janitza UMGUM8G01801 Modular Expandable Power Analyzer Instruction Manual
- June 11, 2024
- janitza
Table of Contents
UMGUM8G01801 Modular Expandable Power Analyzer
Product Information
The product is a UMGUM8G01801 device manufactured by Janitza
Electronics GmbH. The device comes with a DIN-DIN interface and is
compliant with DIN4388 and DIN3-5 standards. The device is also
compliant with IEC610IE1C0-16:12001100-1:2010 standards. The device
has Ethernet ports (EAtheL1rnet A, Ethernet EBtheNrnet B) for
connectivity. The device is UL/IEC certified and comes with L1, L2,
L3, N, PE, V1, V2, V3, I1, I2, I3, I4, S1, S2 inputs/outputs.
Product Usage Instructions
-
Ensure that the device is installed in a safe and secure
location. -
Connect the device to the power source.
-
Connect the device to the Ethernet network using the
EAtheL1rnet A or Ethernet EBtheNrnet B port. -
Connect the input/output cables to the appropriate ports on the
device. The device has L1, L2, L3, N, PE, V1, V2, V3, I1, I2, I3,
I4, S1, S2 inputs/outputs. -
Power on the device.
-
The device is now ready to use. Refer to the user manual for
further instructions on how to use the device.
. 2.053.026.1.c : 02/2023
www.janitza.de
. 2.053.026.1.c : 02/2023
UMGUM8G01801
sEenegrleisahr ssvEieedneresgrileoisanhr:sviedresion:
Janitza electronics GmbH
Vor dem Polstück 6
D-35633 Lahnau .+4964. 4+14996424-1229642-22 .:.info@:jainfiotz@a.jdaenitza.de
www.jawniwtzwa.jdaenitza.de
: :
1
·
..
.Janitza.eJleacntirtzoaniecsleGctrmobnHicsG mbH
·
,,
, ,
.. www.janwitzwaw.d.eja.nitza.de.
, ,
. .
!!
,, , ,
, ,
www.janwitzwaw.d.ejanitza.de««»>» > ,,
««».».
: :
·
·
© 2019 -©Ja2n0i1tz9a-eJleacntirtzoaniecsleGctrmobnHics- GLamhbnHau-.Lahnau.
·
. . , ,
·
,,,,, ,
. .
. .
,,
·, , JanitzaeJleacntirtzoaniecsleGctrmobnHicsGmbH,,
. .
·
..
(www.jan(witzwaw.d.eja)n. itza.de).
2
,,
::
—
.. DIN4388D0IN(43880())
….
,,,, ,, DIN-DIN3-5(13,358(1,38)().(.
..,,..,,,,,.,,,.,,;,1.;,1.)):.:.,,
,·,,,…:.:,!,!
,.,.
..
, , . .
..!!
.. |
---|
2. 2.DIN-DIN-
DIN-DIN-,. ,.
..
,,,,,,..,,.,.,,.,,,.,.,.
UMG80U1M.G801,..,,,.DU,IN,M-G8D.0UIN1M-G8.01..DDIINN–.DDIINN–.,2.,2.,.,1.-.-.1..-
· . .
,,:: ,,!!
· ,:,:, ,
·! ;! ;
(().). ·
·; ; ·«« UL/IECUL/IE»C.». // ! !
. .
·
! !
. . . .
!!
..
(·()24,4.8)24,4.8
, , ..
,, 2.302. 30
!!
L1 L1
1010. .
1 / 16
N
N
UMGUM8G01801
sEenegrleisahr ssvEieedneresgrileoisanhr:sviedresion:
· – – ,,. .
··:.)J:anitza.)eJleacntirtzo,,aniecsle(Gctrmo.,,bnHics(Gm.bH
..
·
((3«3«»).»).
, ,
·
· ,,
!!
· , ,
. .
,,….
www.janwitzwaw.d.eja.nitza.de.
,,,.,.,,
!!
. 2.053.026.1.c : 02/2023 . 2.053.026.1.c : 02/2023
– – ! !
.. · ,,,,,,.,..,,.:,:
www.janwitzwaw.d.ejanitza.de,«,«,.»>,.»>
, , , ,
««».»., , ,,
: :
· ..
·-:-: , ,
,,
·
©2019-©···Ja2n0i1tz9a-e,Jl,eacntirtzo.a,niec,sl,eGctrmo.,bnHic,s,-GLamhb,nHa,u,,-..La,h:,nau,..,:
. .
