heatilator NDV3630I-B Novus Direct Vent Fireplace Series Instruction Manual

June 13, 2024
heatilator

Installation Manual
Installation and Appliance Setup
Models:
NDV3630I-B
NDV3630IL-B
NDV3933I-B
NDV3933IL-B
NDV4236I-B
NDV4236IL-B
NDV4236I-NVR
NDV4842I-B
NDV4842IL-B

NDV3630I-B Novus Direct Vent Fireplace Series

CAUTION! Risk of Fire! DO NOT store instruction manuals inside fireplace cavity.
High temperatures could cause a fire.
INSTALLER: Leave this manual with the appliance, not inside the appliance.
CONSUMER: Retain this manual for future reference. Do not store inside the appliance.
Contact your dealer with questions regarding installation, operation or service.
NOTICE: DO NOT discard this manual!

heatilator NDV3630I-B Novus Direct Vent Fireplace Series
-

This appliance may be installed as an OEM installation in manufactured home (USA only) or mobile home and must be installed in accordance with the manufacturer’s instructions and the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280 in the United States, or the Standard for Installation in Mobile Homes, CAN/CSA Z240 MH Series, in Canada. This appliance is only for use with the type(s) of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
WARNING:
FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury, death, or property damage.

  • DO NOT store or use gasoline or other flam-mable vapors and liquids in the vicinity of this or any other appliance.

  • What to do if you smell gas
    – DO NOT try to light any appliance.
    – DO NOT touch any electrical switch. DO NOT use any phone in your building.
    – Leave the building immediately.
    – Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
    – If you cannot reach your gas supplier, call the fire department.

  • Installation and service must be performed by a qualified installer, service agency, or the gas supplier.

DANGER

HOT GLASS WILL
CAUSE BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.

A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and must be installed for the protection of children and other at-risk individuals.
Decorative barrier front must be ordered separately at time of appliance purchase. See Section 3.B.

Safety Alert Key:

  • DANGER! Indicates a hazardous situation which, if not avoided will result in death or serious injury.
  • WARNING! Indicates a hazardous situation which, if not avoided could result in death or serious injury.
  • CAUTION! Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
  • NOTICE: Used to address practices not related to personal injury.
    Note: The term “recommend” or “recommended” does not indicate a requirement. It is a best practice suggested by Hearth & Home Technologies®. Failure to perform the recommended task will not result in a safety concern.

Installation Standard Work Checklist
ATTENTION INSTALLER:
Follow this Standard Work Checklist

This standard work checklist is to be used by the installer in conjunction with, not instead of, the instructions contained in this installation manual.

Customer:
Lot/Address:
Model (circle one): NDV3630I-B/IL-B NDV3933I-B/IL-B
NDV4236I-B/IL-B NDV4236I-NVR NDV4842I-B/IL-B
Date Installed:
Location of Fireplace:
Installer:
Dealer/Distributor Phone #
Serial #:
WARNING! Risk of Fire or Explosion! Failure to install appliance according to these instructions could lead to a fire or explosion. Install ONLY components and accessories approved by Hearth & Home Technologies.
Unapproved components and accessories could cause fireplace to overheat.

Appliance Install
Verified that the chase is insulated and sealed. (Pg. 14)
Verified clearances to combustibles. (Pg. 11-13)
Fireplace is leveled and secured. (Pg. 36)

Venting/Chimney Section 7 (Pg 37-43)
Venting configuration complies to vent diagrams.
Venting installed, locked and secured in place with proper clearance.
Firestops installed.
Attic insulation shield installed.
Exterior wall/Roof flashing installed and sealed.
Terminations installed and sealed.

Electrical Section 8 (Pg 44-45)
Unswitched power (110-120 VAC) provided to the appliance.
Switch wires properly installed.

Gas Section 9 (Pg 47-48)
Proper appliance for fuel type.
Was a conversion performed?
Leak check performed and inlet pressure verified.
Verified proper air shutter setting for installation type.

Finishing Section 10 (Pg 49-50)
Combustible materials not installed in non-combustible areas.
Verified all clearances meet installation manual requirements.
Mantels and wall projections comply with installation manual requirements.

Appliance Setup Section 11 (Pg 51-53)
All packaging and protective materials removed (inside & outside of appliance).
Refractories, logs, mineral wool, and lava rock installed correctly.
Glass assembly installed and secured.
Accessories installed properly.
Decorative front properly installed.
Manual bag and all of its contents are removed from inside/under the appliance and given to party responsible for use and operation.
Started appliance and verified no gas leaks exist.

Hearth & Home Technologies recommends the following:

  • Photographing the installation and copying this checklist for your file.
  • That this checklist remain visible at all times on the appliance until the installation is complete.

Comments: Further description of the issues, who is responsible (Installer/ Builder/ Other Trades, etc) and corrective action needed


Comments Communicated to party responsible ____ by __on ___
(Builder / Gen. Contractor/) (Installer) (Date)
= Contains updated information.
2382-982 Rev. E 1/23

Product Specific and Important Safety Information

A. Appliance Certification
MODELS: NDV3630I-B, NDV3630IL-B,
NDV3933I-B, NDV3933IL-B
NDV4236I-B, NDV4236IL-B,
NDV4236I-NVR ,
NDV4842I-B, NDV4842IL-B
LABORATORY: Underwriters Laboratories, Inc. (UL)
TYPE: Direct Vent Heater
STANDARD: CSA / ANSI Z21.88-2019 • CSA 2.33-2019
This product is listed to ANSI standards for “Vented Gas Fireplace Heaters” and applicable sections of “Gas Burning Heating Appliances for Manufactured Homes and Recreational Vehicles”, and “Gas Fired Appliances for Use at High Altitudes”.
NOTICE: This installation must conform with local codes.
In the absence of local codes you must comply with the National Fuel Gas Code, ANSI Z223.1-latest edition in the U.S.A. and the CAN/CGA B149 Installation Codes in Canada.
NOT INTENDED FOR USE AS A PRIMARY HEAT SOURCE.
This appliance is tested and approved as either supplemental room heat or as a decorative appliance. It  should not  be  factored as primary heat in residential heating calculations.
B. Glass Specifications
Hearth & Home Technologies appliances manufactured with tempered glass may be installed in hazardous locations such as bathtub enclosures as defined by the Consumer Product Safety Commission (CPSC). The  tempered glass has been tested and certified to the requirements of ANSI Z97.1 and CPSC 16 CFR 1202 (Safety Glazing Certification Council SGCC# 1595 and 1597. Architectural Testing, Inc. Reports 02-31919.01 and 02-31917.01).
This statement is in compliance with CPSC 16 CFR Section 1201.5 “Certification and labeling requirements” which refers to 15 U.S. Code (USC) 2063 stating “… Such certificate shall accompany the product or shall otherwise be furnished to any distributor or retailer to whom  the product is delivered.”
Some local building codes require the use of tempered glass with permanent marking in such locations. Glass meeting this requirement is available from the factory. Please contact your dealer or distributor to order.
C. BTU Specifications

Models (U.S. or Canada)| Maximum Input BTU/h| Minimum Input BTU/h| **Orifice Size (DMS)
---|---|---|---
NDV3630I-B (NG)| (0-2000 FT)| 20,000| 14,000| .083 in.
NDV3630IL-B (Propane)| (0-2000 FT)| 18,500| 13,500| 1.25 mm
NDV3933I-B (NG)| (0-2000 FT)| 22,000| 15,000| #43
NDV3933IL-B (Propane)| **
(0-2000 FT)| 20,000| 14,500| ****

55

NDV4236I-B (NG)| (0-2000 FT)| 25,000| 17,000| #42
NDV4236IL-B (Propane)| (0-2000 FT)| 24,000| 17,000| #54
NDV4236I-NVR (NG)| (0-2000 FT)| 25,000| 17,000| #42
NDV4236I-NVR (Propane)| (0-2000 FT)| 24,000| 17,000| #54
NDV4842I-B (NG)| (0-2000 FT)| 27,500| 19,500| #39
NDV4842IL-B (Propane)| (0-2000 FT)| 26,500| 18,500| #53

D. High Altitude Installations
NOTICE: If the heating value of the gas has been reduced, these rules do not apply. Check with your local gas utility or authorities having jurisdiction. When installing above 2000 feet elevation:

  • In the USA: Reduce input rate 4% for each 1000 feet above 2000 feet.
  • In CANADA: Input ratings are certified without a reduction of input rate for elevations up to 4500 feet (1370 m) above sea level. Please consult provincial and/or local authorities having jurisdiction for installations at elevations above 4500 feet (1370 m).
    Check with your local gas utility to determine proper orifice size.

E. Non-Combustible Materials Specification
Material which will not ignite and burn. Such materials are those consisting entirely of steel, iron, brick, tile, concrete, slate, glass or plasters, or any combination thereof.
Materials that are reported as passing ASTM E 136, Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750 ºC shall be considered non-combustible materials.
F. Combustible Materials Specification
Materials made of or surfaced with wood, compressed paper, plant fibers, plastics, or other material that  can ignite and burn, whether flame proofed or not, or plastered or unplastered shall be considered combustible materials.
G. Electrical Codes
NOTICE: This appliance must be electrically wired and grounded in accordance with local codes or, in the absence of local codes, with National Electric Code ANSI/NFPA 70-latest edition or the Canadian Electric Code CSA C22.1.

  • A 110-120 VAC circuit for this product must be protected with ground-fault circuit-interrupter protection, in  compliance with the applicable electrical codes, when it is installed in locations such as in bathrooms or near sinks.

H. California

WARNING: This product and the fuels used to operate this product (liquid propane or natural gas), and the products of combustion of such fuels, can expose you to chemicals including benzene, which is known to the State of California to cause cancer and reproductive harm. For more information go to: www.P65Warnings.ca.gov.
Note: The following requirements reference various Massachusetts and national codes not contained in this document.
I. Requirements for the Commonwealth of Massachusetts
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not  limited to decks and porches, the following requirements shall be satisfied:
Installation of Carbon Monoxide Detectors
At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gas fitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gas fitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side
wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accordance with the above provisions shall  complywith NFPA720 and be ANSI/UL 2034 listed and IAS certified.
Signage
A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fu- eled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) in. in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
Inspection
The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
Exemptions
The following equipment is exempt from 248 CMR 5.08(2) (a)1 through 4:

  • The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
  • Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.

MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

  • Detailed instructions for the installation of the venting system design or the venting system components; and
  • A complete parts list for the venting system design or venting system.

Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:

  • The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and
  • The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.

A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equip- ment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
See Gas Connection section for additional Commonwealth of Massachusetts requirements.

Getting Started

A. Design and Installation Considerations
WARNING! Risk of Fire or Explosion! Read all instructions before starting the installation.
Heatilator direct vent gas appliances are designed to operate with all combustion air siphoned from outside of the  building and all exhaust gases expelled  tothe outside. No additional outside air source is required.
Installation MUST comply with local, regional, state and national codes and regulations. Consult insurance carrier, local building inspector, fire officials or authorities having jurisdiction over restrictions, installation inspection and permits.

Before installing, determine the following:

  • Where the appliance is to be installed.
  • The vent system configuration to be used.
  • Gas supply piping requirements.
  • Provisions for optional heat management system.
  • Electrical wiring requirements.
  • Framing and finishing details.
  • Whether optional accessories—devices such as a fan, wall switch, or remote control—are desired.

Installation and service of this appliance should be performed by qualified personnel. Hearth & Home Technologies recommends HHT Factory Trained or NFI certified professionals.

heatilator - logo1

Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. For assistance or additional information, consult a qualified service technician, service agency or your dealer.
B. Good Faith Wall Surface

If installing a television (TV) above the appliance, see Section 3 of the appliance Owner’s Manual.
NOTICE: Surface temperatures listed above are taken with a temperature measuring probe as prescribed by the test standard used for appliance certification. Temperatures on walls or mantels taken with an infrared thermometer may yield increased temperatures of up to 30 °F (17 °C) or more depending on the thermometer settings and material characteristics being measured. Use appropriate finishing materials that are able to withstand these conditions. For additional finishing guidelines, see Section 10.
C. Tools and Supplies Needed
Before beginning the installation be sure that the following tools and building supplies are available.

Hand Tools Tape measure
Level Framing material
Manometer Framing square
Voltmeter Electric drill and bits (1/4 in.)
Plumb line Safety glasses/Gloves
Wrenches Reciprocating saw

1/4 in. nut driver
Non-corrosive leak check solution 1/2 – 3/4 in. length, #6 or #8 Self-drilling screws Caulking material (300 ºF minimum continuous exposure rating)

D. Inspect Appliance and Components
WARNING! Risk of Fire or Explosion! Damaged parts
could impair safe operation. DO NOT install damaged, incomplete or substitute components. Keep appliance dry.
WARNING! Risk of Fire, Explosion or Electric Shock!
DO NOT use this appliance if any part has been under water. Call a qualified service technician to inspect the appliance and to replace any part of the control system and/or gas control which has been under water.

  •  Carefully remove the appliance and components from the packaging.
  • The vent system components and decorative barrier fronts may be shipped in separate packages.
  •  If packaged separately, the log set and appliance grate must be installed.
  • Report to your dealer any parts damaged in shipment.

Hearth & Home Technologies disclaims any responsibility for, and the warranty will be voided by, the following actions:

  • Installation and use of any damaged appliance or vent system component.
  • Modification of the appliance or vent system.
  • Installation other than as instructed by Hearth & Home Technologies.
  • Improper positioning of the logs/media (as applicable) or the glass assembly.
  •  Installation and/or use of any component part not approved by Hearth & Home Technologies.

Framing and Clearances

A. Appliance/Decorative Front Dimension Diagrams
Dimensions are actual appliance dimensions. Use for reference only. For framing dimensions and clearances refer to Section 5.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Dimension
Diagrams

Appliance Dimensions Table

| NDV3630I-B/ NDV3630IL-B| NDV3633I-B/ NDV3633IL-B| NDV4236I-B/NDV4236IL-B/ NDV4236I-NVR| NDV4842I-B/ NDV4842IL-B
---|---|---|---|---
Location| Inches| Millimeters| Inches| Millimeters| Inches| Millimeters| Inches| Millimeters
A| 35| 889| 38| 965| 41| 1041| 47| 1194
B| 30| 762| 33| 838| 36| 916| 42| 1067
C| 6-3/8| 162| 6-3/8| 162| 6-3/8| 162| 6-3/8| 162
D| 19-7/8| 505| 19-7/8| 505| 19-7/8| 505| 19-7/8| 505
E| 26-5/8| 676| 29-5/8| 752| 32-5/8| 829| 38-5/8| 981
F| 31-1/2| 800| 31-1/2| 800| 31-1/2| 800| 31-1/2| 800
G| 35-1/4| 895| 35-1/4| 895| 35-1/4| 895| 35-1/4| 895
H| 15-3/4| 400| 15-3/4| 400| 15-3/4| 400| 15-3/4| 400
I| 1-3/4| 44| 1-3/4| 44| 1-3/4| 44| 1-3/4| 44
J| 23-1/2| 597| 23-1/2| 597| 23-1/2| 597| 23-1/2| 597
K| 39-1/2| 1003| 39-1/2| 1003| 39-1/2| 1003| 39-1/2| 1003
L| 3| 76| 3| 76| 3| 76| 3| 76
M| 6-1/2| 165| 6-1/2| 165| 6-1/2| 165| 6-1/2| 165
N| 34-1/2| 876| 34-1/2| 876| 34-1/2| 876| 34-1/2| 876
O| 8-5/8| 219| 11-5/8| 295| 14-5/8| 371| 20-5/8| 524
P| 4-3/8| 110| 5-7/8| 148| 7-3/8| 186| 10-3/8| 262
Q| 11-5/8| 295| 11-5/8| 295| 11-5/8| 295| 11-5/8| 295
R| 19-1/8| 486| 19-1/8| 486| 19-1/8| 486| 19-1/8| 486
S| 2-3/8| 60| 2-3/8| 60| 2-3/8| 60| 2-3/8| 60
T| 8| 203| 8| 203| 8| 203| 8| 203

Figure 3.1 Appliance Dimensions
B. Decorative Barrier Front Dimensions Diagram
SIMON DECORATIVE BARRIER FRONTS
IMPORTANT! This fireplace requires an installed decorative barrier front to prevent direct contact with the hot viewing glass. DO NOT operate the fireplace with the barrier removed.
Decorative barrier front must be ordered at time of fireplace purchase. If decorative barrier front is not present, contact dealer.
Note: See Section 10 for hearth, mantel and finishing requirements.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -
Decorative

| | A| B| C| D| E| F| G
---|---|---|---|---|---|---|---|---


SIM-3630

| in.| 28-3/8| 21| 29-7/8| 1-5/8| 2-3/8| 30| 31-1/2
mm| 721| 533| 759| 41| 60| 762| 800


SIM-3933

| in.| 31-3/8| 21| 32-7/8| 1-5/8| 2-3/8| 30| 31-1/2
mm| 797| 533| 835| 41| 60| 762| 800


SIM-4236

| in.| 34-3/8| 21| 35-7/8| 1-5/8| 2-3/8| 30| 31-1/2
mm| 873| 533| 911| 41| 60| 762| 800


SIM-4842

| in.| 40-3/8| 21| 41-7/8| 1-5/8| 2-3/8| 30| 31-1/2
mm| 1026| 533| 1064| 41| 60| 762| 800

Figure 3.2 Decorative Front Dimensions – SIMON-B
C. Appliance Location and Clearances to Combustibles

When selecting a location for the appliance it is important to consider the required clearances to walls. See Figure 3.6 below and Figure 3.7 on next page.
WARNING! Risk of Fire or Burns! Provide adequate clearance around air openings and for service access. Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.
NOTICE: Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY. Illustrations/diagrams are not drawn to scale. Actual installation may vary due to individual design preference.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Horiz
Term

NOTE: Consider the mantel or cabinet system to be installed and comply with the necessary requirements for elevated hearth.
Refer to instructions included with cabinet system.

Models A B C D E F G H
NDV3630I-B NDV3630IL-B in. 36 33-1/2 19-5/8 43-3/8 47 53-1/4 37
mm 914 851 498 1102 1194 1353 940 216
NDV3933I-B NDV3933IL-B in. 39 35-1/2 19-5/8 43-3/8 47 53-1/4 40
mm 991 902 498 1102 1194 1353 1016 241
NDV4236I-B NDV4236IL-B NDV4236I-NVR in. 42 37-5/8 19-5/8 43-3/8 47
53-1/4 43 10-5/8
mm 1067 956 498 1102 1194 1353 1092 270
NDV4842I-B NDV4842IL-B in. 48 41-7/8 19-5/8 N/A 47 53-1/4 49
mm 1219 1064 498 N/A 1194 1353 1245 324

Figure 3.3 Appliance Locations – Part 1, Columns A-H (For Columns I-L, See Figure 3.4)

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Horiz
Term1

NOTE: Consider the mantel or cabinet system to be installed and comply with the necessary requirements for elevated hearth. Refer to instructions included with cabinet system.

