Tongdy TON-0007 CO2 Monitor with Relay Instruction Manual
- June 12, 2024
- Tongdy
Table of Contents
**Tongdy TON-0007 CO2 Monitor with Relay Instruction Manual
**
Specifications
Power supply | 24VAC/VDC |
---|---|
Consumption | 1.5 W Max ; 0.8 W avg |
CO2 sensor | Infrared Sensor with lifetime of 15 yearsABC Logic Self |
Calibration (default: effective)
CO2 measuring range| 0~2,000ppm
Accuracy@25℃(77℉),2000ppm| ±40ppm + 3% of reading or ±75ppm (whichever is
greater)
Response time| <2 minutes for 90% step change
Warm up time for each turning-on| 2 hours (first time) 2 min (operation)
**** 6 LED lights| 1st green light on as CO2 measurement≤600ppm1st
and 2nd green lights on as CO2 measurement>600ppm and≤800ppm 1st yellow light
on as CO2 measurement>800ppm and≤1,200ppm1st and 2nd yellow lights on as CO2
measurement>1,200ppm and≤1,400ppm 1st red light on as CO2 measurement>1,400ppm
and≤1,600ppm1st and 2nd red lights on as CO2 measurement>1,600ppm
On/Off output for control CO2 level| <240VAC/30VDC 3A switching current
(resistance load),
Operation conditions| 0~50℃(32~122℉); 0~95%RH, non condensing
Storage conditions| 0~50℃(32~122℉);
Dimensions| 100mm×80mm×28mm (H X W X D)
Net weight| 180g
Installment standard| 65mm×65mm (2”×4”) wire box
Housing and protection class| PC/ABS fire proof material with IP30
Standard approval| CE-Approval
Version| TSM-CO2-1A1R-ST02_65 (SE)
Overview
Mounting and Wire Connection
- Notice the supply power voltage of the detector: 24VAC. Do not install the detector on voltages higher than marked on the detector.
- Firstly, prepare a flat head screwdriver and put it inside of the hole on the top of the detector housing following step 1, and then open the cover from step 2 to step 4 in next page fig.1.
- Mount the wall plate first, dimensions see next page fig. 2.
- Connect wires to terminal strips, (see fig. 3).
- Follow step 5 to step7 in fig. 4 to close the cover.
Fig.1 open the cover
Fig.2 wall plate
Fig.3 wiring diagram
Connection Terminal | Function | Electrical Data |
---|---|---|
1 | G+ | Power (+) |
2 | G0 | Power ground (-) |
4 | Ventilator | __ Relay output |
load)
5| Common
Fig.4 close the cover
Select CO2 level to Control the Relay
The CO2 level for control the relay turning on has been set to 1200ppm. If you need to change the CO2 level, open the cover after switch off, you may see two jumpers (J4 and J5) on the top of the circuit board and under the CO2 module. Take off the CO2 module, you can select the CO2 level to control the relay on /off by jumpers as below table.
Jumper | CO2 level | Relay turns on /turns off |
---|---|---|
J4-disconnect; J5-disconnect | 800ppm | CO2>900ppm,the relay on; CO2 |
<700ppm,the relay off
J4-connect; J5-disconnect| 1000ppm| CO2>1100ppm, the relay on; CO2
<900ppm, the relay off
J4-disconnect; J5-connect| 1200ppm (default)| CO2>1300ppm, the relay
on; CO2 <1100ppm, the relay off
J4-connect; J5-connect| 1400ppm| CO2>1500ppm, the relay on; CO2
<1300ppm, the relay off
Important Instructions:
- Don’t shake or hit the CO2 unit too much in shipment or in mounting to protect the internal infrared CO2 sensor from any damage and excursion of infrared receiver.
- When open the cover of the CO2 unit, you’ll see one PCB board mounted over another bigger PCB board. This upper small PCB board is loaded with CO2 sensor. Don’t uninstall the CO2 module without instruction from our engineers, in order not to cause any damage to the CO2 sensor. Please note: the pins on the CO2 module which connect with the bigger PCB board have direction. Wrong connection will cause the CO2 module and processor damage.
CONTACTUS – Weareheretohelp!