Honeywell Mxx3421 and Mxx3500 High Detection Microwave Sensors
Product Information
Only suitably qualified personnel should install this equipment
Part Number| Flush Mount| Switch Input (Mains)| Switched
Live Output| Volt free output| Connect to MLS| Connect to DALI
Bus| 360 degree sensing| Directional Sensing| 24hr mode|
Lighting scenes| One Switch dimming
---|---|---|---|---|---|---|---|---|---|---|---
Part Number|
•
| •| | •| •| •| •| | •| •|
•
MLS3421DRF|
•
| •| | •| •| •| | •| •| •|
•
MLS3500DRF|
•
| •| | •| | •| | •| •| •|
•
MR3500RF| •| •| | •| | | | •|
•
| |
MR3421R2F| •| | •| •| | | •| | •|
•
|
Security
For details of securing the product and system see the General Security Best Practice for Ex-Or Products Information Sheet – D6004.
Determine Position
The Mxx3421 & Mxx3500 sensors are extremely sensitive movement detectors. They must be installed on a rigid surface that will not be subject to movement or vibration. They are not recommended for applications where there are large surface areas of metal, e.g. metal ceiling or floor tiles, as unpredictable sensitivity may result. Microwaves can penetrate lightly built partitions, glass, etc. Movement in adjacent spaces may cause spurious triggering if the orientation and sensitivity setting of the detector is not managed carefully.
Mxx3421
Do not mount within 0.25m of a luminaire. Max distance between sensors = 5m
Recommended maximum mounting height | 3m |
---|---|
Range | Cone-shaped detection pattern, diameter (at floor level) = 2.8 x |
mounting height
Mxx3500
Position the detector where it has a good ‘view’ of the space to be controlled. An ideal location is in a corner adjacent to the entrance of a room or at one end of a corridor. Do not mount within 0.25m of a luminaire.
Recommended maximum mounting height | 3.5m |
---|---|
Range | Adjustable up to 20m |
Horizontal
Vertical
Plan DALI Cable Runs
DALI Topology
DALI permits a free topology which means wiring can be done in daisy chain, star or a combination of these. Do not close the loop or ring connections.
Remove Terminal Cover
Fit Flush Mount Version
Prepare Mounting Location and Run Cables
Route cables through hole and secure LOCKRING (if used)
Make Electrical Connections
Make the electrical connections to the sensor – see “Make Electrical Connections”
Fix Cable Clamps (optional for 1mm²-2.5mm² sheathed round cables)
Note: If using cables larger than 3×1.5mm² the outer sheath on the supply cable should only be removed after the sheathed cable has been clamped in position.
4d) Replace the Terminal Cover 4e) Fix to Ceiling
Insert screw for Class II compliance
Fix to Ceiling
Standard Method
LOCKRING Method
The LOCKRING cannot be used when there is no access to ceiling void.
NOTE: To remove sensor rotate LOCKRING and pull up
Fit Surface Mount Version
Note: If a surface mount version has been ordered a flush mount version and a surface mount kit will be provided.
Remove springs & Attach Shell
Attach Conduit Fittings & Cable Glands to Lower Housing (if required)
Prepare Mounting Location and Run Cables
The sensor may be mounted to any suitable surface, but is most commonly fixed
to a conduit stop-end (BESA) box or bushed to trunking. change image
Make Electrical Connections
Make the electrical connections to the sensor – see “Make Electrical Connections”
Fix to Ceiling
8 segments on the collar allow up to four different rotational positions for
the sensor, when inserting the tabs into slots (1-8).
Make Electrical Connections
WARNING: Do NOT power up until installation is complete.
WARNING: ALL plug-in terminals MUST be connected and the cover must be in place before the unit is powered up.
MLS Bus Connections – MLS variants
Terminal type | Screw less with release lever |
---|---|
Terminal capacity | 1 x 0.5-1.5mm2 solid or stranded |
Recommended cable | 1.5mm² unscreened twisted pair |
Max cable length | Up to 1500m – If using 1.5 mm2 unscreened twisted pair |
cable.
Volt-free Output Connections
The volt-free output can be used as a live switched output by linking it to the live terminal as shown.
Terminal type | Rising cage screw clamp |
---|---|
Terminal capacity | 1 x 0.5-2.5mm2 solid or stranded |
Recommended cable | 2 core 1.5-2.5mm2 |
Switching Capability | 10A |
DALI Bus Connections – DALI variants
To prevent loose strands being outside the terminal a tool, e.g. a screwdriver, must be used to push the button on the terminal when stranded conductors are inserted.
Warning: Do not connect to 230V.
Warning: The DALI Bus is not classified as SELV. The same procedures and safeguards must be applied as when working with mains voltage.