Models I J K L
NDV3630I-B NDV3630IL-B in. 47-3/8 66-1/2 75-3/8
mm 1204 1689 1915 1559
NDV3933I-B NDV3933IL-B in. 50-1/4 66-1/2 75-3/8
mm 1277 1689 1915 1559
NDV4236I-B NDV4236IL-B NDV4236I-NVR in. 53-1/4 66-1/2 75-3/8
mm 1353 1689 1915 1559
NDV4842I-B NDV4842IL-B in. 59-1/4 66-1/2 75-3/8
mm 1505 1689 1915

1559

Figure 3.4 Appliance Locations – Part 2, Columns I-L
Note: If the inside of the framed cavity is to be finished, the framing dimensions must include the finished surface. If drywall is to be attached to the rear wall, the depth must be measured from the drywall surface.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Horiz
Term2

* MINIMUM FRAMING DIMENSIONS|
---|---


NDV MODEL (NG/PROPANE)

| | A| B| C**| D| D
Rough Opening (Width)| Rough Opening (Height)| Rough Opening (Depth)| Rough Opening (DVP Pipe)| Rough Opening (SLP Pipe)
NDV30-IFT| in.| 36| 34-7/8| 19-5/8| 10| 9
mm| 914| 886| 498| 254| 229
NDV33-IFT| in.| 39| 34-7/8| 19-5/8| 10| 9
mm| 991| 886| 498| 254| 229
NDV36-IFT NDV36-IFT-NVR| in.| 42| 34-7/8| 19-5/8| 10| 9
mm| 1067| 886| 498| 254| 229
NDV42-IFT| in.| 48| 34-7/8| 19-5/8| 10| 9
mm| 1219| 886| 498| 254| 229

Elevated Hearth Systems
Some hearth systems will elevate the appliance off the floor at a given dimension. The elevation will also have to be added to the following: Wall penetration referenced in Figure 5.2 (Wall penetration) and Rough Opening Height (header height) referenced in Figure 3.5. Note: Finished floor thickness should also be considered when determining installa- tion dimensions.

  • Adjust framing dimensions for interior sheathing (such as sheetrock)
    C Add 11-1/2 inches for rear vented elbow vented directly off the rear of the appliance.
    Figure 3.5 Clearances to Combustibles
    D. Constructing the Appliance Chase
    NOTICE: Install appliance on hard metal or wood surfaces extending full width and depth. DO NOT install directly on carpeting, vinyl, or any combustible material other than wood.
    WARNING!** Risk of Fire! Maintain specified air space clearances to appliance and vent pipe:

    • Insulation and other materials must be secured to prevent accidental contact.
    • The chase must be properly blocked to prevent blown insulation or other combustibles from entering and making contact with fireplace or chimney.
    • Failure to maintain airspace may cause overheating and a fire.

A chase is a vertical box-like structure built to enclose the gas appliance and/or its vent system. In cooler climates the vent should be enclosed inside the chase.
NOTICE: Treatment of ceiling firestops and wall shield firestops and construction of the chase may vary with the type of building. These instructions are not substitutes  for the requirements of local building codes. Therefore,you MUST check local building codes to determine the requirements to these steps.
NOTICE: Where required by code, install only sprinklerheads with a sprinkler activation temperature classifiedas Extra High.

  • Sprinklers inside of chase: Keep sprinkler head away from vent and chimney.
  • Heat Management applications: Maintain 36 inches of clearance to openings from which heat is discharged such as convection slots, heat zone registers, etc. Refer to Section 6.B for Heat Management options allowed for this appliance.

Chases should be constructed and insulated in the same manner as the thermal envelope of the home based on the code requirements for that climate zone to prevent air leakage and draft problems. The chase is an extension of the building thermal envelope.
To further prevent drafts and air leakage, the wall shield and ceiling firestops should be sealed with caulk with a minimum of 300 ºF continuous exposure rating to seal gaps. Gas line holes and other openings should be sealed with caulk with a minimum of 300 ºF continuous exposure rating or stuffed with unfaced insulation. If the appliance is being installed on a cement surface, a layer of plywood may be placed underneath to prevent conducting cold up into the room.
Minimum height requirements for an exterior chase on a topvented appliance are shown in Figure 3.6. Reference Figure 4.4 for additional clearances.
heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Horiz
Term3 NOTE: If overhang (Dim. A) is less than 2 inches, clearance from top of termination cap to bottom of overhang (Dim. B) may be 0 inches. Dimension A is measured from the edge of the overhang to the surface the termination cap is mounted to.
Figure 3.6 Exterior Chase – Minimum Height Requirements
E. Floor Protection

Vinyl Flooring
Vinyl flooring is sensitive to heat. Hearth and Home Technologies does not recommend adhesive based vinyl flooring due to thermal expansion. Floating- style flooring can be used, but will reach temperatures up to 110 °F in a room with ambient temperature of 70 °F. Consult flooring specifications to ensure compatibility.

Termination Location and Vent Information

A. Approved Pipe
WARNING! Risk of Fire, Delayed Ignition or Asphyxiation.
This appliance requires a separate vent. DO NOT vent to a pipe serving any other appliance.
This appliance is only approved for use with Hearth & Home Technologies DVP or SLP venting systems. Refer to Section 12.A for vent component information and dimensions.Only use listed decorative termination caps/shrouds with Hearth & Home  echnologies approved venting systems DO NOT mix pipe, fittings or joining methods from different manufacturers. The pipe is tested to be run inside an enclosed wall. There is no requirement for inspection openings at each joint within the wall.
B. Vent Termination Minimum Clearances

WARNING

Fire Risk.
Maintain vent clearance to combustibles as specified.

  • DO NOT pack air space with insulation or other materials.
    Failure to keep insulation or other materials away from vent pipe could cause overheating and fire.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Horiz
Term4

Roof Pitch                                                            H (Min.) Ft
Flat to 6/12…………………………………………………..1.0
Over 6/12 to 7/12 ………………………………………….1.25

Over 7/12 to 8/12 ………………………………………….1.5
Over 8/12 to 9/12 ………………………………………….2.0

Over 9/12 to 10/12 ………………………………………..2.5*
Over 10/12 to 11/12 ………………………………………3.25
Over 11/12 to 12/12 ………………………………………4.0
Over 12/12 to 14/12 ………………………………………5.0
Over 14/12 to 16/12 ………………………………………6.0
Over 16/12 to 18/12 ………………………………………7.0
Over 18/12 to 20/12 ………………………………………7.5
Over 20/12 to 21/12 ………………………………………8.0

  • H minimum may vary depending on regional snowfall.
    Refer to local codes.
    Figure 4.1 Minimum Height From Roof to Lowest Discharge Opening
A B
6 in. (minimum) up to 20 in.  152 mm/508 mm 18 in. minimum  457 mm
20 in. and over 0 in. minimum

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -Wood or Fuel
Oil

  • If using decorative cap cover(s), this distance may need to be increased. Refer to the installation instructions supplied with the decorative cap cover.
    If two gas terminations are present, they may be level (B = 0 inches) provided A is a minimum of 6 inches.
    Figure 4.2 Staggered Termination Caps**

CAUTION! Risk of Burns! Termination caps are HOT, consider proximity to doors, traffic areas or where people may pass or gather (sidewalk, deck, patio, etc.). Listed cap shields available. Contact your dealer.

  • Local codes or regulations may require different clearances.
  • Hearth & Home Technologies assumes no responsibility for the improper performance of the appliance when the venting system does not meet these requirements.
  • Vinyl protection kits are suggested for use with vinyl siding.
  • Measure horizontal and vertical termination cap clearances as noted in Figure 4.3.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Wood or Fuel
Oil1

C. Vent Terminal Clearances

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Vent
Terminal

U.S.A. Installations: In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code.
Canadian Installations: In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.

| U.S.A.| CANADA
---|---|---
A| Clearance above grade,veranda, porch, deck, or balcony| 12 in. (305 mm)| 12 in. (305 mm)
B| Clearance to window or door that may be opened, or to permanently closed window| 9 in. (229 mm)| 12 in. (305 mm)

C

| clearance below unventilated soffit| 12 in. (305 mm)| 12 in. (305 mm)
clearance below ventilated soffit| 18 in. (457 mm)| 18 in. (457 mm)
clearance below any vinyl soffits and electrical service| 30 in. (762 mm)| 30 in. (762 mm)
D| clearance to outside corner| 6 in. (152 mm)| 6 in. (152 mm)
E| clearance to inside corner| 6 in. (152 mm)| 6 in. (152 mm)

F

| not to be installed above a gas meter/regulator assembly within 3 feet horizontally from the center-line of the regulator|

3 ft (914 mm)

|

3 ft (914 mm)

G| clearance to gas service regulator vent outlet| 3 ft (914 mm)| 3 ft (914 mm)

H

| clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance termination (mechanical or non-mechanical)|

9 in. (229 mm)

|

12 in. (305 mm)

I

| clearance to a mechanical (powered) air supply inlet
***(All mechanical air intakes within 10 feet of a horizontal termination cap must be a minimum of 3 feet below termination.)|

3 ft (914 mm)***

|

6 ft (1.8 m)

J

| On public property: clearance above paved sidewalk or a paved driveway.|

7 ft (2.1 m)

|

7 ft (2.1 m)**

**(A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.)

K

| clearance from sides of electrical service| 6 in. (152 mm)| 6 in. (152 mm)
Location of the vent termination must not interfere with access to the electrical service.

L

| clearance above electrical service| 12 in. (305 mm)| 12 in. (305 mm)
Location of the vent termination must not interfere with access to the electrical service.

