Literature FSH1BG Heat Pump Split Instruction Manual
- June 12, 2024
- Literature
Table of Contents
iQ Drive Split System Heat Pump
18 SEER
FSH1BG Heat Pump Split
INSTALLATION INSTRUCTIONS
*SH1BG4CVRX-24K, 36K, 48K, & 60K Series
The 18 SEER, iQ Drive® split heat pump operates as part of a larger system
which can provide temperature, air flow, and humidity control for a residence
or other similarly sized building. This system includes this outdoor unit and
a compatible indoor unit, typically an air handler with electric strip heat or
a gas furnace. The electric or gas heat may serve as backup or auxiliary heat
to supplement the heat pump, which is expected to serve as the primary heating
means. However, electric or gas heat is not required for this system to
operate. Accessory equipment which may be used with the system includes
humidifiers, electric or electronic air cleaners, and U/V (ultraviolet)
sterilizing lamps.
Refer to the System Operation section within this document for a description
of how the heat pump operates. In addition, information for troubleshooting
and diagnosing problems is included.
IMPORTANT
ATTENTION INSTALLERS:
It is your responsibility to know this product better than your customer. This
includes being able to install the product according to strict safety
guidelines and instructing the customer on how to operate and maintain the
equipment for the life of the product. Safety should always be the deciding
factor when installing this product and using common sense plays an important
role as well. Pay attention to all safety warnings and any other special notes
highlighted in the manual.
Improper installation of the unit or failure to follow safety warnings could
result in serious injury, death, or property damage.
These instructions are primarily intended to assist qualified individuals
experienced in the proper installation of this appliance. Some local codes
require licensed installation/service personnel for this type of equipment.
Please read all instructions carefully before starting the installation.
Return these instructions to the customer’s package for future reference.
DO NOT DESTROY. PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE
REFERENCE.
OTHER REFERENCE DOCUMENTS
- Installation instruction documents for indoor equipment (furnace or air handler, optional humidifier, etc.)
- local wiring and building codes
- Nordyne Application Guideline for Refrigerant Lines Over 75 Feet, document 044B-0600
- Operation/configuration manual for two-stage thermostat (existing or newly installed)
IMPORTANT SAFETY INFORMATION
INSTALLER: Please read all instructions before servicing this equipment. Pay
attention to all safety warnings and any other special notes highlighted in
the manual. Safety markings are used frequently throughout this manual to
designate a degree or level of seriousness and should not be ignored. WARNING
indicates a potentially hazardous situation that if not avoided, could result
in personal injury or death. CAUTION indicates a potentially hazardous
situation that if not avoided, may result in minor or oderate injury or
property damage.
WARNING:
ELECTRICAL SHOCK HAZARD
Failure to follow safety warnings exactly could result in serious injury or
property damage.
Improper servicing could result in dangerous operation, serious injury, death
or property damage.
- Before servicing, disconnect all electrical power to the unit.
- When servicing controls, label all wires prior to disconnecting. Reconnect wires correctly.
- Verify proper operation after servicing.
WARNING:
iQ Drive Split System Heat Pumps are shipped charged with R410A refrigerant
and ready for installation. When system is installed according to these
instructions, additional refrigerant charging may or may not be required. If
repairs make it necessary for evacuation and charging, it should only be
attempted by qualified trained personnel thoroughly familiar with this
equipment. Under no circumstances should the owner attempt to install and/or
service this equipment. Failure to comply with this warning could result in
property damage, personal injury, or death.
CAUTION:
This unit uses refrigerant R-410A. DO NOT use any other refrigerant in this
unit. Use of another refrigerant will damage the unit.
**WARNING:
Unless noted otherwise in these instructions, only factory authorized parts or
accessory kits may be used with this product. Improper installation, service,
adjustment, or maintenance may cause electrical shock or other hazardous
conditions which may result in personal injury or property damage.
WARNING:**
The information listed below and the next page must be followed during the
installation, service, and operation of this equipment. Failure to follow
safety recommendations could result in possible damage to the equipment,
serious personal injury or death.
-
The installer must comply with all local codes and regulations which govern the installation of this type of equipment.
Local codes and regulations take precedence over any recommendations contained in these instructions. Consult local building codes and the National Electrical Code (ANSI CI) for special installation requirements. -
All electrical wiring must be completed in accordance with local, state and national codes and regulations and with the National Electric Code (ANSI/NFPA 70) or in Canada the Canadian Electric Code Part 1 CSA C.22.1.
-
This equipment contains liquid and gaseous refrigerant under high pressure. DO NOT USE ANY PORTION OF THE CHARGE FOR PURGING OR LEAK TESTING.Installation or servicing should only be performed by qualified trained personnel thoroughly familiar with this type equipment.
-
Installation of equipment may require brazing operations. Installer must comply with safety codes and wear appropriate safety equipment (safety glasses, work gloves, fire extinguisher, etc.) when performing brazing operations.
-
Follow all precautions in the literature, on tags, and on labels provided with the equipment. Read and thoroughly understand the instructions provided with the equipment prior to performing the installation and operational checkout of the equipment.
-
Use caution when handling this appliance or removing components. Personal injury can occur from sharp metal edges present in all sheet metal constructed equipment.
-
Fully annealed, refrigerant grade copper tubing should be used when installing the system. Refrigerant suction line tubing should be fully insulated.
-
This unit is designed for outdoor installations only and should be positioned as described on page 3.
PREPARATION
Before proceeding with installation of iQ heat pump equipment,consult with the
distributor and homeowner to confirm that the equipment listed on the order is
what was ordered, and that it matches labeling on the equipment packaging.
Determine (including consultation with the homeowner) the intended/preferred
location for placement of the compressor/ outdoor coil unit. Unit envelope
dimensions are shown in
Figure 1.
This heat pump is designed for outdoor installation only.Unit placement must
take into consideration the following clearances:
- A minimum of 12 inches must be provided between each of the four sides and any solid barrier or wall which might block free inlet air flow into the coil. A minimum clearance of 18 inches is required between multiple units.
