PCE Instruments PCE-WSAC 50-ABC Wind Speed Alarm Controller User Manual
- June 13, 2024
- PCE Instruments
Table of Contents
PCE Instruments PCE-WSAC 50-ABC Wind Speed Alarm Controller User Manual
User manuals in various languages (français, italiano, español, português,
nederlands, türk, polski, русский , 中文) can be downloaded here: www.pce-
instruments.com
Safety notes
Please read this manual carefully and completely before you use the device for the first time. The device may only be used by qualified personnel and repaired by PCE Instruments personnel. Damage or injuries caused by non- observance of the manual are excluded from our liability and not covered by our warranty.
- The device must only be used as described in this instruction manual. If used otherwise, this can cause dangerous situations for the user and damage to the meter.
- The instrument may only be used if the environmental conditions (temperature, relative humidity, …) are within the ranges stated in the technical specifications. Do not expose the device to extreme temperatures, direct sunlight, extreme humidity or moisture.
- Do not expose the device to shocks or strong vibrations.
- The case should only be opened by qualified PCE Instruments personnel.
- Never use the instrument when your hands are wet.
- You must not make any technical changes to the device.
- The appliance should only be cleaned with a damp cloth. Use only pH-neutral cleaner, no abrasives or solvents.
- The device must only be used with accessories from PCE Instruments or equivalent.
- Before each use, inspect the case for visible damage. If any damage is visible, do not use the device.
- Do not use the instrument in explosive atmospheres.
- The measurement range as stated in the specifications must not be exceeded under any circumstances.
- Non-observance of the safety notes can cause damage to the device and injuries to the user.
We do not assume liability for printing errors or any other mistakes in this manual.
We expressly point to our general guarantee terms which can be found in our general terms of business.
If you have any questions please contact PCE Instruments. The contact details can be found at the end of this manual.
Safety symbols
Safety-related instructions the non-observance of which can cause damage to the device or personal injury carry a safety symbol.
Symbol | Designation / description |
---|---|
Warning: hazardous area Non-observance can cause damage to the device |
and injuries to the user.
| Warning: electrical voltage Non-observance can cause electric shock.
Specifications
Technical specifications
Power supply| 115 V AC
230 V AC
24 V DC
---|---
Supply voltage for sensors (output)| 24 V DC / 150 mA
Measurement range| 0 … 50 m/s or (depending on version)
0 … 112 mph
Resolution| 0.1 m/s or (depending on version)
0.2 mph
Accuracy| ±0.3 m/s or (depending on version)
±0.7 mph
Signal input (selectable)| 4 … 20 mA0 … 10 V
Alarm relay| 2 x changeover contact
250 V AC / 10 A AC
30 V DC / 10 A DC
Interface (optional)| RS 485
Operating temperature| -20 … 60 °C
Dimensions| 191 mm x 125 mm
Delivery contents
- 1 x wind speed alarm controller PCE-WSAC 50
- 1 x user manual
- 1 x plug „Signal Input“
- 1 x plug “RS485 interface” (only versions with communication interface)
Order code
PCE-WSAC 50-ABC
Example: PCE-WSAC 50-711
- Power supply 230 V AC
- Unit mph
- Signal input 4… 20 mA
- Communication RS-485 interface
Accessories
PCE-WSAC 50-A1C:
PCE-FST-200-201-I Wind speed sensor 0 … 50 m/s / Output 4…20 mA
PCE-WSAC 50-SC25 25 m Sensor cable to connect PCE-FST-200-201<->PCE-WSAC 50
PCE-WSAC 50-A2C:
PCE-FST-200-201-U Wind speed sensor 0 … 50 m/s / Output 0…10 V
PCE-WSAC 50-SC25 25 m Sensor cable to connect PCE-FST-200-201<->PCE-WSAC 50
System description
Device description
- Opening groove
- LED „normal“
- LED „pre-alarm“
- LED „alarm“
- Display measured value
- Enter key
- Arrow right key
- Arrow up key
- Display wind scale (wind force)
- Cable gland power supply
- Cable gland relay / wind sensor
- Connection wind sensor
- RS-485 interface (optional)
Electrical wiring
Pin assignment of „Signal Input“ plug
1| Vcc power supply output|
---|---|---
2| GND
3| Signal
4| Protective earth conductor
Pin assignment “RS485 interface” plug
1| B|
---|---|---
2| A
3| GND
|
Getting started
Assembly
Attach the wind speed alarm controller where desired. The dimensions can be taken from the assembly drawing below.