M

| clearance under veranda, porch, deck, balcony or overhang
*(Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.)|  

12 in. (305 mm)

|

12 in. (305 mm)*

vinyl or composite overhang| 30 in. (762 mm)| 30 in. (762 mm)

Figure 4.4 Minimum Clearances for Termination

D. Use of Elbows
Diagonal runs have both vertical and horizontal vent aspects when calculating the effects. Use the rise for the vertical aspect and the run for the horizontal aspect. See
Figure 4.5.
Two 45º elbows may be used in place of one 90º elbow.
On 45º runs, one foot of diagonal is equal to 8-1/2 in. (216 mm) horizontal run and 8-1/2 in. (216 mm) vertical run. A length of straight pipe is allowed between two 45º elbows.
See Figure 4.5.
Figure 4.6 shows the vertical and horizontal offsets for DVP or SLP elbows.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Vent
Terminal1

SLP

Pipe

| Effective Length| Rise/Run
---|---|---
Inches| Millimeters| Inches| Millimeters
SLP4| 4| 102| 2-3/4| 70
SLP6| 6| 152| 4-1/4| 108
SLP12| 12| 305| 8-1/2| 216
SLP24| 24| 610| 17| 432
SLP36| 36| 914| 25-1/2| 648
SLP48| 48| 1219| 34| 864
SLP6A| 3 to 6| 76 to 152| 2-1/8-4-1/4| 54-108
SLP12A| 3 to 12| 76 to 305| 2-1/8-8-1/2| 54-216
DVP

Pipe

| Effective Length| Rise/Run
---|---|---
Inches| Millimeters| Inches| Millimeters
DVP4| 4| 102| 2-3/4| 70
DVP6| 6| 152| 4-1/4| 108
DVP12| 12| 305| 8-1/2| 216
DVP24| 24| 610| 17| 432
DVP36| 36| 914| 25-1/2| 648
DVP48| 48| 1219| 34| 864
DVP6A| 3 to 6| 76 to 152| 2-1/8-4-1/4| 54-108
DVP12A| 3 to 12| 76 to 305| 2-1/8-8-1/2| 54-216

Figure 4.5

Vent
Type
| X| Y
---|---|---
Inches| Millimeters| Inches| Millimeters
DVP| 6-5/8| 168| 16-1/2| 419
SLP| 5-1/4| 133| 11-3/8| 289

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Vent
Terminal3

Vent Type X
Inches Millimeters
DVP 16-1/4
SLP 11-1/4

Figure 4.6 Vertical and Horizontal Offset for DVP and SLP Elbows
Note: Back to back 45 degree or 90 degree elbows have no additional vertical or horizontal value and are not included in determining maximum vent run lengths.
E. Vent Diagrams

General Rules:

  • A maximum of three 90º elbows (or six 45º elbows) may be used in any vent configuration. Some elbows may be installed horizontally. See Figure 4.15.
  • A maximum of four 90º elbows (or eight 45º elbows) may be used in a top vented, vertically terminated vent configuration. See Figure 4.22.
  • Elbows may be placed back to back anywhere in the system.
  • Any 90º elbow may be replaced with two back to back 45º elbows.
  • When penetrating a combustible wall, a wall shield firestop must be installed.
  • When penetrating a combustible ceiling, a ceiling firestop must be installed.
  • Horizontal runs of vent do not require vertical rise;  horizontal runs may be level.
  • When the horizontal termination cap is exposed to high precipitation, the cap should have a 1/4 inch downward slant to allow any moisture in cap to be released. See Figure 4.7. See Figure 4.8 for additional water infiltration prevention information.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Vent
Terminal4

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -Exterior
Chase

Measuring Standards

Vertical and horizontal measurements listed in the vent diagrams were made using the following standards:

  • Pipe measurements are shown using the effective length of pipe. See Section 12.A (Figure 12.1 for DVP, Figure 12.9 for SLP) for information on effective length of pipe components.
  • Horizontal terminations are measured to the outside  mounting surface (flange of termination cap) (see Figure 4.9).
  • Vertical terminations are measured to top of last section of pipe. See Figure 4.10.
  • Horizontal pipe installed level with no rise.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -Exterior
Chase1

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -Exterior
Chase2

Figure 4.11 Measure Horizontal and Vertical Termination Clearance to Trapezoid Portion of Cap
Note: The NDV series appliances can adapt to SLP series vent pipe when venting off the top of the appliance. You must use a DVP-SLP24 adapter or a DVP-2SL and two feet of SLP pipe which can only be attached to the appliance starting collar.
When looking at horizontal termination diagrams, neither adapter is counted as part of the minimum vertical (V1 min.) requirements.
All venting rules for the vent run must still be followed.
Top Vent – Horizontal Termination
Top Vent—Horizontal Termination—Two 45º Elbows Installation requirements to replace the first 90º elbow with two 45º elbows:

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -Exterior
Chase3

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -Exterior
Chase4

Top Vent – Horizontal Termination
One Elbow

**V 1 Minimum| HMaximum NDV3630I-B NDV3933I-B NDV4236I-B NDV4236I-NVR| ****H 1 Maximum NDV4842I-B
---|---|---
0| 0| 24 in.| 610 mm| 18 in.| 457 mm
4 in.| 102 mm| 4 ft.| 1.22 m| 4 ft.| 1.22 m
6 in.| 152 mm| 6 ft.| 1.83 m| 6 ft.| 1.83 m
12 in.| 305 mm| 11 ft.| 3.35 m| 11 ft.| 3.35 m
18 in.| 457 mm| 18 ft.| 5.49 m| 18 ft.| 5.49 m
24 in.| 610 mm| 25 ft.| 7.62 m| 25 ft.| 7.62 m
–| –| 25 ft.| 7.62 m| 25 ft.| 7.62 m
V 1 + H 1 = 50 ft. (15.24 m) Maximum
* You may install the elbow directly on top of the appliance (DVP only).

NOTE: A minimum venting scenario consists of a 90 degree elbow off the top of the appliance with a DVP-TRAP2 horizontal termination cap.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -Exterior
Chase5

Top Vent – Horizontal Termination (continued)
Two or Three Elbows Installed Horizontally

V 1 Minimum H 1 + H 2 Maximum H 1 + H2 + H3 Maximum
6 in. 152 mm 6 ft.
12 in. 305 mm 11 ft.
18 in. 457 mm 18 ft.
24 in. 610 mm 25 ft.

V 1 + H 1 + H 2 = 50 ft. (15.24 m) Maximum
V 1 + H 1 + H 2 + H 3 = 47 ft. (14.33 m) Maximum

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -Exterior
Chase6

Top Vent – Horizontal Termination (continued)
Three Elbows

V 1 min.| V 1 +V 2 max.| H 1 +H 2 max.| heatilator NDV3630I-B Novus Direct Vent Fireplace Series
-Exterior Chase7
---|---|---|---
12 in./305 mm| 24 ft/7.32 m (DVP)|

**** 19 ft/5.79 m

12 in./305 mm| 22 ft/6.71 m (SLP)| **** 19 ft/5.79 m
**Elbows Installed Vertically**

Top Vent – Vertical Termination
Two Elbows

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Two
Elbows

Install Top Vent Flue Visor – No Elbow Configurations

  • Remove screws holding flue visor to firebox top. See Figure 4.18.
  • Remove the flue visor.
  • Using the screws removed and the same holes, install the top vent flue baffle and flue visor.
    – The top vent flue baffle will be turned to install below the level of the firebox top for 12-30 ft. vertical runs of vent. See Figure 4.19.
    – The top vent flue baffle will be turned to install inside for 31-60 ft. vertical runs of vent. See Figure 4.20.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Two
Elbows1

Top Vent – Vertical Termination (continued)
Three Elbows

Top Vent – Vertical Termination (continued) Four Elbows

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Two
Elbows3

Rear Vent – Horizontal Termination
No Elbow
Note:
Use DVP Series components only.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Two
Elbows4

| H 1 Maximum
---|---
NDV3630I-B NDV3933I-B NDV4236I-B NDV4236I-NVR| 18 in.| 457 mm
NDV4842I-B| 12 in.| 305 mm

One 45° Elbow
Note: Use DVP Series components only.
WARNING! Risk of Fire! This vent configuration is not allowed with NDV4842I-B/NDV4842IL-B

| H 1 Maximum
---|---
NDV3630I-B NDV3933I-B NDV4236I-B NDV4236I-NVR| 9 in.| 229 mm
NDV4842I-B|

NOT ALLOWED

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Two
Elbows5

Rear Vent – Horizontal Termination (continued) Two Elbows

V 1 Minimum H 1 Maximum H Total
1 ft. 305 mm 2 ft.
2 ft. 610 mm 4 ft.
3 ft. 914 mm 6 ft.
4 ft. 1.2 m 8 ft.
5 ft. 1.5 m 8 ft.
6 ft. 1.8 8 ft.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Two
Elbows6

Three Elbows

V 1 Minimum H 1 Maximum H Total
1 ft. 305 mm 2 ft.
2 ft. 610 mm 4 ft.
3 ft. 914 mm 6 ft.
4 ft. 1.2 m 8 ft.
5 ft. 1.5 m 8 ft.
6 ft. 1.8 8 ft.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Two
Elbows7

Rear Vent – Vertical Termination
One Elbow

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Two
Elbows8

Two Elbows

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Two
Elbows9

Rear Vent – Vertical Termination – (continued)
Three Elbows

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Two
Elbows10

Vent Clearances and Framing

A. Pipe Clearances to Combustibles
WARNING! Risk of Fire! Maintain air space clearance to vent. DO NOT pack insulation or other combustibles:

  • Between ceiling firestops
  • Between wall shield firestops
  • Around vent system

Failure to keep insulation or other material away from vent pipe could cause overheating and fire.

Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm).

  • DVP heat shield – designed to be used on a wall 4 in. to 7-1/4 in. (102 mm to 184 mm) thick.
  • If wall thickness is less than 4 in. the existing heat shields must be field trimmed. If wall thickness is greater than 7-1/4 in. a DVP-HSM-B will be required.
  • SLP heat shield – designed to be used on a wall 4-3/8 in. to 7-5/8 in. (111 mm to 194 mm thick).
  • If wall thickness is less than 4-3/8 the existing heat shields must be field trimmed.
    If wall thickness is greater than 7-5/8 in. a DVP-HSM-B will be required.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Two
Elbows11

  • When using SLP pipe, minimum clearances from the vent pipe to combustible materials at inside wall firestops are:
    Top: 2-1/2 in. (64 mm)
    Bottom: 1/2 in. (13 mm)
    Sides: 1 in. (25 mm)
    Figure 5.1 Horizontal Venting Clearances To Combustible Materials
    B. Wall Penetration Framing/Firestops
    Combustible Wall Penetration
    Whenever a combustible wall is penetrated, you must frame a hole for the wall shield firestop(s). The wall shield firestop maintains minimum clearances and prevents cold air infiltration.