·· !!.:.:,,,,,,,,
!!
..
· !!
, ,
.).),,,,.(,,.(,.,.JanitzaeJleacntirtzo,aniecsleGctrmo,bnHicsGmbH,,
·.+4964.4+14996424-1229642-22!! ww.w.ja· wniwt:z.wian.fjdaoen@it:jzaian.fidotze@a.jdaenitza.de,!,!
..
,(,(,.,. ). ).
(www.jan(witzwaw.d.eja)n. itza.de).
3
4
»
·,,L1,L2,LL13,(L2,L3()D)IN4388D0IN(43880()) ,,,,,,DIN-DIN3-5(13,358(1,38) ().(. ,,,,,, )):: . ., ..,,, , 1., 1. – ; ;
8
8 ,,,,;.;…/1../5..A./1;…/5.A;.
· ,,
..
..
2. 2. –
DIN-DIN– DIN-DIN-. .
..((((
· ..
))
))
,,
,,
,,..
· ,,,,,,APE/NAPE/N .. . . —
,!,!1. 1.
DIN-DIN- UMG80U1MG801DIN-D IN-
,,
. .
UMG80U1M.G801.DIN-DIN –
1.01.0. .
2 / 16
5 / 5 5(/I51 (I8I)1; I8); . .
.. ,, ::
·
! !
IEC610IE1C0-16:12001100-1:2010
, ,
. .
S1 S2S1S2! !
L1 L2
N
ULLL/NI12·ECUL/ISE1CS2!S1S1S2S2S!1S1S2S2S1S2//
–!:!P:E.PE·-.««.». »
,,
–
. .
. +. + –
,, :P2:E4L4V8 2448
(().)!.!
!!!!!!2.302.30
L1L1
! ! N
N
,,
!!
·..
·,!,!..(..( )) .. !!
5
(DINE(NDI6N10E1N0-611/A010):-1/A1): ,,(IT-) (IT-) ..
L1
L1
((L31«3«»). »).
L1
L2,,L2
,,
! !
N,, N
..
R
L3 L3
L2 L2
L3. .
L3
!
EEE- – IEC UL-N/ULU-LL-:N48/0ULN: 4/88030L!NLL/ 830!
E
E EEE
UL-L 690ULL690,,,,,,U.L,-.L830U.,L,.L830,
UL UL-N/ULU-LL-:N34/7ULN:3/46700LNLL/600 UL-L 600ULL600UL-L600ULL600. .
-:-::,:,
·3-4-3-4-(TN-,T(TT-N-,IT-T-IT),-),
·..
·· !,T!T-A,T!T-AD!D!,!.!!:,!.—!:,,,,,.,.,.,,. ,
TT-TT-(( –
))
6 ::
44
L1 L1
,, L2 L2
..(.(.
L3
)) N N
..
PE PE
,,..,,((UL/IEC)UL/IEC)
—
,,,.,.
:,.:,.
·,,
!,!,::
!,!,,!,!!,!!,!,,
. .««»»
· -((,., . -(,,,(,,,:.:.
,, ,, «« ».».
.).));); -((.,.,
·..,).,). ·
. .
. .
,
»
7
L1, L2,LL13, L(2,L3())
N V3 V2 V1
N V3 V2 V1
N V3 V2 V1
N V3 V2 V1
Ethernet EAtheL1rnet A
L1
L2
L2
L3
L3
Ethernet EBtheNrnet B
N
L1
L1
L2
L2
L3
L3
N
N
(( ((
. .
) )
) )
::
,,, ,5! 5! · PE/NPE/N-
N V3 V2 V1
N V3 V2 V1
AA-
. .– , ,
. .
!!
LLL321IT-LLL321IT.-.
..
. .
8 3 / 16
8
···665;/5;.5(;/I51;…(/1I8I1).;./5..A/1I;8.).;./5A;.
·. .
. .
11..
IEC61I0E1C0-611:2001100-.1:2010.
….
S1 S2 S1 S2
L1 L1 L2 L2
S1 S2 S1 S2
((,«5»),.«5»). N
L3 N
S1 S2 S1 S2 S1 S2 S1 S2
(-(+-1).+1).!:!:PE.. PE..«UM«G8U0M1-GPA80»1-PA»
·(,)(.,). . .
