Only suitably qualified personnel should install this equipment

Part Number| Flush Mount| Switch Input (Mains)| Switched Live Output| Volt free output| Connect to MLS| Connect to DALI Bus| 360 degree sensing| Directional Sensing| 24hr mode| Lighting scenes| One Switch dimming
---|---|---|---|---|---|---|---|---|---|---|---
Part Number|

| •| | •| •| •| •| | •| •|

MLS3421DRF|

| •| | •| •| •| | •| •| •|

MLS3500DRF|

| •| | •| | •| | •| •| •|

MR3500RF| •| •| | •| | | | •|

| |
MR3421R2F| •| | •| •| | | •| | •|

|

Security

For details of securing the product and system see the General Security Best Practice for Ex-Or Products Information Sheet – D6004.

Determine Position

The Mxx3421 & Mxx3500 sensors are extremely sensitive movement detectors. They must be installed on a rigid surface that will not be subject to movement or vibration. They are not recommended for applications where there are large surface areas of metal, e.g. metal ceiling or floor tiles, as unpredictable sensitivity may result. Microwaves can penetrate lightly built partitions, glass, etc. Movement in adjacent spaces may cause spurious triggering if the orientation and sensitivity setting of the detector is not managed carefully.

Mxx3421

Do not mount within 0.25m of a luminaire. Max distance between sensors = 5m

Recommended maximum mounting height 3m
Range Cone-shaped detection pattern, diameter (at floor level) = 2.8 x

mounting height

Determine Position

Mxx3500

Position the detector where it has a good ‘view’ of the space to be controlled. An ideal location is in a corner adjacent to the entrance of a room or at one end of a corridor. Do not mount within 0.25m of a luminaire.

Recommended maximum mounting height 3.5m
Range Adjustable up to 20m

Horizontal

Vertical

Plan DALI Cable Runs

DALI Topology

DALI permits a free topology which means wiring can be done in daisy chain, star or a combination of these. Do not close the loop or ring connections.

Remove Terminal Cover

Fit Flush Mount Version

Prepare Mounting Location and Run Cables

Route cables through hole and secure LOCKRING (if used)

Make Electrical Connections

Make the electrical connections to the sensor – see “Make Electrical Connections”

Fix Cable Clamps (optional for 1mm²-2.5mm² sheathed round cables)

4c\) Fix Cable Clamps \(optional for 1mm²-2.5mm² sheathed round
cables\)

Note: If using cables larger than 3×1.5mm² the outer sheath on the supply cable should only be removed after the sheathed cable has been clamped in position.

4d) Replace the Terminal Cover 4e) Fix to Ceiling

Replace the Terminal Cover

Insert screw for Class II compliance

Fix to Ceiling

Standard Method

Fix to Ceiling

LOCKRING Method

The LOCKRING cannot be used when there is no access to ceiling void.
Fix to Ceiling

NOTE: To remove sensor rotate LOCKRING and pull up

Fit Surface Mount Version

Note: If a surface mount version has been ordered a flush mount version and a surface mount kit will be provided.

Remove springs & Attach Shell

Remove springs & Attach Shell

Attach Conduit Fittings & Cable Glands to Lower Housing (if required)

Attach Conduit Fittings & Cable Glands to Lower Housing \(if
required\)

Prepare Mounting Location and Run Cables

The sensor may be mounted to any suitable surface, but is most commonly fixed to a conduit stop-end (BESA) box or bushed to trunking. change image
Prepare Mounting Location and Run Cables

Make Electrical Connections

Make the electrical connections to the sensor – see “Make Electrical Connections”

Fix to Ceiling

8 segments on the collar allow up to four different rotational positions for the sensor, when inserting the tabs into slots (1-8).
Fix to Ceiling

Make Electrical Connections

WARNING: Do NOT power up until installation is complete.

WARNING: ALL plug-in terminals MUST be connected and the cover must be in place before the unit is powered up.

MLS Bus Connections – MLS variants

Make Electrical Connections

Terminal type Screw less with release lever
Terminal capacity 1 x 0.5-1.5mm2 solid or stranded
Recommended cable 1.5mm² unscreened twisted pair
Max cable length Up to 1500m – If using 1.5 mm2 unscreened twisted pair

cable.

Volt-free Output Connections

The volt-free output can be used as a live switched output by linking it to the live terminal as shown.

Terminal type Rising cage screw clamp
Terminal capacity 1 x 0.5-2.5mm2 solid or stranded
Recommended cable 2 core 1.5-2.5mm2
Switching Capability 10A

DALI Bus Connections – DALI variants

To prevent loose strands being outside the terminal a tool, e.g. a screwdriver, must be used to push the button on the terminal when stranded conductors are inserted.

Warning: Do not connect to 230V.

Warning: The DALI Bus is not classified as SELV. The same procedures and safeguards must be applied as when working with mains voltage.

