AQUAPHOR S550 Water Softener Filter Instruction Manual
- June 10, 2024
- AQUAPHOR
Table of Contents
- S550 Water Softener Filter
- Specifications
- Source water requirements
- Softener delivery set
- General softener device
- Controller
- Installing a softener
- Controller setup
- Quick Setup / Basic Settings
- Mode of enhanced washing from iron
- Recommendations for effective use softener
- Safety regulations
- Disposal
- Troubleshooting
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
S550, S550 P1 Water Softener Filter
Instruction Manual
S550 Water Softener Filter
Congratulations on your purchase of a high quality filter for softening and
deferrization of water Aquaphor.
The Aquaphor water softener filter (hereinafter referred to as the softener)
is a high-performance device that removes high concentrations of hardness
salts, iron and manganese, ensures long-term operation without replacing the
sorbent, and minimizes salt and water consumption during regeneration.
Please read this manual carefully before operating the product and keep it for
future reference.
The manufacturer reserves the right to make changes to the design of the
softener without reflecting them in the instruction manual. This manual
provides installation, operation and maintenance information for the softener
models S550, S550 P1.
Specifications
Maximum capacity, g | 1100 |
---|---|
Maximum compensated hardness, mg/l | 1200 |
Maximum concentration of dissolved iron and manganese, mg/l* | 10 |
Minimum pH | 6 |
Temperature of water and environment, °C | +5…+38 |
Water pressure, MPa | 0.14–0.7 |
Minimum water flow for backwash, l/min** | 7.6 |
Maximum flow to drain during regeneration, l/min | 9.1 |
Nominal / maximum flow, l / min | 23 / 35 |
Pressure loss at flow 22.7 l/min (6 gpm), MPa*** | 0.1 |
Capacity in HE mode, kg of salt / gram of hardness | 0.8 / 465 |
Capacity in HC mode, kg of salt / gram of hardness | 2.1 / 903 |
Maximum capacity in AU mode, kg of salt / gram of hardness | 3.3 / 1100 |
Regeneration method | Intelligent, by water meter |
Power options | 12 VAC; 50/60 Hz; 0.015 kWh |
Connection ports (NPT) | 1″ (MNPT) |
Minimum drain line diameter, mm (in) | 16 (5/8) |
Filtration tank size (ID × H), mm | 267 × 277 |
Height, cm | 55.4 |
Base, cm | 32.2 × 43.2 |
Gross weight, kg | 35 |
Filter medium and its quantity
Superfine monodisperse ion exchange resin, l| 15
Quartzite, kg| 0.8
or KDF85****, l| 0.35
* Reducing the concentration of iron to 0.3 mg/l and below, manganese –
to 0.1 mg/l and below.
** The flow rate must be checked at the end of the drain line.
*** For the correct selection of the filter, use the operating capacity
and pressure drop. Long-term operation at flows higher than those tested (more
than 30 l/min) may lead to a decrease in cleaning efficiency.
**** Only for version S550 P1.
Source water requirements
Source water requirements | Softener S550 | Softener S550 P1 |
---|---|---|
Water hardness, mg-eq / I* | no more than 24 | |
Content of divalent iron, mg/I* | no more than 10 | |
Content of ferric iron, mg/I | no more than 0.3 | |
Manganese content, mg/I* | no more than 3 | |
pH | 6 to 9 | |
Temperature, °C | from +5 to +38 | |
Content of oil products, mg/I | no more than 1 | |
Hydrogen sulfide, mg/I | no more than 0.03 | no more than 1 |
Permanganate oxidizability, mg02/1 | no more than 5 | |
Silicon, mg/I | no more than 10 |
- The total “iron + hardness + manganese”, in terms of calcium carbonate, should not exceed the maximum compensated hardness indicated in the “Technical characteristics” table.
ATTENTION! The softener does not purify water from colloidal iron or iron contained in organic complexes.
Softener delivery set
1 | Complete softener | 1 pc. |
---|---|---|
2 | Overflow fitting | 1 pc. |
3 | Drainage tube D=16 mm (5/8″), L=2.5 m | 1 pc. |
4 | Flexible hose 1″ by 3/4″ (3/4″ by 3/4″) with o-rings | 2 pcs. |
5 | Power supply 12 VAC | 1 pc. |
6 | Controller | 1 pc. |
7 | Drain pipe 1/2″ | 1 pc. |
For Owner’s Reference
Aquaphor Softener Model|
---|---
Serial #|
Date of Installation:|
Hardness:|
Iron:|
pH:|
Water Pressure:|
Water Temperature:|
General softener device
Appearance
Lid removal
To access the valve and controller, first remove the front part by grasping
the cutout at the front of the lid, then remove the rear lid by pulling it up
and towards the front of the softener housing.
