ROSEMOUNT 0085 Pipe Clamp Sensor User Guide
- October 30, 2023
- ROSEMOUNT
Table of Contents
- ROSEMOUNT 0085 Pipe Clamp Sensor
- Product Information
- Product Usage Instructions
- Horizontal Orientation
- Vertical Orientation
- Special Considerations
ROSEMOUNT 0085 Pipe Clamp Sensor
Product Information
Rosemount 0085 Pipe Clamp Sensor Assembly
The Rosemount 0085 Pipe Clamp Sensor Assembly is a device used to measure temperature in pipes. It can be mounted on any orientation of the pipe and is designed for full or partial pipe flow applications. The assembly consists of a transmitter, a sensor with spring loaded adapter, nipple union of the extension, nut, O-ring, mounting hardware, corrosion protection inlay (optional), and a pipe clamp. The transmitter can be ordered assembled with the sensor, or separately.
Safety Messages
The document provides safety messages to ensure the protection of the end user’s assets. Unauthorized personnel must not have physical access to the equipment.
Product Certification
Refer to the Product Certification section of the Quick Start Guide documentation for certification information.
Product Usage Instructions
Location and Orientation
The Rosemount 0085 Pipe Clamp Sensor can be mounted in any
orientation for full pipe flow applications. For best practice,
mount the pipe clamp sensor on the upper half of the pipe. It can
be installed in any position around the circumference of the pipe
for partial pipe flow applications.
Horizontal Orientation
For full pipe flow applications, mount the pipe clamp sensor on the upper half of the pipe. Refer to Figure 3-1 in the Quick Start Guide for the recommended zone.
Vertical Orientation
The pipe clamp sensor can be installed in any position around the circumference of the pipe. Refer to Figure 3-2 in the Quick Start Guide for more information.
Special Considerations
- If the expected process temperature is near or beyond specification limits, consider using a remote mount configuration to isolate the transmitter from the process. Refer to the appropriate transmitter reference manual for temperature effects. Refer to Figure 3-3 in the Quick Start Guide for more information.
- Wireless transmitters with external antennas allow for multiple antenna configurations. All wireless transmitters should be appropriately 3 ft. (1 m) from any large structure or building to allow clear communication to other devices. Wireless transmitters with external antennas should be positioned vertically, either straight up or straight down.
About this guide
- This guide provides basic guidelines for Rosemount 0085 Pipe Clamp Sensor. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, explosion-proof, flameproof, or intrinsically safe (I.S.) installations. Refer to the Emerson.com/Rosemount.
- If the Rosemount 0085 Sensor was ordered assembled to a temperature transmitter, see the appropriate Quick Start Guide for information on configuration and hazardous locations certifications.
Safety messages
WARNING
Physical access
- Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’ equipment. This could be intentional or unintentional and needs to be protected against.
- Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility.
CAUTION
Conduit/cable entries
- Unless otherwise marked, the conduit/cable entries in the housing enclosure use a ½- NPT form. Only use plugs, adapters, glands, or conduit with a compatible thread form when closing these entries.
- Entries marked M20 are M20 x 1.5 thread form. On devices with multiple conduit entries, all entries will have the same thread form.
- When installing in a hazardous location, use only appropriately listed or Ex certified plugs, glands, or adapters in cable/conduit entries.
CAUTION
- Refer to Product Certification section of this Quick Start Guide documentation.
Rosemount 0085 Pipe Clamp Sensor Assembly exploded view
- A. Transmitter
- B. Sensor with spring loaded adapter
- C. Nipple union of the extension
- D. Nut
- E. O-ring
- F. Mounting hardware
- G. Corrosion protection inlay (optional)
- H. Pipe clamp
Location and orientation
- The pipe clamp sensor should be mounted on the outside section of the pipe where the process medium is in contact of the inside of the pipe wall.
- Ensure that the pipe surface is clean of debris.
- The pipe clamp sensor should be mounted in a secure position to ensure there is no rotational movement after installation.
