inverter’s output to continue powering the connected electrical appliances.
1.3 What Appliances will run from a Modifi ed Sine Wave Inverter
Today’s inverters come in two basic output waveforms: modifi ed sine wave
(which is actually a modifi ed square wave) and pure sine wave. Modifi ed sine
wave inverters approximate a pure sine waveform and will run most appliances
and electronics without any problems. These inverters are less expensive, and
therefore, offer a viable alternative to more expensive pure sine inverters.
The output of a modifi ed sine wave inverter will run most electronic and
household items, including but not limited to: TV, VCR, satellite dish
receiver, computers, and printers. Some devices such as rechargeable power
supplies for phones, drills, and other like items may not run, and could even
be at risk for damage from modifi ed sine wave inverters.
1.4 Appliances and Run Time
The RD Series inverter/charger can power a wide range of household appliances
including small motors, hair dryers, clocks, and other electrical devices. As
with any appliance using batteries for power, there is a certain length of
time that it can run – this is called “run time.” Actual run time depends on
several variables, including: the size and type of appliance, the type of
batteries installed in your application, as well as the battery’s capacity and
age. Other factors such as the battery’s state of charge and temperature can
also affect the length of time your appliances can run.
Appliances such as TVs, VCRs, stereos, computers, and lights can all be
successfully powered by your inverter. Depending on your inverter capacity,
electrical appliances that use larger loads such as coffee pots and hair
dryers can be used for short durations. However, loads that are used for
longer periods (stoves, water heaters, etc.) can quickly drain your batteries
and are not recommended for inverter applications.
All electrical appliances are rated by the amount of power they consume (see
Table 1-1). The rating is printed on the product’s nameplate label, usually
located on its chassis near the AC power cord. Even though it is diffi cult to
calculate exactly how long an inverter will run a particular appliance, the
best advice is trial and error. Your RD Series inverter has a built-in
safeguard that automatically protects your batteries from over-discharge.
Info: For optimum performance, a minimum battery bank of 200 AH is
recommended for moderate loads (<1000W) and greater than 400 AH for heavy
loads (≥1000W).
Table 1-1, Typical Appliance Power Consumption
Device | Load | Device | Load |
---|---|---|---|
Blender | 400W | Coffee Mak | 1200W |
Computer | 300W | Color TV | 150W |
VCR | 40W | Hair Dryer | 1000W |
Hot Plate | 1800W | Iron | 1000W |
Light (Flo) | 10W | Light (Inc) | 100W |
Microwave | 1000W | Refrigerator | 500W |
Installation
WARNING: Installations should be performed by qualifi ed personnel, such
as a licensed or certifi ed electrician. It is the installer’s responsibility
to determine which safety codes apply and to ensure that all applicable
installation requirements are followed.
Applicable installation codes vary depending on the specifi c location and
application of the installation.
CAUTION: Review the “Important Product Safety Information” on page ii,
and the “Important Battery Safety Instructions” on page iii before any
installation.
CAUTION: The inverter is heavy. Use proper lifting techniques during
installation to prevent personal injury.
The simplifi ed system diagram shown in Figure 2-1 should be reviewed to assist
you in planning and designing your installation. This drawing is not intended
to override or restrict any national or local electrical codes. This drawing
should not be the determining factor as to whether the installation is
compliant, that is the responsibility of the electrician and the onsite
inspector.
2.1 Pre-Installation
Before installing the inverter, read the entire installation section to
determine how you are going to install your RD inverter/charger. The more
thorough you plan in the beginning, the better your inverter needs will be
met.
2.1.1 Unpacking and Inspection
Carefully remove the RD Series inverter/charger from its shipping container
and inspect all contents. Verify the following items are included:
- The RD Inverter/Charger
- Red and black DC terminal covers with Phillips screws
- AC access cover with two Phillips screws
- Two 5/16” Kep or Flange nuts (installed on the DC terminals)
- Battery Temperature Sensor
- Warning label
- RD Series Owner’s Manual
If items appear to be missing or damaged, contact your authorized Magnum
Energy dealer or Magnum Energy. If at all possible, keep your shipping box. It
will help protect your inverter from damage if it ever needs to be returned
for service. Save your proof-of-purchase as a record of your ownership; it
will also be needed if the unit should require in-warranty service.
Record the unit’s model and serial number in the front of this manual in case
you need to provide this information in the future. It is much easier to
record this information now, instead of trying to gather it after the unit has
been installed.
2.1.2 Required Tools and Materials
Hardware/Materials
- Conduit, strain-reliefs, and appropriate fi ttings
- Electrical tape
- 1/4” mounting bolts and lock washers
- Wire ties
Tools
- Miscellaneous screwdrivers
- Drill and drill bits
- Level
- Pliers
- Pencil or marker
- 1/2” wrench
- Wire strippers
- Multimeter
2.1.3 Locating the Inverter
Only install the inverter in a location that meets the following requirements:
Clean and Dry – The inverter should not be installed in an area that allows
dust, fumes, insects, or rodents to enter or block the inverter’s ventilation
openings. This area also must be free from any risk of condensation, water, or
any other liquid that can enter or fall on the inverter. The inverter uses
stainless steel fasteners, plated copper busbars, and a power-coated aluminum
base. The internal circuit boards are conformal coated. All of this is done to
help fi ght the harmful effects of corrosive environments. However, the
inverter’s life is uncertain if used in the above types of environments, and
inverter failure under these conditions is not covered under warranty.
Info: If the inverter is installed in an area where moisture may occur,
we recommend putting silicone dielectric grease compound into the electrical
ports (see Figure 1-1, Items 3-6). Before installing the cables, or if leaving
any ports open, squirt a liberal amount into each port. Silicone dielectric
makes an effective moisture and corrosive barrier to help protect and prevent
corrosion to the RJ11 connections.
Cool – The inverter should be protected from direct sun exposure or
equipment that produces extreme heat. The ambient temperature around the
inverter must not exceed 77°F (25°C) to meet power specifi cations.
Ventilation – In order for the inverter to provide full output power and
avoid over-temperature fault conditions; do not cover or block the inverter’s
ventilation openings, or install this inverter in an area with limited airfl
ow. The inverter uses two fans to provide forced-air cooling. These fans pull
in air through the intake vents (see Figure 1-2, Item 9) and blow out air
through the exhaust vents (see Figure 1-3, Item 13). Allow at the minimum an
airspace clearance of 6” (15.2 cm) at the intake and exhaust vents, and 3”
(7.6 cm) everywhere else to provide adequate ventilation.
If installed in an enclosure, a fresh-air intake opening must be provided
directly to the front side (intake vents) of the inverter, and an exhaust
opening on the back side (exhaust vents) of the inverter. This allows cool air
from the outside to fl ow into the inverter, and heated air to exit the
inverter and the enclosure. When mounted in an enclosed compartment, airfl ow
must be ≥ 100 cfm in order to maintain no more than a 68°F (20°C) rise in
compartment temperature.
CAUTION: Do not mount this inverter in a zero clearance compartment, nor
cover or obstruct the ventilation openings – overheating may result.
Safe – Keep any fl ammable/combustible material (e.g., paper, cloth,
plastic, etc.) that may be ignited by heat, sparks, or fl ames at a minimum
distance of 2 feet (61 cm) away from the inverter. Do not install this
inverter in any area that contains extremely fl ammable liquids like gasoline
or propane, or in locations that require ignition-protected devices.
Close to the battery bank – As with any inverter, it should be located as
close to the batteries as possible. Long DC wires tend to loose effi ciency and
reduce the overall performance of an inverter.
However, the unit should NOT be installed in the same compartment as the
batteries, or mounted where it will be exposed to gases produced by the
batteries. These gases are corrosive and will damage the inverter; also, if
these gases are not ventilated and allowed to collect, they could ignite and
cause an explosion.
Info: The battery bank should be installed in a clean, dry, ventilated
environment where they are protected from high and low temperatures. The
batteries must be mounted upright (if using liquid batteries) and securely
fastened. The location must be fully accessible and protected from exposure to
heat producing devices, and away from any
fuel tanks.
Accessible – Do not block access to the inverter’s remote control and
accessory ports, as well as the inverter’s controls and status indicator. Also
allow enough room to access the AC and DC wiring terminals and connections, as
they will need to be checked and tightened periodically. See Figure 2-3 for
the RD Series’ inverter/charger dimensions.
Away from sensitive electronic equipment – High-powered inverters can generate
levels of RFI (Radio Frequency Interference). Locate any electronic equipment
susceptible to radio frequency and electromagnetic interference as far away
from the inverter as possible.
2.2 Mounting the Inverter
The inverter base can reach a temperature up to 90°C (194°F) and it is
recommended that it should be mounted on a non-combustible surface*. This
surface and the mounting hardware must also be capable of supporting at least
twice the weight of the inverter. To meet regulatory requirements, the RD
Series must be mounted in one of the following positions, as shown in Figure
2-2:
- above or under a horizontal surface (shelf or table)
- or, on a vertical surface (wall) with the DC terminals to the right
- or, on a vertical surface (wall) with DC terminals toward the bottom, MP-HOOD (inverter hood) installed on the top, and either the ME-CB (Conduit Box) or MMP Series (single inverter) enclosureinstalled on the inverter’s bottom.
Info: The ME-CB and the MMP Series enclosure prevent material from
falling out the bottom in the event of an internal fi re, and also allow suffi
cient ventilation to prevent the inverter from overheating under normal
operating conditions. The MP-HOOD inverter hood helps prevent items from
falling inside, causing damage to the inverter.
Info: Magnum provides a backplate with a suitable surface for mounting
the inverter. These backplates also provide the ability to mount the MMP
Series enclosure (PN: BP-MMP).
After determining the mounting position, refer to the physical dimensions as
shown in Figure 2-3, or use the base of the inverter as a template to mark
your mounting screw locations.
- Non-combustible surface – A surface made of material that will not ignite, burn, support combustion, or release fl ammable vapors when subjected to fi re or heat as per the ASTM E136 standard. For the most part, these are materials that are largely comprised of inorganic matter such as stone, steel, iron, brick, tile, concrete, slate, and glass. Avoid common building materials such as gypsum board, painted surfaces, wall coverings, and any type of wood. 2.3 Wiring the Inverter – General Requirements
This section describes the requirements and recommendations for wiring the RD Series inverter/ charger. Before wiring the inverter/charger, read all instructions.
All wiring should meet all local codes and industry standards, and be performed by qualifi ed personnel such as a licensed electrician.
The NEC (National Electric Code, ANSI/NFPA 70) for the United States and the CEC (Canadian Electrical Code) for Canada provide safe wiring standards. The NEC/CEC list requirements for wire sizes, overcurrent protection, and installation ethods/standards.
Inverter/charger systems involve power from multiple sources (e.g., inverter, generator, utility power, batteries, etc.) which makes the wiring more hazardous and challenging.
The input and output AC and DC circuits are isolated from the inverter chassis. The inverter system grounding is the responsibility of the installer in accordance with the NEC/CEC and local codes.