Terminal type Rising cage screw clamp
Terminal capacity 1 x 0.5-1.5mm2 solid or stranded.
Recommended cable 2 core 0.5-1.5mm2
Max cable length Copper

Copper
Copper
Copper| Cross Section
0.5 mm2
0.75 mm2
1.0 mm2
1.5 mm2| Maximum cable length at 25 °C
112m
168m
224m
300m
Max devices| 25 DALI control gears (ballasts or drivers) – 50 mA

Note:

  1. DALI gears (ballasts or drivers) are normally wired from an un switched supply.
  2. Ballasts or drivers must be DALI Control Gears complying to IEC 62386 V1 or V2.

Power Connections

Terminal type Rising cage screw clamp
Terminal capacity 1 x 0.5-2.5mm2 solid or stranded.
Recommended cable Refer to appropriate regulations
Max cable length Refer to appropriate regulations
Operating voltage 220 – 240V 50-60Hz.
Quiescent power consumption 1W
Recommended circuit protection 10A MCB

Note: In accordance with current wiring regulations a means of disconnection (e.g switch) must be incorporated into the fixed wiring.

Switch Input (Mains) Connections – Not MR3421R2

Switch Input \(Mains\) Connections - Not MR3421R2

Terminal type Rising cage screw clamp
Terminal capacity 1 x 0.5-2.5mm2 solid or stranded.
Recommended cable Derive from appropriate wiring regulations
Max cable length Derive from appropriate wiring regulations
Operating voltage 100 – 240V 50-60Hz.
Power consumption Negligible

Switch Live Output Connections – MR3421R2F only

Terminal type Rising cage screw clamp
Terminal capacity 1 x 0.5-2.5mm2 solid or stranded.
Recommended cable 2 core 1.5-2.5mm2
Operating voltage 100 – 240V 50-60Hz

Perform Walk Test

In order to verify correct installation, walk testing is recommended. Follow the instructions provided with the QuicksetPro (QSP). During the walk test the connected lights will be switched off until movement is detected.
Perform Walk Test
Stand out of the unit’s viewable footprint or remain motionless within the viewable footprint and wait for the lights to go out.
Perform Walk Test
Wait a further 2 seconds for the unit to stabilize then make a movement, the lights should come back on. Observe that the detection / non-detection is as expected.

Out of Box Behavior

This range of products features a rich set of adjustable parameters that may be programmed via the hand-held infrared commissioning tools in order to create a sophisticated lighting control installation.

Time Delay 20 Minutes
Photocell   Mode Ignore (Always turn on when occupied)
Occupancy Mode Presence (lights Auto On, Auto OFF)
Movement Sensitivity Medium

Diagnostics

LED indications are provided to help with fault-finding.

LED indication Meaning
Green Movement detected

Flashing Red| Hardware or firmware fault. Check DALI connections for shorts.

Flashing Blue| IR communication in progress

Configuration

Once installed the unit must be configured using the QuicksetPro (QSP) to create the required lighting control installation – see the QuicksetPro Engineering Manual

  • W6001 available from www.Ex-Or.com. The QSP provides context help on the individual parameters.


www.Ex-Or.com

Uninstall surface mount variants

Insert a flat headed screwdriver into the slot as shown and twist the collar anticlockwise to release. To separate the sensor from the surface mount casing, push a flat headed screwdriver onto the tab via the inside void of the casing and pull the unit appart.
Replace the Terminal Cover

Specifications

Photocell Adjustable 0 – 5000 lux (with a 20% reflective work plane)
IP Rating IP20
Operating temperature 0°C to 50°C

Dimensions
Flush mounting| Height 93.5mm, diameter 87mm
Surface mounting| Height 108.5mm, diameter 87mm
Weight
Flush mounting| 154g
Surface mounting kit| 259g
Colour| White (RAL9010)
Material| Flame retardant PC/ABS
Max recommended load| 10 Amps per output (not exceeding 10A in total)

This symbol on our product shows a crossed-out ‘wheelie-bin’ as required by law regarding the Waste of Electrical and Electronic Equipment (WEEE) disposal. This indicates your responsibility to contribute in saving the environment by proper disposal of this waste i.e. Do not dispose of this product with your other wastes. To know the right disposal mechanism please check the applicable law.

At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre.

Do not dispose of with normal household waste. Do not burn

IMPORTANT NOTES

  1. The sensor must be positioned such that it detects a substantial proportion of artificial light from the luminaire(s) under its control for effective light regulation
  2. Only suitably qualified personnel should install this equipment.
  3. A means for disconnection must be incorporated in the fixed wiring in accordance with current wiring regulations.
  4. Frequent switching may adversely affect the life of the luminaire. Please check with the manufacturer of the luminaires to ensure that they are compatible with automatic controls in this respect.
  5. All information given in this document was correct at the time of publication.

Customer Support

EU contact for regulatory questions:
PEHA Elektro GmbH & Co.
KG Gartenstraße 49,
58511 Lüdenscheid
Germany
Web: www.peha.de

Honeywell
St Marks Court, North Street
Horsham, West Sussex RH12 1BW
Tel: +44 (0)1942 719229
Web: www.ex-or.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Honeywell User Manuals

Related Manuals