- The corner of the unit covered by the control access cover must be clear enough to allow comfortable access by a serviceperson.
- The top of the unit must be open and unobstructed to prevent recirculation of outdoor fan discharge air, particularly for air conditioning usage. A minimum distance of 4 feet overhead clearance is recommended. Do not locate the unit in a pit with high walls on all sides.
Locate the unit away from overhangs which would allow water runoff or ice to fall directly onto the heat pump. In low temperature climates, place the unit where it is not directly in prevailing winds. Avoid placing the heat pump near sleeping quarters or windows. As the unit goes through defrost cycles, a change in sound will occur.
Slab Mounting
- The preferred unit mounting is on an outdoor slab (concrete or plastic), on the ground, in an area with good drainage unlikely to be affected by heavy runoff, ground settling, or deep snowdrift accumulation.
- The support slab should be level. If the area is subject to heavy snowfall or drift accumulation, the use of a snow stand is recommended as well. Make sure that the drain holes in the bottom of the unit are not obstructed.
Roof Mounting
The method used for roof mounting should be designed so as not to overload
roof structures nor transmit noise to the interior of the structure.
Refrigerant and electrical lines should be routed through suitably
waterproofed openings to prevent leaking into the structure. Make sure that
the roof structure can adequately support the weight of the equipment. Consult
local building codes for rooftop installations.
After a location has tentatively been selected, trace routing of new (or pre-
existing) refrigerant lines (two), and power and control wiring. See further
discussion below.
- Maximum recommended length for refrigerant lines: 100 ft.
- Maximum elevation difference, compressor base to indoor coil base (compressor higher or lower): 50 feet. NOTE: An oil trap is required for elevations exceeding 50 feet.
- Refrigerant lines should NOT be buried. (in concrete or otherwise).
- Refer to Nordyne Application Guideline for Refrigerant Lines Over 75 Feet document 044B-0600, for piping details.
Once the above information has been confirmed and potential questions
regarding location, refrigerant line routing, and wire routing have been
resolved, proceed with unpacking the equipment. It is strongly recommended
that inspection of the hardware be performed prior to bringing it to the
installation site. Inspect for cosmetic as well as functional damage (such as
obvious holes or gaps in tubes and joints, cut or pinched wires or wire
insulation).
Verify that the iQ Drive® heat pump unit package includes the following:
- Coil/compressor/control unit.
- Packet containing installation instructions and one filterdrier.
ELECTRICAL CONNECTIONS
WARNING:
ELECTRICAL SHOCK HAZARD
Failure to follow safety warnings exactly could result in serious injury or
property damage.
Improper servicing could result in dangerous operation, serious injury, death
or property damage.
- Before servicing, disconnect all electrical power to the unit.
- When servicing controls, label all wires prior to disconnecting. Reconnect wires correctly.
- Verify proper operation after servicing.
Electrical Power Wiring
Electrical power wiring shall comply with the current provisions of the
National Electrical Code (ANSI/NFPA 70) as supplemented by applicable local
building codes. The installer should become familiar with the wiring diagram
before making electrical connections to the outdoor unit. An equipment wiring
diagram is included in this instruction (Figure 10 (page 16)& Figure 11 (page
17) and inside the unit control panel cover. Refer to the unit rating label
located on the exterior of the control box cover for operating voltage,
minimum circuit ampacity, and maximum fuse size. See Table 1 for wire sizing.
-
Electrical connections to the heat pump are made at the bottom of the control panel compartment. Remove the control panel cover to gain access to this compartment.
Figure 4 (page 12) shows a typical control panel compartment. -
A properly sized branch circuit and disconnect switch must be installed where it is easily accessible and within line of sight of the outdoor unit.
-
Remove the control panel cover. Route the power and ground wires (3 wires, including earth ground) from the disconnect box to the unit. Use of outdoor shielded conduit (metal lined Sealtite®) is required. The electrical conduit opening is located on the right side of the panel forming the bottom of the control compartment. See Figure 4.
-
Connect the power wires to L1 and L2 box lugs of the contactor, and the ground wire to the grounding lug located to the right of the contactor. Refer to Figure 4 and Figure 5 (page 13). Only copper wires should be used.
-
Replace the control panel cover before applying power.
Control Circuit Wiring
The heat pump is designed to operate with a 24 vac Class II control circuit.
Control circuit wiring must comply with the latest version of the National
Electrical Code (ANSI/NFPA 70) as supplemented by local building codes.
In general, 24 vac control power wiring must be run to interconnect the two-
stage thermostat, the indoor unit, and the outdoor unit. The source of the 24
vac is located within the indoor unit (air handler or furnace). The C side of
this power source may be grounded or ungrounded, typically determined by the
indoor equipment electrical design.
Six wires must be run to the heat pump’s control panel. R, C, and W will
originate from the indoor unit (furnace or air handler).
Y1, Y2, and O originate at the thermostat. W2 provides a signal to turn on
auxiliary (indoor) heat during a defrost cycle. If present, the seventh L
should not be connected to anything.
Pass each field-run control wire into the hole in the lower left side of the
base of the heat pump’s control panel compartment.
Refer to Figure 4 and Figure 6 (page 13). Connect each of the field-run wires
to its corresponding factory wired lead (with stripped ends) using a wire nut
or other solderless connector within the low voltage compartment. See Table 2
below.
COPPER WIRE SIZE – AWG (1% VOLTAGE DROP)
SUPPLY CIRCUIT
AMPACITY| SUPPLY WIRE LENGTH – FT
UP TO 50| 51 – 100| 101 – 150| 151 – 200
15| 14| 10| 8| 6
20| 12| 8| 6| 4
25| 10| 8| 6| 4
30| 10| 6| 4| 4
35| 8| 6| 4| 3
40| 8| 6| 4| 3
45| 6| 4| 3| 2
50| 6| 4| 3| 2
Wire Sized based on N.E.C. for 60°C type copper conductors
Table 1. Copper Wire Ampacity Tables
WIRE COLOR (OUTDOOR UNIT) | ID | FUNCTION | INDOOR CONNECTION |
---|---|---|---|
RED | R | 24VAC | Air Handler or Furnace |
BLK | C | 24 VAC common or ground | |
WHT | W2 | Heat during defrost | |
YEL | Y1 | 1st Stage call | Thermostat |
BLU | Y2 | 2nd Stage call | |
ORN | O | Heat (RV) |
Table 2. 24 Volt Control Wiring
REFRIGERANT LINE CONNECTIONS
Line Design and Routing
Refrigerant lines must be connected by a licensed EPA certified technician
following sound established installation practice. Once the heat pump location
has been determined and the unit set in place the refrigerant lines should be
routed and connected.