    • The opening must be framed on all four sides using the same size framing materials as those used in the wall construction.
    • SLP pipe – A wall shield firestop must be placed on each side of an interior wall. A minimum 1-1/2 in. (38 mm) overlap of attached heat shields must be maintained.
    • DVP pipe – A wall shield firestop is required on one side only on interior walls. If your local inspector requires a wall shield firestop on both sides, then both wall shield firestops must have a heat shield (refer to Section 12.A.) attached to them.
    • See Section 7.F. for information for regarding the installation of a horizontal termination cap.

Non-Combustible Wall Penetration
If the hole being penetrated is surrounded by non-combustible materials such as concrete, a hole with diameter one inch greater than the pipe is acceptable. Whenever a non-combustible wall is penetrated, the wall shield firestop is only required on one side and no heat shield is necessary.
If your local inspector requires the wall shield firestop on both sides, then both wall shield firestops must have a heat shield attached to them.
heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Two
Elbows12

| A| B| C| D
---|---|---|---|---
Inches| 40-1/2| 24-1/2| 39-1/2| 23-1/2

  • Shows center of vent framing hole for top or rear venting. The center of the hole is one (1) in. (25.4 mm) above the center of the horizontal vent pipe.
    Figure 5.2 Wall Penetration

C. Ceiling Firestop/Floor Penetration Framing
WARNING! Risk of Fire! DO NOT pack insulation around the vent. Maintain clearances tovent to prevent overheating.

A ceiling firestop MUST be used between floors and attics.

  • DVP pipe only – Frame an opening 10 in. by 10 in. (254 mm by 254 mm) whenever the vent penetrates a ceiling/floor (see Figure 5.3).
  • SLP pipe only – Frame opening 9 in. x 9 in. (229 mm x 229 mm) whenever the vent penetrates a ceiling/floor (see Figure 5.3).
  • Frame the area with the same sized lumber as used in ceiling/floor joist.
  • The ceiling firestop may be installed above or below the ceiling joists when installed with an attic insulation shield. It must be under joists between floors that are not insulated. Refer to Figure 5.4.
  • Secure in place with nails or screws.

D. Install Attic Insulation Shield

WARNING! Fire Risk. The use of an attic shield is required to prevent loose materials or insulation from contacting the vent causing overheating and a fire.
The International Fuel Gas Code requires an attic shield constructed of 26 gauge minimum steel that extends at least 2 in. (51 mm) above insulation.

  • Attic insulation shields must meet specified clearances to combustible materials and be secured in place.
  • An attic insulation shield kit is available from Hearth & Home Technologies. Contact your dealer to order. Install attic insulation shield according to instructions included with kit.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Two
Elbows13

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Two
Elbows14

Appliance Preparation

A. Vent Collar Preparation
CAUTION! Risk of Cuts, Abrasions or Flying Debris.
Wear protective gloves and safety glasses during installation. Sheet metal edges are sharp.
NOTICE: Once appliance is set up for top or rear venting,  it CANNOT be changed at a later time.
Top Vent

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Top
Vent

  • Remove the cover plate by removing the two screws holding it to the top of the appliance. Remove and discard the cover plate.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Top
Vent1

  • Remove the center insulation plug.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Top
Vent2

  • Cut the metal retaining band and fold the sides out.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Top
Vent3

  • Fold the center parts of the retaining band up and use to remove the vent cap.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Top
Vent4

  • Discard the vent cap, remove and discard the insulation basket from the inner vent pipe. Note: Once the vent cap has been removed it cannot be reattached. Remove insulation from outer vent pipe.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Top
Vent5

  • Attach the first vent section. It will snap into place.

Proceed to Section 6.B or 6.C.
Rear Vent
NOTICE: Once appliance is set up for top or rear venting, it CANNOT be changed at a later time.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Top
Vent6

  • Fold the tabs toward the center of the fire plug (90º) and remove the insulation gasket.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Top
Vent7

  • Cut the metal retaining band and fold the sides out.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Top
Vent8

  • Fold the center parts of the retaining band out and use to remove the vent cap.
    NOTICE: Once the vent cap has been removed it CANNOT be reattached.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Top
Vent9

  • Discard the vent cap, remove and discard the insulation basket.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Top
Vent10

  • Attach the first vent section (it will snap into place). Slide the insulation gasket onto the vent section, up against the appliance and over the tabs.

B. Securing and Leveling the Appliance
WARNING

Risk of Fire!
Prevent contact with:

  • Sagging or loose insulation
  •  Insulation backing or plastic
  • Framing and other combustible materials

DO NOT remove standoffs or notch the framing around the appliance standoffs.
Failure to maintain air space clearance could cause overheating and fire.
Block openings into the chase to prevent entry of blown-in insulation. Make sure insulation and other materials are secured.
The diagram shows how to properly position and secure the appliance. See Figure 6.12. Nailing tabs are provided to secure the appliance to the framing members.

  • Bend out nailing tabs on each side.
  • Place the appliance into position.
  • Keep nailing tabs flush with the framing.
  • Level the appliance from side to side and front to back.
  • Shim the appliance as necessary. It is acceptable to use wood shims underneath the appliance.
  • Secure the appliance to the framing by using nails or screws through the nailing tabs. Use a minimum of one fastener per nailing tab.
  • Optional: Secure the appliance to the floor by inserting two screws through the pilot holes at the bottom of the appliance.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Proper
Positioning

Venting and Chimneys

A. Assemble Vent Sections (DVP Pipe Only)

WARNING! Risk of Fire or Explosion! Vent sections MUST be installed correctly. Improperly installed vent sections could leak or cause appliance to overheat.
Attach Vent to the Firebox Assembly
Note: The end of the pipe sections with the lanced tabs will face toward the appliance.
Attach the first pipe section to the starting collar:

  • Lanced pipe end of the starting collar.
  • Inner pipe over inner collar.
  • Push the pipe section until all lanced tabs snap in place.
  • Lightly tug on pipe to confirm it has locked.

Requirement for Commercial, Multi-family (Multi-level exceeding two stories), or High-Rise Applications
WARNING! Risk of Fire or Explosion!
DO NOT break silicone seals on slip sections. Use care when removing termination cap from slip pipe. If slip section seals are broken during removal of the termination cap, vent could leak.
All outer pipe joints must be sealed using one of the methods below, including the slip section that connects directly to the horizontal termination cap.

  • Apply a bead of silicone sealant (300 ºF minimum continuous exposure rating) inside the female outer pipe joint prior to joining sections. See Figure 7.1 OR Apply a bead of silicone sealant (300 ºF minimum continuous exposure rating) to the outside of connecting joint after joining sections OR
    Apply aluminum foil tape (300 ºF minimum continuous exposure rating) to the outside of connecting joint after joining sections. On horizontal pipe runs, it is recommended that the tape seam is positioned on the bottom side of the vent pipe.

  • Only outer pipes need to be sealed. All unit collar, pipe, slip section, elbow and cap outer flues shall be sealed in this manner, unless otherwise stated.

Assemble Pipe Sections
Per Figure 7.2:

  • Start the inner pipe on the lanced end of section A into the flared end of section B.
  • Start the outer pipe of section A over the outer pipe of section B.
  • Once both vents sections are started, push firmly until all lanced tabs lock into place.
  • Lightly tug on the pipe to confirm the tabs have locked.

It is acceptable to use screws no longer than 1/2 in. (13 mm) to hold outer pipe sections together. If predrilling holes, DO NOT penetrate inner pipe.
For 90º and 45º elbows that are changing the vent direction  from horizontal to vertical, one screw minimum should beput in the outer flue at the horizontal elbow joint to prevent the elbow from rotating. Use screws no longer than 1/2 in. (13 mm). If predrilling screw holes, DO NOT penetrate inner pipe.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Proper
Positioning1

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -
Seams

Assemble Vent Sections (SLP Only)

To attach the first vent component to the starting collars of the appliance:

  • Attach a DVP-SLP24 adapter to the starting collar of the appliance.
  • Lock the vent components into place by sliding the pipe section onto the collar.
  • Align the seam of the pipe and seam of collar to allow engagement. Rotate the vent component to lock into place. Use this procedure for all vent components. See Figure 7.5.
  • Slide the gasket over the first vent section and place it flush to the appliance. This will prevent cold air infiltration.  Caulk with a minimum of 300 ºF continuous exposure rating may be used to hold the part in place.
  • Continue adding vent components, locking each succeeding component into place.
  • Ensure that each succeeding vent component is securely fitted and locked into the preceding component.

Required Commercial, Multi-family (Multi-level exceeding two stories), or High-Rise Applications
All outer pipe joints must be sealed with 100% silicone (300 ºF minimum continuous exposure rating), including the slip section that connects directly to the horizontal termination cap.

  • Apply a bead of silicone sealant (300 ºF minimum continuous exposure rating) inside the female outer pipe joint prior to joining sections. See Figure 7.1. OR
    Apply a bead of silicone sealant (300 ºF minimum continuous exposure rating) to the outside of connecting joint after joining sections OR Apply aluminum foil tape (300 ºF minimum continuous exposure rating) to the outside of connecting joint after joining sections. On horizontal pipe runs, it is recommended that the tape seam is positioned on the bottom side of the vent pipe.

  • Only outer pipes need to be sealed. All unit collar, pipe, slip section, elbow and cap outer flues shall be sealed in this manner, unless otherwise stated.

WARNING! Risk of Fire or Explosion! DO NOT break silicone seals on slip sections. Use care when removing termination cap from slip pipe. If slip section seals are broken during removal of the termination cap, vent could leak.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -
Components

B. Assemble Slip Sections

  • Slide the inner flue of the slip section into the inner flue of the pipe section and the outer flue of the slip section over the outer flue of the pipe section. See Figure 7.6.
  • Slide together to the desired length.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -
Components1

  • Maintain a 1-1/2 in. (38 mm) overlap between the slip section and the pipe section.
  • Secure the pipe and slip section with two screws no longer than 1/2 in. (13 mm), using the pilot holes in the slip section. See Figure 7.7.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -
Components2

  • Continue adding pipe as necessary following instructions in “Assembling Pipe Sections.”
    NOTICE: If slip section is too long, the inner and outer flues of the slip section can be cut to the desired length.
    NOTICE: When installing a vent system with an HRC termination cap, all pipe system joints shall be sealed using a high temperature silicone sealant (300 ºF minimum continuous exposure rating).

