ADASH Ltd A4300 Loop-Relay Module User Manual
- June 12, 2024
- ADASH Ltd
Table of Contents
**ADASH Ltd A4300 Loop-Relay Module User Manual
**
Introduction
Adash also offers relay and loop modules. This manual is used for description
of these modules and their
specifications.
Relay module is mostly used for signalization in practice. Just to imagine how it can work in practice, see simple scheme below.
Let’s explain this scheme. We have connected all components (motor, online unit, relay module and some bulb) together. In this example, imagine, that value 5 mm/s is value of vibration which we would like to know that it is exceeded. For such a situation we can use relay module. We get 5 mm/s value on motor. Online unit will measure this value. This value is in this moment also known to relays – relay is closed. The bulb is lightened up. In that moment we know, that value on the motor exceeded the value we set – 5 mm/s.
Loop module takes advantage of the excellent property of the current – it is well transferred over long distances; therefore, it is possible to “lead” the current out of the high-interference environment. Then it is great to use loop module to identify error states. Every measured value is linearly converted to a 4-20 mA current loop value. Values shown outside of this range are good indicators for error states.
More specifications and descriptions of modules is shown in next chapters. If you are interested in more information about Adash online units (A3800), you can find them in the manual for online monitoring systems – www.adash.com.
Description – relay module
Relay module is described in this chapter. Relay module specification is in chapter: Technical specifications .
Front panel of the module
**Bottom panel of the module
**
Top panel of the module
Top panel of the relay module is shown in the picture below.
**
**Terminal blocks are used to connect supply wire or to connect several wires together in electrical engineering. Where to connect these terminal blocks and how they look like is shown in the following picture. We connect terminal block for relay 1 – 4.
Description – loop module
Loop module is described in this chapter. Relay module specification is in
chapter: Technical specifications.
Front panel of the module
**Bottom panel of the module
** Note:
AUX power is not needed for USB connection. It is needed only for Ethernet
connection.
Top panel of the module
Terminal blocks are used to connect supply wire or to connect several wires together in electrical engineering. Where to connect these terminal blocks and how they look like is shown in the following picture. We connect terminal block for loop 1 – 4 and their powering.
You can see top panel of loop module with terminal block connected in the following picture.
How to make module and A3800 communicate
Firstly, you need to connect module to online unit A3800. You do this with USB cable. USB port (module):
USB port (online unit A3800):
Next steps described below are for modules which were not set by Adash.
Modules and online
units A3800 are configured by Adash in production when you order them
together.
When module is ordered separately and you already have A3800, you need to
configure it by yourself.
See following steps to proceed with it further.
Connect to online unit with remote desktop connection. Once you are connected
you need to open device
manager to configure communication ports (between online unit and module).
There is a different guide how to open device manager based on version of
operating system in your online unit. OS – Windows 10/11: click to Windows
start button with right mouse button and go to Device manager.
OS – Windows 7: press Win + R and fill in devmgmt. msc command (see screenshot below). Confirm with OK and device manager opens.
Once you have Device manager window opened, go to section for Ports (shown in the next picture).
Find the port where your relay/loop module is connected (in our case it is
port COM6). On which port your
module is connected? Open Ports tab in device manager as shown in the
following picture.
Then disconnect the module from online unit. You can see which COM port number
is shown/hidden when you connect/disconnect your module.
Click on module port with right mouse button – Properties. Click on Port
Settings.
Click on Advanced
COM Port Number set to COM10 as below (it is default port set for communication between A3800 and module)
Confirm with OK button (confirm also the ‘Properties’ window).
Now you need to change config file for online unit. You can find it in this
location C:\A3716\data. There is config
file with name VA4.cfg. Open it with notepad. You need to change this part in
config file:
[ONLINE BOARD]
port=-1
Port value set to -1 means that online board is not connected. So, we need to
change it like this:
[ONLINE BOARD]
port=10
baud=115200
wdt=10000
keep vals=off
turn off when icp error=1
Once you paste this into config file, save the changes.
The next step is to create database in DDS and send this project to online
unit A3800 (in other words – start data collection – DDS – Online tab – Start)
– how to create database in DDS is described in manual for online monitoring
systems.
When correct communication between online unit A3800 and module is established
you can see LED light on for
RDY and PWR.
More settings
Next parameters for loops and relays are set in DDS software. More information
(how to do it, which parameters are set and what they mean) you can find in
DDS manual – www.adash.com .
DDS window for loop setting:
DDS window for relay setting:
ICP error signalization
In case of relay module, there is an option to signalize ICP error for sensors. For example, if the cable is corrupted or sensor is not working you can use this option of relay disconnection. What this actually means? When you turn on this function and cable connected to relay is corrupted, the system relay is closed (disconnected). It means that RDY LED turns off. In this case, you know that ICP error occurred.
How to set it correctly in configuration file?
As mentioned in chapters above, it depends if you order module with online
unit A3800 or separately. If module
is already set from production, this function (to disconnect the relay) is
automatically turned on.
If you order module separately, you need to set it according to following
steps.
Go to config file – you find it in this location C:\A3716\data – config file
is named VA4.cfg.
Find section for online board:
[ONLINE BOARD] port=-1
This section you need to change.
[ONLINE BOARD]
port=10
baud=115200
wdt=10000
keep vals=off
turn off when icp error=1
Technical specifications
References