- Refrigerant lines should follow a direct path from the indoor coil to the outdoor unit avoiding sharp bends. When lines pass through walls, make sure to properly seal and support them so that vibration is not transmitted to the structure.
- Refrigerant tubing should be supported in a manner which assures that the tubing will not vibrate or wear as a result of contact with sharp materials or edges during system operation.
- Lines must be clean refrigeration-grade copper.
- Avoid removing caps and plugs from heat pump valves or lines until they are ready to be connected.
- Insulate the vapor line with refrigerant line insulation wall thickness ¼” or greater.
Proper system performance and oil management depend on properly selecting the
liquid and vapor line sizes. Refer to Table 3 below for the proper size of
field supplied lines. The maximum allowable refrigerant line length is 100 ft.
The maximum vertical elevation between the heat pump and indoor coil is 50 ft.
Systems that require more elevation will need to have an oil trap installed in
the vapor line. Refer to Nordyne Application Guideline for Refrigerant Lines
Over 75 Feet (document 044B-0600) for piping details.
A filter drier is supplied with the heat pump. It is required and recommended
that it be installed near the indoor coil.
It is recommended to replace existing refrigerant lines that were previously
used for an R-22 system. If the lines are not replaced, they must be properly
flushed by a licensed EPA certified technician in accordance with the
manufacturer’s instructions and established procedures.
MODEL | LINE SET LENGTHS |
---|---|
VAPOR LINE | LIQUID LINE |
UP TO 24 FT. | 25 TO 39 FT. |
-024K Units | 3/4 in. |
(19 mm) | 7/8 in. |
(22 mm) | 1 1/8 in. |
(29 mm) | 3/8 in. |
(10 mm)
-036K Units| 7/8 in.
(22 mm)| 1 1/8 in.
(29 mm)| 3/8 in.
(10 mm)
-048K Units| 7/8 in.
(22 mm)| 1 1/8 in.
(29 mm)| 3/8 in.
(10 mm)
-060K Units| 7/8 in.
(22 mm)| 1 1/8 in.
(29 mm)| 3/8 in.
(10 mm)
Table 3. Permissible Refrigerant Line Sizes
Brazing
Use the appropriate safety equipment while brazing. Items such as gloves,
safety glasses, proper ventilation, and a fire extinguisher should be used.
- Route the refrigerant lines from the indoor coil to the service valves on the heat pump. Avoid sharp radius bends and turns. See Figure 7 (page 13)
- Make sure that the vapor line is properly insulated for the entire length of the run for maximum system efficiency. Improper insulation may also create condensation and result in water damage to the equipment and building structure.
- Remove the valve cores from the heat pump service valves. Wrap the valves completely with wet rags to protect them from overheating during the brazing operation.
- Connect both the vapor and liquid lines. Tubes should be round, de-burred and free of debris. Use a phosphorous and copper or silver brazing alloy for the joints. Do not use soft solder with a low melting point.
- Connect the indoor lines according to the indoor unit instructions. The indoor coil will require the same alloys and wet rags to protect the sensors from excessive heat on the refrigerant lines.
- Allow the service valves to cool and replace the valve cores.
- Leak test the connections using low pressure dry nitrogen.
System Evacuation
-
Connect the refrigerant gauge manifold to both the vapor and liquid service valves. Figure 7. Connect the center port to the vacuum pump.
-
Open both manifold valves and start the vacuum pump.
After a short time, it is recommended to close the manifold valves and stop the vacuum pump to look for a rapid loss of vacuum. Loss of vacuum indicates that there is a leak in the system. Repeat the leak test if required. -
Evacuate the system to at least 500 microns to remove non-condensables and water vapor. Close the manifold valves and remove the vacuum pump.
-
Connect the refrigerant tank to the center manifold port of the gauge set. Pressurize the system enough to break the vacuum.
-
Open both service valves by turning the valve stems ¼ turn counterclockwise. The stem will be in line with the tubes.
Replace the stem caps and tighten. Proceed with Refrigerant Charging section.
WARNING:
The heat pump system contains liquid and gaseous refrigerant under pressure.
Adjustment of refrigerant charge should only be done by a qualified, EPA
certified technician thoroughly familiar with this type of equipment. Under no
circumstances should the homeowner attempt to install and/or service this
equipment. Failure to comply with this warning could result in equipment
damage, personal injury, or death.
Refrigerant Charging
NOTES:
- The unit must be charged at a fixed speed setting. For this purpose the thermostat needs to be wired and powered prior to charging.
- The heat pump is factory charged for field installed lines 15 ft. in length with the matching indoor equipment. Adjustments to the refrigerant charge will be required for other length and tube sizes. For lines longer than 15 ft with a 3/8” OD liquid line, add 0.52 oz. per ft. See Table 4 (page 5).
- Small variations in the temperatures and pressures are normal due to differences in the installation.
- Large variations in the temperatures and pressures could indicate incorrect charge or another problem with a component in the system.
The preferred method of charging is by weighing in the additional refrigerant required. If a charging scale is not available, the next preferred charging method would be to use the sub-cooling method in cooling mode.
