Hipac Door Top Alarm User Manual
- June 12, 2024
- Hipac
Table of Contents
- Introduction
- Components
- Pre-Manufacturing Form
- Door and Frame Preparation
- Door Alarm Fitment
- Wiring
- Testing
- Normal Operation
- Failsafe
- Alarm Delay Settings
- Control Box Version
- Troubleshooting
- Contact Information
- Disclaimer
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Door Top Alarm Manual
Introduction
Intastop Door Alarms are available to suit 44mm and 54mm door widths and are made to the specified length to suit the application.
An additional 12mm is to be taken off the overall height of the door to
accommodate each alarm.
All components are quality checked, tested and signed off before dispatch. The
sign off includes a unique serial number which is engraved onto the bottom of
the alarm, which is recorded on our records and certificates for quality
assurance. The components that make up the Door Alarm system need to be
handled with care and must be installed with care.
Notes:
The electrical transfer hinge above is only for illustration, see datasheets
for specific transfer hinge detailing.
Door alarms pre-July 2018 have orange and white plugs, not black plugs.
Further information on these can be provided if required.
Components
Door Top Alarm Order Form| Project ——————————-Date:———————————-
Company: —————————-Duress System:———————-
Checked by:————————– Signed:——————————–
---|---
Door Reference No.| | | | | | | | | |
Door Width (mm)| | | | | | | | | |
Door Thickness (mm)| | | | | | | | | |
| Door
Handing| Fig 1 or 3| | | | | | | | | |
Fig 2 or -:| | | | | | | | | |
| Hinge
Type| Single Swing| | | | | | | | | |
| Double Swing| | | | | | | | | |
| Shrouded Double
Swing| | | | | | | | | |
Pre-Manufacturing Form
Door and Frame Preparation
Hipac can take no responsibility for incorrect operation for Door Alarms that
are not fitted as per these instructions.
4.1 Door Preparation
The joining 6mm x 6mm channel (highlighted in yellow below) is only required
if the Door Top Alarm is being used with a Door Bottom
This is accurate for the Securahinge application. If using a double swing
hinge, the 19mm dimension needs altering to the centre point of the hinge
position.
Alarm and connects the 50mm x 20mm x 40mm pockets.
4.2 Frame Preparation
Door Alarm Fitment
When installing the Door Alarm systems, the electrically modified section
positioning is very important. Install the alarm in the door then position the
200mm section as shown in the below diagrams. Once this section is fixed,
install the full-length hinge butted up tight to the 200mm electronically
modified section.
The hinge is supplied in 2 pieces, the main section of the hinge which takes
most of the door’s weight and the electrically modified section, at the top,
which has the cables running through it. The reason for this is for ease of
service, if at any time there is a problem, the electrically modified piece
can simply be taken out without having to take the door off. The door top
alarm should be supplied with a test kit (as per image) this should be used to
test the operation of the sensor and electrically modified hinge section.
These components should be tested after installing on the door and prior to
connection to the control box. Testing is completed by connecting the test box
to the sensor directly and then via the electrically modified hinge and
following the test sequence in section 7. This is to ascertain that the sensor
and hinge are functioning correctly and have not been damaged during install.
If there is a fault Hipac should be contacted to assist in resolving.
5.1 44mm Securahinge and Domed Cap
5.2 54mm Securahinge and Domed Cap
5.3 Double Swing Hinge/Shrouded Double Swing Hinge
Wiring
Order of installation:
- Door Alarm(s)
- Electrically modified hinge then full-length hinge
- Cabling to the control box
- Control box
- 12V transformer for control box
- Wire into staff attack system
6.1 Door Top Alarm
The Door Top Alarm plugs directly into the door side of the electronically
modified hinge.
6.1.1 Other Door Alarms (If applicable)
Other Door Alarms will use an adapter wiring loom to join to the Door Top
Alarm. This will plug in between the door side of the hinge and the Door Top
Alarm if the additional alarm is attached to the door. If the alarm is located
elsewhere the loom will plug in between the frame side of the hinge and the
control cable. Where possible the standard black plugs are used. Where the
cable needs trimming to length to suit the application a Wagon connector is
used. Simply lift the orange lever on the terminal, insert the cable and close
the lever. This will connect the 2 cables in a secure way with no need for any
special tools.