WARNING: Ensure the sources of DC power (i.e., batteries) and AC power (utility power or AC generator) are de-energized (i.e., breakers opened, fuses removed) before proceeding – to prevent accidental shock.
2.3.1 Protecting Wire – Conduit Box
The AC and DC wires into and out of the inverter must be protected as required
by code. This can be done by using jacketed wires or by feeding wires through
a conduit. Magnum offers for purchase a DC conduit box (ME-CB), or a single
inverter enclosure (MMP Series) that includes the AC and DC inverter breakers
that allow both the AC and DC conduits to be connected to the inverter.
Info: If using the ME-CB conduit box or the MMP enclosure, and the AC
wires are individual conductors (i.e., not jacketed), the strain reliefs can
be removed and replaced with 3/4” grommets.
2.3.2 Wiring Requirements
All conductors that are at risk for physical damage must be protected by tape,
or placed in a raceway.
Always check for existing electrical, plumbing, or other areas of potential
damage prior to making cuts in structural surfaces or walls.
Do not mix AC and DC wiring in the same panel unless specifi cally
approved/designed for both AC and DC wiring. Where DC wiring must cross AC or
vice-versa, try to make the wires 90° to one another at the crossing point.
Both AC and DC overcurrent protection must be provided as part of the
installation.
The inverter requires a reliable negative and ground return path directly to
the battery.
Use only copper wires with a minimum temperature rating of 90°C.
2.3.3 Wire Routing
Before connecting any wires, determine all wire routes to and from the
inverter. Conductors passing through walls or other structural members must be
protected to minimize insulation damage, such as chafi ng. During installation,
always avoid placing conductors near sources of chafi ng caused by vibration or
constant rubbing. Typical routing scenarios include:
- AC input wiring from utility power source to the inverter
- AC input wiring from a generator (optional) to the inverter
- DC input wiring from the batteries to the inverter
- AC output wiring from the inverter to the AC main panel or to dedicated circuits
- Battery Temperature Sensor cable from the inverter to the batteries
- Remote control cable (optional) to the inverter
- Ground wiring to and from the inverter
2.3.4 Torque Requirements
Torque all AC wiring connections to 16 in lbf (1.8 N-m). Torque DC cable
connections from 10 to 12 ft lbf (13.6 to 16.3 N-m).
2.4 DC WiringThis section describes the inverter’s required DC wire sizes, the
recommended disconnect/overcurrent protection, and how to make the DC
connections to the inverter and the battery bank.
Refer to Figure 2-4 when connecting the DC wires.
WARNING: Even though DC voltage is “low voltage”, signifi cant hazards may
be present, particularly from short circuits of the battery system.
CAUTION: The inverter is NOT reverse polarity protected, which means that
if the negative and positive battery voltage is connected backwards to the
inverter, the inverter will likely be damaged. You should verify the correct
voltage polarity using avoltmeter BEFORE connecting the DC wires.
CAUTION: Before wiring the DC cables, review the safety information at
the beginning of this manual and the instructions below to ensure a safe and
long-lived system. Info: DO NOT connect the battery cables to the inverter
until all wiring is complete.
- When the inverter is installed in a Photovoltaic System, the NEC requires that the DC circuit conductors and overcurrent devices to the inverter be sized to carry not less than 125% of the inverter’s maximum current rating.
- The DC positive and negative cables connected to the inverter from the battery bank should be tied together with wire ties or electrical tape approximately every 6 inches (153mm). This helps improve the surge capability and reduces the effects of inductance, which improves the inverter waveform and reduces the wear of the inverter’s fi lter capacitors.
- Crimped and sealed copper ring terminal lugs with a 5/16” hole should be used to connect the DC wires to the inverter’s DC terminals.
- The battery bank voltage MUST match the DC voltage required by the inverter (i.e., 24-volt battery bank for a 24-volt inverter), or the inverter may be damaged.
- To ensure the maximum performance from the inverter, all connections from the battery bank to the inverter should be minimized. The exceptions are the DC overcurrent disconnect in the positive line, and a shunt in the negative line. Any other additional connection will contribute to additional voltage drops and these extra connection points may loosen during use.
- All wiring to the battery terminals should be checked periodically (once a month) for proper tightness. The torque requirement for the DC terminals is between 10 to 12 ft lbf (13.6 to 16.3 N-m). If you don’t have a torque wrench, ensure all DC terminals are tight and cannot move.
- Be aware that overtightening or misthreading the nuts on the DC terminals can cause the bolts to strip and snap/break off.
- Make sure cables have a smooth bend radius and do not become kinked. Place long cable runs in conduit and follow existing wire runs where possible.
- A brief spark or arc may occur when connecting the battery cables to the inverter DC terminals; this is normal and due to the inverter’s internal capacitors being charged.
- Color code the DC cables/wires with colored tape or heat shrink tubing: RED for positive (+), WHITE for negative (-), and GREEN (or bare copper) for DC ground to avoid polarity problems.
2.4.1 DC Wire Sizing
It is important to use the correct DC wire to achieve maximum effi ciency from
the system and reduce fi re hazards associated with overheating. Always keep
your wire runs as short as practical to help prevent low voltage shutdowns and
keep the DC breaker from nuisance tripping (or open fuses) because of
increased current draw. See Table 2-1 to select the required minimum DC wire
size (and corresponding overcurrent device) based on your inverter model. The
cable sizes listed in Table 2-1 for your inverter model are required to reduce
stress on the inverter, minimize voltage drops, increase system effi ciency,
and ensure the inverter’s ability to surge heavy loads.
If the distance from the inverter to the battery bank is greater than 5 feet
(1.5 m), the DC wire size will need to be increased. Longer distances cause an
increase in resistance, which affects the performance of the inverter.
Continue to use the overcurrent device previously determined from Table 2-1,
and then refer to Table 2-2 to determine the minimum DC wire size needed for
various distances based on your inverter model.
2.4.2 DC Overcurrent Protection
DC overcurrent protection is not included in the inverter, it must be provided
as part of the installation. This requirement is needed in order to comply
with electrical code regulations and for safety reasons. The DC overcurrent
protection device must be installed in the positive DC cable line, it can be a
fuse or a circuit breaker, and it must be DC rated. It must be correctly sized
according to the size of DC cables being used, which means it is required to
open before the cable reaches its maximum current carrying apability, thereby
preventing a fi re. The NEC requires both overcurrent protection and a
disconnect switch. If a circuit breaker is used as the overcurrent protection
device, it can also be used as the required DC disconnect.
If a fuse is used as an overcurrent device, a Class-T type or equivalent is
recommended. This fuse type is rated for DC operation, can handle the high
short-circuit currents, and has a time delay that allows for momentary current
surges from the inverter without opening the fuse. However, because the fuse
can be energized from both directions, if it is accessible to unqualifi ed
persons the NEC requires that it be installed in such a manner that the power
must be disconnected on both ends of the fuse before servicing.
The recommendations in Table 2-1 may not meet all local code or NEC
requirements.
Table 2-1, Recommended DC Wire/Overcurrent Device for Rated Use
Inverter Model| Maximum
Continuous
Current’| Using Conduit| DC Grounding Electrode Wire Size’s
---|---|---|---
Minimum DC Wire
Size (90°C rating)2| Maximum DC
Breaker Size3
RD2212| 293 amps| #4/0 AWG
[107.2 mm2] (260 amps)| 250 ampss| #6 AWG
(13.3 mm2)
RD1824| 120 amps| #2/0 AWG
[67.4 mm2] (195 amps)| 175 amps| #6 AWG
(13.3 mm2)
RD2824| 186 amps| #4/0 AWG
[107.2 mm2] (260 amps)| 250 amps| #6 AWG
(13.3 mm2)
RD3924| 260 amps| #4/0 AWG
[107.2 mm2] (260 amps)| 250 ampss| #6 AWG
(13.3 mm2)
Note 1 – Maximum Continuous Current is based on the inverter’s continuous
power rating at the lowest input voltage with an ineffi ciency factor.
Note 2 – Wire size is based on the requirements needed to increase effi
ciency and reduce stress to the inverter.
Note 3 – The next larger standard size overcurrent device may be used if
the de-rated cable ampacity falls between the standard overcurrent devices
found in the NEC.
Note 4 – Per the NEC, the DC grounding electrode conductor can be a #6
AWG (33.6 mm2) conductor if that is the only connection to the grounding
electrode and that grounding electrode is a rod, pipe, or plate electrode.
Note 5 – May not allow continuous operation at full rated power as defi
ned by the NEC.
Table 2-2, DC Wire Size For Increased Distance (in free air)
Inverter
Model| **Minimum Recommended DC Wire Size (one way)*
---|---
1-3 feet| 3-5 feet| 5-10 feet**
RD2212| #4/0 AWG (107.16 mm2)| #4/0 AWG x2 (107.16 mm2)| not recommended
RD1824| #2/0 AWG (67.4 mm2)| #2/0 AWG (67.4 mm2)| #4/0 AWG (107.16 mm2)
RD2824| #4/0 AWG (107.16 mm2)| #4/0 AWG (107.16 mm2)| #4/0 AWG x2 (107.16 mm2)
RD3924| #4/0 AWG (107.16 mm2)| #4/0 AWG x2 (107.16 mm2)| not recommended
- Copper wire rated with 90°C (194°F) insulation at an ambient temperature of 30°C (86°F).
2.4.3 DC Cable Connections
Do not put anything between the DC cable ring lug and the battery terminal
post or the fl at metal part of the inverter’s DC terminal. When connecting the
DC cable to the battery or inverter DC terminals, the cable should be placed
directly against the inverter or battery terminals. Incorrectly installed
hardware causes a high resistance connection, which could lead to poor
inverter/charger performance and may melt the cable and terminal connections.
Follow the examples in Figures 2-5 and 2-6 to connect the DC cables and stack
the hardware correctly. Tighten the terminal connections from 10 to 12 ft lbf
(13.6 to 16.3 N-m).
CAUTION: The DC terminal and Kep nuts are made of stainless steel, which
has a high likelihood of seizure. To help prevent the bolt and nut from
seizing — causing the bolts to strip or snap/break-off — the use of anti-seize
lubricant is highly recommended.
Info: If antioxidant grease or spray is used, apply it after all the
connections have been made and are properly tightened.
Info: A 1/2-inch wrench or socket is used to tighten the 5/16 SAE Kep
nuts.
2.4.4 Wiring the Battery Bank
WARNING: Lethal currents will be present if the positive and negative
cables attached to the battery bank touch each other. During the installation
and wiring process, ensure the cable ends are insulated or covered to prevent
touching/shorting the cables.
Info: DO NOT connect the DC wires from the battery bank to the inverter
until: 1) all DC and AC wiring are completed, 2) the correct DC and AC
overcurrent protection have been installed, and 3) the correct DC voltage and
polarity have been verifi ed.