MODEL | 2 TON (-024K) | 3 TON (-036K) | 4 TON (-048K) | 5 TON (-060K) |
---|
Factory Charge
for 15 ft. line set| 188 oz| 184 oz| 282 oz| 282 oz
Additional Charge
for 40 ft. line set| 16 oz| 16 oz| 18 oz| 18 oz
Additional Charge
for 75 ft. line set| 39 oz| 43 oz| 44 oz| 44 oz
Additional Charge
for 100 ft. line set| 57 oz| 62 oz| 63 oz| 63 oz
Table 4. Refrigerant Charge Quantities
Charging Operation
For charging in the field, the unit should be run with a call for second stage
cooling (or heating, if the outdoor ambient temperature is below 60° F), with
both Y1 and Y2 outputs energized. This may be accomplished by setting the
thermostat to cool with a setpoint substantially lower than room temperature.
This will provide 45 minutes of operation at the nominal rating speed
(interface board display “C4” or “H4”) before there is a speed change (to a
higher speed). If this speed change occurs before the charging process is
complete, turn the system off, turn control power off and on again, and then
restart the process.
Alternate Procedure for Charging Heat Pump in Cooling Mode
With outdoor temperature above 60° F (Based on Subcooling) While charging
based on weight is preferred, this method is acceptable. Use this method when
the outdoor temperature is 60° F or higher to verify the correct charge in
cooling mode.
The indoor temperature should be between 70° F and 80° F.
-
Connect the gauge manifold to the liquid and vapor service valves. See Figure 7 (page 13).
-
Start the system in cooling mode. Allow the system to run 15 minutes to stabilize.
-
Record the refrigerant pressure in psig at the liquid service valve.
-
Record the liquid refrigerant line temperature (in ° F) at or near the liquid service valve.
-
Using the temperature value recorded, determine the corresponding liquid refrigerant pressure from the upper curve (for cooling) in the charging chart. See Figure 8 (page14).
• If the pressure measured in step 3 is less than the required liquid refrigerant pressure determined in step 5, then refrigerant needs to be added.
• If the pressure measured in step 3 is greater than the required liquid refrigerant pressure determined in step 5, then the system is over-charged. -
Add or remove charge from the system depending on the measurements recorded. Allow the system to stabilize for 15 minutes before taking the next readings.
Alternate Procedure for Charging Heat Pump in Heating Mod e
with outdoor temperature below 60 ° F (Based on Subcooling):
Use this method when the outdoor temperature is 60° F or lower to estimate the
correct charge in heating mode. The indoor temperature should be between 65° F
and 75° F.
The preferred method of charging is by weighing in the additional refrigerant
required. If a charging scale is not available, the correct charge can be
estimated by this method.
Refrigerant can be stored in the receiver and accumulators and result in an
over-charged system. If it is necessary to use this method, follow up service
should be scheduled when the temperature is above 60° F, and then charge
should be verified in cooling mode.
-
Connect the gauge manifold to the liquid service valve and suction service port located at the left side of the access panel above the liquid service valve. See Figure 7 (page 13).
-
Start the system in heating mode. Allow the system to run 15 minutes to stabilize.
-
Record the refrigerant pressure in psig at the liquid service valve.
-
Record the liquid refrigerant line temperature (in ° F) at or near the liquid service valve.
-
Using the temperature value recorded, determine the corresponding liquid refrigerant pressure from the lower curve (for heating) in the charging chart. See Figure 8 (page 14).
• If the pressure measured in step 3 is less than the required liquid refrigerant pressure determined in step 5, then refrigerant needs to be added.
• If the pressure measured in step 3 is greater than the required liquid refrigerant pressure determined in step 5, then the system is over-charged. -
Add or remove charge from the system depending on the measurements recorded. Allow the system to stabilize for 15 minutes before taking the next readings.
NOTE: Small variations in charge will have a more significant effect on liquid line pressure in heating mode compared to cooling.
SYSTEM OPERATION
Thermostat
The primary control for the overall heating and cooling system is provided by
the indoor thermostat. Any standard two-stage heat pump capable thermostat
will be sufficient for operation.
Refer to the manual for the thermostat selected or installed for configuration
and usage details. For this control the O signal (operating the reversing or
4-way valve) to the heat pump should be energized for cooling and not for
heating.
Blower Flow Rates
Depending on the indoor equipment installed, blower air flow may be
adjustable. When paired with a matching model air handler or gas furnace, the
airflow is set by DIP switches on the blower control board, providing one flow
for second stage compressor speeds and a lower flow for first stage compressor
speeds. Refer to the indoor equipment manuals for instructions on how to
select the desired air flows. High stage airflows used for equipment ratings
are as follows:
- 2 ton – 800 cfm
- 3 ton – 1200 cfm
- 4 ton – 1350 cfm
- 5 ton – 1500 cfm
Refer to indoor equipment installation instructions for options, operation,
and field wiring relating to dehumidification and humidification.
Auxiliary Heat
The W2 output calling for auxiliary heat (electric strip or gas furnace) will
be energized by the heat pump controls during the coil heating phase of each
defrost cycle, and whenever there is a call for heat and the heat pump is in a
fault condition or if outdoor air temperature is below the 0° F low
temperature lockout. See Low Temperature Lockouts (page 8).
NOTE: The response of the auxiliary heating system to the W2 output will
depend upon the wiring and capabilities of that portion of the indoor system
equipment.
Start-Up Sequence
The recommended sequence is to provide 208/230 volt line
power to the outdoor unit first (via the disconnect), then apply 24vac control
power second. This sequence will avoid generating
potentially confusing fault codes, which will continue to be
displayed as part of fault history when the unit is subsequently
operating normally.
Run Sequence
After power-up and between cycles (after the preceding shutdown) there will
always be a five minute compressor (re)start delay imposed. With a call for
heat pump heating or cooling and before the compressor is turned on, the
outdoor fan will run for one minute to assure that the outdoor temperature
measurement is close to that of the ambient airThe compressor will then ramp
up to a speed selected by the capacity control scheme.
The 18 SEER heat pump is a true variable speed unit. Normallythe heat pump
compressor will operate at one of 5 speeds in cooling and 5 in heating, each
predetermined for a balance of optimum efficiency and capacity.The outdoor fan
motor will also operate at multiple speeds, following the compressor.