  • Apply a bead of silicone sealant (300 ºF minimum continuous exposure rating) inside the female outer pipe joint prior to joining sections.

  • Only outer pipes are sealed, sealing the inner flue is not required.

  • All unit collar, pipe, slip section, elbow and cap outer flues shall be sealed.

C. Secure the Vent Sections

  • Vertical runs originating off the top of the appliance, with  no offsets, must be supported every 8 ft. (2.44 m) afterthe maximum allowed 25 ft. (7.62 m) of unsupported rise.
  • Vertical runs originating off the rear of the appliance, or after any elbow, must be supported every 8 ft. (2.44 m).
  • Horizontal runs must be supported every 5 feet (1.52 m).
  • Vent supports or plumbers strap (spaced 120º apart) may be used to support vent sections. See Figures 7.8 and 7.9.
  • Wall shield firestops may be used to provide horizontal support to vent sections.
  • SLP ceiling firestops have tabs that may be used to provide vertical support.

WARNING! Risk of Fire, Explosion or Asphyxiation!
Improper support could allow vent to sag and separate.
Use vent run supports and connect vent sections per installation instructions. DO NOT allow vent to sag below connection point to appliance.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -
Components3

D. Disassemble Vent Sections

  • Rotate either section (see Figure 7.10) so the seams on both pipe sections are aligned as shown in Figure 7.11.
  • Pull carefully to separate the pieces of pipe.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -
Components4

E. Vertical Termination Requirements
Install and Seal Metal Roof Flashing

  • See minimum vent heights for various pitched roofs (Section 4, Figure 4.1) to determine the length of pipe to extend through the roof.
  • Slide the roof flashing over the pipe sections extending through the roof as shown in Figure 7.12.
  • Use an elastomeric or silicone sealant with a minimum of 150 ºF temperature rating to seal the metal roof flashing.

NOTICE: Failure to properly seal the roof flashing and pipe seams could permit entry of water.

  • Seal the gap between the roof flashing and the outside diameter of the pipe.
  • Seal the perimeter of the flashing where it contacts the roof surface. See Figure 7.12.
  • Seal the exposed pipe section seams that are located above the roof.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -
Components5

Assemble and Install Storm Collar
CAUTION! Risk of Cuts, Abrasions or Flying Debris.
Wear protective gloves and safety glasses during installation. Sheet metal edges are sharp.

  • Slide the storm collar onto the exposed pipe section and align brackets.
  • Insert a bolt (provided) through the brackets and install nut. Do not completely tighten.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -
Components6

  • Slide the assembled storm collar down the pipe section until it rests on the roof flashing (see Figure 7.13).
  • Tighten nut and make sure the collar is tight against the pipe section.
  • Seal around the top of the storm collar. See Figure 7.14.

Install Vertical Termination Cap

  • Attach the vertical termination cap by sliding the inner collar of the cap into the inner flue of the pipe section while placing the outer collar of the cap over the outer flue of the pipe section.
  • Secure the cap by driving three self-tapping screws (supplied) through the pilot holes in the outer collar of the cap into the outer flue of the pipe (see Figure 7.14).

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -
Components7

F. Horizontal Termination Requirements
Heat Shield Requirements for Horizontal
Termination
WARNING! Risk of Fire! To prevent overheating and fire, heat shields must extend through the entire wall thickness.

  • DO NOT remove the heat shields attached to the wall shield firestop and the horizontal termination cap (shown in Figure 7.15).
  • Heat shields must overlap 1-1/2 in. (38 mm) minimum.

There are two sections of the heat shield. One section is factory-attached to the wall shield firestop. The other section is factory-attached to the cap. See Figure 7.15.
If the wall thickness does not allow the required 1-1/2 in. (38 mm) heat shield overlap when installed, an extended heat shield must be used.

  •  If the wall thickness is less than 4 in./102 mm (DVP) or 4-3/8 in./ 111 mm (SLP), the heat shields on the cap and wall shield firestop must be trimmed. A minimum 1-1/2 in. (38 mm) overlap MUST be maintained.
  •  Use an extended heat shield if the finished wall thickness is greater than 7-1/4 in. (184 mm).
  • The extended heat shield may need to be cut to length maintaining sufficient length for a 1-1/2 in. (38 mm) overlap between heat shields.
  • Attach the extended heat shield to either of the existing heat shields using the screws supplied with the extended heat shield. Refer to vent components diagrams in the back of this manual.
  • Rest the small leg on the extended heat shield on top of the pipe section to properly space it from the pipe section.

Important Notice : Heat shields may not be field constructed.

Install Horizontal Termination Cap (DVP and SLP Pipe)
WARNING! Risk of Fire! The telescoping flue section of the termination cap MUST be used when connecting vent.

  • 1-1/2 (38 mm) minimum overlap of flue telescoping section is required.
    Failure to maintain overlap could cause overheating and fire.

  • Vent termination must not be recessed in the wall. Siding may be brought to the edge of the cap base.

  • Flash and seal as appropriate for siding material at outside edges of cap.

  • When installing a horizontal termination cap, follow the cap location guidelines as prescribed by current ANSI Z223.1 and CAN/CGA-B149 installation codes and refer to Section 4 of this manual.
    CAUTION! Risk of Burns! Local codes may require installation of a cap shield to prevent anything  oranyone from touching the hot cap.

NOTICE: For certain exposures which require superior resistance to wind- driven rain penetration, a flashing kit and HRC caps are available. When penetrating a brick wall, a brick extension kit is available for framing the brick.
Note: When using termination caps with factory-supplied heat shield attached, no additional wall shield firestop is required on the exterior side of a combustible wall.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -
Components8

Cap Speci cation Chart (depth without using additional pipe sections).




NDV Series

| DVP-TRAPK1

Top Vent Depth

| DVP-TRAP1

Rear Vent Depth

| DVP-TRAPK2

Top Vent Depth

| DVP-TRAP2

Rear Vent Depth

| SLP-TRAP1

Top Vent Depth

| SLP-TRAP2

Top Vent Depth

---|---|---|---|---|---|---
4 1/2 to 6 3/8 in.| 3 to 4 7/8 in.| 6 7/8 to 10 7/8 in.| 5 3/8 to 9 3/8 in.| 2 to 3 7/8 in.| 4 3/8 to 8 3/8 in.
DVP-HPC1

Top Vent Depth

| DVP-HPC1

Rear Vent Depth

| DVP-HPC2

Top Vent Depth

| DVP-HPC2

Rear Vent Depth

|
4 1/2 to 6 5/8 in.| 3 to 5 1/8 in.| 6 5/8 to 10 3/4 in.| 5 1/8 to 9 1/4 in.

DVP-TRAP1 can adjust 1 1/2 in. (3 1/8 to 4 5/8)
DVP-TRAP2 can adjust 4 in. (5 3/8 to 9 3/8)
SLP-TRAP1 can adjust 1 5/8 in. (3 1/8 to 4 3/4)
SLP-TRAP2 can adjust 4 in. (5 1/4 to 9 1/4))
DVP-HPC1 can adjust 2 1/8 in. (4 1/4 to 6 3/8)
DVP-HPC2 can adjust 4 1/8 in. (6 3/8 to 10 1/2)

G. Shrouds
HHT Shrouds

  • You may install a shroud with this fireplace. See Section 12.B for a list of UL Listed shrouds. Follow the instructions included with these optional components

Field Constructed Shrouds
WARNING! Risk of Fire! Shrouds must be constructed as specified. Improper construction may overheat chase top.

  •  Chase top shrouds may be field constructed where permitted by regional building codes.
    NOTICE: Some regional codes require an agencyListed shroud. Consult your local building officials.

  •  The following field constructed shroud designs have been tested for Hearth Technologies fireplace systems and termination caps.

  •  The shrouds must be constructed from a minimum .018 in. (26 ga) thick aluminized steel.

  • The wire mesh is optional but recommended and must be .018 in. thick minimum, 1/2 in. mesh.

Mailbox Style Shroud (may be used with DVP-TV, DVP-TVHW, SLP-TVHW)

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -
Components9

Open Top Shroud (may be used with DVP-TV, DVPTVHW, SLP-TVHW)

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Shroud
Dimensions

Roofed Style Shroud (may be used with DVP-TV, DVP-TVHW, SLP-TVHW)

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Shroud
Dimensions1

Electrical Information

A. General Information
WARNING! Risk of Shock or Explosion! DO NOT wire 110-120 VAC to the valve or to the appliance wall switch. Incorrect wiring will damage controls.
NOTICE: This appliance must be electrically wired and grounded in accordance with local codes or, in the absence of local codes, with National Electric Code ANSI/NFPA 70-latest edition or the Canadian Electric Code CSA C22.1.

  • Wire the appliance junction box to unswitched 110-120 VAC. This is required for use of optional accessories (standing pilot ignition) or proper operation of the appliance (Intellifire ignition).
  • A 110-120 VAC circuit for this product must be protected with ground-fault circuit-interrupter protection, in compliance with the applicable electrical codes, when it is installed in locations such as in bathrooms or near sinks.
  • Low voltage and 110-120 VAC voltage cannot be shared within the same wall box.

Junction Box Installation

If the box is being wired from the INSIDE of the appliance:

  • Remove the screw attaching the junction box/receptacle to the outer shell, rotate the junction box inward to disengage it from the outer shell. See Figure 8.1.
  • Pull the electrical wires from outside the appliance through the opening into the valve compartment and secure wires with a Romex connector. See Figure 8.1.
  • Make all necessary wire connections to the junction box/ receptacle and reattach the junction box/receptacle to the outer shell.