Info: For the RD Series inverter/charger to perform optimally, a minimum
battery bank of 200 AH is recommended for moderate loads (<1000W) and greater
than 400 AH for heavy loads (≥1000W).
Depending upon the voltage of the batteries you use in the installation (6 or
12 VDC), the batteries must be wired in series, parallel, or series-parallel
to provide the correct voltage (see Appendix B – Battery Information for
guidance on wiring batteries together). The interconnecting DC wires must be
sized and rated exactly the same as those that are used between the battery
bank and the inverter.
Place the batteries as close as practical to the inverter, preferably in an
insulated and ventilated enclosure. Allow adequate space above the batteries
to access the terminals and vent caps (as applicable). Also, allow at least 1”
(2.5 cm) of space between the atteries to provide good air flow. DO NOT mount
the batteries directly under the inverter.
CAUTION: Install batteries in a well ventilated area. Batteries can
produce explosive gases. For compartment/enclosure installations, always vent
batteries to the outside.
Info: To ensure the best performance from your inverter system, batteries
should be of the same size, type, rating, and age. Do not use old or untested
batteries.
2.4.5 Battery Temperature Sensor Installation and Wiring
The Battery Temperature Sensor (see Figure 2-7) provides the inverter with
precise battery temperature information to automatically adjust the ABSORB and
FLOAT charge voltage setpoints. This enables the batteries to be correctly
charged under extreme temperature changes.
If the temperature sensor is NOT installed and the batteries are subjected to
large temperature changes, battery life may be shortened.
The BTS provided may be extended to a maximum length of 40’ (12 m) using a
RJ11 connector (female to female) and a standard phone cable with RJ-11
connectors.
However, your inverter to battery cable length shouldn’t exceed the
recommended distance shown inTable 2-2.
To install the BTS:
- Attach the ring terminal end of the Battery Temperature Sensor to the negative battery terminal; see Figure 2-5 for proper connection to the battery terminal.
- Route the sensor’s cable to the inverter following existing wire runs.
- Connect the RJ11 connector end of the BTS cable to the yellow-labeled BTS Port on the inverter (see Figure 1-1, Item 6).
2.4.6 Wiring the Inverter to the Battery Bank
CAUTION: The inverter is NOT reverse polarity protected. If this happens,
the inverter will be damaged and will not be covered under warranty. Before
connecting the DC wires from the batteries to the inverter, verify the correct
battery voltage and polarity
using a voltmeter. If the positive terminal of the battery is connected to the
negative terminal of the inverter and vice versa, severe damage will result.
If necessary, color code the cables (with colored tape); red for positive (+),
and marked white for negative (-) to avoid polarity confusion.
Info: The DC overcurrent device (e.g., circuit breaker or fuse) must be
placed in the positive (red) DC cable line between the inverter’s positive DC
terminal and the battery’s positive terminal (red); as close to the battery as
possible.
DC Ground Wire
Route an appropriately sized DC grounding wire (green or bare wire) from
the inverter’s DC Equipment Ground Terminal (see Figure 1-2, Item 7) to a
dedicated system ground. Recommended tightening torque is 45 in lbf (5.1 N-m).
Refer to Section 2.6 for grounding information and sizing the DC ground wires.
DC Negative Wire
Route an appropriately sized DC negative wire (marked white) from the negative
terminal of the battery bank to the inverter’s Negative DC Terminal (see
Figure 1-2, Item 11).
Info: If installing a battery monitor such as Magnum’s ME-BMK, install a
DC shunt inline with the negative battery cable.
DC Positive Wire
Mount the circuit breaker or fuse assembly as near as practical to the
batteries and leave open (i.e., no power to inverter).
WARNING: DO NOT close the DC circuit breaker or connect the fuse to
connect battery power to the inverter at this time. This will occur in the
Functional Test after the installation is complete.
CAUTION: If connecting live battery cables to the inverter DC terminals,
a brief spark or arc may occur; this is normal and due to the inverter’s
internal capacitors being charged.
Route and connect an appropriately sized DC positive wire (red) from the
inverter’s Positive DC Terminal (see Figure 1-2, Item 10) to one end of the
circuit breaker (or DC fuse block).
Connect a short wire (same rating as the DC wires) to the other side of the DC
circuit breaker (or one end of the fuse/disconnect assembly), and the other
end of the short wire to the positive terminal of the battery bank (see Figure
2-1 for reference). This is essential to ensure even charging and discharging
across the entire battery bank.
Ensure the DC wire connections (on the batteries, inverter, and DC circuit
breaker/fuse lugs) are flush on the surface of the DC terminals, and the
hardware (lock washer and nut) used to hold these connections are stacked
correctly (Figures 2-5 and 2-6). Verify all DC connections are torqued from 10
to 12 ft lbf (13.6 to 16.3 N-m).
Once the DC connections are completely wired and tested, coat the terminals
with an approved anti-oxidizing spray.
Attach the red and black terminal covers over the inverter’s DC connectors,
and then secure them in place with the supplied screws.
If the batteries are in an enclosure, perform a fi nal check of the connections
to the battery terminals, and then close and secure the battery enclosure.
2.5 AC Wiring
This section provides information on how to make the AC connections to the
inverter using the correct AC wire size and the corresponding overcurrent
protection.
2.5.1 Pre-AC Wiring Requirements
CAUTION: Before installing any AC wiring, review the safety information
and cautionary markings at the beginning of this manual and the directions
below to ensure a safe and long-lived system:
- Always use properly rated circuit-breakers. If using an electrical sub-panel, circuit breakers can only be moved from the main electrical panel to the sub-panel if the breakers are also listed to be installed in the sub-panel.
- AC wiring must be no less than #12 AWG (3.3 mm 2 ) gauge copper wire and be approved for the application (i.e., house or cabin wiring).
- DO NOT connect the inverter’s output to an AC power source. This could cause severe damage to the inverter and is not covered under warranty.
WARNING: To reduce the risk of fi re, do not connect this inverter to an
AC load center (circuit breaker panel) having multi-wire branch circuits
connected.
2.5.2 AC Wire Size and Overcurrent Protection
The AC input and output wiring must be sized per the local electrical safety
code requirements to ensure the wire’s ability to safely handle the inverter’s
maximum load current. After determining the proper AC wire sizes, they are
required to be protected from short circuits and overloads by an overcurrent
protection device, and have a means to disconnect the AC circuits.
The RD Series allows the AC input and output wiring to be permanently wired.
The inverter’s input is wired to the service/distribution panel (main panel).
The inverter’s output is then wired to a dedicated panel (sub-panel). The
inverter uses the circuit breakers provided in the panels as the overcurrent
protection and the AC disconnect device.
AC overcurrent protection isn’t included in the inverter and must be provided
as part of the inverter installation. The AC overcurrent protection device
must be a circuit breaker or a fuse/disconnect, be properly sized, and branch
circuit rated for the wire it’s protecting and the appliances being powered.
When in Standby Mode, the full AC continuous pass-thru capacity of the RD
Series inverter/charger is 30 amps for each AC leg (AC HOT1 and AC HOT2).
However, the AC HOT1 and AC HOT2 may be combined to obtain a 60 amps pass-thru
capability (see Figure 2-12 for the SISO-60A confi guration).
For a 30 amp continuous pass-thru capability, each AC HOT IN input to the
inverter requires a 30 amp continuous duty rated breaker 1 , which corresponds
to a minimum cable size of #10 AWG (5.3 mm 2 ). When tying the AC HOT1 and
HOT2 together for a 60 amp continuous pass-thru capability, the AC input to
the inverter requires a 60 amp continuous duty rated breaker, which
corresponds to a minimum cable size of #6 AWG. If you are using other circuit
breakers/wire sizes, refer to the appropriate electrical codes for proper
sizing requirements.
CAUTION: The inverter’s internal AC transfer relay contacts are rated for
30 amps per leg, the pass-thru current must be no greater than 30 amps per leg
or damage to this relay may occur.
Note 1 – The breaker must be de-rated by 80% if not rated for continuous
duty. The NEC requires that circuits are not to be operated continuously at
more than 80% of rating unless listed with a 100% continuous rating.
2.5.3 Recommended GFCI (Ground Fault Circuit Interruption) Breakers
Some electrical safety codes require the use of GFCI’s. In compliance with UL
standards, Magnum Energy has tested the following GFCI’s and fi nd that they
function properly when connected to the inverter’s AC output:
Shock Sentry ™#XGF15V-SP
Leviton Smart Lock #8899-A
Hubbel #GF520EMBKA
2.5.4 AC Terminal Block Connections
The inverter has a six-pole AC terminal block and one AC ground terminal to
connect the inverter’s AC input and output wiring. To access and view the AC
terminal block and ground terminal, remove the two Phillips screws holding the
AC Access Cover plate (see Figure 1-3, Item 15).
Each connection on the AC terminal block is rated to accept one #14 to #6 AWG
(2.1 to 13.3 mm 2 ) CU stranded wire, or two #12 AWG (3.3 mm 2 ) CU stranded
wires. The connection uses a M3.5 slotted head screw, and the maximum
tightening torque is 16 in lbf (1.8 N-m).
Info: One of the AC wiring confi gurations [SI/SO (60A), Figure 2-12] uses
a #6 AWG (13.3 mm2 ) CU wire to carry 60 amps, and splits to two wires to
allow 30 amps for each leg (i.e., AC HOT1 and AC HOT2). IDEAL Industries Inc.
(www.idealindustries.com)) manufactures a
crimp connector (PN: 412) and a separate insulator (PN: 417) that allow up to
two #8 AWG (8.4 mm2 ) wires, with one #6 AWG (13 mm2 ) wire to be connected
together.
Info: For alternative energy installations and to comply with standard
safety requirements, the six-pole AC terminal is provided with a stainless
steel wire protector to prevent wire damage from the set-screw.
Info: The inverter’s NEUT IN and NEUT OUT terminals are connected
together internally.
The AC ground terminal can accept one #14 to #6 AWG (2.1 to 13 mm 2 ) CU
stranded wire. It uses a slotted head screw and has a recommended maximum
tightening torque of 45 in lbf (5.1 N-m).
For multiple ground wires, use a pressure or mechanical connector to attach
the single wire from the AC ground terminal to the input and output ground
connections.
2.5.5 AC Conductor Wiring
The following steps are basic guidelines for installing and connecting the AC
wiring into and out of the inverter. Refer to Table 2-3 to determine your AC
wiring confi gurations before beginning.
WARNING: Before making any AC connections, make sure the inverter is
disconnected from the battery and there is no other source of live power
connected to the inverter.
Wiring the Inverter AC Input
-
Remove the two Phillips screws on the AC Access Cover (see Figure 1-3, Item 15) to access the internal AC Terminal Block (see Figure 2-10).
-
Route the cable from the AC electrical main panel through one of the strain relief clamps to the AC INPUT. Tighten the strain relief clamp securely on the cable. Always leave a little extra slack in the wiring.
-
Connect the hot wire (black) from the main panel’s dedicated breaker to the “HOT 1 IN” terminal. Tighten the “HOT 1 IN” terminal to 16 in lbf (1.8 N-m).