Bypass valve
The softener is equipped with a bypass valve (fig. 1). The bypass valve will
allow you to turn off the softener in the event of a malfunction or leakage.
It also makes it possible to use untreated water for watering plants.
The bypass valve is located in the main control valve assembly. To switch to
the bypass line, turn the valve handle to the “Bypass” position (fig. 1).
Water will enter the house past the softener, without treatment. To prevent
untreated water from entering the house, do not use the water in the house
when the softener is in Bypass mode. Do not forget to switch the softener to
normal operation (filtration) by turning the knob to the “Service” position
(fig. 1), after repairing the device or using untreated water.
To obtain water of comfortable hardness, you can use the scheme shown in fig.
5, mixing the source water with purified water.
NOTE: It is not recommended to use source water admixture with high
content of iron and/or manganese.
Controller
The controller has four control buttons, LCD display (fig.
2). The controller controls the valve actuators during regeneration. Using the
control panel of the controller, the value of the compensated hardness, the
current time, the regeneration time are entered and the parameters of the
softener are selected, as well as the status of the device is viewed. For the
filter to work correctly, the controller must be configured correctly.
The controller receives data on water consumption from the flow meter. Based
on these data and the selected operating parameters, the controller starts the
regeneration of the softener at the appointed time.
The controller saves settings in non-volatile memory even after a power
outage.
The controller is equipped with a non-volatile power supply that allows for
two days to maintain the built-in timer
Control buttons
User Settings.
Change user settings.
Start regeneration manually. It is used when the softener is connected for the
first time or for forced regeneration, for example, if the softener runs out
of salt.
Start regeneration manually.
-
Press and hold the button for about 5 seconds.
-
The softener will start regenerating and will display the current stage of regeneration on the display.
-
After all regeneration steps have been completed, the display will return to normal operating mode.
Interruption of a running regeneration cycle (only used for system diagnostics). -
Press and hold the button for 5 seconds after the regeneration process starts.
-
The display will show the stage number (for example – 01).
-
If the controller does not move to the next stage within 20 seconds, press and hold the button for about 2 seconds, the controller will proceed to the next stage.
NOTE: Each regeneration step can only be interrupted once it has started.
To move to the next stage of the regeneration mode, press .
Enable / disable the enhanced regeneration function.
This function can be performed as part of the service in the following cases:
- operation of the softener on water containing dissolved iron,
- with a decrease in the quality of cleaning due to water consumption, significantly exceeding the resource of the softener before regeneration,
- with virtually no regeneration due to insufficient salt, lack of input water or electricity.
In this mode, the softener will be flushed every other day, consuming 1.6 kg salt per regeneration. The softener in the mode of enhanced cleaning from iron should work for at least 2 weeks. The increased frequency of regenerations will help to remove the accumulated iron in the ion exchange resin bed. This service procedure is recommended to be carried out at least once a year.
Controller Screen The main screen displays the volume of water in liters
(or gallons) that will be treated by the softener before the next automatic
regeneration. On average, an adult spends 280 l water per day. The volume of
water until the next water regeneration is indicated in hundreds or thousands
of liters, depending on the value. For example, the number 33 would mean 33
000 l if x 1000 is shown on the display at the same time, and 3300 l if this
indicator is inactive.
During regeneration, the number of the stage currently in progress will flash
on the main screen:
- – First backwash.
- – salt regeneration / slow washing.
- – second backwash
- – topping up the brine tank.
HO – return to working position. After the regeneration is completed, the
display will again show the amount of water until the next regeneration in
hundreds of gallons or hundreds / thousands of liters. The duration of
regeneration is 30– 40 minutes.
Regeneration progress indicator.
Indicates that the softener is auto-regenerating or a manual regeneration has
started.
Water consumption indicator. “Droplets” on the display “run” as water
flows through the softener. It is convenient for monitoring water consumption
and for detecting water leaks. Mode 96h. When this mode is enabled,
regeneration occurs once every three to four days (72–96 hours) if there is no
regular regeneration during this period of time. This is necessary so that the
dissolved iron extracted from the water does not precipitate inside the
softener. If there is dissolved iron and / or manganese in the source water,
the 96h mode must be turned on. Time of day indicator. Displayed when the system is set to
the time of day.
Regeneration time indicator. The dial with the symbol R is displayed if
the time of day is set for the regeneration process.
Enhanced regeneration indicator from iron is displayed when the function
is active
Installing a softener
The water softener must be connected in accordance with local plumbing
regulations.
To connect the softener, it is recommended to contact the Aquaphor service
department or Aquaphor regional dealers.