For either heating or cooling mode, the speeds used will depend on several
factors, including:
- Whether first or second stage operation is called for by the thermostat (which must be two stage-capable),
- Outdoor ambient temperature.
- The length of time the equipment has been operating duringthe current cycle
- The operating speed history, for both the current and the previous operating cycles.
For example, with a first stage call in cooling, if the setpoint was satisfied
quickly (within 20 minutes), the unit will restarthe next time at a lower
speed. At a low or intermediate speed, if the setpoint is not satisfied within
45 minutes for cooling or 30 minutes for heating, the speed will be increased.
If the unit cycles off after having a speed increase, the entire next cycle
will be at the higher speed. Also, the outdoor fan will run for an extra
minute after the compressor shuts off at the end of a cycle.
The actual current operating compressor speed can bedetermined by checking the
2-character display on the interfaceboard. Refer to Figure 9 (page 15) and
Table 5.
Control operation is protected under U.S. patent numberUS 8,011,199 B1.
Diagnostic Display
The interface board located inside the control panel has a two character
display which provides information regarding operational status and fault
history. When 24 vac control power is provided to the board, the display will
show some combination of characters. In order to diagnose a problem with the
unit, or to determine its operational status, remove the control panel cover,
then observe the 2-character lighted display on the interface board. Refer to
Table 5 (page 7)and Table 6 (page 8).
If the interface board has version 4.0 or later software, when control power
is first applied to the control board, the 2-characterdisplay will show the
following three items in sequence, twice:
DISPLAY | CAPACITY STAGE OR STATUS |
---|---|
Cooling, Stage One Call, Low | |
Cooling, Stage One Call, Intermediate | |
Cooling, Stage One Call, Low High | |
Cooling, Stage Two Call, Nominal High | |
Cooling, Stage Two Call, Boost | |
Heating, Stage One Call, Low | |
Heating, Stage One Call, Intermediate | |
Heating, Stage One Call, LowHigh | |
Heating, Stage Two Call, Nominal High | |
Heating, Stage Two Call, Boost | |
Startup Delay (5 minutes) | |
System Powered but Idle | |
In Defrost | |
Low Temperature Lockout |
(< 50 ° F in cooling, < 0 ° F in heating)
Table 5. Interface Board Operating Codes
- Unit size (tons):
- Unit type: HP for heat pump
- Software version, e.g. 4.0
This power-up display sequence is intended to confirm the correct programming
of the inverter control board.
After power-up, the display will alternate between an operating code (Table 5)
and a list of the codes for up to the last 10 different faults or warnings.
When this list is being displayed, each diagnostic code in memory will be
displayed for 5 seconds.
The most recent code will be the first one appearing in the series of codes
displayed.
NOTE: If there is a fault that is “active” when the display is viewed,
the decimal point to the right of the right side character will be lit. The
code for the most recent active fault will flash three times before the
remainder of the fault history list is shown.
Fault codes are retained through loss of power. Any fault which has been in
the list for more than 7 days (with control power applied) will be removed.
When there are no active faults, the list of past fault codes can be cleared
by shorting the TEST pins (J4, at the lower right side of the inverter control
board) when the unit is powered up but not running.
NOTE: This action may also have other consequences – See Short Cycle
Timer Override and Defrost Cycle sections on page 7.
Short Cycle Timer Override
When performing startup tests or while troubleshooting, the 5 minute startup
delay can be skipped by shorting the two J4 Test pins indicated in Figure 9
for about 1 second while the compressor is off and waiting to start.
NOTE: Use this feature with forethought because it will also clear the
fault codes stored in memory, which can make troubleshooting more difficult.
Defrost Cycle
This equipment features an adaptive demand defrost in heating mode, which is
enabled when the outdoor coil temperature is below 35° F. After approximately
34 minutes of operating in this condition for the first time, a defrost will
be forced to check the difference between the coil temperature and outdoorair
temperature, with the coil unfrosted. Subsequent defrosts will be triggered
when this temperature difference increases (coil temperature drops) by an
additional 6° F, referenced to the outdoor ambient at that time. If this has
not occurred by 6 hours of operation (with the coil below 35°), a defrost will
be run regardless. Following each defrost sequence, the unfrostedair-to-coil
temperature difference is rechecked, and that value is used to determine the
next defrost trigger temperature. In this way the effect of frosting up is
always compared to the unfrosted performance of the coil in its current
condition.
During every defrost cycle the compressor first shuts off, the W2 output is
energized, the reversing valve shifts, the cycle reverses to heat up the
outdoor coil until the coil reaches the defrost termination temperature
setting (70° F by default), then the compressor shuts off again for the
reversing valve to shift back to the heating mode. During the following 8
minutes (approximately), the unit will heat at the speed in use immediately
prior to the defrost to perform the coil differential temperature check
described above, after which the system will return to normal heating capacity
control.
If a defrost termination temperature setting other than 70° F is desired, it
can be adjusted between 50° F & 80° F by placing a jumper between pairs of
pins on J1 near the lower right side of the interface board inside the control
panel (Figure 9). A jumper is not required, however.
The defrost cycle may be artificially triggered for service and
troubleshooting purposes. With the unit running in heating mode, simply short
together the two J4 Test pins shown in Figure 9 for about 1 second. NOTE: This
will also clear the faults stored in memory. The 2-character display will
flash “dF” when the defrost cycle is under way. ”
Low Temperature Lockouts
The control will not permit the unit to operate in cooling modeat ambient
temperatures below 50° F. If there is a call for air conditioning when the
temperature drops below this point, the unit will shut down (if running), and
diagnostic code will be displayed on the interface board. The status code
(for Low Temperature) will also appear. Once this lockout is in effect, the
unit can resume cooling after ambient temperature has risen again above 55° F.
The control will not permit the unit to operate in heating mode at ambient
temperatures below 0° F. If there is a call for heat pump heating when the
temperature drops below this point, the unit will shut down (if running), the
W2 auxiliary heat output will be energized, and the status code (for Low
Temperature) will appear. Heat pump operation will be permitted again when
ambient temperature rises above 1° F and 60 minutes have passed. (This delay
can be bypassed by temporarily switching the system mode to cooling.) The W2
output will shut off when either the call is removed or heat pump operation is
again permitted.