Info: Depending on the AC wiring confi guration, you may need to connect a wire to the “HOT 2 IN” terminal, refer to your confi guration drawing (Figure 2-11 to 2-14). -
Connect the neutral (white) from the main panel’s neutral busbar to the “NEUT IN” terminal.
Tighten the “NEUT IN” terminal to 16 in lbf (1.8 N-m).
Wiring the Inverter AC Output
-
Route the cable from the inverter’s AC OUTPUT to the AC electrical sub-panel through the other strain relief clamp. Tighten the strain relief clamp securely on the cable.
-
Connect the hot (black) wire from the “HOT 1 OUT” terminal to the sub-panel main breaker.
Tighten the “HOT 1 OUT” terminal to 16 in lbf (1.8 N-m).
Info: Depending on the AC wiring confi guration, you may need to connect a wire to the “HOT 2 OUT” terminal, refer to your confi guration drawing (Figure 2-11 to 2-14). -
Connect the neutral (white) from the “NEUT OUT” terminal to the sub-panel’s neutral busbar.
Tighten the “NEUT OUT” terminal to 16 in lbf (1.8 N-m).
Wiring the Inverter AC Ground
- Combine the ground (green) wire from the main panel’s ground busbar and the ground (green) wire from the sub-panel’s ground busbar. After these grounds are combined, connect them to the “AC GROUND” terminal. Tighten the “AC GROUND” terminal to 16 in lbf (1.8 N-m).
AC Wiring Inspection
- Verify all cable runs are secured.
- Verify strain reliefs or grommets are in place to prevent damage to the wiring or conduit where it passes through walls or other openings.
- After verifying all AC connections are correct and all inverter AC terminal screws are torqued to 16 in lbf (1.8 N-m), replace the AC wiring access cover and the covers on the main electrical/ distribution panel.
2.5.6 AC Wiring Confi guration
The following table provides the different wiring confi gurations for
installing and connecting the AC conductors into and out of the inverters (see
Figures 2-11 to 2-14 for installation diagrams showing these confi gurations).
Table 2-3, AC Input/Output Wiring Confi gurations
| SI/SO (30A) Single In/ Single Out
(30A)| SI/SO (60A) Single In/ Single Out 60A)| DI/SO Dual In/
Single Out| DI/DO Dual In/ Dual Out
---|---|---|---|---
AC Source’
Required| 120 VAC @ < 30 amps| 120 VAC @ > 30 amps (60 amps maximum).| 120/240
VAC (or 2 separate legs of 120 VAC) @ < 30 amps per leg| 120/240 VAC (or 2
separate legs of 120 VAC) @ < 30 amps per leg
Reason to
Use| Have an 120
VAC source that is < 30 amps.
Requires a separate inverter sub-panel.| Have an 120
VAC source that is > 30 amps. Requires a separate inverter sub-panel.| Want
dedicated charging and dedicated pass- thru while the
AC source is on.
Requires a separate inverter sub-panel.| May need to power 240 VAC loads when
AC source is on (requires 120/240 VAC
source).
Requires a separate inverter sub-panel.
Appropriate
Models| RD2212 RD1824 RD2824 RD3924| RD2212 RD1824 RD2824 RD3924| RD2212
RD1824 RD2824 RD3924| RD2212 RD1824 RD2824 RD3924
Maximum Input Breaker Required – Minimum Wire Size| 30A (single pole) – #10
AWG (In & Out)| 60A (single pole) #6 AWG (In & Out);
Can be split to two #10 AWG (for HOT 1 & HOT 2)| 30A (dual pole) – #10 AWG (In
& Out)| 30A (dual pole) #10 AWG (In & Out)
Maximum Inverter Pass-thru capacity| 3600W (30A @ 120 VAC)| 7200W (60A @ 120
VAC)| 3600W (30A @ 120 VAC)| 7200W (2 legs of 30A @ 120/240 VAC or
2 legs of 30A @ 120 VAC)’
Wiring
Diagram| Figure 2-11| Figure 2-12| Figure 2-13| Figure 2-14
Note 1 : AC Source is from either utility power or a generator.
Note 2: If two legs of 30A @ 120 VAC are used, they must be from the same
source.
2.6 Grounding Inverters
The inverter/charger should always be connected to a permanent, grounded
wiring system. An inverter system that is properly grounded will limit the
risk of electrical shock, reduce radio frequency noise from the inverter and
minimize excessive surge voltages induced by lightning. This is done by
ensuring there is a well-defi ned, very low-resistance path from the electrical
system to the grounding system. This low-resistance path helps stabilize the
electrical system voltage with respect to ground and carries fault currents
directly to ground if the electrical system malfunctions.
To understand how the conductors in the electrical circuit will be connected
to the system ground, the following terms should be understood:
- Grounded Conductor (GC): The wire/cable in the electrical system that normally carries current (usually the AC neutral and/or the DC negative); and is intentionally connected or “bonded” to the ground system. This wire or the ends of this wire should be colored white or gray.
- Equipment Grounding Conductor (EGC): A wire/cable that does not normally carry current and is used to connect the exposed metal parts of equipment that might be accidentally energized to the grounding electrode system or the grounded conductor. This wire or the ends of this wire should be green or green with a yellow stripe; or this wire can be bare copper.
- Grounding Electrode Conductor (GEC): The wire/cable that does not normally carry current and connects the grounded conductor and/or the equipment grounding conductor to the grounding electrode at the service equipment.
- Grounding Electrode (GE): A ground rod or conducting element that establishes an electrical connection to the earth.
- System bonding jumper (SBJ) The connection between the grounded circuit conductor in the electrical system and the equipment grounding conductor at a separately derived system.
The RD Series inverter/charger uses both AC and DC power; however, the AC
electrical system is isolated from the DC electrical system by an internal
transformer. Although this inverter/charger has two electrical systems, each
electrical system must be properly grounded and connected to a common “earth”
reference; refer to Figure 2-15.
For proper grounding, each electrical system must connect all exposed metal
parts of equipment (via Equipment Grounding Conductors – EGC) and one of the
current-carrying conductors (Grounded Conductor – GC) together at a common
point (Ground Busbar – GBB), usually by a System Bonding Jumper (SBJ) in an
electrical service disconnect panel. The common point of each electrical
system is then connected (via Grounding Electrode Conductor – GEC) to the
common ground reference, such as a ground rod (Grounding Electrode – GE). This
connection to earth should only be made at one point in each electrical
system; otherwise, parallel paths will exist for the currents to flow.
These parallel current paths would represent a safety hazard and are not
allowed in installations wired per the NEC/CEC. 2.6.1 Sizing the Grounding Electrode
Conductors
AC Side – The size of the AC Grounding Electrode Conductor (GEC –AC) depends
on the size of the largest ungrounded conductor feeding the AC load center.
One #8 AWG (8.4 mm 2 ) copper conductor will serve as an AC Grounding
Electrode Conductor (GEC AC) for AC power conductors smaller than and
including #2 AWG (33.6 mm2 ) copper. See Table 2-4 for additional values.
AC Side – The size of the AC Grounding Electrode Conductor (GEC –AC) depends
on the size of the largest ungrounded conductor feeding the AC load center.
One #8 AWG (8.4 mm 2 ) copper conductor will serve as an AC Grounding
Electrode Conductor (GEC –AC) for AC power conductors smaller than and
including #2 AWG (33.6 mm 2 ) copper. See Table 2-4 for additional values.
Table 2-4, AC Grounding Electrode Conductor Sizing
Size of Largest Ungrounded Conductor| Minimum Size of Grounding Electrode
Conductor
---|---
2 AWG or smaller| #8 AWG (8.4 mm 2)
1 to #1/0 AWG| #6 AWG (13.3 mm2 )
2/0 or #3/0 AWG| #4 AWG (21.1 mm2 )
Over #3/0 AWG through 350 kcmil| #2 AWG (33.6 mm2 )
DC Side – To size the DC grounding electrode conductor, you must fi rst
determine which one of the following three methods will be used to connect the
DC and AC grounding points in the inverter’s two electrical systems to the
common “earth” ground:
Method 1 (see Figure 2-16) : This method uses a separate grounding
electrode for the DC system and the AC system. In this method — since there
are multiple connections to the DC Grounding Electrode (GEC – DC) — the size
of the DC grounding electrode conductor cannot be smaller than the largest
conductor in the DC system (usually the battery-to-inverter cable).
The DC Grounding Electrode (GE – DC) must be bonded to the AC Grounding
Electrode (GE – AC) to make a grounding electrode system; this bonding
conductor (BC) cannot be smaller than the largest grounding electrode
conductor, either AC or DC.
Method 2 (see Figure 2-17): When the AC and DC service panels are near each other, then the AC Grounding Electrode Conductor (GEC – AC) and DC Grounding Electrode Conductor (GEC – DC) can be connected to a single grounding electrode. In this method — since there are multiple connections to the DC Grounding Electrode (GEC – DC) — the size of the DC grounding electrode conductor can not be smaller than the largest conductor in the DC system (usually the batteryto-inverter cable).
Method 3 (see Figure 2-18): The AC Grounding Electrode Conductor (GEC –
AC) is bonded to the DC ground point and the DC Grounding Electrode Conductor
(GEC – DC) is the only connection to the grounding electrode, which must be a
rod, pipe, or plate electrode.
In this method, since there is only one connection to the ground rod, the DC
grounding electrode conductor is not required to be larger than #6 AWG (13 mm2
) copper. The reasoning for allowing this smaller grounding electrode
conductor is that it is only required to stabilize the system voltage with
respect to earth and the other properly sized conductors in each electrical
system will safely carry any fault currents if they occur.
2.6.2 System Bonding Jumper
The RD Series inverter does not include an internal bond between the grounded
conductor (AC neutral/DC negative) and the equipment grounding terminals. This
bond [System Bonding Jumper (SBJ)] is usually done in the main distribution
panel for each electrical system.
CAUTION: There should be one and only one point in each electrical system
(both AC and DC) where the grounded conductor is attached to the grounding
electrode conductor.
AC Side – The size of the System Bonding Jumper (SBJ) in the AC
electrical system is based on the area of the largest AC ungrounded conductor.
In accordance with the NEC, use Table 2-4 to determine the system bonding
jumper size compared to the largest AC ungrounded conductor.
DC Side – The size of the System Bonding Jumper (SBJ) in the DC
electrical system must not be smaller than the DC Grounding Electrode
Conductor (GEC – DC) used, which is determined from the grounding method that
will be used (see Section 2.6.1).
2.6.3 Equipment Grounding Conductor
The inverter case and all other non-current carrying exposed metal surfaces in
the entire electrical system that may be accidentally energized must be
grounded. The equipment grounding conductor must be sized to safely carry the
maximum ground-fault current likely to be imposed on it from where a ground-
fault may occur. In accordance with the NEC, use Table 2-5 to size the
equipment grounding conductors. This table requires that the equipment
grounding conductor be sized according to the rating of the overcurrent device
protecting the circuit.