The connection, setup and operation of the device must be carried out within
the limits of operation specified in this manual. Failure to comply with the
requirements of the manual can reduce the effectiveness of flushing and lead
to improper operation of the softener and its failure.
Before installing the softener, check the quality of the water and the
parameters of the water supply, power supply and sewerage:
Water quality
Undissolved impurities
If the source water contains sand, sulfur, micro-organisms, algae, oils or
other impurities, the water must be pretreated.
We recommend installing an Aquaphor pre-filter.
Iron
The concentration of dissolved iron should not exceed 7 mg/l for the S550
softener, and it is also important to know what form it is in.
- divalent iron (often referred to as “dissolved iron”) – The only form of iron that can be removed by the S550 softener.
- ferric iron (undissolved iron) – Precipitation of iron hydroxide. Particles of such iron can clog the ion exchanger layer. Trivalent iron must be filtered before water is supplied to the softener.
- iron in organic compounds – a dissolved form of iron associated with organic compounds, usually humic or folic acids. Water containing iron in this form is usually colored brown (“peaty water”). Additional equipment is needed to remove this form of iron.
If the water contains ferrous iron, it is recommended to flush the softener
with an ion exchanger cleaner every 6 months. Follow the instructions given in
the ion exchanger cleaner data sheet.
Manganese
The manganese content should not exceed 3 mg/l.
ATTENTION! The total content of iron and manganese should not exceed 7
mg/l.
The pH of the water must be greater than 6. If the pH of the source water
is less than 6, it is recommended to install a corrective pH filter.
Hardness of water
Model S550 softens water with hardness up to 17 mg-eq / l (840 mg/l in terms
of CaCO3).
Water supply parameters
Water pressure should be within 0.14 to 0.7 MPa (1.4 – 7 bar). For stable
suction of the brine during regeneration, it is recommended to supply water
with a pressure of at least 0.2 MPa (2 bar).
Plumbing performance
The minimum required flow for regeneration is 9 l in a minute.
Water temperature not less than +5 and not more than +38 °C.
Sewerage
The unit drain must be routed to a waste water outlet, such as a drain or
washing machine drain, in accordance with all local and national plumbing
codes. An air gap or siphon must be provided to prevent backflow (see the
“Installation and commissioning step by step” section).
Power supply
The power supply is designed for mains voltage of 220 VAC with a frequency of
50 Hz. If there is a possibility of voltage deviation from the specified
values by more than 5–10 %, use a voltage stabilizer. This will prevent
malfunctions and failure of both the power supply and the electronic
components of the softener.
ATTENTION! It is not recommended to separately connect the softener to
uninterruptible power supplies, as this may cause failures in the regeneration
processes. Connection is only possible in conjunction with a pumping station.
If you have any questions, please contact support. For support information,
see the General Information section and the warranty card.
Step-by-step instructions for installing a softener
The softener connection must be made in accordance with local plumbing
codes.
The connection, setup and operation of the device must be carried out within
the limits of operation specified in this manual. Failure to follow these
guidelines may reduce flushing efficiency and result in softener malfunction
or failure.
How to do:
- The softener must be installed after the hydraulic accumulator tank and pump control automation systems.
- The softener must be installed in front of the water heater and other appliances that consume water.
- The softener must be installed at least 1 m from heating appliances.
- It is not recommended to install the softener on a heated floor, as this may cause excessive evaporation from the brine tank and fouling of the softener surfaces with salt crystals.
- Water for watering a lawn or garden does not require softening and filtration, so this water can be drained before the softener.
- When connecting the softener, it is recommended to provide a bypass valve – “bypass” (see fig. 5). The by pass valve will simplify the maintenance of the softener and will provide the supply of unsoftened water in case of emergency when the softener is dismantled. It is also recommended to drain the first portions of contaminated water through the bypass after maintenance work on the well, water supply or pump.
- If the length of the pipe between the softener and the water heater is less than 3m, it is recommended to install a non-return valve on this line as close as possible to the water heater. Make sure the water heater is set to the correct temperature and the safety valve is correct and in good working order.
You cannot do:
- Install and operate the softener in a room where the temperature can drop below +5 °C.
- Install and operate the softener in a room with humidity over 70 %.
- Install the softener near heating appliances.
- Connect the softener to the water supply in the opposite direction.
Step 1. Prepare a place for connection
-
Turn off the power and water supply to the water heater. For gas water heaters, additionally turn the gas valve to the “Maintenance” or “Off” position. (See instructions for your water heater).
-
Turn off the water supply. Open hot and cold water taps to relieve pressure in the lines. Check the water supply for lime deposits, rust or other contaminants.