Other Speed Overrides
When ambient temperature is high, exceeding 105° F, the compressor speed may
be reduced to limit current draw or inverter component temperature. Whether or
not this occurs and to what degree the speed is reduced depends upon the unit
model and the specific operating conditions as detected by the inverter. Speed
will return to the normal value when the high current or temperature condition
is relieved. In addition, any time outdoor ambient temperature exceeds 100° F,
the fan will operate at its maximum speed.
Instrumentation
The 18 SEER iQ Drive split system heat pump includes instrumentation as listed
in Table 7. All items listed are connected to the interface board except for
the high pressure switch. Refer to Figure 4 (page 12), Figure 9 (page 15),
Figure 10 (page 16), and Figure 11 (page 17). The five temperature sensors are
color coded so that the color of the wire insulation matches the color of the
connector base on the left side of the circuit board. All temperature sensors
are 10k ohm thermistors. The resistances of these sensors (when disconnected
from the interface board) may be checked against Figure 12 (page 18) for
troubleshooting purposes. Figure 12 shows the thermistor resistance-
temperature curve broken into two parts for ease of use.
DISPLAY | CAPACITY STAGE |
---|---|
Inverter Power Module Overcurrent | |
General Inverter Drive Fault | |
High Compressor Current | |
Current Sampling Error (Inverter) | |
High Inverter Heat Sink Temperature | |
High DC Bus Voltage (Inverter) | |
Low DC Bus Voltage (Inverter) | |
Low Line Voltage at Inverter | |
Line Overcurrent at Inverter | |
Line Voltage Sampling Error (Inverter) | |
Loss of Communication (Inverter Internal) | |
Inverter Heat Sink Sensor Failure | |
Loss of Communication (Inverter Internal) | |
Loss of Communication (IFB to Inverter) | |
Override, High Compressor Current | |
Override, High Line Current | |
Override, High Inverter Heat Sink Temp | |
Outdoor Fan Motor Fault | |
Low Pressure Switch Open | |
High Compressor Discharge Temperature | |
Interface Board Software Error | |
Sensor Failure – Compressor Dischg Temp | |
Sensor Failure – Ambient Temperature | |
Sensor Failure – Coil Temp #1, Defrost | |
Cooling Low Temperature Lockout |
Table 6. Interface Board Diagnostic Codes
FUNCTION | TYPE | CONNECTION |
---|---|---|
High Pressure Switch | Opens 650 ±15 psig, recloses 460 ±15 psig | See Figure |
10, and Figure 11
Low Pressure Switch| Opens 20 ±5 psig, recloses 35 ±5 psig| IFB LP1-LP2
Ambient Air Temp| Thermistor 10Kn @ 25° C (Fig. 10)| IFB “OUTDOOR TEMP” (BLK)
Compressor Discharge Temp| Thermistor 10Ko @ 25° C (Fig. 10)| IFB “DISCHARGE
TEMP” (RED)
Coil Defrost Temp| Thermistor 10KO @ 25° C (Fig. 10)| IFB “COIL #1 TEMP”
(WHT)
Coil Saturation Temp| Thermistor 10Ko @ 25° C (Fig. 10)| IFB “COIL #2 TEMP”
(YEL)
Suction Temp| Thermistor 10Ko @ 25° C (Fig. 10)| IFB “SUCTION TEMP” (BLU)
*IFB=Interface Board
Table 7. Instrumentation List
TROUBLESHOOTING
The 2-character LED display on the inverter control board is intended to be
helpful in diagnosing problems. Under normal operation the display will always
show both a status indicator (Table 5) along with fault indications (Table 6).
The fault indications are a sequential listing of fault historyThe last 10
fault codes recorded are displayed in sequencewith the most recent first. If
there is an “active” fault, one which is currently detected and responsible
for interrupting operation, the right hand decimal point in the display will
be lit, and the first number in the list will double-blink at first, then
appear again. If this decimal point is not lit, all codes listed are
historical only, and none are “active”. Also, if no code numbers are
displayed, there have been no faults recorded, or the history has been
cleared.
NOTE: As standard practice, write down the fault codes in the history before
attempting to clear the history. In troubleshooting,focus on fault codes that
return as “active” after the history has been cleared. Do not replace hardware
based on history alone, i.e., on faults that are not “active”.
WARNING:
Do not touch inverter conductors or the tops of its large capacitors until
power has been off for at least 30 seconds. The inverter will retain a high
voltage for a time after power has been removed.Failure to comply with this
warning could result in serious injury, death or property damage.
The list of past faults can be cleared by shorting the TEST pins (J4), at the
lower right side of the inverter control board (when the unit is powered up
but not running). This procedure will also force the unit to bypass the normal
5 minute stopto-start delay.
Fault and warning codes are listed in Figure 8 (page 14and on a label affixed
to the inside surface of the control panel cover.
Inverter Circuit Board LEDs
For some inverter-related fault codes, it is helpful to note at least whether
or not LEDs are lit on the main inverter circuit boards, which are mounted
behind the interface board on which the codes are displayed. For 2, 3, and
4-ton modelslook for a lit LED about 3 inches directly behind the 2-character
display. For the 5-ton model look for a lit LED about 3 inches directly behind
the lower edge of the secondary contactor that is mounted on the left side of
the upper mounting bracket.NOTE: There are other LEDs on the inverter circuit
boards as well as those described above.
For normal operation the inverter LEDs located as described above will blink
green slowly. When there is an inverter- generated fault, a red LED next to
the green one will flash.
Normally this will be translated into a 2-digit fault code on the main
display.
If the green LED (described above) is not lit, it generally indicates that
line voltage is not getting to the inverter via the contactor. Check for the
presence of 208/230 volts between the top two terminals of the main contactor.