CAUTION: The connections and wiring for the equipment grounding conductor
must be continuous to allow fault currents to properly operate overcurrent
devices. Where equipment is removed and this disconnects the bonding
connection between the
grounding electrode conductor and exposed conducting surfaces, a bonding
jumper must be installed while the equipment is removed.
AC Side – Where the AC output from the inverter is connected to an AC
load center, there should be an equipment grounding conductor connected
between the inverter case and the grounding point in the AC load center. The
AC Equipment Grounding Conductor (EGC – AC) is sized per Table 2-5 and is
connected to the inverter’s AC equipment grounding terminal shown in Figure
2-10.
DC Side – Since the currents on the DC side are higher than the AC side
(10 times at 12 volts, 5 times at 24 volts), the equipment grounding needs are
different. The DC Equipment Grounding Conductor (EGC – DC) is sized per Table
2-5 and connected to the DC equipment grounding terminal on the inverter shown
in Figure 1-2 (Item 7).
Table 2-5, Equipment Grounding Conductor Sizing
Rating of Overcurrent Device | Minimum Size of Copper Ground Wire |
---|---|
15 amp | #14 AWG |
20 amp | #12 AWG |
30 – 60 amp | #10 AWG |
100 amp | #8 AWG |
200 amp | #6 AWG |
300 amp | #4 AWG |
400 amp | #3 AWG |
2.7 Inverter Notifi cation Requirements
A warning label as shown in Figure 2-19 is provided to inform all personnel
that an inverter is installed in your electrical system. Affi x this label in a
clearly visible location by the electrical panel that is being powered by the
inverter. This is because it might be falsely assumed that the panel is no
longer “hot” after the AC power has been shut off, when power may actually
still be available due to the inverter automatically powering the panel.
2.8 Final Inspection
- Verify all cables/conduit runs are secured with wire ties or other non-conductive fasteners to prevent chafi ng, or damage from movement and vibration.
- Verify strain reliefs or grommets are in place to prevent damage to the wiring or conduit where it passes through walls or other openings.
- Verify all AC connections are correct and torqued to a maximum of 16 in lbf (1.8 N-m).
- Replace the covers on the main electrical/distribution panel.
- Replace the chassis access cover.
- Verify the inverter’s front panel switch is in the OFF position.
Info: If required by code, have the installation inspected by an electrical inspector.
2.9 Functional Test
After all electrical connections to the inverter, batteries, AC source, and
sub-panel have been completed, follow these steps to test the installation and
the inverter operation.
CAUTION: Use a multimeter to verify the correct DC voltage for your
particular inverter model (i.e., 24-volt battery bank for a 24-volt inverter),
and to ensure the polarity of the battery voltage is correct (battery positive
connected to inverter positive, and battery negative connected to inverter
negative).
-
Apply battery power to the inverter by closing the DC circuit breaker or inserting a fuse. The inverter will remain OFF, but the green status indicator on the front of the inverter will quickly blink once to indicate that DC power has been connected and is ready to be turned on.
-
Prior to turning on the inverter, make sure all AC loads (e.g., appliances) are NOT connected to the inverter’s output or to any AC outlets powered by the inverter.
-
Lightly press and release the inverter’s ON/OFF switch to turn the inverter ON. Verify the inverter’s status indicator is blinking – indicating the inverter is ON.
-
Connect a small light bulb no larger than 75 watts to the inverter output and verify it comes on and shines normally. DO NOT connect anything but a light bulb until all wiring and voltages are confi rmed to be correct.
Info: The inverter’s AC output voltage will not be correct until a load greater than atts (5 watts is the default setting) is connected to the inverter; or, when the Search Mode is turned OFF with a remote display (ME- RC50). -
Check the AC output voltage of the inverter by connecting an AC voltmeter to the output terminals (see Figure 2-20) and verify the correct output voltages.
-
Press and release the inverter’s ON/OFF switch to turn the inverter off. The inverter’s status indicator and the connected load should go off.
-
Apply AC power to the inverter’s AC input. After the AC input power is qualifi ed (approximately 15 seconds), the incoming AC power will transfer through the inverter to the inverter’s AC output and power the light bulb. Verify the inverter’s status indicator and that the light bulb comes on.
-
Even though the light bulb is on, the inverter is currently disabled (off). Press and release the ON/OFF switch on the inverter to enable (turn-on) the inverter.
-
Disconnect the incoming AC power to the inverter. Verify the light bulb remains on and is now powered by the inverter.
If the inverter passes all the previous steps, the inverter is ready for use. If the inverter fails any of the steps, refer to the Troubleshooting section.
Operation
The RD Series inverter has two normal operating routines; Inverter Mode, which
powers your loads using the batteries, and Standby Mode, which transfers the
incoming AC power (e.g., utility power or a generator) to power your loads and
also uses this incoming power to recharge the batteries. This inverter also
includes an extensive protection circuitry to shut down the inverter under
certain fault conditions.
3.1 Inverter Mode
When the RD Series is fi rst powered up, it defaults to the OFF mode. The
momentary Power ON/OFF Switch (see Figure 1-1, Item 1) must be lightly pressed
to turn the inverter ON. Subsequently, pressing this switch alternately turns
the inverter OFF and ON.
Inverter OFF – When the inverter is OFF, no power is used from the
batteries to power the AC loads, and the status LED will be OFF. If AC power
from an external source (utility power or generator) is connected and qualifi
ed on the inverter’s AC input, this AC input power will pass through the
inverter to power the AC loads. However, if this AC power is lost, the AC
loads will no longer be powered because the inverter is OFF.
When the inverter is turned ON, it operates either by “searching” or
“inverting”, depending on the connected AC loads.
Searching – When the inverter is fi rst turned ON, the automatic Search feature
is enabled. This feature is provided to conserve battery power when AC power
is not required. In this mode, the inverter pulses the AC output looking for
an AC load (e.g., electrical appliance). Whenever an AC load (greater than 5
watts) is turned on, the inverter recognizes the need for power and
automatically starts inverting. When there is no load (or less than 5 watts)
detected, the inverter automatically goes back into Search Mode to minimize
energy consumption from the battery bank. When the inverter is “searching”,
the inverter’s green LED fl ashes (fast).
Info: The factory default value for the Search feature is 5 watts, it can
be turned off or adjusted from 5 to 50 watts using the ME-RC50 remote display.
Inverting – When a load greater than 5 watts is connected to the inverter
output, the RD Series “inverts” the DC power from the battery and supplies 120
VAC power to your sub-panel. The inverter’s green LED fl ashes once every 2
seconds (medium fl ash) to indicate it is inverting. The amount of time the
inverter can be inverting and providing power is directly related to the
amount of AC loads that are connected, and the capacity of the battery bank.
Refer to Figure 3-1 to see the fl ow of power from the DC input to the AC
output while in the Inverter Mode.
3.2 Standby Mode
The RD Series features an automatic transfer relay and an internal battery
charger when operating in Standby Mode. Standby Mode begins whenever AC power
(utility power or generator) is connected to the inverter’s AC input. Once the
AC voltage and frequency of the incoming AC power is within the AC input
limits, an automatic AC transfer relay is activated. This transfer relay
passes the incoming AC power through the inverter to power the AC loads on the
inverter’s output. This incoming power is also used to activate a powerful
internal battery charger to keep the battery bank charged in case of a power
failure. Refer to Figure 3-2 to see the fl ow of power from the AC input to the
DC and AC output while in Standby Mode.
3.3 Battery Charging
Magnum Energy’s RD Series is equipped with an active PFC (Power Factor
Corrected) and PI (Proportional-Integral) multi-stage battery charger. The PFC
feature is used to control the amount of power used to charge the batteries in
order to obtain a power factor as close as possible to 1 (or unity). This
causes the battery charger to look like a resistor to the line (forces the
charge current waveshape to mirror the voltage waveshape). The PI feature
allows the charger voltage and current to change independently. These two
features maximize the real power available from either utility power or
generator AC power sources, which translates into less power wasted and
greater charging capabilities than most chargers available today.
When an AC source is connected to the AC input, the inverter begins monitoring
for acceptable AC voltage. Once the inverter has accepted this AC voltage, the
AC transfer relay closes and the Charge Mode begins. After Charge Mode begins,
the DC voltage is monitored to determine the charging stage. If the DC voltage
is low (≤ 12.8 VDC/12 volt models or ≤ 25.6 VDC/24-volt models), the charger
begins Bulk Charging. If the DC voltage is high (> 12.8 VDC/12 volt models or
25.6 VDC/ 24-volt), the charger will skip the Bulk and Absorb Charging stages and go directly to Float Charging.
The multi-stage charger can use up to fi ve different charging stages to help monitor and keep the batteries properly maintained. The fi ve stages include an automatic 4-stage charging process: Bulk, Absorb, Float, and Full Charge; and a manual Equalization (EQ) Charge stage. The automatic 4-stage charge process provides complete recharging and monitoring of the batteries without damage due to overcharging. The EQ stage (requires the ME-RC50 remote to enable equalization charge) is used to stir up stratifi ed electrolyte and to try to reverse battery plate sulfation that may have occurred.
While charging, the unit may go into Charger Back-off protection, which automatically reduces the charge current to the batteries. This is caused by:
- the internal temperature is too hot – the charger automatically reduces the charge rate to maintain temperature; or, 2) the AC input voltage falls below 90 VAC – the charger will stop charging to help stabilize the incoming AC voltage.
The Charge Mode provides up to four separate charging stages: Bulk Charging, Absorb Charging, Float Charging, and Full Charge (see Figure 3-3).
Bulk Charging: This is the initial stage of charging. While bulk charging, the charger supplies the battery with constant current. The charger will remain in bulk charge until the absorption charge voltage (determined by the battery type selection) is achieved. The inverter’s green LED stays ON (solid) to indicate bulk charging.
Absorb Charging: This is the second charging stage and begins after the absorb voltage has been reached. Absorb charging provides the batteries with a constant voltage and reduces the DC charging current in order to maintain the absorb voltage setting. The inverter’s green LED fl ashes once every second (medium fl ash) to indicate absorption charging for 2 hours (determined by the Battery AmpHrs selection), then switches to fl oat charging.
Float Charging: The third charging stage occurs at the end of the absorb charging time. While fl oat charging, the charge voltage is reduced to the fl oat charge voltage (determined by the battery type selection*). In this stage, the batteries are kept fully charged and ready if needed by the inverter. The inverter’s green LED fl ashes once every 8 seconds (slow fl ash) to indicate fl oat charging. The Float Charging stage reduces battery gassing, minimizes watering requirements (for fl ooded batteries), and ensures the batteries are maintained at optimum capacity.
Full Charge (Battery Saver™ mode): The fourth stage occurs after four hours in the Float Charging stage. The Full Charge stage is designed to keep batteries fully charged over long periods and prevent excessive loss of water in fl ooded batteries, or drying out of GEL/AGM batteries. In this stage, the charger is turned off and begins monitoring the battery voltage; if the battery voltage drops low (12.7 VDC or less on 12-volt models or 25.4 VDC or less on 24-volt models), the charger automatically initiates another four hours in fl oat charge.