Clean or replace clogged plumbing. -
Organize the insertion point of the softener, according to fig. 3 so as to prevent axial distortions and tensions during installation, as this can lead to damage to the bypass assembly or softener valve.
-
Arrange an electrical outlet at a distance of no more than 2 m.
NOTE: The bore diameter of the pipe from the accumulator tank to the
softener must be at least 3/4″.
Step 2: Connect the softener to the water supply
The softener must be connected to the water line in accordance with national
and local building, plumbing, and electrical codes.
- Remove the softener lid, to do this, first remove the front lid by grasping the cutout in its front part, then remove the lid by pulling it up and towards the front of the softener housing.
- Empty the salt compartment from all packaging and installation materials.
- Make sure that the shims are inserted into the union nuts of the flexible hoses. Connect the softener to the water supply using flexible hoses.
NOTE: Teflon tape or sealant must not be used when connecting with flexible hoses. When connecting with other supply fittings, use only Teflon tape to seal the connections.
- Check that the direction of water flow is correct using the arrow on the bypass valve (see section “Bypass valve”).
ATTENTION! Do not connect the softener to the water supply in the opposite direction! This can lead to softener failure.
- Tighten the flexible hose nuts. Do not apply excessive force so as not to damage the threaded part of the fittings.
ATTENTION! To ensure the possibility of dismantling the filter, it is
recommended to use a bypass circuit from standard components (fig. 5).
Step 3. Connect the overflow line
- The overflow line is designed to drain excess water when the brine tank is overfilled or the softener depressurizes.
- Screw the elbow overflow fitting included with the softener into the hole on the back of the softener housing and point downwards (see fig. 6).
- Install a flexible tube with an inner diameter 12 mm (1/2”) (smaller tubing is not permitted) between an overflow fitting and a drain, washing machine drain, or other suitable waste water outlet. This pipe is not included with the softener.
- Removal of excess water through the overflow line occurs by gravity. Make sure the overflow line terminates at a drain that is at least 8 cm below the edge of the overflow fitting. Provide an air gap of at least 5 cm.
- It is not allowed to bend the outlet tube of the overflow line and lift it in height.
ATTENTION! The overflow line is part of the
emergency leak protection system. In its absence, in case of malfunction of
the softener and overflow of the brine tank, water leakage is possible.
Step 4 Connect the drain line
The drain line is designed to drain water during regeneration.
- Connect the drain line to the drain port (see fig. 7) using the 5/8” ID (~16mm) flexible hose supplied with the softener. Reducing the diameter is not allowed.
- Run a drain line to a drain, washing machine drain, or other suitable sewage outlet. Provide an air gap of at least5 cm between the drain line and the maximum fill level of the wastewater receiver in order to prevent backflow.
- The drainage line must be laid in such a way that the distance to the drain is minimal. The drainage line can be raised to a height of up to 1.5 m above the drain hole of the device, while the pressure in the water supply must be at least 0.275 MPa (2.75 bar).
- The drain line may be extended with a pipe or hose of at least 3/4”.
- The drainage line should not have kinks, creases, twists or other damages that restrict the flow of water.
ATTENTION! It is not allowed to combine drainage (pressure) and overflow
(gravity) lines by means of tees, etc.
ATTENTION! During the regeneration process, small solid particles may
appear in the drain line, which does not indicate a malfunction of the
softener.
Step 5. Flushing the water supply
- Make sure the softener valve is in the “Bypass” position (see fig. 1) Turn on the water supply.
- Open the nearest cold water faucet and flush the pipes of solder flux residue and other foreign material.
NOTE: When the softener is in Bypass mode, the water is not treated.
Step 6. Make sure the connections are tight
Close all outlet taps to pressurize the system.
Check all lines and connections for leaks. If a leak is found:
a) turn off the water supply;
b) fix all leaks;
c) turn on the water supply.
Slowly move the valve to the “Service” position (see fig. 1), slowly, to avoid
water hammer, fill the softener.
Open the nearest cold water faucet to bleed air from the system. When water
comes out of the faucet without air, close the faucet and check for leaks.
Step 7. Connecting the controller and power supply
NOTE: Make sure the controller is securely attached to the three latches
on top of the valve.
Connect to the back of the controller:
- flow sensor connector (fig. 8),
- motor connector,
- power supply connector.
|
---|--- - Lay the power supply wire at the outlet of the water lines. Connect the power supply to an outlet.
- Make sure the outlet to which the softener is connected does not have an ON/OFF switch.
Step 8. Adjust the softener controller according to the Controller Setup
section.
Step 9. Flush the softener
- Pour 8 l of water into the brine tank.
- Make sure the softener is in filtration mode and the water supply is turned on.