- To ensure ingress protection, the nut of the Rosemount 0085 Pipe Clamp sensor can be tightened to a torque of 2 lbf · in to compress the O- ring to form a seal. The nut can be accessed and tightened by removing the sensor and the nipple union of the extension. Refer to the Rosemount 0085 Pipe Clamp Sensor Assembly exploded view for the location of each part.
Horizontal orientation
- Though the Rosemount 0085 Pipe Clamp Sensor can be mounted in any orientation for full pipe flow applications, the best practice is to mount the pipe clamp sensor on the upper half of the pipe.
Vertical orientation
- The pipe clamp sensor can be installed in any position around the circumference of the pipe.
Special considerations
- Under most circumstances, the Rosemount 0085 Pipe Clamp Sensor can be mounted in a direct mount configuration. Since heat from the process is transferred from the pipe clamp sensor to the transmitter housing, if the expected process temperature is near or beyond specification limits, consider using a remote mount configuration to isolate the transmitter from the process. Refer to the appropriate transmitter reference manual for temperature effects.
- Wireless transmitters with external antennas allow for multiple antenna configurations. All wireless transmitters should be appropriately 3 ft. (1 m) from any large structure or building to allow clear communication to other devices. Wireless transmitters with external antennas should be positioned vertically, either straight up or straight down.
Install pipe clamp sensor
- Select the area for pipe clamp sensor installation with the recommendations outlined in Horizontal orientation. Mount the pipe clamp sensor on the pipe and tighten the bolts. Ensure the sensor passes through the hole of the pipe clamp and has direct contact between the sensor tip and pipe. Refer to Figure 3-3 for more information. Tighten the bolts to secure the pipe clamp sensor to the pipe.
- A. Sensor
- B. Extension of pipe clamp
- C. Pipe clamp
- D. Pipe
Install transmitter
- See the appropriate transmitter reference manual for sensor-transmitter installation.
Commission transmitter
- See the appropriate transmitter reference manual for transmitter commissioning instructions.
Installing optional accessories
Corrosion protection inlay
- The corrosion protection inlay provides a layer of protection to help minimize the possibility of dissimilar metal corrosion between the pipe clamp and pipe. The inlay is installed in between the pipe clamp and the pipe. Ensure the sensor is clearing the hole in the protection inlay after installation.
- A. Extension of pipe clamp
- B. Pipe clamp
- C. Sensor
- D. Corrosion protection inlay
- E. Pipe
Replacement sensor
- Procedure for replacing the spring-loaded sensor in the pipe clamp sensor.
- The spring-loaded sensor can be ordered for replacement using the Rosemount 0085 Pipe Clamp Sensor Product Data Sheet.
Procedure
- Loosen and remove the original sensor from the extension of the pipe clamp.
- Add pipe compound or PTFE tape (where local piping codes allow) to the threads of the new sensor.
- Insert the new sensor into the extension of the pipe clamp sensor and ensure the sensor tip passes through the hole of the pipe clamp. Refer to the Replacement sensor for more information.
- Screw in the sensor and tighten to 24 ft-lbs of torque.
Rosemount X-well™ Technology considerations
- Rosemount X-well Technology is for temperature monitoring applications and is not intended for control or safety applications. It is available in the Rosemount 3144P Temperature Transmitter and 648 Wireless Temperature Transmitter in a factory-assembled direct mount configuration with a Rosemount 0085 Pipe Clamp Sensor. It cannot be used in a remote mount configuration.
- Rosemount X-well Technology will only work as specified with factory supplied and assembled Rosemount 0085 Pipe Clamp silver tipped single element sensor with an 80 mm extension length. It will not work as specified if used with other sensors.
- Installation and use of an incorrect sensor will result in inaccurate process temperature calculations. It is extremely important the above requirements and installation steps are followed to ensure Rosemount X-well Technology works as specified.