·
. . ,,(:(,«:3»),. «3»).
·! ! · ··(!,(«!6»),.«6»().!(!-1).!!-1). !! ·(,(,!«,»),.!«»).
!.!.1(ESC1) (ESC) .(.(.. ). ).(( ))
..,,
!!
..
9
(DINEN(D6IN10E1N0-611/A01)0:-1/A1):
10 1044
L1 L1
I1I4I1I5I4I8I5I8
(IT-)(IT-)
….
L2 N
L2 N
I1 I2
I3
I4
30 31 32 33 34 35 36 37
I1 I2
I3
I4
30 31 32 33 34 35 36 37
I1 I2
I3
I4
30 31 32 33 34 35 36 37
L1
L1
L1
L2
L2
L2
!
L3
L3
L3
N
N
N
UL-N
/
UUL-:N48/ 0ULN:4/88030LN/
830
U690U 69022U830U
3UL-N/U3UL-:N34/7ULN:3/46700LN/60022U600U600(Aron-(Ar)on-)U 600U
830 600
: : 3- 4-3-4-(TN-,T(TT-N-,ITT-T-I)T,-),
. .
I1 I2
I3
I4
30 31 32 33 34 35 36 37
I1 I2
I3
I4
30 31 32 33 34 35 36 37
L1DL1D
L2,TT-, TT-L2
L3
L3
AA
· , , · GridVisG®.ridVis . . .
TT2-TT2-((3 3 )(Aron)-(Ar)on-)
312… (DHOCD-PPHC-CUP(DA-OHOCPD-PPECHC-t!hCUeUPArA- nOePt)EC,t!hUeArn/e:t!).,!(///I:P-!.!,(!/.//:IPIP–,!UU/!U.MMM::GGGI,P.888-000111UU!,UMMM.:GGG,..88800011(1,.PE.-(.UPL····./EIE,-C.),U,,L./.-IE,C»),,./,,..-.-,-»,.«/«..-.,,-.««.,,.,.:,-».:,,-»,
Ethe Ethe
);); .. . .
((2Ethe2rneE).tt,herne)..t,.
. .
,
TCP/ITPCP/IP
22 EtherneEtth(TeCrnPe/tIP(T)CPD/IHPC) P-DHCP-:: 1. 1.((IP-IP-))
IP-IP-,, . . Ethernet AEthernet A DHCP-DHCP-.. 2. DHC2.P DHCP Ethernet
EBthernetB IP- IP,, DHCP-DHCP-..
DHCP !DHCP!
,:,:,,5!5!
EtherneEtthernet..
…. IT-I.T-. — GridVisGridVis..
. . EtherneEtth(TeCrnPe/tIP(T) CP/IP)
EtherneEtth(TeCrnPe/tIP(T) CP/IP) 11 11 . .EtherneEtth(TeCrnPe/tIP(T)CP/IP) ««».».
4 / 16
11
OPC-OUPAC-UA
66OPCUOAPCUA ·EtherneEtth.ernet . ·..; ;
· . .
EtherneEtthernet 1··1….OPGCridUVOAisPGC.ridUVAis .
·.(ESC).
·..
(·,(«5»).,«5»).
Ether·neEtthernet((+1)..+1). .
. .UMG8U01M-GPA801-PA
·()(..)..
–.. ·(Grid(,V«is3Gr»id).,V«is3»). 1(ESC1) (ESC)
. (.(. .
· ).).
(, «(6»)., «6»). ·((-1). -1).
,,
·((,«»)., «»).
. .
10 10
I1 I4I1I5I4 I8I5 I8
00000 0(0000().). . .
12«OPCU·«AOPCUA/».E/t»h.erEn:.tehte-U1rMnEG:.Se80Ct1-U,1MEGS8C01,–IP-.Kon,figu
..raE-tito,hner.ne-t(TCPD/IPH)CP-,-,
(·(OPECthUeArnOetP)ECthUeArnet2.)«5/M»2.en«5ü/5«/»6»5/«6»INGPea-tAtzedmwreaa
/syssk-ee/-,211995225…112,,665885…25335.,:…17740.:
Ethe Ethe
22
3 322 (Aron-(A)ron-)
DHCP- DHCP-
Leistung
UMG 801UMG 801
ESC ….Ether.neEtth(TeCr.nPe/tIP(T)CP/IP)
, , GridVisG.ridVis .