- Perform a forced regeneration. To do this, press and hold the R button for about 5 seconds until the numbers 01 appear on the display and the regeneration process starts.
- During the regeneration, which lasts 30–40 minutes, the device will first take and then add water to the brine tank to the desired level.
ATTENTION! The brine tank should only be filled with water when the
softener is started. After starting, topping up water is carried out
automatically.
Step 10. Load Salt into the Brine Tank
Load salt into the brine tank up to 25 kg. Use purified tableted or granulated
table salt (NaCl). Do not use these two types of salt at the same time. Use
only high-quality tableted or granulated salt, such as AQUAPHOR. Poor quality
salt can cause a decrease in the efficiency of regeneration or the failure of
the softener.
NOTE: Always keep the salt level above the water level.
For convenience, when adding salt, fully load the tank.
After adding salt, including adding after salt is completely used up, wait at
least two hours before starting regeneration. This is necessary for the
formation of a saturated saline solution.
Step 11. Complete the installation process
Make sure the bypass valve is in the “Service” position (see fig. 1).
Make sure the water supply is turned on.
If there is an external bypass circuit, make sure the taps are in the correct
position (see fig. 5).
Turn on the power and water supply to the water heater (if any). For gas water
heaters, turn the gas valve to the “Operation” position (see the instructions
for your water heater).
Open the nearest cold water faucet and run the softener for 20 minutes or
until about 270 liters water.
Make sure that the water consumption indicator on the controller display is
working – this indicates the water consumption and the operation of the liter
counter.
Replace the softener cover.
Controller setup
For the correct operation of the softener, it is necessary to enter into the
processor data on the content of hardness salts, iron and manganese in the
water.
To do this, it is necessary to calculate the total parameter, which will
include all these pollutants. This parameter is called “compensated
stiffness”.
Generally, in water analysis, total hardness is expressed in mg-eq / l.
ATTENTION! German (DH) and French (ºF) are differ from mg-eq / l.
To calculate the “compensated hardness” it is necessary:
- Multiply the number of mg-eq / l by 50.
- Add the concentrations of iron (mg/l) and manganese (mg/l) and multiply the sum by 85.
- Add up both items.
EXAMPLE:
Total hardness = 6.84 mg-eq / l
Ferrous iron (dissolved) = 3 mg/l
Manganese = 1 mg/l
Compensated hardness = 6.84 × 50 + (3+1) × 85 = 682
Note. If the total hardness is presented in the analysis as a
concentration of CaCO3 (mg/l), it is not necessary to multiply the value by
50.
EXAMPLE:
General hardness = 342 mg/l CaCO3
Ferrous iron (dissolved) = 3 mg/l
Manganese = 1 mg/l
Compensated hardness = 342 + (3+1) * 85 = 682
If you have any questions, please contact Aquaphor support.
Quick Setup / Basic Settings
Step 1. Set the hardness value
A. Click . After approximately 4 seconds, the controller will beep and
the display will show ppm
B. Press until the number on the display corresponds to the required
hardness to be compensated (see section “Checking before installation”).
C. Click to save the settings and proceed to the next step.
Step 2. Setting the current time
A. Press until you set the current hour. Press to save the setting and move on
to setting the minutes.
B. Press until you set the current minutes. Press to save the setting and go
to the home screen.
NOTE: The current time is shown in 24 hour format.
Mode of enhanced washing from iron
Step 1. Turning on / off the enhanced iron washing mode
Press and hold to turn the feature on or off. In the mode of enhanced
washing from iron, a more intensive washing of the softener with saline
occurs, which contributes to more efficient cleaning of the sorbent from iron.
When this mode is enabled, regeneration occurs every other day. To achieve the
desired effect, the mode of enhanced iron washing should be switched on for at
least 2 weeks. Depending on the iron content of the water, it is recommended
to carry out this procedure at least once a year.
Advanced settings Advanced settings allow you to select the brine regeneration
mode, turn on the 96h mode, change the liter/gallon and mg/L/gpg units, and
set the regeneration start time. Please be careful when using advanced
settings.
Salt regeneration mode change
A. Press and hold and for about 4 seconds, the controller will beep and
display the brine regeneration mode on the display.
B. Press to cycle through AU, HC, and HE modes.
Press to save the selected option and proceed to step 2.
Salt regeneration modes:
AU (Auto mode) – in this mode, the controller monitors the daily water
consumption and regulates the amount of salt for regeneration. If the 96h
mode is disabled, the controller will regenerate 2 times a week if there is
water demand.
HC (High capacity mode) – fixed setting of salt regeneration, which
allows less frequent washing of the sorbent.