Power supply
Establish power supply by means of the relevant connections and set up the connection of the relay outputs to your system or signalling device (see 3.2). Make sure that the polarity and the power supply is correct.
ATTENTION: Excessive voltage can destroy the device! Ensure zero voltage when establishing the connection!
The device will power on immediately when connected to the power supply. The current reading will be displayed when a sensor has been connected. If no sensor has been attached, the display will show “00,0“ if you have one of the PCE-WSAC 50-A2C versions (signal input 0…10 V) or. “Err“ if you have a PCE- WSAC 50-A1C version (Signal input 4…20 mA).
Connecting the sensors
Connect the sensor (not included in the standard package) and the (optional) interface, using the plugs as described in 3.3 and 3.4. Make sure that the polarity and the power supply are correct.
ATTENTION: Non-observance of the polarity can destroy the wind speed alarm controller and the sensor.
Operation
Measurement
The device measures continuously as long as it is connected to the power supply. The factory default setting for the pre-alarm (S1) is from 8 m/s and for the alarm (S2), the default setting is from 10.8 m/s.
The pre-alarm will make the pre-alarm relay switch, a yellow LED will glow and a beep sound will be emitted in intervals.
In case of an alarm, the alarm relay will switch, the red LED will glow and a continuous beep sound will be activated.
Settings
To get to the setup menu, press the ENTER key (6) until the first digit flashes. Then enter “888“. With the Arrow right key (7), you can navigate through the digits and change the value of the digit with the Arrow up key (8). Confirm with ENTER (6).
The following options can be selected using the Arrow up key (8):
Display | Meaning | Description |
---|---|---|
Ext | Exit | Back to normal measuring mode |
S1 | Pre-alarm | Enter the desired value (max. 50 m/s). You can move the cursor |
with the Arrow right key (7) and change the value of the digits with the Arrow up key (8). Confirm with ENTER (6).
Please note:
The pre-alarm value must not be higher than the alarm value and the alarm
value must not be lower than the pre- alarm value.
S2| Alarm| Enter the desired value (max. 50 m/s). You can move the cursor with the Arrow right key (7) and change the value of the digits with the Arrow up key (8). Confirm with ENTER (6).
Please note:
The pre-alarm value must not be higher than the alarm value and the alarm
value must not be lower than the pre- alarm value.
Flt| Filter| You can use the Arrow right key (7) to navigate through the digits and the Arrow up key (8) to change the value of the digits. Confirm with ENTER (6).
The following options can be selected:
“000“ Current wind speed
Change interval of display: 200 ms
Change interval of relay: 200 ms
“002“ 2-minute average value
Change interval of display: 120 s
Change interval of relay: 120 s
“005“ 5-minute average value
Change interval of display: 300 s
Change interval of relay: 300 s
Str| Factory settings| Resets all parameters to factory settings
To enter the relevant menu, select the menu with the Arrow up key (8) and confirm with ENTER (6).
You can leave the menu by selecting “Ext“ and confirming with the ENTER (6) key. If no key is pressed for 60 seconds, the device enters normal measuring mode automatically.
RS-485 interface (optional)
The communication with the wind speed alarm controller PCE-WSAC 50 is enabled by the MODBUS RTU protocol and the serial RS-485 port. This allows different registers containing the measured wind speed, the wind scale and other information to be read.
Communication protocol
- The registers can be read by means of the Modbus function 03 (03 hex) and written into by the function 06 (06 hex).
Supported baud rates| 1200, 2400, 4800, 9600, 14400, 19200,38400, 56000,
57600, 115200
---|---
Data bits| 8
Parity bit| None
Stop bits| 1 or 2
Data type of registers| 16-bit unsigned integer
Standard setting
Baud rate | 9600 |
---|---|
Parity | None |
Stop bit | 1 |
Address | 123 |
Excerpt from register addresses
Register address (dec)| Register address (hex)| Description|
R/W
---|---|---|---
0000| 0000| Current wind speed in m/s| R
0001| 0001| Current wind scale| R
0034| 0022| Pre-alarm| R/W
0035| 0023| Alarm| R/W
0080| 0050| Modbus address| R/W
0081| 0051| Baud rate (12 = 1200 baud, 24 = 2400 baud, etc.)| R/W
0084| 0054| Stop bits (1 or 2)| R/W
Warranty
You can read our warranty terms in our General Business Terms which you can find here: https://www.pce-instruments.com/english/agb.