- In general, pipe clamp sensor installation best practices shall be followed
- (see Location and orientation ) as well as the specific Rosemount X-well Technology requirements noted below:
- Direct mounting of the transmitter on a pipe clamp sensor is required for Rosemount X-well Technology to properly function. Figure 6-1 displays a transmitter/pipe clamp assembly that is in a direct mount configuration.
- Assembly shall be installed away from dynamic external temperature sources such as a boiler or heat tracing.
- The pipe clamp sensor makes direct contact with the pipe surface. Moisture buildup between the sensor and the pipe surface or the sensor hangup in the assembly can cause inaccurate process temperature calculations. Refer to Install pipe clamp sensor for more information on proper sensor to pipe surface contact.
- Insulation at least ½-in. thick (with R-value of > 0.42 m2 × K/W) is required over the sensor clamp assembly and the sensor extension up to the transmitter head to prevent heat loss. Apply a minimum of six inches of insulation on each side of the pipe clamp sensor. Care should be taken to minimize air gaps between insulation and pipe. See Figure 6-2 for more information.
Note
- DO NOT apply insulation over the transmitter head.
- Although it will come from the factory configured as such, ensure that the pipe clamp RTD sensor is assembled in the correct wire configuration. Refer to the appropriate transmitter reference manual for correct wire configurations.
Product certifications
Rev 1.26
European Directive information
- A copy of the EU Declaration of Conformity can be found at the end of this guide. The most recent revision of the EU Declaration of Conformity can be found at Emerson.com/Rosemount.
Ordinary location certification
- As standard, the transmitter has been examined and tested to determine that the design meets the basic electrical, mechanical, and fire protection requirements by a nationally recognized test laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).
North America
- The US National Electrical Code® (NEC) and the Canadian Electrical Code
(CEC) permit the use of Division marked equipment in Zones and Zone marked equipment in Divisions. The markings must be suitable for the area classification, gas, and temperature class. This information is clearly defined in the respective codes.
E5 USA Explosionproof
- Certificate: FM17US0170X
- Standards: FM Class 3600:2011, FM Class 3611:2004, FM Class 3615:2006, FM Class 3810:2005, ANSI/NEMA 250:1991
- Markings: XP CL I, DIV 1, GP B, C, D; T5 (-50 °C ≤ Ta ≤ 85 °C) ; Type 4X; Installed per 00068-0013
E6 Canada Explosionproof
- Certificate: 70044744
- Standards: CAN/CSA C22.2 No. 0:2010, CAN/CSA C22.2 No. 30-M1986
- (R2012), CAN/CSA C22.2 No. 94-M1991 (R2011), CAN/CSA C22.2 No. 61010-1:2012
- Markings: XP CL I, DIV 1, GP B, C, D; T6 (-50 °C ≤ Ta ≤ +80 °C), T5 (-50 °C ≤ Ta ≤ +95 °C); Seal not required; installed per Rosemount drawing 00068-0033; Type 4X and IP 66/67; Vmax 35 VDC, 750 mW max
Europe
E1 ATEX Flameproof
- Certificate: DEKRA 19ATEX0076X
- Standards: EN IEC 60079-0:2018, EN 60079-1:2014
- Markings: II 2 G Ex db IIC T6…T1 Gb, (-60 °C ≤ Ta ≤ +80 °C)
Special Conditions for Safe Use (X):
- Flameproof joints are not intended for repair.
- Non-Standard Paint options may cause risk from electrostatic discharge. Avoid installations that cause electrostatic build-up on painted surfaces, and only clean the painted surfaces with a damp cloth. If paint is ordered through a special option code, contact the manufacturer for more information.
- When provided on their own, the adapter style sensors must be assembled to a suitable Ex db enclosure with a free internal volume no greater than 550 cm3.