Energie
//
Multifunktionskanäle
DHCP-DHCP- IP-IP-.
Konfiguration
·Ethern,eEtt.herne, t. .,,,,,2,2 E.therneEt.t,hernet,
S ystem-Informationen
UMG
801UMG
801
(().).
–..
C)
. .
,
2 2
3 3
(Aron-(Ar)on-)
IP-IP. -.
. . ««»»
33. . · EtherneEtth(TeCrnPe/tIP(T).CP/IP).
22 .. EtherneEt,thernet, (().).
·
2«5»2«55«»6»5«6»EtherneEtth(TeCrnPe/t (TCP/
IP) IP)33. .
·EtherneEtth(TeCrnPe/tIP(T).CP/IP).
13
TCP/ITPCP/IP
22(RCM(/RCM/)) Konfiguration
EtherneEtt(hTeCrnPe/tIP(UT) MCGPD/8HIP0CU1)MPG-D8H0C1P-: :
1.1.((IP-IP-)- )-Ethernet(TCP/IP)(RCM)(RCM)
(RCM)(RCM).IP-.IP,-.,.FeUldMbGus8U01MG801
44D(HCP-D(4H,C2/P2,-3/41.,2/2,13/31.). 1/3). Stromwandler. .. .
2. L1
DLH1C2P. DHCPIP-IP-Spannungswandle(rRCM)(RCM)
L2 L2,, DHCP-DHCP-. . Anzeige, ,
0..30 00….3300 0..30
DHC P!DHCP! ESC. .
N
N
. .
PE PE
UMG 8U01MEGth8e0r1neEtt(hTeCrnPe/tIP(T)CP/IP) IEC/TRIE6C07/T5R5:60755:
·
Ethernet (TCP/IP)
EtherneEtthernet 2xPT10.20xPT10.0
»
· 78971801191120113111421314..
IP-KonBfiguBra+tiBon B+ DHCP ((
·
IP-A)dresse)
192. 168. 3. 177
—
Netzmaske
255. 255. 255. 0
GridVisG® ridVis
Gateway
192. 168. 3. 4
EtherneEtt(hTeCrnPe/tIP(T) C P/IP)
ESC
11 11 . .EtherneEtt(hTeCrnPe/tIP(T) CP/IP) ««».».
14OPC-UOAPC-UA
OPCUOAPC UA
EtherneEtthernet
..
EtherneEtthernet
3030«».«»O.PGCridUVAOisPGC.ridUVAis®. ,/,,/,!!
(( ))
··.Ethern.eEtthernet…,.,//
..
·!! :: — GridVisGridVis®
(() ) ! !
GridVisG.ridVis . ((). ).
!!
. .
5 / 16
15
312…312…3.00.00.03.(02.0«050.»0(25«5«6»»51«E6SC»),.1ESC),.111345…
13. I1..I4I1..I4.. 14. 3 3 1ESC. 1 ESC. 15.1ESC 1 ESC . .
2«5» 25«5«6»»5«6»
3.3 .
4. 4. . .
5..8(I5..5I8..)8(I5..I8)
5. 5. I1..I4. I1..I4.
3.3 .
6. 6. ««». ».
Stromwandler
10 10. . 7. 7.
3 . .
Geraet
Basisgeraet
8. 8. 5«6»5«6»
Primaer
Sekundaer
C)
1..4 (1..4 (I1..I4)I1..I4)
Wandler 1..4
5 A
5 A
3.3 . 9. 9.
Wandler 5..8
5 A
5 A
I1..I4«I1..I4«». ».
ESC
10. 10. 4(3)46((3))6()
. .««»»
,
,,
2(5)25((56))5(6) (-1/+1)(.-1 / +1).
11. 11. 3 3
1ESC. 1 ESC.
–
12. 12. 6()6()
I1..I4. I1..I4. GridVis®G. ridVis .
EthernEetht-ernet-
16
«1.1«.»…».1ESC,1ESC,
11. 11. 33 1ESC.1 ESC.
2. 2. 2«5» 2 «55«6» » 5«6» 12.12.1 1
1ESC,1ESC, ESC ESC . .
3..3..
3.3.2«5»25«5«6»»5«6»
2«5»2«55«6»»5«6»
Spannungswandler
3.3 . 4. 4…
Primaer Sekundaer
5. 5.