HE (High economy mode) – fixed salt regeneration setting, which reduces
the amount of water to be treated between flushes, but significantly saves
salt.
Enabling / Disabling the forced regeneration mode “7296 hours” In this mode,
the controller will regenerate automatically, at the appointed time once every
3–4 days, if normal regeneration did not occur during this interval.
Press to turn 96h mode on or off. The display on the right side will show or
turn off the indicator 96h. Click to save your settings and move on to the
next step.
96h mode. Activation of the 96h mode ensures that the regeneration process is
carried out at least 2 times a week. This mode must be switched on if there is
iron and/or manganese in the source water.
NOTE: More frequent regenerations help the softener to recover more
effectively from iron.
Unit switching: gallon / liter
Press C to switch gallon/liter units. The changes will be displayed on the
screen as gallons or liters. Click to save your settings and move on to the
next step.
Setting the regeneration start time
A. Press to set/change regeneration start time (hours). Press to save the
settings and go to the minutes setting.
B. Press to change the minutes at which regeneration starts. Click to
save the settings and go to the home screen.
NOTE: Time is shown in 24 hour format.
Recommendations for effective use softener
To get the most out of your softener, follow these guidelines:
- Add salt if the level is below the water level in the brine tank. The salt level must always be at least 1/3 of the full load.
- It is recommended to use pure salt in tablets or granules. Don’t use rock salt.
- Once every 6 months it is recommended to use an ion exchanger cleaner.
ATTENTION! Do not mix different types of salt.
- In the event of a power outage, check the correctness of the controller settings (type of regeneration, water parameters, time); if necessary, set the correct values. (See the Controller Setup section).
- Program the softener to regenerate at times of the day when you don’t normally use water. If you have several water treatment devices that require regeneration, the time between device regenerations should be at least two hours.
- Please note that other water-using devices, such as washing machines and dishwashers, should not be running while the softener is regenerating.
- Protect the softener from freezing, including the drain line.
- Follow the requirements for operation, maintenance and placement of the softener.
- If the softener runs out of salt during operation: add salt; wait at least two hours for the salt to dissolve and then start the regeneration. To do this, press and hold the R button for 5 seconds; regeneration will be com- pleted in approximately 30–40 minutes, after which the softener will return to normal operation.
- If the incoming water contains sediment, sand or other undissolved particles, a pre-filter should be used. For example, pre-filter Aquaphor Gross or Gross Midi.
- The device can be disinfected with 5.25% sodium hypochlorite solution, which is the active ingredient in household bleach. To disinfect the device, pour 120 ml of bleach solution or 25 ml of concentrated sodium hypochlorite solution into the brine tank’s brine shaft. There must be water in the brine tank. Start regeneration manually.
- Use the bypass to flush the plumbing after repair or maintenance. • Check and clean the brine tank and air release valve annually or when sediment appears in the tank.
Safety regulations
- During operation, observe the general electrical safety rules when using electrical appliances.
- It is forbidden to repair the softener by persons who do not have special training.
- Before connecting, check that the mains voltage matches the operating voltage of the softener’s power supply.
- It is forbidden to use homemade adapters and extension cords. Protect the electrical cord from damage.
Precautions when connecting your Softener to the mains
Check that the main voltage matches the parameters specified in this Manual
before connecting your Softener to the mains. Only use a power supply unit
with output characteristics specified in this Manual.
Make sure that your Softener is protected from freezing, water, direct
sunlight, contact with hot objects, including hot water, heating pipes and
heating devices before installing. Keep your Softener from hitting and
falling.
The power cord must not be tensioned when your Softener is connected. Make
sure that the power cord does not touch surfaces that could damage it.
Do not immerse the Softener, as well as the AC adapter, power cord, and power
cord plug, in water or other liquid, and do not wash them under running water
or in a dishwasher.
To avoid electric shock, do not touch your Softener connected to power with
wet hands, as well as the power supply unit, the power cord and the plug.
Keep your Softener housing clean. Disconnect your Softener from the power
supply and wipe, if necessary, with a dry cloth.
Do not disassemble your Softener nor open its housing!
Do not use the Softener and the power supply in case of malfunction or damage
to the cord. Do not repair the device yourself. First disconnect the power
supply from the mains, then disconnect it from the Softener if any malfunction
is detected. It is recommended to contact your service provide.
Rules for storage and transportation
- The softener is stored in a polyethylene package, in a closed cardboard container, in enclosed spaces with natural ventilation, at a relative humidity of not more than 80%, at a temperature not lower than +5 °С and not higher than +38 °С. The shelf life before the start of operation is no more than 2 years.
- The softener is transported and stored in an upright position. It is forbidden to tilt the softener, subject it to shocks and other mechanical influences.