Terminal type | Rising cage screw clamp |
---|---|
Terminal capacity | 1 x 0.5-1.5mm2 solid or stranded. |
Recommended cable | 2 core 0.5-1.5mm2 |
Max cable length | Copper |
Copper
Copper
Copper| Cross Section
0.5 mm2
0.75 mm2
1.0 mm2
1.5 mm2| Maximum cable length at 25 °C
112m
168m
224m
300m
Max devices| 25 DALI control gears (ballasts or drivers) – 50 mA
Note:
- DALI gears (ballasts or drivers) are normally wired from an un switched supply.
- Ballasts or drivers must be DALI Control Gears complying to IEC 62386 V1 or V2.
Power Connections
Terminal type | Rising cage screw clamp |
---|---|
Terminal capacity | 1 x 0.5-2.5mm2 solid or stranded. |
Recommended cable | Refer to appropriate regulations |
Max cable length | Refer to appropriate regulations |
Operating voltage | 220 – 240V 50-60Hz. |
Quiescent power consumption | 1W |
Recommended circuit protection | 10A MCB |
Note: In accordance with current wiring regulations a means of disconnection (e.g switch) must be incorporated into the fixed wiring.
Switch Input (Mains) Connections – Not MR3421R2
Terminal type | Rising cage screw clamp |
---|---|
Terminal capacity | 1 x 0.5-2.5mm2 solid or stranded. |
Recommended cable | Derive from appropriate wiring regulations |
Max cable length | Derive from appropriate wiring regulations |
Operating voltage | 100 – 240V 50-60Hz. |
Power consumption | Negligible |
Switch Live Output Connections – MR3421R2F only
Terminal type | Rising cage screw clamp |
---|---|
Terminal capacity | 1 x 0.5-2.5mm2 solid or stranded. |
Recommended cable | 2 core 1.5-2.5mm2 |
Operating voltage | 100 – 240V 50-60Hz |
Perform Walk Test
In order to verify correct installation, walk testing is recommended. Follow
the instructions provided with the QuicksetPro (QSP). During the walk test the
connected lights will be switched off until movement is detected.
Stand out of the unit’s viewable footprint or remain motionless within the
viewable footprint and wait for the lights to go out.
Wait a further 2 seconds for the unit to stabilize then make a movement, the
lights should come back on. Observe that the detection / non-detection is as
expected.
Out of Box Behavior
This range of products features a rich set of adjustable parameters that may be programmed via the hand-held infrared commissioning tools in order to create a sophisticated lighting control installation.
Time Delay | 20 Minutes |
---|---|
Photocell Mode | Ignore (Always turn on when occupied) |
Occupancy Mode | Presence (lights Auto On, Auto OFF) |
Movement Sensitivity | Medium |
Diagnostics
LED indications are provided to help with fault-finding.
LED indication | Meaning |
---|---|
Green | Movement detected |
Flashing Red| Hardware or firmware fault. Check DALI connections for shorts.
Flashing Blue| IR communication in progress
Configuration
Once installed the unit must be configured using the QuicksetPro (QSP) to create the required lighting control installation – see the QuicksetPro Engineering Manual
- W6001 available from www.Ex-Or.com. The QSP provides context help on the individual parameters.
Uninstall surface mount variants
Insert a flat headed screwdriver into the slot as shown and twist the collar
anticlockwise to release. To separate the sensor from the surface mount
casing, push a flat headed screwdriver onto the tab via the inside void of the
casing and pull the unit appart.
Specifications
Photocell | Adjustable 0 – 5000 lux (with a 20% reflective work plane) |
---|---|
IP Rating | IP20 |
Operating temperature | 0°C to 50°C |
Dimensions
Flush mounting| Height 93.5mm, diameter 87mm
Surface mounting| Height 108.5mm, diameter 87mm
Weight
Flush mounting| 154g
Surface mounting kit| 259g
Colour| White (RAL9010)
Material| Flame retardant PC/ABS
Max recommended load| 10 Amps per output (not exceeding 10A in total)
This symbol on our product shows a crossed-out ‘wheelie-bin’ as required by law regarding the Waste of Electrical and Electronic Equipment (WEEE) disposal. This indicates your responsibility to contribute in saving the environment by proper disposal of this waste i.e. Do not dispose of this product with your other wastes. To know the right disposal mechanism please check the applicable law.
At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre.
Do not dispose of with normal household waste. Do not burn
IMPORTANT NOTES
- The sensor must be positioned such that it detects a substantial proportion of artificial light from the luminaire(s) under its control for effective light regulation
- Only suitably qualified personnel should install this equipment.
- A means for disconnection must be incorporated in the fixed wiring in accordance with current wiring regulations.
- Frequent switching may adversely affect the life of the luminaire. Please check with the manufacturer of the luminaires to ensure that they are compatible with automatic controls in this respect.
- All information given in this document was correct at the time of publication.
Customer Support
EU contact for regulatory questions:
PEHA Elektro GmbH & Co.
KG Gartenstraße 49,
58511 Lüdenscheid
Germany
Web: www.peha.de
Honeywell
St Marks Court, North Street
Horsham, West Sussex RH12 1BW
Tel: +44 (0)1942 719229
Web: www.ex-or.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>