If voltage is present, the inverter needs to be replaced, or internal wiring
is incorrect. If line voltage is absent, check for 24 vac across the main
contactor coil, and verify line voltage between the lower terminals of the
contactor. If 24 volt coil voltage is absent, check continuity through the
high pressure switch, and verify that the COMMUNICATIONS PORT plug is in
place at J6 at the bottom edge right of the interface board.
No Control Board Display
If the 2-character display on the interface board shows nothing, verify that
24 vac control voltage is present between R and C (red and black wires of the
field wiring harness plugged into the right side of the control board. If
voltage is absent, check field wiring back to the indoor unit and transformer
and thermostat.
If voltage is present but the display is blank, the control board needs to be
replaced. Check wiring for indications of a direct short before trying a new
board.
Troubleshooting Individual Fault Codes (when active)
Follow the recommended troubleshooting procedures in Table 8 for “active”
faults. In some cases more than one fault code or different active codes may
be generated by one issue, e.g.
interruption of line power. Always cycle line power (30 seconds off, then on
for at least 1 minute) to confirm that an active fault returns, is re-
declared, before considering replacing hardware.
Most inverter-related faults are at least temporarily cleared by cycling power
in this manner. Do not replace hardware based on history alone, on faults that
are not “active”.
CODES | DESCRIPTION |
---|---|
These codes indicate abnormal high current or high inverter temperature. If |
they persist and return as active fault codes, they may indicate a faulty
inverter drive or a wrong interface board/inverter combination.
| Compressor Drive Failure – This generally indicates a compressor problem
which may be temporary or permanent. If the compressor has just been replaced,
recheck the U, V, and W compressor leads for a connection mistake. Before the
inverter declares this fault during an attempted startup, it will try to start
the compressor 4 times, with approximately 20 seconds pause between attempts.
During start attempts, listen for compressor noise; if none, the compressor
may need to be replaced. Check compressor phase-to-phase resistances; they
should all be less than 1.5 ohms and within 0.2 Q of each other. If compressor
noise is loud, squealing, or otherwise unusual, the compressor may need to be
replaced. If the compressor restarts normally, this fault code may be simply
an indication that the compressor speed has been temporarily disrupted by
either starting or shutting down abruptly against a high pressure ratio. In
either case, the system may be normal but only temporarily affected by
abnormal running conditions.
| These fault codes refer to internal inverter operation and are likely to
indicate inverter failure. If they persist and return as active fault codes,
replace the inverter assembly.
| High DC Bus Voltage – This is an indication that line voltage exceeded 10%
over nominal value. The cause is likely to be power grid abnormalities or a
poorly controlled generator.
Table 8. Individual Fault Codes
| Low DC Bus Voltage – In most cases This is an
---|---
indication that 208/230 volt hue power was interrupted Of disconnected. It may
also indicate low line voltage or. rarely, an internal inverter failure.
| Low AC Line Voltage – This indicates that line voltage has dropped below
approximately 170 volts. 11 may also indicate loss of tine power. in which
case Code .21 may appear in addition to or instead of this code.
| Loss of Communication Between Inverter and Interlace Board – Check the
inverter LEDs (as described in Inverter Circuit Board LEDs section) for an
indication that the inverter has line power. Follow the troubleshootirg steps
described in that section first If the inverter LEDs are lit but the code
isactive. verify that the 4-pth plug atJ5 (INVERTER PORT) is connected at the
bottom edge center of the interlace board. If these checks do not resolve the
fault and the fault remains active, replace the Oterface board.
| These are warning codes that simply indicate that a high current or
temperature condition was reached. and that the Oveder was able to keep the
parameter in an acceptable range by automatically reducing speed. These
conditions do not result in the unit shutting down (unless the current or
temperature increased further and reached a shutdown limit, in which case
another code would be displayed). NOTE: If a high current or temperature
shutdown occurs, these warning codes are not necessarily displayed and stored.
| Outdoor Fan Fault-Check that 208/230 vac line power is being provided
through the main contactor to the fan. In 5-ton models this is through a
hymnal block located to the right of the contactor. If ok, check that the
2-wire fan power harness (brown and black wires) is connected as indicated on
the wiring diagram. If olu check that the fan control harness is property
connected at ..115 (PWM FAN CONTROL) at the top edge, center, of the control
board. II ok, check the small square white label on the interlace board which
has two numbers printed along its edges. Examine the date code number, the one
that does not begin with “tACT. II this other number begins with -1235” or
lower, replace the interlace board. II this date code starts with -1245′ or
higher. and the other checks do not reveal the source of the problem replace
the fan motor.
| Low Preens Switch Open – A low pressure condition (less than 20 psig (:5))
must exist in the suction tine for more than 4 milutes to trigger this fault,
A pressure of 35 psig (*5) is required to reclose the switch. Check liquid
line temperature and pressure against the charging chart to confirm that
charge level is not significantly low. Compare gage measurement against the 20
psi switch lirrit (with the system running). II gage measurements are good.
check that the pressure switch is depressing the Schrader pit Verily that the
blue wires Imn the switch are propedy connected to the LOW PRESSURE SWITCH
terminals at the lower edge. left of center, on the interlace board. If the
system is normal, an active low pressure switch fault should clear when the
compressor is off. Check continuity across the wire terminals. If the
connection is electrically open. and manual pressure checks show that system
pressure is good while running but the fault remains active. replace the
switch.
| High Compressor Discharge Temperature – II compressor discharge line
temperature exceeds 221` F. this fault is triggered. Check for conditions that
would cause high discharge temperature and pressure, e.g. fouled orblocked cot
overcharge. See alsof wit code 23.
| Interface Board Software Corruption — This code indicates that the interface
board needs to be replaced. It should never be encountered.
---|---
| Compressor Discharge Temp Sensor Failure — This fault code indicates an open
or shorted sensor. See also fault code 20.
| Ambient Temp Sensor Failure — This fault code indicates an open or shorted
sensor. The tip of the sensor should be mounted near the louvers at the base
of the control compartment. Look for a pinched wire with cut insulation.
| Coil Temp Sensor Failure — This fault code indicates an open or shorted
sensor. NOTE: For the SH1 BG4CV heat pump, only the COIL #1 TEMP sensor with
the white wires (used for defrost) is checked.
| Cooling Low Temperature Lockout – This is an informational code that
indicates that the unit attempted to start or run in cooling mode when outdoor
ambient temperature was below 50° F, which is not permitted. If such a lockout
occurs, the unit will restart when ambient temperature exceeds 55° F. If the
ambient temperature sensor fails open or is disconnected, this code will also
appear.
