HILTI CP 660 Flexible Firestop Foam Instruction Manual

June 4, 2024
HILTI

HILTI CP 660 Flexible Firestop Foam

Product description

  • The ideal solution for installing reliable, smoke-resistant firestop seals in small to medium-sized openings — one product is all that is needed

Product features

  • Neat and tidy application
  • Quick and easy to install — a reliable firestop seal with only one product
  • Easy subsequent installation of additional single cables
  • Outstanding sound insulation properties thanks to flexible foam structure
  • Smoke resistance and firestopping with one system
  • Paintable

Areas of application

  • Permanent firestop seals in small- and medium-sized openings (optimum size range: 100 x 100 mm to 300 x 300 mm)

  • Cable trays, bunched and single cables

  • Plastic pipes (can also be installed as a system in conjunction with Hilti firestop collars and wraps)

  • Openings accommodating pipes and cables

  • Metal pipes (uninsulated or with flammable or non-flammable insulation)
    For use with floor and wall assemblies

  • Concrete, drywall and masonry

Installation instructions

  • See Hilti literature or third-party listings for complete application and installation details

Technical Data

  • Chemical basis                  Two-component polyurethane foam

  • Color                                Red

  • Fire foam yield                  Up to 128 in3

  • Application temperature  Product: 50°F to 95°F (10°C to 35°C)

  • Curing time                    Tack free: 5 min
    Cut time: 10 min

  • Temperature resistance of cured foam      –22°F to 140°F (–30°C to 60°C)

  • Sound transmission classification (ASTM E90-97)  47 (Relates to specific construction)

  • Mold and mildew (ASTM G21)          0

  • Shelf life                                              9 month from date of manufacture

  • Recommended storage temperature   40°F to 77°F (4.5°C to 25°C)

  • Tested in accordance with                  UL 1479, ASTM E81, CAN/ULC-S115
    Refer to applicable UL listings for specific installation requirements

At 73°F (23°C) and 50% relative humidity

FILL, VOID OR CAVITY MATERIAL FOR USE IN THROUGH-PENETRATION FIRESTOP SYSTEMS SEE UL FIRE RESISTANCE DIRECTORY 66Y7