Wandler 1..4
400 V
400 V
1..4(1..4(
. E. therneEt t(hTeCrnPe/ItP()TCP/IP)
L1LL41) L4) 3.3 .
EtherneEt.thernet.
6. 7.
6. 1..4«1..4«».». 7. 4(3) 46(3())6() , ,
22 EtherneEt,thernet, ((ESC).).
2(5) 25(5(6))5(6)(-1/+1)(.-1 / +1).
. «. «»»
8. 8…««1E»S3C.1E»S3C.
91.0E.thern91e.0Et.2t(hT«eC5rnP»e/ItP2L()T15«.3C5«P16»./L.I4LP»461))(5.(..3«1)6.L.446»)E(.(.t1h.e.)4rneEt1t(h.T.e4CrnPe/t(TCP/
.. GridVisG.ridVis®.
IP) IP)EtherneEt.t(hTeCrnPe3/.ItP()T.CP.3/IP)..
17
(RCM(/RCM/))
»
UMG801UMG801
(RCM1)4(RC1M)4(15AA15(4AA,2/2,(R3/C14M.,2)/2(,R13/C3/1M)..)–1/3).-30(3302,3801(3U2(M,(383012G),818(30U2()1,M81G).8.0)1(R.C.M)(RC)M))
L1 L1
L2
L2
IEC/TR 60IE7C55/T(R2060087-0515)(,2008-01),
A / BAB/ +(BB+( ) )
11(RCM) (RCM) · , ,. 33 ..33.
0..30 00….3300 0..30
L3
N N 1
1
PE (PE ()). 4 . 4
<= 30 (3<2=,8310(3)2,81)
· 0/4…20 0/4…20. . · 0,20,2. . UMG80U1MG801.300.300 IEC/TRIE60C7/T55R: 1600755:10
30 (32>,8310(3)2,81) KTY823x, PKKTTTY1Y8084203,x,PKPTT1TY018004, 0,PPTT11000, PT1000
3-3-RS485RS48A5,B,GNDA., B, GND.
. …
7897108119121013111412 13 14 4 4, ,, , . .
20 20
(B(B+BMMooddBbbuu+ssRRMMTTooUUdd//bbSGuulaasstveRRewTTaUUy//SGlaatveeway )) 95,76,6//,951, ,79161,,625,2///,1,,/9131,825,4,2//,/3, 8,4 /,
18 … 2818 … 2.8. ((4) 4 )
DIP-DIP-
0…
5 0….5,. , 0,5 0,5
EtherneEt thernet
2 x RJ452 x RJ45
Modbus GMaotdebwuasyGateway
4 4, ,, ,
. .
OMPodCbUusA/,TOMDCPoHPdC,CbNUuPTs,A/P,TDCHP,CNPT, P
. 60. 6.0.
.50.50.. CCNTP
NTP
30,··/30(RS,4/85,.E(RthSe4r8n5e,t.)Eth«ernet»)..«,»..,,,–((,,(()/,,((,),))/.)000,,,,)222),.000),,,222555000,,,(222222,,,000AAA,,,222WWW555!GGG222(666222!,,,—AAA111222WWWGGG!222666!—111222
…..!.(RC(!M,(RCI.(E)MC,61010-I.1E):C20610)1.0-1:2010).((·(,(),.,,.).,,.2)2!/)!/
Ethernet,ERtSh4e8rn5e,t/,:RS.485,/:.//
(())2 2 !! (())
((IEC61010I-E1C:2G6011r0i0d1).0V-(1iIs:/2OG0.s1r0)i)d.V(Ii/sO®s.-)(·().)..!.!
..,,Ethernet,E,thernet,, ((.).) !!
RS485 RS485..
,,,0,08,4 0,20, 8AW4G282,-A12WG 28-12
((//)0,25)2,5 0,252,A2W,5G242,-A14WG 24-14
. 500 . 500
89 (08,319500(,03,53413500,354)3 )
(().2)0 . 20
6 / 16
18 181.1.1ESC, 1ESC, 13. 13.
. .
I1..I4I1..I4..