- The softener is transported packed by any type of covered transport in a fixed state.
Disposal
Disposal in accordance with environmental, sanitary and other requirements
established by national standards in the field of environmental protection and
ensuring the sanitary and epidemiological welfare of the population.
Terms of Service and Warranties
Aquaphor water Softener – Two Year Warranty from the date of purchase under
normal use and service. This does not apply, however, to filter material
and/or ion exchange resin.
Exclusions and Limitations
- Aquaphor warrants its products to be free from manufacturing defects under normal use and service. This warranty is extended only to the ORIGINAL PURCHASER.
- Aquaphor obligations under this warranty are limited to repairs or replacement, at Aquaphor’s option, of products or parts found to be defective, provided that such products were properly installed and used in accordance with instructions. Aquaphor reserves the right to make such inspections as may be necessary in order to determine the cause of the defect. Aquaphor will not charge for labor or parts in connection with warranty repairs for the first full year from date of purchase on all products except those that may be subject to commercial use limitations.
- Aquaphor is not responsible for the cost of removal, return (shipping) and/or reinstallation of products.
This warranty does NOT apply to:
Damage or loss which occurs during shipment.
Damage or loss sustained through any natural or manmade causes beyond the
control of Aquaphor, including but not limited to fire, earthquake, floods,
etc.
Damage or loss resulting from sediments or foreign matter contained in a water
system.
Damage or loss resulting from negligent or improper installation including
installation of a unit in a harsh or hazardous environment.
Damage or loss resulting from removal, impro per repair, modification of the
product, or improper maintenance including dama ge caused by chlorine or
chlorine related products.
Damage or loss resulting from acts which are not the fault of Aquaphor or
which the Product is not specified to tolerate.
This warranty gives you specific legal rights. You may have other rights which
may vary from state. to state THIS WRITTEN WARRANTY IS THE ONLY WARRANTY MADE
BY AQUAPHOR. REPAIR OR REPLACEMENT AS PROVIDED UNDER THIS WARRANTY SHALL BE
THE EXCLUSIVE REMEDY AVAILABLE TO THE PURCHASER.
AQUAPHOR SHALL NOT BE RESPONSIBLE FOR LOSS OF USE OF THE PRODUCT OR FOR OTHER
INCIDENTAL, SPECIAL, FOR CONSEQUENTIAL DAMAGES OR EXPENSES INCURRED BY THE
PURCHASER OR FOR LABOR OR OTHER COSTS DUE TO INSTALLATION OR REMOVAL OR COSTS
OF REPAIRS BY OTHERS, OR FOR ANY OTHER EXPENSE NOT SPECIFICALLY STATED ABOVE.
EXCEPT TO THE EXTENT PROHIBITED BY APPLICABLE.
LAW, ANY IMPLIED WARRANTIES, INCLUDING THAT OF MERCHANTABILITY, ARE EXPRESSLY
LIMITED TO THE DURATION OF THIS WARRANTY. SOME STATES DO NOT ALLOW
LIMITATIONS, SO THE ABOVE LIMITATION AND EXCLUSION MAY NOT APPLY TO YOU.
Any defects covered by this warranty should be promptly reported to the
AQUAPHOR: AQUAPHOR INTERNATIONAL OÜ, L. Tolstoy 2A, Sillamäe, Estonia, 40231.
www.aquaphor.com
The service life of the softener (excluding filter material and/or ion
exchange resin) is not more than 5 years from the date of sale (determined by
the shop stamp in this manual).
The softener shelf life is 2 years before operation when stored at + 5 to + 40
ºС, without breach of packaging.
If you have any issue with the operation of your Softener, please, contact the
seller or the manufacturer.
For further information on parts and service please contact EU customer
service department at: +372 39 24 116; +48 22 870 24 32
sales@aquaphor.com,
www.aquaphor.com
Troubleshooting
Probable Cause | Solution |
---|---|
Problem: | No soft water output after softener regeneration |
There is no salt in the brine tank | Add salt |
Solids in the brine tank clogged the brine line, brine valve, air check valve
or injector| Dismantle the brine line together with the air cut-off valve Air
check. Rinse them with clean water.