NOTE: NDV4236I-NVR contains a junction box with a 6 foot 14/2 AWG wire installed at the factory.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Shroud
Dimensions2

Accessories Requirements

  • This appliance may be used with a wall switch, wall mounted thermostat and/or a remote control. Wiring for optional Hearth & Home Technologies approved accessories should be done now to avoid reconstruction. Follow instructions that come with those accessories.

Electrical Service and Repair
WARNING! Risk of Shock! Label all wires prior to disconnection when servicing controls. Wiring errors could cause improper and dangerous operation. Verify proper operation after servicing.
WARNING! Risk of Shock! Replace damaged wire with type 105º C rated wire. Wire must have high temperature insulation.

B. Wiring Requirements
Intellifire Ignition System Wiring

  • Wire the appliance junction box to 110-120 VAC for proper operation of the appliance.
    WARNING! Risk of Shock or Explosion! DO NOT wire IPI controlled appliance junction box to a switched circuit.
    Incorrect wiring will override IPI safety lockout.

  • Refer to Figure 8.2, Intellifire Pilot Ignition (IPI) Wiring Diagram.

  • This appliance is equipped with an Intellifire control valve which operates on a 3 volt system.

  • Plug the 3-volt AC transformer into the appliance junction box to supply power to the unit OR install two D cell batteries (not included) into the battery pack before use.
    NOTICE: Batteries should not be placed in the battery pack while using the transformer. Remove batteries before using the transformer, and unplug the transformer before installing the batteries. Battery polarity must be correct or module damage will occur.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Pilot
Assembly

Figure 8.2 Intellifire Pilot Ignition (IPI) Wiring Diagram
Optional Fan Installation Methods

A fan can be added to your appliance to push more warmth into your space.
Option 1:
The optional fan can be used with the fan control module that is included in the fan kit. Fan speed is controlled through the control knob on the fan control module. See Figure 9.3.
Option 2:
The optional fan can be used in conjunction with a remotely located wall mounted switch or a BC10 (Blower Control Wall Switch).

  • The power supply for the appliance must be brought into the appliance junction box.
  • The wires to the remotely mounted switch or BC10 must plug into the black female terminals on harness. See Figure 9.4.
  • The white wire connector on harness is not used and must be capped or terminated per local electrical code requirements.
  • All wiring to remotely mounted switch or BC10 to be compliant with all local electrical code requirements.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Kit
Components

Gas Information

A. Fuel Conversion

  • Make sure the appliance is compatible with available gas types.
  • Conversions must be made by a qualified service technician using Hearth & Home Technologies specified and approved parts.

B. Gas Pressure

WARNING

Fire Risk.
Risk of Fire! Risk of Explosion!
Incorrect pressure will damage valve.

  • Isolate gas supply piping BEFORE pressuretesting gas line at test pressures above 1/2 psig.
  • Close the manual shutoff valve BEFORE pressure testing gas line at test pressures equal to or less than 1/2 psig.
  • Optimum appliance performance requires proper input pressures.
  • Gas line sizing requirements will be determined in ANSI Z223.1 National Fuel Gas Code in the USA and CAN/ CGA B149 in Canada.
  • Pressure requirements are:
Gas Pressure Natural Gas Propane
Minimum inlet pressure 5.0 in. w.c. 11.0 in. w.c.
Maximum inlet pressure 10.0 in. w.c. 13.0 in. w.c.
Manifold pressure 3.5 in. w.c. 10.0 in. w.c.
  •  Verify inlet pressures. Verify minimum pressures when other household gas appliances are operating.
  • Install regulator upstream of valve if line pressure is greater than 1/2 psig.

Note: Have the gas supply line installed in accordance with local codes, if any. If not, follow ANSI Z223.1. Installation should be done by a qualified installer approved and/or licensed as required by the locality. (In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fitter).
Note: A listed (and Commonwealth of Massachusetts approved) 1/2 in. (13 mm) T-handle manual shut-off valve and flexible gas connector are connected to the 1/2 in. (13 mm) control valve inlet.

  • If substituting for these components, please consultlocal codes for compliance.

C. Gas Connection

  •  Refer to Section 3 for location of gas line access in appliance.
  • Gas line may be run through knockout(s) provided.
  • The gap between supply piping and gas access hole may be sealed with caulk or aluminum foil tape with a  minimum of 300 ºF continuous exposure rating or stuffedwith non-combustible, unfaced insulation to prevent cold air infiltration.
  • Ensure that gas line does not come in contact with outer wrap of the appliance. Follow local codes. Pipe incoming gas line into valve compartment.
  • Connect incoming gas line to the 1/2 in. (13 mm) NPT connection on manual shutoff valve.

WARNING! Risk of Fire or Explosion! Support control when attaching pipe to prevent bending gas line.
WARN ING! Risk of Fire or Explosion! Gas build-up during line purge could ignite.

  • A small amount of air will be in the gas supply lines.
  • Ensure adequate ventilation.
  • Ensure there are no ignition sources such as sparks or open flames.

Light the appliance. It will take a short time for air to purge from lines. When purging is complete the appliance will light and operate normally.
WARNING! Risk of Fire, Explosion or Asphyxiation!
Check all fittings and connections with a non-corrosive commercially available leak-check solution. DO NOT use open flame. Fittings and connections could have loosened during shipping and handling.
D. High Altitude Installations
NOTICE: If the heating value of the gas has been reduced, these rules do not apply. Check with your local gas utility or authorities having jurisdiction.
When installing above 2000 feet elevation:

  • In the USA: Reduce input rate 4% for each 1000 feet above 2000 feet.
  • In CANADA: Input ratings are certified without a reduction of input rate for elevations up to 4500 feet (1370 m)above sea level. Please consult provincial and/ or local authorities having jurisdiction for installations at elevations above 4500 feet (1370 m).
    Check with your local gas utility to determine proper orifice size.

E. Air Shutter Setting
Air shutter setting should be adjusted by a qualified installer at the time of installation.

  • The air shutter is set at the factory for minimum vertical vent run. It may need to be adjusted for other venting scenarios.
  • Adjust air shutter for longer vertical runs. See Figure 9.1.
    Turn the thumbscrew to open or close the air shutter. It may be necessary to use a pliers or crescent wrench to adjust the shutter. See chart below for correct shutter settings. The shutter measurement is taken from the bottom of the tub to the bottom of the thumbscrew. See Figure 9.1.

Note: Adjust air shutter after flame has reached full maturity (approximately 20-40 minutes).
CAUTION! Risk of Burns! Components are HOT. Wear protective gloves when adjusting shutter.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Air
Shutter

Note: The air shutter is equipped with a compression spring that helps to maintain the shutter position during transportation. It may be necessary to relieve this spring pressure on the thumb screw to adjust the shutter.
Air Shutter Settings (Factory Set to Minimum Vent Run)

MODEL GAS TYPE MINIMUM VENT RUN MAXIMUM VENT RUN
NDV3630I-B NG 1-3/8 IN. 1-1/4 IN.
NDV3630IL-B PROPANE 1-3/8 IN. 1-1/4 IN.
NDV3933I-B NG 1-3/8 IN. 1-1/8 IN.
NDV3933IL-B PROPANE 1-1/4 IN. 1-1/4 IN.
NDV4236I-B NG 1-1/4 IN. 1-1/4 IN.
NDV4236IL-B PROPANE 1-1/8 IN. 1 IN.
NDV4236I-NVR NG 1-1/4 IN. 1-1/4 IN.
NDV4842I-B NG 1-1/8 IN. 1 IN.
NDV4842IL-B PROPANE 1-1/8 IN. 3/4 IN.

Minimum and maximum shutter settings are set up to appear like Figure 4.22.

  • Minimum vent run consists of enough horizontal vent pipe to exit 2 X 6 wall construction (approximately 8 inches).
  • Maximum vent run consists of “H Maximum” on Figure 4.22.

Note: All vent runs may need to be evaluated for ideal shutter settings. Shutter distances may vary due to vent run, fuel quality, and elevation.

Finishing

A. Facing Material
WARNING

Risk of Fire!
DO NOT apply combustible materials beyond the minimum clearances.
Comply with all minimum clearances to combustibles as specified in this manual. Materials overlapping into non-combustible zones could ignite and will interfere with air  flowthrough decorative barrier  ronts.

  • Metal front of appliance may be covered with noncombustible materials only.
  • Facing and/or finishing materials must not interfere with air flow through decorative barrier fronts, removal of decorative barrier fronts or access for service.
  • Facing and/or finishing materials must never overhang into the glass opening.
  • Observe all clearances when applying combustible materials.
  • Seal gaps between the finished wall and appliance top and sides using a 300 ºF minimum sealant.

NOTICE: Surface temperatures around the appliance will become warm while the appliance is in operation. Ensure finishing materials used for all surfaces (floor, walls, mantels, etc.) will withstand temperatures up to 190 °F.

B. Combustible Mantel and Wall Projections
WARNING! Risk of Fire!
Comply with all minimum clearances as specified. Framing closer than the minimums listed must be constructed entirely of non- combustible materials (i.e., steel studs, concrete board, etc.).
Note: Mantel Measurement is taken from top of the opening, NOT the top of the fireplace.
Combustible Mantels

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Air
Shutter1

Figure 10.1 Minimum Vertical and Maximum Horizontal  Dimensions for Combustible Mantels
Combustible Mantel Legs or Wall Projections

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Air
Shutter2

Figure 10.2 Combustible Mantel Leg or Wall Projections (Acceptable on both sides of opening)
C. Non-combustible Mantel and Wall Projections

Only decorative barrier fronts certified for use with this appliance model may be used. Contact your dealer for a list of decorative fronts that may be used. The finishing material thicknesses allowed are noted below.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Air
Shutter3

Figure 10.3 Minimum Vertical and Maximum Horizontal Dimensions for Non- Combustibles Mantels
Non-Combustible Mantel Legs or Wall Projections

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Air
Shutter4

Figure 10.4 Non-Combustible Mantel Leg or Wall Projections (Acceptable on both sides of opening)

Appliance Setup

A. Remove the Shipping Materials
Remove shipping materials from inside or underneath the firebox.

  • The splatter guard is a piece of corrugated material used to protect the appliance during the installation process before finishing work on the whole hearth is complete. Splatter guards may be factory installed or accompany the decorative barrier front of the  appliance, depending on the fireplace model. Splatter guards must be removed before appliance is fired.