Info: If the battery voltage falls to the re-bulk voltage (12.1 VDC on 12-volt models or 24.2 VDC on 24-volt models) or lower, the unit will begin another bulk charge.
- These settings in the RD Series are changeable and leave the factory with default values (see Table 3-2, Inverter/Charger Default Values). These default values are adequate for most installations, however, if you determine that some of the values need to be changed for your particular system, the ME-RC50 remote control may be purchased to adjust these settings. 3.4 Transfer Time
While in Standby Mode, the AC input is continually monitored. Whenever AC power falls below the VAC dropout voltage (80 VAC, default setting), the inverter automatically transfers back to the Inverter Mode with minimum interruption to your appliances – as long as the inverter is turned on. The transfer from Standby Mode to Inverter Mode occurs in approximately 16 milliseconds.
While the RD Series is not designed as a computer UPS system, this transfer time is usually fast enough to hold them up. However, the VAC dropout setting has an effect on the ability of the loads to transfer without resetting. The lower this setting, the longer the effective transfer will be and therefore, the higher the probability for the output loads to reset. This occurs because the incoming AC voltage is allowed to fall to a level that is so low that when the transfer does occur, the voltage on the inverter’s output has already fallen to a level low enough to reset the loads.
The disadvantage of a higher VAC dropout setting is that smaller generators (or large generators with an unstable output) may nuisance transfer. This commonly happens when powering loads that are larger than the generator can handle – causing the enerator’s output voltage to constantly fall below the inverter’s input VAC dropout threshold.
Info: When switching from Inverter Mode to Standby Mode, the inverter waits approximately 15 seconds to ensure the AC source is stable before transferring.
3.5 Battery Temperature Sensor Operation
The plug-in Battery Temperature Sensor (BTS) is used to determine the battery
temperature around the batteries. This information allows the multi-stage
battery charger to automatically adjust the battery charge voltages for
optimum charging performance and longer battery life.
When the BTS is installed, if the temperature around the BTS is below 77°F
(25°C) the absorb and fl oat charge voltage increases, and if the temperature
around the BTS is higher than 77°F (25°C), the absorb and fl oat charge voltage
decreases. See Figure 3-4 to determine how much the charge voltage changes
(increases or decreases) depending on the temperature reading of the BTS. For
example, the nominal absorb charge voltage for a fl ooded battery at 77°F
(25°C) on a 24-volt model is 29.2 VDC. If the battery temperature is 95°F
(35°C), the absorb charge voltage would decrease to 28.6 VDC (29.2 VDC – 0.6
change).
If the temperature sensor is NOT installed, the charge voltages will not be
compensated and the battery will maintain the charge it had at a temperature
of 77°F (25°C). The life of the batteries may be reduced if they are subjected
to large temperature changes when the BTS is not installed.
Info: When the BTS is connected, the battery charger uses a value of
5mV/°C/Cell from 0-50°C to change the charge voltage based on
temperature.
3.6 Protection Circuitry Operation
The inverter is protected against fault conditions, and in normal usage it
will be rare to see any.
However, if a condition occurs that is outside the inverter’s normal operating
parameters, it will shut down and attempt to protect itself, the battery bank,
and your AC loads. If there is a condition that causes the inverter to shut
down, it may be one of the following conditions [also refer to the
Troubleshooting section (Section 4.2) to help diagnose and clear the fault
condition]:
-
Low Battery – The inverter will shut off whenever the battery voltage falls to the Low Battery Cut Out (LBCO) level to protect the batteries from being over-discharged. After the inverter has reached the LBCO level and turned off, the inverter will automatically restart after one of the following conditions:
AC Power is applied and the inverter begins operating as a battery charger, or battery voltage rises to the Low Battery Cut In (LBCI) level. The inverter’s status LED turns off when a low battery fault condition occurs. Refer to Table 3-1 to determine the LBCO and LBCI levels for your particular inverter model. -
High Battery – In the event the battery voltage approaches the High Battery Cut Out (HBCO) level, the inverter will automatically shut down to prevent the inverter from supplying unregulated AC output voltage. The inverter’s status LED turns off when a high battery fault condition occurs. The inverter will automatically restart when the battery falls to the High Battery Cut In (HBCI) level. Refer to Table 3-1 to determine the HBCO and HBCI levels for your inverter model.
Info: High battery voltage may be caused by excessive or unregulated voltage from solar panels or other external charging sources. -
Overload – During inverter and standby operation, the inverter monitors current levels. In the event of a short-circuit or an overload condition for more than a few seconds, the inverter will shut down. To start operating after this fault, the inverter would need to be restarted (turned back on) after the inverter’s AC loads are reduced/removed.
-
Over-temperature – If internal power components begin to exceed their safe operating temperature level, the inverter will shut down to protect itself from damage. The inverter’s status LED turns OFF to indicate the over-temperature fault condition. The inverter will automatically restart after the units cool down.
-
Internal Fault – The inverter continually monitors several internal components and the processor communications. If a condition occurs that does not allow proper internal operation, the inverter will shut down to protect itself and the connected loads. The inverter will need to be reset to start operating again (refer to Section 4.3 for information on resetting the inverter).
Table 3-1, Inverter Battery Turn On/Off Levels
Inverter battery turn ON/OFF Levels | Inverter Model |
---|---|
RD2212 | RD1824 |
HBCO | >15.8 VDC |
HBCI | 15.5 VDC |
LBCI | 12.5 VDC |
LBCO*
(1 minute delay)| 10.0 VDC
(9.0 – 12.2 VDC)| 20.0 VDC
(18.0 – 24.4 VDC)| 20.0 VDC
(18.0 – 24.4 VDC)| 20.0 VDC
(18.0 – 24.4 VDC)
LBCO (immediate)| 8.5 VDC| 17.0 VDC| 17.0 VDC| 17.0 VDC
*adjustable with remote control
3.7 Inverter Startup
ON/OFF Switch – The inverter can be turned on and off by lightly pressing and
releasing the Power ON/OFF switch on the front of the inverter (see Figure
3-5). When the inverter is fi rst connected to the batteries, or when its
automatic protection circuit has turned the inverter off, the ON/OFF switch
will need to be pressed to start the unit (or reset per Section 4.3). Once the
inverter has been turned on, pressing the Power ON/OFF switch alternately
turns the inverter on and off.
WARNING: The Power ON/OFF control switch does not turn on or off the
charger feature. If AC power (utility power or generator) is connected and
qualifi ed on the AC input, this AC power will also be available on the AC
output and is not controlled by the Power ON/OFF switch.
Status LED Indicator – The status indicator is a green LED (Light Emitting
Diode) that provides information on the operational mode of the inverter.
Watch this indicator (see Figure 3-5) for at least 10 seconds to determine the
inverter’s operational condition from the information below:
-
Off – Indicates the inverter is off; there is no AC power (inverter, utility power, or generator) at the inverter’s output terminals. If the LED stays off after pressing the ON/OFF switch, there is a “fault condition” such as low battery, high battery, overload, over-temperature, or an internal fault. Refer to the Troubleshooting section to help diagnose/clear the fault condition.
-
Slow fl ash (blinks on once every 8 seconds) – Indicates fl oat charging; the inverter is in Standby Mode (the external AC power that is connected to the inverter’s input is passing through the inverter and is powering the AC loads connected to the inverter’s output).
-
Medium fl ash (blinks on once every second):
When AC power is not connected to inverter input – Indicates the inverter is on and using energy from the battery. The inverter is either: 1) Inverting – providing full power to the loads connected to the inverter; or, 2) Searching – conserving power and waiting for a load to be turned on that meets or exceeds the search watts parameter (5 watts is the inverter default setting).
When AC power is connected to inverter input – Indicates absorb charging; the inverter is in Standby Mode (the external AC power that is connected to the inverter’s input is passing thru the inverter and is powering the AC loads connected to the inverter’s output). -
On (solid) – Indicates bulk charging; the inverter is in Standby Mode (the external AC power that is connected to the inverter’s input is passing thru the inverter and is powering the AC loads connected to the inverter’s output).
3.8 Factory Default Values
Your RD Series inverter/charger uses default values for the adjustable
settings (see Table 3-2) that are adequate for most installations. If some of
your operating parameters need to be changed from the default values, the
optional ME-RC50 remote control can be used to make those changes. To help you
determine if you need the ME-RC50 remote display, information on the
inverter/charger settings that can be changed is provided below. The settings,
once programmed, are saved in the remote’s non-volatile memory and are
preserved until changed – even if DC power to the inverter is lost (as long as
the ME-RC50 remote is connected). For information on the full range of
settingsfor each function, refer to the ME-RC50 Owner’s Manual at
www.magnumenergy.com.
- Shore: This setting ensures the inverter AC loads receive the maximum current available from the utility power or generator. When the total current used to power the AC loads and to charge the batteries begins to approach the “Shore” setting, the current that was used for charging the batteries will automatically be reduced.
- 01 Search Watts: This setting allows you to turn off the power-saving Search Mode circuitry or adjust the power level at which the inverter will “wake up” and start inverting.
- 02 LowBattCutOut: This setting determines when the inverter will turn off based on low battery voltage. The inverter turns off automatically after the battery voltage has been below this setting for more than one minute. This protects the batteries from overdischarge and the AC loads from unregulated power (brown-outs).
- 03 Batt AmpHrs: This setting allows the user to input the battery bank size in amp hours, which tells the charger how long to charge the batteries in the Absorb Charge stage.
- 04 Battery Type: Sets the type of batteries being used in the system; this information tells the charger what voltage level to use to charge the batteries.
- 05 Charge Rate: This setting can be used to turn off the charger, limit the amount of current that the charger can use (leaving more current available to power loads); or, to ensure small battery banks are not overheated because of a too high charge rate.
- 06 VAC Dropout: Sets the minimum AC voltage that must be present on the AC input before the unit transfers from Standby Mode to Inverter Mode. This protects the AC loads from utility power outages and brown-outs.
Using the ME-RC50 remote also provides the following features:
- allows you to enable an equalize charge for certain battery types
- displays inverter/charger’s operating status
- provides fault information for troubleshooting
Table 3-2, Inverter/Charger Default Values
Adjustable Settings | Default Values |
---|---|
Shore | 30 amps |
01 Search Watts | 5 watts |
02 LowBattCutOut | 10 VDC (12-volt models), 20 VDC (24-volt models) |
03 Batt AmpHrs | 600 Amp Hours (Absorb Time = 120 minutes) |
04 Battery Type | Flooded – Liquid Lead Acid |
05 Charge Rate | 100% |
06 VAC Dropout | 80 VAC |
Maintenance and Troubleshooting
The following information is provided to help you keep your RD Series
inverter/charger in optimum operational condition.