Process temperature range (°C)1| Ambient temperature range (°C)1| Temperature
class
---|---|---
-60 °C to +80 °C| -60 °C to +80 °C| T6
-60 °C to +95 °C| -60 °C to +80 °C| T5
-60 °C to +130 °C| -60 °C to +80 °C| T4
-60 °C to +195 °C| -60 °C to +80 °C| T3
-60 °C to +290 °C| -60 °C to +80 °C| T2
-60 °C to +440 °C| -60 °C to +80 °C| T1
I1 ATEX Intrinsic Safety
- Certificate: Baseefa16ATEX0101X
- Standards: EN 60079-0:2012+A11:2013, EN 60079-11:2012
- Markings: II 1 G Ex ia IIC T5/T6 Ga SEE CERTIFICATE FOR SCHEDULE
Thermocouples; Pi = 500 mW | T6 -60 °C ≤ Ta ≤ +70 °C |
---|---|
RTDs; Pi = 192 mW | T6 -60 °C ≤ Ta ≤ +70 °C |
RTDs; Pi = 290 mW | T6 -60 °C ≤ Ta ≤ +60 °C |
T5 -60 °C ≤ Ta ≤ +70 °C
Special Condition for Safe Use (X):
- The equipment must be installed in an enclosure that affords it a degree of ingress protection of at least IP20.
International
E7 IECEx Flameproof
- Certificate: IECEx DEK 19.0041X
- Standards: IEC 60079-0:2017, IEC 60079-1:2014
- Markings: Ex db IIC T6…T1 Gb, (-60 °C ≤ Ta ≤ 80 °C)
Special Conditions for Safe Use (X):
- Flameproof joints are not intended for repair.
- Non-Standard Paint options may cause risk from electrostatic discharge. Avoid installations that cause electrostatic build-up on painted surfaces, and only clean the painted surfaces with a damp cloth. If paint is ordered through a special option code, contact the manufacturer for more information.
- When provided on their own, the adapter-style sensors must be assembled to a suitable Ex db enclosure with a free internal volume no greater than 550 cm3.
Process temperature range (°C)1| Ambient temperature range (°C)1| Temperature
class
---|---|---
-60 °C to +80 °C| -60 °C to +80 °C| T6
-60 °C to +95 °C| -60 °C to +80 °C| T5
-60 °C to +130 °C| -60 °C to +80 °C| T4
-60 °C to +195 °C| -60 °C to +80 °C| T3
-60 °C to +290 °C| -60 °C to +80 °C| T2
-60 °C to +440 °C| -60 °C to +80 °C| T1
EACH
EM Explosionproof/Flameproof
- Markings: 1Ex db IIC T6…T1 Gb X; T6 (-55 °C to 40 °C), T5…T1 (-55 °C to 60 °C) IP66, IP68
- Special Condition for Safe Use (X): See certificate.
- IM Intrinsic Safety
- Markings: 0Ex ia IIC T5/T6 Ga X; T5, Pi = 0.29 W, (-60 °C to +70 °C); T6, Pi = 0.29 W, (-60 °C to +60 °C); T6, Pi = 0.192 W, (-60 °C to +70°C)
- Special Condition for Safe Use (X):
- See certificate.
Korea
- EP Explosionproof/Flameproof
- Certificate: 13-KB4BO-0560X
- Markings: Ex d IIC T6…T1; T6(-50 °C ≤ Tamb ≤ +40 °C), T5…T1(–50 °C ≤
- Tamb ≤ +60 °C)
- Special Condition for Safe Use (X): See certificate.
Process temperature limits
Table 7-1: Sensor Only (No Transmitter Installed
Extension length
| Process temperature (°C)
---|---
Gas| Dust
T6| T5| T4| T3| T2| T1| T130 °C
Any extension length| 85| 100| 135| 200| 300| 450| 130
Table 7-2: Transmitter
Extension length
| Process temperature (°C)
---|---
Gas| Dust
T6| T5| T4| T3| T2| T1| T130 °C
No extension| 55| 70| 100| 170| 280| 440| 100
3-in. extension| 55| 70| 110| 190| 300| 450| 110
6-in. extension| 60| 70| 120| 200| 300| 450| 110
9-in extension| 65| 75| 130| 200| 300| 450| 120
Adhering to the process temperature limitations of Table 7-3 will ensure that
the service temperature limitations of the LCD cover are not exceeded. Process
temperatures may exceed the limits defined in Table 7-3 if the temperature of
the LCD cover is verified to not exceed the service temperatures in Table 7-4
and the process temperatures do not exceed the values specified in Table 7-2.