Table 8. Continued
MAINTENANCE
WARNING:
ELECTRICAL SHOCK HAZARD
Failure to follow safety warnings exactly could result in serious injury or
property damage.
Improper servicing could result in dangerous operation, serious injury, death
or property damage.
- Before servicing, disconnect all electrical power to the unit.
- When servicing controls, label all wires prior to disconnecting. Reconnect wires correctly.
- Verify proper operation after servicing.
- Inspect the indoor air filter monthly. Clean or replace it at the start of each heating and cooling season or when an accumulation of dust or dirt is visible. If the indoor coil needs to be cleaned, contact a qualified service technician.
- Inspect the condensate disposal line from the indoor coil at the beginning of the cooling season to make sure it is not obstructed.
- Remove any leaves, grass clippings, and debris from the outdoor unit coil, being careful not to damage the aluminum fins. Dirt may be cleared from the coil by using a water hose directed through the discharge fan grille toward the outside of the unit.
- Have a yearly inspection by a qualified service technician to ensure that the system is performing at its optimum level.
- At least once a season open the control panel (with power off) to inspect for and clear out insect structures and/or cobwebs which might impede airflow through the control panel compartment and the air inlet louvers at the bottom of the control compartment.
Panel Removal
- Remove screws securing the panel.
- Slide the panel up towards the top pan in order to clear the bottom flange from the base pan. See Figure 2.
- Swing the bottom of the panel out and pull the panel down to remove it from the unit.
Panel Installation
- Insert the top corners of side panel flanges into the corner post channels as shown in Detail A in Figure 3.
- Slide the panel up into the top pan. (You may need to push on the center of the panel at the top in order to clear the top pan edge).
- Swing the panel in and push down until the panel is resting on the top edge of the base pan wall as shown in Detail B.
- Insert screws into the panel to secure it to the unit.
FIGURES & CHARTS
Cooling Charging Chart (Outdoor Temperature above 60° F) Figure 8. Charging Charts
WIRING DIAGRAM
Split system invertar heart pump -2,3,4 ton
NOTES:
- Disconnect all power before servicing.
- For supply connections use copper conductors only.
- Not suitable on systems that exceed 150 volts to ground.
- For replacement wires use conductors suitable for 105 deg.C.
- For ampacities and overcurrent protection, see unit rating plate
- Connect to 24 vac/60va/class 2 circuit. See furnace/air handler installation instructions for control circuit and optional relay/ transformer kits.
- Ferrite chokes are shown by an ellipse enclosing wires. The number of turns per wire through the choke is shown by 2X, for example.
Figure 10. Wiring Diagram (2, 3, & 4 Ton Models)
WIRING DIAGRAM
Split system invertar heart pump -5 ton
NOTES:
- Disconnect all power before servicing.
- For supply connections use copper conductors only.
- Not suitable on systems that exceed 150 volts to ground.
- For replacement wires use conductors suitable for 105 deg.C.
- For ampacities and overcurrent protection, see unit rating plat
- Connect to 24 vac/60va/class 2 circuit. See furnace/air handler installation instructions for control circuit and optional relay/ transformer kits.
- Ferrite chokes are shown by an ellipse enclosing wires. The number of turns per wire through the choke is shown by 2x , for example.
Figure 11. Wiring Diagram (5 Ton Models)
Temperature vs. Resistance for All Thermistors (Part 1) Temperature vs. Resistance
for All Thermistors (Part 2)
INSTALLATION CHECK LIST
ATTENTION INSTALLERS:
It is your responsibility to know this product better than your customer.
This includes being able to install the product according to strict safety
guidelines and instructing the customer on how to operate and maintain the
equipment for the life of the product. Safety should always be the deciding
factor when installing this product and using common sense plays an important
role as well. Pay attention to all safety warnings and any other special notes
highlighted in the manual. Improper installation of the furnace or failure to
follow safety warnings could result in serious injury, death, or property
damage.
These instructions are primarily intended to assist qualified individuals
experienced in the proper installation of this appliance. Some local codes
require licensed installation/service personnel for this type of equipment.
Please read all instructions carefully before starting the installation.
Return these instructions to the customer’s package for future reference.
INSTALLATION ADDRESS:
CITY ____
S TAT E ____
UNIT MODEL # ____
UNIT SERIAL # ____
Unit Installed Minimum clearances perFigure 1 (page 3)?
YES
NO
INSTALLER NAME:
CITY ___
S TAT E ____
PROPOSITION 65 WARNING:
WARNING: This product contains chemicals known to the state of California
to cause cancer.
WARNING: This product contains chemicals known to the state of California
to cause birth defects or other reproductive harm.
ELECTRICAL SYSTEM
Electrical connections tight? | YES | NO |
---|---|---|
Line voltage polarity correct? | YES | NO |
Rated Voltage: _ VOLTS
L1-L2 Volts: ___ VOLTS
Max. deviation of voltage
from rated volts: ____ VOLTS
% Volt imbalance: __ VOLTS
Blower Motor HP: __
Has the thermostat been calibrated?| YES| NO
s the thermostat level?| YES| NO
REFRIGERATION SYSTEM
Was unit given 24 hr warm up period for
crankcase heaters?| YES| NO
---|---|---
Stage-1 Liquid Pressure (high side) ____
Stage-1 Suction Pressure (low side) ____
Has the owner’s information been reviewed with the customer?| YES| NO
Has the Literature Package been left with the unit?| YES| NO
www.ahridirectory.org
Specifications & illustrations subject to change without notice or
incurring obligations (09/22).
© Nortek Global HVAC LLC 2022. All Rights Reserved. 10408830
(Replaces 1017412A)
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>