4.1 Recommended Inverter and Battery Care
The RD Series inverter/charger is designed to provide you with years of
trouble-free service.
Even though there are no user-serviceable parts, it is recommended that every
6 months you perform the following maintenance steps to ensure optimum
performance and extend the life of your batteries.
WARNING: Prior to performing the following checks, switch OFF both the AC
and DC circuits.
- Visually inspect the batteries for cracks, leaks, or swelling – replace if necessary.
- Use baking soda to clean and remove any electrolyte spills or buildups.
- Check and tighten all battery holddown clamps (if applicable).
- Clean and tighten all battery terminals and connecting cables [10 to 12 ft lbf (13.6 to 16.3 N-m)].
- Check and fi ll battery water levels (Liquid Lead Acid batteries only).
- Check individual battery voltages (load test those that have a voltage difference of more than 0.3 VDC from each other) – replace if necessary.
- Check all cable runs for signs of chafi ng – replace if necessary.
- Check the inverter’s cooling vents – clean as necessary.
- Check and tighten the inverter’s internal AC terminal block connections [16 in lbf (1.8 N-m)].
4.2 Troubleshooting
The RD Series inverter/charger is a fairly simple device to troubleshoot.
There are only two active circuits (AC and DC) as well as a charging circuit.
The following chart is designed to help youquickly pinpoint the most common
inverter failures.
Table 4-1, Bask Troubleshooting
Symptom| Possible Cause| Recommended Solution
No output power/ Inverter LED is OFF.| Inverter is switched OFF.| Switch the
inverter ON.
Battery voltage is too low. The battery voltage level has dropped below the
Low Battery Cut Out (LBCO) set-point for more than one minute.| Check
fuses/orcuit breakers and cable connections. Check battery voltage at the
inverter’s terminals. your batteries may need to be charged, and this fault
condition will automatically clear when the battery voltage exceeds the LECI
voltage.
The battery voltage is too high. The Inverter automatically resets and resumes
operation when the battery voltage drops to the NBC voltage or lower.| This
condition usually only occurs when an additional charging source (alternator,
solar panels, or other external charging sources) is used to charge the
battery bank. Reduce or turn off any other charger to the inverter batteries
to allow the voltage level to drop.
Over-temperature condition: The internal temperature of the inverter has risen
above acceptable limits; caused by loads too great for the Inverter to operate
continuously, or by lack of ventilation to the inverter. When the unit RS
cooled, it will automatically reset and resume operation.| Reduce the number
of electrical loads that you are operating. This will avoid a repeat over-temp
shutdown if the cause was too many loads for the ambient conditions.
Check ventilation around the inverter, ensure cool air is available to pass
through the inverter (refer to the ventilation requirements in Section 2.1.3).
AC overload condition: The Inverter has turned off because the connected loads
are larger than the inverter’s output capacity, or the output wires are
shorted.| Reducethe AC loads connected to the inverter, or remove all AC
output wiring and restart the inverter.
Internal fault: This fault occurs when an internal fault is detected.| To
clear this fault, an inverter reset is required. Remove DC power to the
inverter, or press and hold down the power switch on the inverter for 15
seconds (until the green status LED comes on). If this fault does not clear,
the unit will need to be serviced.
No output power/ Green LED Is flashing.| Unit is in Search Mode, which means
the load is too small for Search Mode Grant detection.| Turn on a load greater
than 5 watts to bring the inverter to full output power, or turn off Search
with remote.
Low output or surge power/Green LED 15 flashing.| Loose or corroded battery
cables.| Clean and tighten all cables.
Low batteries.| Recharge or replace batteries.
Loose AC output connections.| lighten AC output connections.
Battery cables are the wrong length or gauge.| Verify recommended cede lengths
and gauges from the manual. Replace cables as necessary.
Low charging rate when connected to AC power.| Charge rate set too low.|
Adjust charge rate or SHORE settings on remote.
Low AC voltage (< 90 VAC).| Check AC input wiring.
LowchargIng ratewhen using a generator.| Generator output is too low to power
both the load and the charger.| Reduce the load, Increase the generator’s
RPM5.
Check the SNORE settings (if remote connected).
Charger doesn’t
charge.| Loose or corroded battery cables.| Clean and tighten battery cables.
Defective batteries.| Replace batteries.
Wrong charger settings.| Adjust the charger settings, ensure the unit is not
In Charger Standby.
Wrong AC input voltage.| Verify proper AC input voltage and frequency.
While charging, the DC charge voltage is higher or lower than expected.| If
the Battery Temperature Sensor (BTS) is Installed, the DC voltage will
increase or decrease depending on the temperature around the BTS.| This is
normal; see Section 3.5 (Battery Temperature Sensor Operation) for more
information.
4.3 Resetting the Inverter
Under some fault conditions (e.g., an internal fault), the inverter will need
to be reset.
To reset the inverter:
Press and hold the Power ON/OFF pushbutton (see Figure 4-1) for approximately
fi fteen (15) seconds until the Charging/Inverting Status LED comes on and fl
ashes rapidly; once the rapid fl ashing has begun, release the Power ON/OFF
pushbutton. The Status LED will go off after the pushbutton is released.
After the inverter reset is completed, press the ON/OFF pushbutton to turn the
inverter ON.
Info: The Power ON/OFF pushbutton is a small momentary type switch which
operatesby lightly pressing and releasing.
Appendix A – Specifi cations and Optional Equipment
A-1 Inverter/Charger Specifi cations
| RD2212| RD1824| RD2824| RD3924
---|---|---|---|---
Inverter Specifications
Input Battery Voltage Range| 9 to 16 VDC| 18 to 32 VDC| 18 to 32 VDC| 18 to 32
VDC
Absolute Maximum DC Input| 25 VDC| 35 VDC| 35 VDC| 35 VDC
AC Output Voltage Accuracy| 120 VAC ±5% (≤ continuous power)
Output Frequency and Accuracy| 60 Hz ± 0.1 Hz
Continuous Power Output (at 25° C)| 2200 VA| 1800 VA| 2800 VA| 3900 VA
1 msec Surge Current (amps AC)| 60| 70| 100| 150
100 msec Surge Current (amps AC)| 37| 40| 60| 90
5 sec Surge Power (real watts)| 3700| 4000| 6000| 9000
30 sec Surge Power (real watts)| 3450| 3300| 4800| 6400
5 min Surge Power (real watts)| 3100| 2850| 3950| 5800
30 min Surge Power (real watts)| 2400| 2400| 3500| 4750
Maximum Continuous Input Current| 293 ADC| 120 ADC| 186 ADC| 260 ADC
Inverter Efficiency (peak)| 95%| 94%| 93%| 93%
HBCO/HBCI (High Battery Cut Out/In)| ≥15.8 VDC| ≥31.6 VDC| ≥31.6 VDC| ≥31.6
VDC
LBCO/LBCI (Low Battery Cut Out/In)| 9 VDC (adj)/12.5 VDC| 18 VDC (adj)/25 VDC|
18 VDC (adj)/25 VDC| 18 VDC(adj)/25 VDC
Series Stacking 120/240 VAC| No
Transfer Time| 16 msecs
Search Mode (typical)| 5 watts
No Load (120 VAC output, typical)| 20 watts| 12 watts| 19 watts| 25 watts
Waveform| Modified Sine Wave
Charger Specifications
Continuous Output at 25°C| 110 ADC| 50 ADC| 80 ADC| 105 ADC
Input Current – Rated Output (AC amps)| 15| 15| 21| 29
Charger Efficiency| 85%| 85%| 85%| 92%
AC Input Frequency Range| 50 to 70 Hz
AC Input Voltage Range| 60 to 140 VAC (120 VAC nominal)
Power Factor| > 0.95
General Features and Capabilities
Transfer Relay Capability| Two input legs at 30A each, or combine for 60A
Five-stage Charging Capability| Bulk, Absorb, Float, Equalize (requires
remote), and Battery Saver™
Battery Temperature Compensation| Yes, 15 ft Battery Temp Sensor standard
Internal Cooling| 0 to 120 cfm variable speed drive using dual 92 mm brushless
DC fan
Overcurrent Protection| Yes, with two overlapping circuits
Over-temperature Protection| Yes, on transformer, MOSFETS, and battery
Corrosion Protection| PCB’s conformal coated, powder coated chassis/top, and
stainless steel fasteners
Safety Listings| ETL listed to UL1741
Warranty| 2 years parts and labor
Dual Branch-Rated Output Breakers| No
Environmental Specifications
Operating Temperature| -20°C to +60°C (-4°F to 140°F)
Non-operating Temperature| -40°C to +70°C (-40°F to 158°F)
Operating Humidity| 0 to 95% RH non-condensing
Physical Specifications
Unit Dimensions (h x w x d)| 13.75” x 12.65” x 8.0” (34.9 cm x 32.1 cm x 20.3
cm)
Shipping Dimensions (h x w x d)| 18.5” x 17.5” x 12.5” (47 cm x 44.5 cm x 31.8
cm)
Mounting| Shelf (top or bottom up) or wall (no uncovered vents on top or
bottom)
Unit Weight| 37 lb (16.8 kg)| 35 lb (15.9 kg)| 42 lb (19.1 kg)| 53 lb (24 kg)
Shipping Weight| 42 lb (19.1 kg)| 40 lb (18.1 kg)| 47 lb (21.3 kg)| 58 lb
(26.3 kg)
Max operating altitude| 15,000’ (4570 m)
Specifications @ 25°C – Subject to change without notice.
Appendix A – Specifi cations
A-2 Optional Equipment and Accessories
The following Magnum Energy components are available for use with the RD
Series inverter/charger.
Some of these items are required depending upon the intended use of the
inverter.
MMP Series Enclosures
The MMP175-30D, MMP175-60S, MMP250-30D, and MMP250-60S enclosures are for
single inverter applications. The MMP Series enclosures have been specifically
designed to combine all of the major components required for a renewable
energy system —
inverter/battery disconnect, AC overcurrent protection, grounding connections,
and a full system inverter bypass switch as a convenient way to isolate the
inverter for battery maintenance — into a single, easy to install pre-wired
enclosure.
Smart Battery Combiner
The Smart Battery Combiner (ME-SBCTM ) is designed to monitor and charge a
second battery us- ing a portion of the current that is charging the main
battery. The ME-SBC eliminates a signifi cant voltage drop, and provides
automatic turn-on and turn-off based on adjustable voltage set-points.
This allows different batteries to be charged from a single charging source,
and prevents overcharging/undercharging.
Remote Switch Adapters
The ME-RSA TM and ME-RSA-M TM pigtail adapters allow the inverter to be
remotely switched on and off – with or without the ME-RC50 remote display.
Basic Remote Control
The ME-RC50 Remote Control Panel is simple to use; an LCD screen and “at a
glance” LEDs display complete inverter/charger status. Soft keys provide
simple access to menus and a rotary encoder knob allows you to scroll through
and select a wide range of settings such as Inverter ON/OFF, Charger ON/OFF,
Utility Power Breaker Setting, AGS Control, Meter Button, Setup and Tech
menus.
