CAUTION
Do NOT turn ON the power source, unless the preparation for test running is completed.
- Read this manual carefully before installation work for correct performance.
- Read this manual together with the “Installation & Maintenance Manual” for the indoor unit and Wireless Remote Control Switch.
- s the blank box for checking. Mark the blank box for the item after checking.
Before Installation and Operation
- This packing contains the following parts. Check the contents and number of the parts.
Model | Name | Q’ty | Remarks |
---|---|---|---|
SPWRK-V02 | Band | 1 | For Fixing Cable |
Screw | 2 | For Fixing Receiver Kit | |
Screw | 2 | For Fixing Clamp | |
Screw | 2 | For Fixing Receiver Kit | |
Screw | 2 | For Fixing Receiver Kit | |
Clamp | 2 | For Fixing Cable |
Installation of Wireless Receiver Kit
SPWRK-V02
NOTE:
Install the receiver kit onto the wall or ceiling near the indoor unit.
- Install the wireless receiver kit and indoor unit at the same time.
- In case that the wireless receiver kit is installed after installing the indoor unit, turn OFF the power source of the indoor unit.
- Check to ensure that the distance between the wireless receiver kit and the indoor unit is shorter than 5m. )
- Check to ensure that the distance between the wireless receiver kit and the EMI Source is larger than 3m.
- Remove the cover by using slotted screwdriver.
- Install the wireless receiver kit onto the wall or ceiling as follows:
- Prepare the following box (Field-Supplied).
- Insert the cable into the rigid metal conduit.
- Fix the fixing bracket of kit by using screw (Field-Supplied).
- Attach the cover same as A-(4).
- Remove the cover of indoor unit electrical control box and connect the cable to the terminals A and B of the terminal board (white).
After connecting the cable, bind up the remaining cable length portion by band (Factory-Supplied) and put them in the electrical control box.
NOTES:
- Protective box recommend size 3-59/64in.(99.5) by 3-41/64in. (92.5) by 1-3/8in.(35) mm, fixed hole center is 3 5/64in.(78) mm.
- Receiver panel with transparent plastic protective film, the official may required removed according to user.
- Remove the cover by using slotted screwdriver.
- When the back cover installation, to tidy up wiring, attention to the back cover marked \”switch\” that justify the board of SW1 switch position.
- If not according to the requirements of sequenced operations,may cause install or remove substrate difficulties.
Optional Functions
SPWRK-V02
-
Optional Function Setting
Open the lid of cover so that the following functions are available. -
Optional Setting for Dip Switch (SW3)
Operation Function | Dip Switch Setting (SW3) |
---|---|
1 | 2 |
Setting of Sub Receiver Kit | 0 |
Identifying of Indoor Units | x |
: ON, ✕: OFF
Others
-
Proceed the “TEST RUN” mode by using “Operation & Installation Manual” for the wireless remote control switch.
★ Turn OFF all power sources before setting the dip switches. -
Emergency Operation Setting (Refer to the figure of the item 3 “Optional Functions”.) In case that wireless remote control switch is unusable by batteries shortage, etc., perform emergency operation as follows.
(1) Switch “COOL”: Press “COOL” so that the cooling operation is started.
Press “COOL” again so that the cooling operation is stopped.
(2) Switch “HEAT”: Press “HEAT” so that the heating operation is started.
Press “HEAT” again so that the heating operation is stopped.
NOTE: During the emergency operation, the LED (yellow) blinks (0.5 second ON / 0.5 second OFF). -
Alarm Code Indication
-
In case that some trouble occures because of activation of safety device, etc., “RUN” (red lamp) blinks (0.5 second ON / 0.5 second OFF).
-
Refer to the Installation Manual for outdoor unit about Alarm Code List.
-
Alarm Code indicates the blinking times of “DEF” (green lamp) and “FILER” (yellow lamp) as shown bellow. “DEF” (green lamp):
The blinking is shown at the 2 digit of Alarm Code “FILTER” (yellow lamp): The blinking is shown at the 1 digit of Alarm Code (Alphabet Code: A=10 times, B=11 times, C=12 times, …..)
– Example – -
Run” (red lamp) blinking (1 second ON / 1 second OFF) indicates abnormal transmitting between Indoor Units and Outdoor Unit.
08.2022 V00
Documents / Resources
|
SPWRK SPWRK-V02 Wireless Receiver
Kit
[pdf] Instruction Manual
SPWRK-V02, SPWRK-V02 Wireless Receiver Kit, Wireless Receiver Kit, Receiver
Kit
---|---
|
SPWRK SPWRK-V02 Wireless Receiver
Kit
[pdf] Instruction Manual
SPWRK-V02, SPWRK-V02 Wireless Receiver Kit, Wireless Receiver Kit, Receiver
Kit
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>