astro Trimless Slimline Round Fixed Fire Rated
INTRODUCTION
Please read the instructions carefully before commencing assembly
Live: Normally Brown / Red
Neutral: Normally Blue/ Black
Earth: Normally Green/ Yellow
If the external cord of this luminaire is damaged, it must be replaced by the manufacturer or a qualified person.
PACKAGE CONTENT
-
NOT SUITABLE FOR COVERING WITH THERMAL INSULATION.
-
For Ceiling Use Only.
-
Glare guard.
CEILING TYPES
Ceiling lining secured directly to timber joists/
| Fire resistance periods to/EN 1365-2: 2014 (mins)
---|---
Minimum 1 x 15 mm thick Type A or Type F gypsum wallboard to EN 520 /|
30 minutes
Minimum 2 x 12.5 mm thick Type F gypsum Fireline to EN 520
| 60 minutes
Minimum 3 x 12.5 mm thick Type F gypsum Fireline to EN 520|
90 minutes
These products are suitable to install in fire protected timber floor and ceiling systems which have previously been successfully tested for at least 30 minutes, 60 minutes or 90 minutes to EN 1365-2 : 2014 /.
JOIST TYPES
Solid softwood or hard wood timber joists manufactured from strength grade C16 or greater, installed at centres not exceeding 600 mm.
INSTALLATION INSTRUCTIONS