WARNING! Risk of Fire! Close the ball valve before installing the splatter guard to prevent accidental lighting.
Remove the splatter guard before lighting the appliance.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Appliance
Unwrapped

B. Clean the Appliance
Clean/vacuum any sawdust that may have accumulated inside the firebox or underneath in the control cavity.
C. Install Optional Refractory Kit
An optional refractory kit is available for the NDV models.
Contact your dealer to order the kit. Install according to instructions included with kit.
D. Install Burner Mineral Wool
WARNING! Risk of Explosion! Follow mineral wool placement instructions. DO NOT place mineral wool on or near rear burner ports. Replace mineral wool material annually. Improperly placed mineral wool interferes with proper burner operation.
Note: It may be helpful to temporarily remove Log #5 to place the mineral wool. If removed, replace log according to log placement instructions.

  • Mineral wool is shipped with this gas appliance.
  • Place a small amount of 1/2 in. diameter pieces (dimesize) mineral wool on the burner pan as shown in Figure 11.3. The mineral wool may be placed loosely over the front burner port holes in the burner pan. Do NOT press them onto or into the burner port holes. This will provide the “glowing embers” look.
  • It is not necessary to use the entire bag. Save the remaining mineral wool for future use.
  • It is permissible to place a small amount of mineral wool or lava rock over screw heads that are used to fasten the rear logs.

WARNING
RISK OF EXPLOSION!

  • Place lava rock and mineral wool according to instructions.

  • Do NOT place lava rock or mineral wool in a position that they may fall into pilot area.
    Delayed ignition could occur.

  •  Use ONLY Hearth & Home Technologies-approved lava rock or mineral wool.

  •  Some models may not require use of entire contents of bag.

Place the Lava Rock
Place the lava rock in an even layer just heavy enough to cover the metal surface. Stay within the zone indicated in Figure 11.3. It is not necessary to use the entire bag. Save the remaining amount for future use.

E. Install Fixed Glass Assembly
WARNING! Risk of Asphyxiation! Handle fixed glass assembly with care. Inspect the gasket to ensure it is undamaged and inspect the glass for cracks, chips or scratches.

  • DO NOT strike, slam or scratch glass.
  • DO NOT operate fireplace with glass removed, cracked, broken or scratched.
  • Replace as a complete assembly.
  • Set the glass panel on the lower two glass assembly latches, ensuring the glass panel is centered in the opening.
  • Pull out and latch the four glass assembly latches into the groove on the glass frame. See Figure 11.2.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Appliance
Unwrapped 1

F. Install Decorative Barrier Front
WARNING! Risk of Fire! Install ONLY doors or fronts approved by Hearth & Home Technologies. Unapproved doors or fronts could cause fireplace to overheat.
DO NOT operate the applaince with the barrier removed.
Contact your dealer or Hearth & Home Technologies if the barrier is not present or help is needed to properly install one.
For more information refer to the instructions supplied with your decorative barrier front.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series - Appliance
Unwrapped2

G. Install the Log Assembly
LOG PLACEMENT INSTRUCTIONS

Log Set Assembly:
SRV2380-070 SRV2381-070 SRV2382-070 SRV2383-070
Models: NDV3630I-B, NDV3630IL-B, NDV3933I-B, NDV3933IL-B,
NDV4236I-B, NDV4236IL-B, NDV4236I-NVR, NDV4842I-B, NDV4842IL-B
NBV3630I-B, NBV3933I-B, NBV4236I-B, NBV4842I-B
See Table 1 for corresponding log set and individual logs for each size Novus model.

SIZE 3630 3933 4236 4842
ASSEMBLY SRV2380-070 SRV2381-070 SRV2382-070 SRV2383-070
LOG 1 SRV2380-071 SRV2380-071 SRV2382-071 SRV2383-071
LOG 2 SRV2380-072 SRV2381-072 SRV2381-072 SRV2383-072
LOG 3 SRV2380-073 SRV2381-073 SRV2381-073 SRV2383-073
LOG 4 SRV2380-074 SRV2380-074 SRV2382-074 SRV2382-074
LOG 5 SRV2380-075 SRV2380-075 SRV2380-075 SRV2383-075

Table 1.
CAUTION: Logs are fragile, handle with care.
The log set is shipped from the factory with three logs already in place on the hearth pan. See Figure 1. In case of damage, the log will need to be removed from the base pan. See Figure 2 for locations of fasteners for each log.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -
Locations

LOG #4: Place Log #4 into position by setting the left end of Log #4 into the flat spot on Log #2 and then resting the right end, or nose, of Log #4 on the flat spot on Log #1. Figure 3 shows locations of flat spots. Figure 4 shows Log #4 installed.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -
Locations1

Log #5 : Place Log #5 into position. The forked end of Log #5 is positioned toward the front of the appliance, with the two slots on the back side resting on the bent lip of the hearth pan. See Figure 6. Slide Log #5 toward the right until it contacts the log pin as shown in Figure 6.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -
Locations2

Reference Materials

A. Vent Components Diagrams

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -
Locations3

A. Vent Components Diagrams (continued)
Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm). The heat shield is designed to be used on a wall 4 in. to 7-1/4 in. (102 mm to 184 mm) thick. If wall thickness is less than 4 in. (102 mm) the existing heat shields must be field trimmed. If wall thickness is greater than 7-1/4 in. (184 mm) a DVP-HSM-B will be required.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -
Locations4

Figure 12.2 DVP Vent Components
A. Vent Components Diagrams (continued)

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -
Locations5

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -
Locations6

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -
Locations7

DECORATIVE TERMINATIONS/SHROUDS
Only use listed decorative termination caps/shrouds with Hearth & Home Technologies approved venting systems.
This applies to both DVP and SLP venting systems.
Decorative Terminations Caps/Shrouds
DTO134
DTO146
DTS134
DTS146
LDS33
LDS46
LDS-BV

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -
Locations8

Optional Wire Harness

DESCRIPTION| PART NUMBER
10 FT PV Wire Harness| PVI-WH10
20 FT PV Wire Harness| PVI-WH20
40 FT PV Wire Harness| PVI-WH40
60 FT PV Wire Harness| PVI-WH60
80 FT PV Wire Harness| PVI-WH80
100 FT PV Wire Harness| PVI-WH100

Note: Wire harnesses required to power the PVI-SLP-B connect to the appliance and are ordered separately from PVI-SLP-B. Contact your dealer to order.
Note: The PVI-SLP-B requires a PV-IPI-CK be installed on this appliance. The PV-IPI-CK is ordered separately from the PVI-SLP-B. Contact your dealer to order.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -
Locations9

Figure 12.6 PVI-SLP-B Vent Components

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -
Locations10

Note: Wire harnesses required to power the PVLP-SLP connect to the appliance and are ordered separately from PVLP-SLP. Contact your dealer to order.
Note: A PVLP-HS heat shield is available and sold separately. Use if the PVLP-SLP is installed in a high traffic area.
Note: The PVLP-SLP requires a PV-IPI-CK be installed on this appliance. The PV-IPI-CK is ordered separately from the PVLP-SLP. Contact your dealer to order.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -
Locations11

Optional Wire Harness

DESCRIPTION| PART NUMBER
10 FT PV Wire Harness| PVI-WH10
20 FT PV Wire Harness| PVI-WH20
40 FT PV Wire Harness| PVI-WH40
60 FT PV Wire Harness| PVI-WH60
80 FT PV Wire Harness| PVI-WH80
100 FT PV Wire Harness| PVI-WH100

Figure 12.7 PVLP-SLP Vent Components

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -
Locations12

Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm). The heat shield is designed to be used on a wall 4 in. to 7-1/4 in. (102 mm to 184 mm) thick. If wall thickness is less than 4 in. (102 mm) the existing heat shields must be field trimmed. If wall thickness is greater than 7-1/4 in. (184 mm) a DVP-HSM-B will be required.

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -
Locations13

Figure 12.9 SLP Series Vent Components

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -
Locations14

Figure 12.10 SLP Series Vent Components
B. Optional Components


Catalog #

| A| B| C| D
---|---|---|---|---
in.| mm| in.| mm| in.| mm| in.| mm
LDS33| 36| 914| 36| 914| 8.5| 216| 11| 279
LDS46| 48| 1219| 72| 1829| 8.5| 216| 11| 279

heatilator NDV3630I-B Novus Direct Vent Fireplace Series -
Locations16

Catalog # A B C E E

LDS-BV

| in.| 26| 12.5| 15.5| 22| 23
mm| 660| 318| 394| 533| 584

LDSCP-M Shroud Leg Multipack (not shown)

See your Heatilator dealer for a complete listing of optional components.

C. Accessories
Remote Controls, Wall Controls and Wall
Switches
Follow the instructions supplied with the control installed to operate your fireplace:
For safety:

  • Install a switch lock or a wall/remote control with child protection lockout feature.
  • Keep remote controls out of reach of children.
    See your dealer if you have questions.

Optional Fan
Follow the instructions supplied with the fan kit to operate your fan. See your dealer if you have questions.
Optional Refractory Kit
If desired, a refractory kit may be added. Contact your dealer to order the correct refractory kit. Detailed installation instructions are included with the refractory kit.

Heatilator, a brand of Hearth & Home Technologies
7571 215 th Street West, Lakeville, MN 55044
www.heatilator.com
Please contact your Heatilator dealer with any questions or concerns.
For the location of your nearest Heatilator dealer,
please visit www.heatilator.com.
Printed in U.S.A. – Copyright 2023
Heatilator • NDV3630I-B, NDV3933I-B, NDV4236I-B, NDV4842I-B, NDV4236I-NVR Installation Manual • 2382-980 Rev. AB •