2. 2.2«5»25««56»»5«6» 420(0,942260(0,9)26)
1·4.14.,,1ESC.13ESC.3
3.3.3.3HT=.=B79.6=014HT4(2=(.=3,B97,5996=4(051,6474(2(3,9,)59),4(5,6),7)),),
1·5D.INIEC156.D0I7N21IE-3C-36.0.721-3-3….1ESC 1 ESC
4. 4.2«5»25««564(4»0»0L05i0th«i6Uu4(4mL0»1C063RL04i022th0)i3Uu2mL,..13C36R4220)32,..3 5. 5.(50%(50%))
· IIII IEC60536IE(CVD6E0503160(6V, DE01016), 1), ! !
-10C°(14-1F0°)C°(14F°) 5..8(I5..5I8..)8(I5..I8)+555C°(9153+15%55F°C)°(9215531%CF°°()772F5°)C°(77F°) I1..I4.I1..I4.
63.5(16,3.85/DIN(1-,3)8/DIN-···)TTTSSS333555///711,055TTTxSSS«1,3335555///711,055xE»3«1N.,56071.5»3E.N6071.5//214000000000C((12A214,,24T00049I000II000;60:C((0312))A0,,24T049CIIIA;CT6I0A:V0T3))I0I0:CACTIAVTII:
1010IK07.IK07IEC. 62262IEC 62262
::
7. 7.
..
600 CAT6I0II0; CATIII; :300CA: T3I0I0
2
2
CATII
8.1..4(8.1.3.4(.31+570-«.2(C3569°C(,»13°571+(8-571F0-3«2°(CI6)3F519°°.C(),».13I°)457(8)-1F3°I)F1,°..)I)4).,.IP20IP.20EN60.529EN60529 9.9.595%59255%C°(772F5°)C°(77F°)
I1..I4«I1..I4«». ». 10. 10.4(3) 46 (3) 6()
,,
. :244. 8,: P24EL4V8 , PELV
..««+/-10%+/-10%»»
2(5) 25 (56) 5(6) (-1/ +1).(-1 / +1).
. 4 . 4
11. 33 1ESC. 1 ESC.
-101210(UM1G208,081(UM4G08,081)410)
10
12. 12.6() 6()
I1..I4. I1..I4. 26A(2.B6)A,(G.rBidI)E,VCis/UG.LridIVECis/U.L
1. 1.1ESC, 1 ESC, 11. 11. 3 3
432333…—432((333…334——2«5((3»43—2)5«)35«6683448903670»2000.»«LLNN5)5.3)//68»«66834(((03+++486903002///70.000—»5111«LL000LLL5NN«.((—%%%++LLL//6//»68–)))(((0311+++»00///—%%5111LL))LL000«3((%%%++6//–)))11»IUI00EEL%%CCIU))E..3LCIUIEELCCUI..ELC12.-ESC12(.-ESC)(../(1A)(..)(/5.0581.A/,,A1092)08A5)..(…6/5058··1AA,,A092)08(5L..1..,6L2A,1L3(EL.,1SN,)CL2.,1L13E,SNC). 1
5.5.60100001·6(C.+.0A41/0-T01(0I0I0LI-%L1)(.C+.4A/-T(1I0II%IE)CULIECUL1 1
120 A (120A() ) 0,1 (0,1 ( 0,01A) 0,01A)
6.6.3.38161000A.CL·81A1T6100II0AILC4LA)1TIIIULL4)BU,LB,320,50CAT32I0,I50 CATII
(1.I.E4C«-/UL1(-..IE4C«-»/U.L)-». )
.0,2 ·(.R0,2= 5·(Ri) = 5 )
897… -897…-2(5)N-LLP2–5ENL((560(0(114116,1).)6M)4)…..N41.(6.-0LL(P17..(35.0–(E20NL0/00(,)61010(0141()16,1.)M6)4).6…6.41.06(.(00((317…0(,20(0/-00),1L1)0)-/N66+)1011(010E)0,(.0-0S010)3LC-/N.+)1111E)00.)0S0)030C.))··.«.21«5..4,.663.(L(2115.,.4,.L6623,.(LR3(LC;(1NM,)L)),2/,(LR3C;NM))),/»»
L151L,24L)1. 51L,24).
30G30ridVisG.ridVis .
10.10.
0… 40 0…40
40…7040…17.0.4 1..4 0,01.0,01 .
1… 127. 1… 127.