Table 7-3: Transmitter with LCD Cover – Process Temperature (°C)
Extension length
| Gas| Dust
---|---|---
T6| T5| T4…T1| T130 °C
No extension| 55| 70| 95| 95
3-in. extension| 55| 70| 100| 100
6-in. extension| 60| 70| 100| 100
9-in. extension| 65| 75| 110| 110
Table 7-4: Transmitter with LCD Cover – Service Temperature (°C)
Extension length
| Gas| Dust
---|---|---
T6| T5| T4…T1| T130 °C
No extension| 65| 75| 95| 95
Declaration of Conformity
Figure 8-1: Rosemount 0085 Pipe Clamp Sensor Declaration of Conformity
Specifications
Material selection
Emerson provides a variety of Rosemount product with various product options
and configurations including materials of construction that can be expected to
perform well in a wide range of applications. The Rosemount product
information presented is intended as a guide for the purchaser to make an
appropriate selection for the application. It is the purchaser’s sole
responsibility to make a careful analysis of all process parameters (such as
all chemical components, temperature, pressure, flow rate, abrasives,
contaminants, etc.), when specifying product, materials, options and
components for the particular application. Emerson is not in a position to
evaluate or guarantee the compatibility of the process fluid or other process
parameters with the product, options, configuration or materials of
construction selected.
Rosemount pipe clamp platinum RTD
- Nominal resistance
- In accordance with DIN EN 60751/IEC 751:1983 incorporating Amendments 1 and 2, the nominal resistance is defined:
- 100 Ω RTD at 0 °C
- α = 0.00385 Ω x °C/Ω, averaged between 0 and 100 °C
- Limit deviations
- Tolerance Class B, as standard t = ±(0.3 + 0.005 x [t]); temperature range
- -328 to 572 °F (-200 to 300 °C)
- Tolerance Class A, as option t = ±(0.15 + 0.002 x [t]); temperature range -58 to 572 °F (-50 to 300 °C)
- Process temperature range
- -328 to 572 °F (-200 to 300 °C)
- Ambient temperature range
- -40 to 185 °F (-40 to 85 °C)
- Self-heating
- 0.15 K/mW when measured as defined in DIN EN 60751:1996
- Insulation resistance (RTD)
- 1,000 MΩ minimum insulation resistance when measured at 500 Vdc at room temperature
- Sheath material
- 321 SST with mineral-insulated cable construction and silver or nickel tip
- Lead wires
- PTFE-insulated, silver-coated copper wire (Figure 10-1)
- Identification data
- The model and serial numbers are engraved directly on the spring-loaded adapter.
- Ingress Protection (IP) rating for connection head
- IP68 and NEMA® 4X
- A. Red
- B. White
- C. Yellow
- D. Black
- E. Blue
- F. Green
- Vibration effect
- The Rosemount 0085 Pipe Clamp Sensor is tested to the following
- specifications with no effect on performance per IEC 60770-1, 2010:
Frequency | Vibration |
---|---|
10 to 60 Hz | 0.075 mm displacement |
60 to1000 Hz | 1 g (10 m/s2) peak acceleration |
Functional specifications
- Power Overvoltage Category I
- Environmental Pollution Degree 4
- For more information: Emerson.com
- ©2022 Emerson. All rights reserved. Emerson Terms and Conditions of Sale are available upon request.
- The Emerson logo is a trademark and service mark of Emerson Electric Co.
- Rosemount is a mark of one of the Emerson family of companies.
- All other marks are the property of their respective owners
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>