Tuncmatik 1500VA Uninterruptible Power Supply UPS User Manual
- June 13, 2024
- Tuncmatik
Table of Contents
LIFT
1500 / 2000VA
UNINTERRUPTIBLE POWER SUPPLY UPS
USER MANUAL
INTRODUCTION
LIFT 1500/2000 VA
Front Panel
- On/Off Button
- AC Mode: Green Lighting
- Battery Mode: Orange Flashing
- Fault: Red Lighting
- Input Terminal
- Output Terminal
- Circuit Braker
This UPS is specially designed for Lifts. Its light weight, compact design
perfect fits to the limited working E environment. The line of UPS is equipped
with boost and buck AVR to stabilize input voltage range. It is also built-in
with DC start function.
This function enables the UPS to be started up without AC power supplied.
The main features of UPS are listed below:
- Compact size, light weight.
- Microprocessor control guarantees high reliability.
- Equipped with Boost and Buck AVR.
- Green Power Function for energy saving.
- DC Start Function. (Cold Start)
- Provides AC Overload protection.
Inspection
Remove the UPS from its packaging and inspect it for damage that may have occurred during shipping. If any damage is discovered, repack the unit and return it to the place of purchase.
Charging
This unit is shipped from the factory with its internal battery fully charged,
however, some charge may be lost during shipping and the battery should be
recharged prior to use. Turn on the UPS, plug the unit into an appropriate
power supply and allow the UPS to charge fully by leaving it plugged in for at
least 6 hours. Green LED flashes while UPS charging.
Placement
Install the UPS unit in any protected environment that provides adequate
airflow around the unit, and is free from excessive dust, corrosive fumes and
conductive contaminants. Do not operate your UPS in an environment where the
ambient temperature or humidity is high.
Turn On/Off
- To turn on the UPS unit, press the power lightly
- To turn off the UPS unit, press the power switch again.
DC Start
All Series are equipped with DC Start (Cold Start). To start the UPS when AC
utility power is not available, simply press the smart button for minimum 1
second.
TECHNICAL SPECIFICATIONS
CAPACITY | 1500VA 900 | 2000VA 1200W |
---|
Input
Voltage| 220/230/240 VAC
Voltage range| 162-265 VAC
Output
Voltage range| +10%
Transfer time| 2-6 ms, 10 ms max
Waveform| Simulated sine wave
Type & Number| x 12V 9Ah
Charging time| 4-6 hours recover to 90% capacity
Battery
Dimensions D x W x H (mm)| 300x180x190| 300x213x190
Net weight (kg)| 12.0| 13.3
Environment
Humidity| 0-40°C 0-90% [non-condensing)
Noise level| <40 dB
TROUBLE SHOOTING
Use the table below to solve minor problems.
Symptom | Possible Cause | Remedy |
---|---|---|
No LED display on the front panel. | 1. Battery weak. | 1. Charge battery up |
to 8 hours.
2. Battery defect.| 2.Replace with the same type of battery.
3.Power switch is not pressed.| 3. Press the power switch again.
Alarm buzzer beeps continuously when AC supply is normal.| Overload of the
UPS.| Verify that the load matches the UPS
capability specified in the specs.
When power failure, back-up time is shorten.| 1. Overload of the UPS.| 1.
Remove some non-critical load.
2. Battery voltage is too low.| 2.Charge battery 8 hours or more.
3.Battery defect due to high temperature operation environment, or improper
operation to battery.| 3. Replace with the same type of battery.
Mains normal but Yellow LED is flashing.| Power cord is loose.| Check the
power cord.
If any abnormal situations occur that are not listed above, please call service people immediately.
SAFETY – WARNING
This UPS utilizes voltages that may be hazardous. Do not attempt to
disassemble the unit. The unit contains no user serviceable parts. Only
technical service personnel may perform repairs.
Internal battery voltage is 12Vdc. Sealed, lead-acid, 6 cells battery.
The unit must be connected to only 2-pole 3-wire grounded power.
In the event of an emergency, press the Smart On/Off Button for 4 seconds and
disconnect the power cord from the AC power supply to properly disable the
UPS.
Do not allow liquids or any foreign object to enter the UPS. Do not place
beverages or any other liquid-containing vessels on or near the unit.
This unit intended for installationina controlled environment (temperature
controlled, indoor area free of conductive contaminants). Avoid installing the
UPS in locations where there is standing or running water, or excessive
humidity.
Do not plug the UPS input into its own output.
Do not attach to non-computer-related items, such as medical equipment, life-
support equipment, microwave ovens, vacuum cleaners, laser printers or washing
machine.
To reduce the risk of overheating the UPS, do not cover the UPS cooling vents
and avoid exposing the unit to direct sunlight or installing the unit near
heat emitting appliances such as space heaters or furnaces.
Unplug the UPS prior to cleaning and do not use liquid or spray detergent.
Do not dispose of batteries in a fire as they may explode.
Do not open or mutilate the battery or batteries. Released electrolyte is
harmful to the skin and eyes. It may be toxic.
Attention, hazardous through electric shock. Also with disconnection of this
unit from the mains, hazardous voltage still may be accessible through supply
from battery. The battery supply should be therefore disconnected in the plus
and minus pole of the battery when maintenance or service work inside the UPS
is necessary.
Servicing of batteries should be performed by authorized personnel. Keep
unauthorized personnel away from batteries.
A battery can present a risk of electrical shock and high short circuit
current. The following precautions should be observed when working on
batteries:
- Remove watches, rings, or other metal objects from the hands.
- se tools with insulated handles.
- Wear rubber gloves and boots.
- Do not lay tools or metal parts on top of batteries.
- Disconnect charging source prior to connecting or disconnecting batteries terminals.
When replacing batteries, replace with the same number and type of sealed
lead-acid battery. The maximum ambient temperature raling is 40°C.
This pluggable type A equipment with battery already installed by the supplier
is operator installable and may be operated by laymen.
During the installation of this equipment it should be assured that the sum of
the leakage currents of the UPS and the connected loads does not exceed 3.5
mA.
The mains socket outlet that supplies the UPS shall be installed near the UPS
and shall be easily accessible.
www.tuncmatik.com
Manufacturer :
TMK Power Products Manufacturing Ltd.
Silicon Valley Power Intelligent terminal Industrial park Area, Building
No:A12,4th floor Dafu
Industrial guanylin, Shenzhen City, China
Importer:
Tunçmatik Elektrik Malzemeleri San ve Tic .A.S.
T : +90.216.314.51.51
F : +90.216.420.35.29
info@tuncmatik.com