50 50
1 A (1A ( 0,01A) 0,01A)
—
1,414 (1,414(40) 40 )
…
1)…,,
4
4
L-N>10L-N>10L-L>18L-L>.18 .20 20 50 A 50 A
(RCM) (RCM)
1 1 5 A
5 A
1A
1 A
(()) 30 (32,8310 (32),81 ) 30(32,8310 (32),81 )
IEC/TR 60I7E5C5/T(2R060087-0515),(2008-01), A / BAB/+(BB+(- ) )
1 1
. 33 ..33.
0/4…20 0/4…20. .
1
1
0,2 0,2
(
()).
4
.
4
. 300. 300
<= 30 (32<,=8130(3)2,81)-
10 10
30 (32,>8130(3)2,81) RS485 RS485
KTY83, KKTTYY8843, ,PKTT1Y008,4P, PT1T010000, PT1000
3-3- A, B, GNDA., B, GND. ….
4 4, ,,,
Modbus RMToUd/bSulasvReTU/Slave Modbus RMToUd/bGuasteRwTaUy/Gateway
.. 20 20
95,76,6//,1,9591,761,,265,2///,,1,/39181,2,54,2//,/,38,4 /,
18 … 2818 …2. 8. ((4) 4 )
DIP-DIP-
0…
5 0…. 5,. , 0,5 0,5
EthernetEthernet
2 x RJ45 2 x RJ45
Modbus GMaotedwbuasy Gateway
4 4, ,,,
..
OMPodCbUusA/,TOMDCPoHPdC,CbNPUuT,sAP/,TDCHP,CNPT, P
. 60 .6. 0.
CC NTP NTP
. 50 . 50..
. 500 . 500
(())
(RS485, E(RthSe4rn8e5t,)Ethernet) ·
. . ! !
. .
,, ,0,,20,25 0,22,0A,2W5G262,-1A2WG 26-12
,·,,,,, -(()0,20,)25
0,22,0A,2W5G262,-1A2WG 10 (0.3937 in)
26-12
//. .
(()0,2)0,25 0,22,0A,2W5G262,-1A2WG 26-12
– 13
(IE(C61010-I1E:C2061100)1. 0-1: 2010).
10
(RCM,(RC.)M, .)
· . . · . .
(() ) . . ! !
,, ,, 0.22 – 2.5 2, AWG 26-12
· Ethernet, RESth4e8rn5e, t,RS485,// . .
(()) –
// (())
–
((IEC61010I-E1:C260101).0-1:2010).
0.22 – 2.5 2, AWG 26-12 10 (0.3937 in) 0.2 – 2.5 mm2, AWG 26-12 13 (0.5118 in)
10 (0.3937 in)
(I/Os) (I/Os)
0.2 Nm (1.77 lbf in)
··..,,Ethernet,E,thernet,,((.).)!!
RS485 RS485..
,, ,0,08,4 02,0, A8W4G282,-1A2WG 28-12
((//) 0,25)2,5 0,225,A2W,5G242,-1A4WG 24-14
89 (08,319500(,03,53413500,354)3 )
(().20) . 20
7 / 16
((A/D) A/D)
(RS485) (RS485)
.. !! , ,,0,,2420, ,A2W4G242-,1A2WG 24-12 (()0,24) 20, ,A2W4G242-,1A2WG 24-12 (()0,2)2,5 0,22, A2W,5G262-,1A4WG 26-14
, ,,0,,21,50,22, A1W,5G242-,1A6WG 24-16
(()0,21,5) 0,22, A1W,5G262-,1A6WG 26-16
(()0,2)1 20, ,A2W1G262-,1A8WG 26-18
0,20,25 0,·2(01,,27572·,21(1,772,21 ) )
0,40,5 0·,4(30,5,544·,43(3,544,43 ) )
7 (0,2756(0,275)6 )
7 (0,2756(0,275)6 )
(RCM,(RC.M) , .) ..
!!
www.janwitwzwa.djaen.itza.de.
, ,,0,,21,50,22, A1W,5G242-,1A6WG 24-16
(()0,21,5) 0,22, A1W,5G262-,1A6WG 26-16
(()0,2)1 20, ,A2W1G262-,1A8WG 26-18
0,20,25 0,·2(01,,27572·,21(1,772,21 ) )
7 (0,2756(0,275)6 )
((//, , ) )
, ,,0,,21,50,22, A1W,5G242-,1A6WG 24-16
(()0,21,5) 0,22, A1W,5G262-,1A6WG 26-16
(()0,2)1 20, ,A2W1G262-,1A8WG 26-18
0,20,25 0,·2(01,,27572·,21(1,772,21 ) )
7 (0,2756(0,275)6 )
19
,,
. .