Clean brine valve and injector. Remove impurities from the salt tank
Clogged or improperly installed brine line flow restrictor| Dismantle the
brine valve, clean and properly install the salt flow restrictor
Drain line kinked, frozen, or clogged| Straighten the line, let it thaw or
clean it
Clogged injector| Remove the injector cap, clean the nozzle with a wooden
toothpick. Reinstall the removed items
A salt bridge has formed (appearance of salt) in the salt compartment due to
high humidity or the use of the wrong type of salt| Try to break the crust
with a blunt object, you can use hot water. Add salt if there was none. Use
only high quality granular or tablet salt
Problem:| No soft water at softener outlet
Bypass valve is in Bypass position or deviated from Service position| Set
bypass valve to normal operation. Service
The device is connected to the water supply in the opposite direction| Check
if the device is connected correctly
Prolonged power failure| Reset the current time
Lack of accounting for water consumption| See if the water consumption
indicator on the softener works when the water is being drawn. If not, see
below.
The composition of the source water has changed| Explore the water, make
changes to the settings according to the new data
Source water is mixed with purified| Make sure that there is no admixture of
the source water
Problem:| Sensor registers water flow when water is not flowing
Water leak after softener| Fix the leak
Problem:| No indication on the display
Power wire not connected| Connect the power supply
No mains power| Check for power at the outlet.
Faulty power supply| Check the power supply with a voltmeter. Should be 12
VAC. If the voltage is less than 10 VAC, check the voltage at the 220 VAC
outlet
Faulty controller| If 12 VAC is being supplied to the controller, replace the
controller
High ambient temperature. At air temperature +38 °C or higher, the display
will not show characters. The functionality of the controller is preserved| No
option but to lower the temperature
Problem:| The device does not exit the regeneration mode
Controller incorrectly installed| Make sure the controller is fixed on the
screw mechanism cover correctly
Defective magnetic arm| Replace magnetic arm
Foreign object in control valve mechanism| Disassemble valve, remove foreign
object
The control valve is out of order, the engine is running| Repair or replace
control valve
Problem:| Excess water in brine tank
Drain line clogged, kinked, or frozen| Remove the blockage, straighten the
kink in the drain line
Clogged brine line, brine line flow restrictor or Air check valve| Clean the
brine line, brine line flow restrictor and air check valve. Remove dirt from
the salt tank
Clogged injector| Clean or replace injector. If the injector neck has been
removed, replace it with a new one.
Problem:| Regeneration sequence broken
Damaged magnetic lever| Replace magnetic arm
Faulty controller| Replace controller
Problem:| Softened water is salty
Damaged injector| Replace injector including the neck
Low inlet water pressure| Minimum working pressure 0.14 MPa
Drain restrictor clogged| Remove blockage
Salt line clogged or damaged| Remove blockage, replace line if damaged
Too much water in brine tank| Check that the water level in the tank* and the
brine regeneration settings are correct. Check brine, drain lines and
tightness of valve assemblies
Unstable pressure of the supplied water, the formation of a vacuum at the
inlet| Install a check valve in front of the softener. Stabilize the inlet
pressure
Brine valve leak| Clean brine valve, replace brine valve seals
Problem:| Controller errors
E1 – Home position not detected| Turn the power off and on by unplugging and
plugging in the AC adapter. The search for the home position will start again.
Make sure the controller is fully and securely attached to the screw mechanism
cover
E2 – Engine malfunction| Disable electric power and connect the motor. If it
was already connected, replace the motor.
Make sure the power supply is 12V AC voltage
E3 – Shift of home position| The magnetic arm does not start from the correct
home position. The controller will automatically attempt to adjust by
searching for the home position and continue regeneration.
Make sure the controller and magnetic arm are fully and securely attached.
E4 – Home position locked| Transmission teeth not engaged or stripped.
Something has jammed the valve mechanism. Clear the jam, then to reset the
error, turn off and turn on the softener power
E5 – Memory error| To reset the error, turn off and turn on the softener
power. If error persists, replace controller.
*** The water level must not reach the level of the float and the overflow
fitting.
Warranty coupon Aquaphor Softener**
Aquaphor Softener Model|
---|---
Serial #|
Date of Sell|
Seller’s stamp|
Seller’s signature|
Installation information
Name of the company which carried out installation:|
---|---
Name of the service engineer:|
Service engineer’s signature:|
Client’s signature:|
For installation, operational and technical maintenance, please, contact:|
For further information on parts and service please contact EU customer service department at + 372 39 24 116; + 48 22 870 24 32 sales@aquaphor.com, www.aquaphor.com
The Quality Management System is certified according to ISO 9001.
The manufacturer reserves the right to make improvements to the design of the
Aquaphor water softener without being mentioned in this Manual.
Manufacturer: AQUAPHOR INTERNATIONAL OÜ, L. Tolstoi 2A, Sillamäe, Estonia,
40231. www.aquaphor.com
Aquaphor water softener models: 1. S550 2. S550 P1
The number of the Aquaphor water softener model, the manufacturing and quality
control date, as well as the product’s serial number are indicated on a
special sticker on this page.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>