6.2 Electronically modified hinge
All electrically modified hinges use
Note: Control boxes manufactured before 2019 will have a black cable
instead of the yellow cable.
the standard black plugs (2019 onwards). One connects with the Door Alarm(s),
the other connects to the control box via the control cable.
6.3 Control Box
6.3.1 Control Cable
The control cable needs to connect the electronically modified hinge to the
control box. This cable must be fitted inside cable conduit with a minimum
internal diameter of 12mm to allow future servicing.
IF THIS CONDUIT IS NOT USED, SERVICING MAY BE IMPOSSIBLE WITHOUT DAMAGE TO THE
FRAMEWORK AND/OR WALLS.
Cable Colour | Function | Board Reference |
---|---|---|
Green | Green LED | LDG |
Red | Red LED | LDR |
Blue | Switch circuit | SW |
Yellow | Common | COM |
The green, red, blue and yellow wires in the control cable for the Door
Alarm(s) needs wiring into the top left set of terminals as shown in the
wiring diagram.
6.3.2 Power Cable
The power supply for the control box must be 12V DC rated to at least 1A. This
needs wiring into the ‘GND’ and ‘+12V’ terminals on the on the right side of
the box as shown on the diagram. We recommend that a maximum of 3 control
boxes are wired into one 3A fused spur and the one spur does not power more
than one room.
Once the control box has 12V DC, the red power LED will illuminate on the
outside of the box.
At this stage, the Door Alarm(s) should function as intended however when
triggered the control box will beep, the staff attack system will not alarm.
This should be tested at this stage and the staff attack should only be wired
in if the alarms pass the testing.
6.3.3 Staff Attack Cable
This cable needs to be installed by the staff attack company. This has the
option of either being irked into the normally closed or normally open
contacts. We recommend wiring into the Normally Closed (N/C) contacts as in
the event of a break in the cable between the control box and the staff
attack system, the alarm will be triggered. If wired to the Normally Open
(N/O) contacts, the alarm will not be triggered in the event of a cable break.
The staff attack should not be connected until the Door Alarm(s) and control
box are powered and working correctly.
Testing
The Door Alarm systems should be tested on a regular basis. The frequency of
the testing should be decided though your risk assessment policy.
Once the system is powered up, the red power LED should always be visible on
the outside of the control box, showing the system has power. The status LED
next to the power LED indicates what state the system is in. The status LED is
duplicated on the leading edge of the Door Top Alarm, which is only activated
when a magnet is held below or to the side of the LED.
- When the alarm is powered up and has cycled through the initial 3 status colours (red, amber then green), which is roughly 3 seconds, it is ready to test.
- Whilst looking at the LED on the Door Top Alarm, press the alarm bar down once and release. The LED should display green, this shows it is powered up. Remember a magnet is required if the LED on the Door Top Alarm is being used.
- Whilst the LED is still green, press and release again, this should temporarily change the LED from green to orange then back to green when released. This shows the system is registering the presses. This should be done at each end and along the centre of each alarm on the doorstep to ensure the presses are being registered throughout the system.
- If a full test is being carried out, a long press should be carried out to test the entire system. After the pre-set time delay the LED should go red and the staff attack system should be activated.
- After approximately 20 seconds for the Mk1 box or 5 seconds for the Mk2 box, the unit will reset
Green LED
Door Alarm has been pressed once and it has power.
Amber LED
Door Alarm has been pressed whilst in green light mode. This indicated the
presses are being registered.
Red LED
Door Alarm is sending out alarm signal and has either been held down for the
set duration, has repeatedly been pressed or has a fault if continuous. itself
and the red LED will disappear. See control box version section (Section 13)
to identify if your box is Mk1 or Mk2. The control box resets but the staff
attack system still needs resetting as per Staff Attack Instructions.