Advanced Remote Control
The ME-ARC50 Remote Control Panel uses an LCD screen and “at a glance” LEDs to
provide operating information and allow advanced features to be confi gured
(requires Magnum inverters with advanced confi gurable features). This LCD
remote control also provides advanced monitoring/ troubleshooting and includes
a FAVS button to access your favorite features quickly.
Auto Generator Start Controller
The ME-AGS-N Automatic Generator Start controller (Network version) is
designed to automatically
start your generator based on low battery condition or high temperature. The
AGS controller includes an input voltage jumper (for 12, 24, and 48 volt
battery banks) and a 4-position DIP (Dual In-line Package) switch which
provides the ability to change the relay timing confi gurations to allow
compatibility with a wider range of generators. Adjustable settings when using
the MEARC50 include starting the generator based on: Battery
Voltage, Time Of Day, Battery ‘State of Charge’ or High Temperature.
Battery Monitor Kit
The ME-BMK Battery Monitor Kit is a single battery bank amp-hour meter that
monitors the condition of the battery and provides information to let you know
how much energy you have available and let you plan your electrical usage to
ensure the battery is not being over-discharged. The ME-BMKNS version does not
include a DC shunt – order the ME-BMK to receive a 500A/50mv DC shunt.
Fuse Block/Fuses
The Magnum Fuse/Fuse-blocks are used to protect the battery bank, inverter,
and cables from damage caused by DC short circuits and overloads. They
include aslow-blow fuse with mounting block and protective cover. The 125 and
200 amp models use an ANL type fuse and the 300 and 400 amp models use a
Class-T fuse.
Appendix B – Battery Information
B-1 Battery Location
Periodic maintenance (e.g., checking connections, cleaning, watering) on
batteries is required.
Locate the batteries in an accessible location to perform this maintenance.
Batteries must be mounted in a clean, dry, ventilated environment where they
are protected from high and low temperatures. The battery bank should be
located as close to the inverter as possible without limiting access to the
inverter’s disconnects. Longer battery cable runs tend to lose effi ciency and
reduce the overall performance of an inverter.
To ensure optimum performance, a ventilated battery enclosure is recommended.
Two feet (61 cm) of clearance above the batteries is recommended for access to
the battery terminals and removable caps (lead acid battery types).
WARNING: Be very careful when working around batteries, they can produce
extremely high currents if they are short-circuited. Read the important safety
instructions at the beginning of this manual and the precautions from the
battery supplier before
installing the inverter and batteries.
CAUTION: Do not mount the batteries beneath the inverter (or in the same
compartment). Batteries emit corrosive fumes which could damage the inverter’s
electronics. Never locate dedicated batteries near a home fuel tank containing
propane.
B-2 Battery Types
Batteries are available in different sizes, amp-hour ratings, voltage, and
chemistries. They are also available for starting applications (such as an
automobile starting battery) and deep discharge applications. Only the deep
cycle types are recommended for inverter applications; using a starting
battery in an inverter (deep cycle) application will greatly shorten their
useful life. Choose the batteries best suited for the inverter installation
and cost. Use only the same battery type for all batteries in the bank. For
best performance, all batteries should be from the same lot and date. This
information is usually printed on a label located on the battery.
B-3 Battery Temperature
Battery performance of lead-acid type batteries is greatly affected by extreme
temperatures. When a lead-acid type battery is cold, its effective amp-hour
capacity is reduced. When determining the battery requirements needed for the
inverter system, realize that the battery capacity will be reduced if they
will be installed in a climate where extremely cold temperatures are expected.
In this type of environment, the batteries should be located in a heated area.
At the minimum, the batteries should be installed in an insulated enclosure;
which will keep the batteries warmer as they are being charged.
The battery bank should also be protected from high temperatures, which will
shorten battery life. In high heat situations the battery room/enclosure
should be ventilated to bring in cooler air and exhaust the hotter air. The
performance of the battery bank/inverter system will substantially increase by
monitoring and preventing extreme temperatures around the batteries.
B-4 Battery Bank Sizing
The size of the battery bank determines how long the inverter will power the
AC loads without recharging. The larger the battery bank, the longer the run
time. Size your battery bank to the systems AC load requirements and length of
time required to run from the batteries. In general, the battery bank should
not be discharged more than 50%. Additional DC charging devices such as solar,
wind, hydro, etc., can provide longer run times by recharging the batteries in
the absence of AC utility power or generator power.
Info: For the RD Series inverter/charger to perform optimally, a minimum
battery bank of 200 AH is recommended for moderate loads (<1000W) and greater
than 400 AH for heavy loads (≥1000W).
B-5 Battery Bank Sizing Worksheet
Complete the steps below to determine the battery bank size required to power
your AC loads:
-
Determine the daily power needed for each load
a) List all AC loads required to run; and
b) List the Watt-Hours for each load (see Table B-1 for common loads/wattage); and
c) multiply by how many hours per day (or a fraction of an hour) each load will be used; and
d) multiply by how many days per week you will use the listed loads; and
e) divide by seven = Average Daily Watt-Hours Per Load. Average Daily Watt- Hours Per LoadAC load| Watt-Hours| (x) hours per day| (x) days per week| (47) = total power
| | | |
| | | |
| | | |
| | | |
| | | |
| | | |
| | | | -
Determine the total power needed each day for all the loads.
• Add the Average Daily Watt-Hours Per Load together = Total Daily Watt-Hours. -
Determine the battery Amp-Hour capacity needed to run all the loads before recharging.
• Divide the Total Daily Watt-Hours by the nominal battery voltage of the inverter (i.e., 12, 24 volts); and • Multiply this by how many days the loads will need to run without having power to recharge the batteries (typically 3 to 5 days of storage) = Storage Amp-Hours. -
Determine how deeply you want to discharge your batteries.
• Divide the Storage Amp-Hours by 0.2 or 0.5 to get the Total Amp-Hours:
a) 0.2 = Discharges the batteries by 20% (80% remaining), this is considered the optimal level for long battery life; or
b) 0.5 = Discharges the batteries by 50% (50% remaining), this is considered a realistic trade-off between battery cost and battery life.
Additional compensation:
Low battery temperature: If the batteries are installed in a location that
will be exposed to low temperatures, the available output will be less. In
these instances, you will need to determine the lowest temperature the battery
bank will experience and multiply the Total Amp-Hours by the Multiplier below.
Temperature | 80F/27C | 70F/21C | 60F/15C | 50F/10C | 40F/4C | 30F/-1C | 20F/-7C |
---|---|---|---|---|---|---|---|
Multiplier | 1 | 1.04 | 1.11 | 1.19 | 1.3 | 1.4 | 1.59 |
Inverter effi ciency: When the inverter is used in a back-up power application
the inverter effi ciency will not be a large concern; however if the inverter
is the primary AC source for the calculated load, the Total AmpHours should be
multiplied by 1.2 to factor in an average 80% inverter efficiency.
B-6 Battery Wiring Confi gurations
The battery bank must be wired to match the inverter’s DC input voltage. In
addition, the batteries can be wired to provide additional run time. The
various wiring confi gurations include:
B-6.1 Series Wiring
Wiring batteries in series increases the battery bank’s output voltage. A
series connection combines each battery in a string until the total voltage
matches the inverter’s DC requirement. Even though there are multiple
batteries, the capacity remains the same. In Figure B-1 below, two 6 VDC/200
AH batteries are combined into a single string resulting in a 12 VDC, 200 AHr
bank.
B-6.2 Parallel Wiring
Wiring batteries in parallel increases the battery bank’s amp-hour capacity,
which allows the AC loads to operate for a longer time. A parallel connection
combines the number of batteries in the string to increase overall battery
capacity; however, the voltage remains the same. In Figure B-2 below, two 12
VDC/100 AH batteries are combined into a single 12 VDC, 200 AH battery
bank. B-6.3
Series-Parallel Wiring
A series/parallel confi guration increases both voltage (to match the
inverter’s DC requirements) and Amp-Hour capacity (to increase run-time for
operating the loads) using smaller, lower-voltage batteries. In Figure B-3
below, four 6 VDC/200 AH batteries are combined into two strings resulting in
a 12 VDC, 400 AH battery bank.
Limited Warranty
Magnum Energy, Inc., warrants the RD Series inverter/charger to be free from defects in material and workmanship that result in product failure during normal usage, according to the following terms and conditions:
-
The limited warranty for the product extends for 24 months beginning from the product’s original date of purchase.
-
The limited warranty extends to the original purchaser of the product and is not assignable or transferable to any subsequent purchaser.
-
During the limited warranty period, Magnum Energy will repair, or replace at Magnum Energy’s option, any defective parts, or any parts that will not properly operate for their intended use with factory new or remanufactured replacement items if such repair or replacement is needed because of product malfunction or failure during normal usage. The limited warranty does not cover defects in appearance, cosmetic, decorative or structural parts or any non-operative parts. Magnum Energy’s limit of liability under the limited warranty shall be the actual cash value of the product at the time the original purchaser returns the product for repair, determined by the price paid by the original purchaser. Magnum Energy shall not be liable for any other losses
or damages. -
Upon request from Magnum Energy, the original purchaser must prove the product’s original date of purchase by a dated bill of sale, itemized receipt.
-
The original purchaser shall return the product prepaid to Magnum Energy in Everett, WA. After the completion of service under this limited warranty, Magnum Energy will return the product prepaid to the original purchaser via a Magnum-selected non-expedited surface freight within the contiguous United States and Canada; this excludes Alaska and Hawaii.
-
This limited warranty is voided if:
• the product has been modifi ed without authorization
• the serial number has been altered or removed
• the product has been damaged from abuse, neglect, accident, high voltage or corrosion
• the product was not installed and operated according to the owner’s manual
How to Receive Repair Service
If your product requires warranty service or repair, contact either:
- An Authorized Service Center, which are listed on the Magnum Energy website at www.magnumenergy.com/servicecenters.htm; or
- Magnum Energy, Inc. at: Telephone: 425-353-8833
Fax: 425-353-8390
Email: warranty@magnumenergy.com
If returning the product directly to Magnum Energy for repair, you must:
return the unit in the original, or equivalent, shipping container
receive a Return Materials Authorization (RMA) number from the factory prior to the return of the product to Magnum Energy for repair place RMA numbers clearly on the shipping container or on the packing slip
BEFORE RETURNING ANY UNIT TO MAGNUM ENERGY INC.,
A RETURN MATERIAL AUTHORIZATION (RMA) NUMBER IS REQUIRED.
RD Series Owner’s Manual (PN: 64-0006 Rev A)
Documents / Resources
|
MAGNUM ENERGY RD2212 RD Series Modified Sine Wave Inverter
Chargers
[pdf] Owner's Manual
RD2212 RD Series Modified Sine Wave Inverter Chargers, RD2212 RD Series,
Modified Sine Wave Inverter Chargers, Sine Wave Inverter Chargers, Inverter
Chargers, Chargers
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>