Disposal
For the disposal of batteries in the EU, the 2006/66/EC directive of the European Parliament applies. Due to the contained pollutants, batteries must not be disposed of as household waste. They must be given to collection points designed for that purpose.
In order to comply with the EU directive 2012/19/EU we take our devices back. We either re-use them or give them to a recycling company which disposes of the devices in line with law.
For countries outside the EU, batteries and devices should be disposed of in accordance with your local waste regulations.
If you have any questions, please contact PCE Instruments.
PCE Instruments contact information
Germany
PCE Deutschland GmbH
Im Langel 4
D-59872 Meschede
Deutschland
Tel.: +49 (0) 2903 976 99 0
Fax: +49 (0) 2903 976 99 29
info@pce-instruments.com
www.pce-instruments.com/deutsch
United States of America
PCE Americas Inc.
711 Commerce Way suite 8
Jupiter / Palm Beach
33458 FL
USA
Tel: +1 561-320-9162
Fax: +1 561-320-9176
info@pce-americas.com
www.pce-instruments.com/us
The Netherlands
PCE Brookhuis B.V.
Institutenweg 15
7521 PH Enschede
Nederland
Telefoon: +31 (0) 900 1200 003
Fax: +31 53 430 36 46
info@pcebenelux.nl
www.pce-instruments.com/dutch
China
CE (Beijing) Technology Co.,Ltd
1519 Room, 4 Building
Men Tou Gou Xin Cheng
Men Tou Gou District
102300 Beijing
China
Tel: +86 (10) 8893 9660
info@pce-instruments.cn
www.pce-instruments.cn
France
PCE Instruments France EURL
76, Rue de la Plaine des Bouchers
67100 Strasbourg
France
Telephone: +33 (0) 972 3537 17 Numero de
fax: +33 (0) 972 3537 18
info@pce-france.fr
www.pce-instruments.com/french
United Kingdom
PCE Instruments UK Ltd
Units 12/13 Southpoint Business Park
Ensign Way, Southampton
Hampshire
United Kingdom, S031 4RF
Tel: +44 (0) 2380 98703 0
Fax: +44 (0) 2380 98703 9
info@industrial-needs.com
www.pce-instruments.com/english
Chile
PCE Instruments Chile SPA
RUT 76.423.459-6
Badajoz 100 oficina 1010 Las Condes
Santiago de Chile / Chile
Tel. : +56 2 24053238
Fax: +56 2 2873 3777
info@pce-instruments.cl
www.pce-instruments.com/chile
Turkey
PCE Teknik Cihazlari Ltd.Sti.
Halkali Merkez Mah.
Pehlivan Sok. No.6/C
34303 Klicakcekmece – Istanbul
Tlirkiye
Tel: 0212 471 11 47
Faks: 0212 705 53 93
info@pce-cihazIari.com.tr
www.pce-instruments.com/turkish
Spain
PCE lberica S.L.
Calle Mayor, 53
02500 Tobarra (Albacete)
Espana
Tel. : +34 967 543 548
Fax: +34 967 543 542
info@pce-iberica.es
www.pce-instruments.com/espanol
Italy
PCE Italia s.r.l.
Via Pesciatina 878 / B-Interno 6
55010 LOC. GRAGNANO
CAPANNORI (LUCCA)
Italia
Telefono: +39 0583 975 114
Fax: +39 0583 974 824
info@pce-italia.it
www.pce-instruments.com/italiano
Hong Kong
PCE Instruments HK Ltd.
Unit J, 21/F., COS Centre
56 Tsun Yip Street
Kwun Tong
Kowloon, Hong Kong
Tel: +852-301-84912
jyi@pce-instruments.com
www.pce-instruments.cn
User manuals in various languages (français, italiano, español, português,
nederlands, türk, polski, русский, 中文)can be downloaded here: www.pce-
instruments.com
Specifications are subject to change without notice.
References
- France.fr : Explore France and its wonders - Explore France
- iberica.es
- instruments.cn - The domain is available for purchase
- Computer Instruments | Home
- Discover Italy: Official Tourism Website - Italia.it
- N.E.E.D.S., (Nutritional Ecological Environmental Delivery System) specializes in providing products, information, and education
- PCE(北京)科技有é™å…¬å¸
- Improtek LTDA Distribuidor oficial de PCE Instruments | PCE Instruments
- PCE Teknik Cihazlar Paz. Tic. Ltd.Şti. | PCE Instruments
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>