Normal Operation
In normal operation, the Door Alarms are passive and should not do anything until a ligature attempt occurs. Once the alarm senses a ligature attempt or that the system is being tampered with, the control box will send out an alarm signal until the problems is resolved. Once the issue is resolved, the staff attack system can be reset and the system will return to monitoring. After every alarm, a test should be carried out to check the system functionality.
Failsafe
The Door Alarm system has a built-in failsafe function. If any functional part of the system experiences a fault, the alarm will be triggered. On the Mk2 boxes this will send out the alarm signal until the problem is resolved. If there is no capability to isolate the Door Alarms from the staff attack system, the 12V power supply for the control box can be switched off to stop the alarm signal. If the alarm goes into this state of constant alarm, contact Hipac.
Alarm Delay Settings
As standard, the system will be set with a 10 second delay.
Mk1 control boxes have delay settings of: 5, 10, 20 or 30 seconds.
Mk2 control boxes have delay settings of: 5, 10, 15 or 20 seconds.
See control box version section (Section 13) to identify if your box is Mk1 or
Mk2.The timing
settings are printed on the circuit board next to the switch on the Mk2 box.
Inside the control box, as highlighted on the below image with the large white
arrow, is the timing switch with 2 toggles.
By altering these switches, the delay can be adjusted. The options are as
follows:
*The timing for 2020 control box onwards / timing for pre-2020 control boxes. The specific timings are printed on the circuit board near the switch on the new revision boxes. If they are not printed on the board it will be 5, 10, 20, 30.
Control Box Version
11.1 Identification
There was a new version of the control box referred to as the Mk2 released at
the start of 2020. The previous revision box is referred to as the Mk1.
Externally you can identify the model variant. Firstly, the power needs to be
disconnected from the box.
The MK1 has a red and a clear LED when there is no power to the box however
the Mk2 has 2 clear LEDs.
To identify the box internally, the Mk1 has 1 set of blue switches, where the
Mk2 has 2 sets.
11.2 Mk2 New Features
- It will alarm until the cause for the alarm has been dealt with.
- The latching feature has been added.
- The timing options have changed and are now printed on the circuit board.
12. Latching Function
There is an optional latching function on all Door Alarm control boxes from
2020 onwards. This function ensures that the Door Alarm which triggered the
alarm is physically checked every time it is triggered as some alarms can be
reset remotely.
Once the latching function is activated, and the alarm is triggered, the
control box will alarm (with the red LED displayed). To reset the alarm, the
Door Alarm trigger needs to be pressed down 3 times once the initial cause for
the alarm has been dealt with then the alarm system can be reset as usual.
The red LED will remain on for an additional 5 second once the reset presses
have been carried out, but the box is no longer sending out a trigger signal.
As standard, the latching function is deactivated. This feature is controlled
by toggle 2 on the ‘latching
Latching deactivated (as standard from Hipac) | Latching activated |
---|---|
Note: Toggle 1 is for manufacturer use and has no effect on the operation of the box switch’ in the control box, which is highlighted on
Please Note: Once the alarm has been activated it can take up to 30
seconds to reset dependent on control box model. If you hold the magnet to the
LED, whilst it is still in alarm it will display red. Once the LED has turned
off, the door alarm system has reset.
If the door is not fitted with the required perimeter gap, the door frame or
seals can trigger the alarm when the door is closed. This could be the problem
if the alarm triggers when the door is closed for the set delay time, which is
10 seconds as standard. If this is the case, the door has not been fitted
correctly and needs to be adjusted.
the wiring diagram, near the normally open contacts. When this feature is
activated or deactivated, the control box must be disconnected from 12V then
reconnected for any changes to take effect.
Troubleshooting
Contact Information
Address
Hipac Healthcare Pty Ltd
Unit 15, 16 Berners Road
Preston’s, NSW 2170
Phone
1800 75 93 93
hipac.com.au
Disclaimer
Please note that Intastop offers a range of measures designed to reduce the
risk of self-harm or suicide and does not offer any guarantee that it will not
take place. The solutions have been designed as a deterrent only. To be fitted
as per the global assessment.
All products must be installed and maintained as per Hipac’s fitting
instructions and/or the operation and
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>