..
..
. .
.. . .
. . ..
.. ..
. .
..
.. ..
. …
. .
…
.
,, .. .,.,–.. . . ..
.. !!,, . . . .
)
8 / 16
Doc no. 2.053.026.1.c Status: 02/2023
www.janitza.de
Power Analyser
UMG 801
Installation instructions
Installation Device settings
Janitza electronics GmbH Vor dem Polstück 6 35633 Lahnau, Germany Support tel.
+49 6441 9642-22 E-mail: info@janitza.de www.janitza.de
User manual:
1
General information
Disclaimer Observing the usage information for the devices is a prerequisite
for safe operation and for achieving the specified performance characteristics
and product features. Janitza electronics GmbH assumes no liability for
personal injuries, property damage and financial losses resulting from the
failure to observe the usage information. Make sure that your information
products are legible and accessible.
Further usage information, such as e.g. the user manual, can be found on our
web site www.janitza.de under Support > Downloads.
Copyright notice © 2019 – Janitza electronics GmbH – Lahnau. All rights
reserved. Any duplication, processing, distribution and any other kind of use,
even in part, is prohibited.
· Keep the usage information accompanying the product accessible through its
service life and hand it over to the subsequent owner where applicable.
· Please refer to www.janitza.de for information concerning device revisions
and the associated adjustments to the usage information accompanying the
product.
Disposal Please observe the national regulations. Dispose of individual parts,
where necessary, depending on the properties and existing country-specific
regulations, e.g. as: · Electronic waste · Batteries and accumulators ·
Plastic · Metals or commission a certified disposal company with the
scrapping.
Subject to technical changes. · Make sure that the installation instructions
match your device. · Make sure you have first read and understood
the usage information accompanying the product.
Relevant laws, applied standards and directives Please refer to the Declaration of Conformity on our web site (www.janitza.de) for the laws, standards and directives applied by Janitza electronics GmbH for the device.
2
Safety instructions The installation instructions do not include a complete list of all safety measures necessary for operating the device. Special operating conditions may require additional measures. The installation instructions contain notes that must be observed for your personal safety and to prevent property damage.
are highlighted with a warning triangle and are presented as follows depending
on the level of risk:
DANGER
Warns of an imminent danger that will result in serious or fatal injuries in
the event of noncompliance.
Symbols used on the device:
The additional symbol on the device itself indicates an electrical danger that
can result in serious injuries or death.
The general warning symbol calls attention to possible risks of injury.
Observe all the instructions listed under this symbol in order to prevent
injuries or even death. Safety instructions in the installation instructions
Warns of a potentially dangerous situation that can result in serious injuries
or death in the event of noncompliance.
CAUTION
Warns of an imminently dangerous situation that can result in minor or
moderate injuries in the event of noncompliance.
ATTENTION
Warns of an imminently dangerous situation that can result in property damage
or environmental damage in the event of noncompliance.
INFORMATION
Points out procedures in which there are dangers of personal injuries or
property damage.
9 / 16
Safety measures When operating electrical devices, specific parts of these
devices inevitably carry dangerous voltage. As a result, serious personal
injuries or property damage can occur if they are not handled correctly: ·
Before connecting the device, ground it
at the ground wire connection if available. · Dangerous voltages may be
present in all
circuit parts connected to the voltage supply. · There may still be dangerous
voltages present
in the device even after it is disconnected from the supply voltage (capacitor
storage). · Do not operate equipment with open current transformer circuits. ·
Do not exceed the threshold values specified in the user manual and on the
rating plate. This must also be observed during inspections and commissioning.
· Observe the safety instructions and warning notices in the usage information
that accompanies the devices and their components!
WARNING
Danger due to noncompliance with warning and safety instructions.
Noncompliance with warning and safety instructions on the device itself and in
the information on using the device and its components can lead to injury or
even death. Observe safety instructions and warning notices on the device
itself and in the usage information associated with the devices and their
components, such as: · Installation instructions. · User manual. · Safety
instructions supplement.
Qualified personnel To prevent personal injuries and property damage, only
qualified personnel with electrical engineering training may work on the
baseunit and its components. They must also have knowledge · of the national
accident prevention regulations. · of safety technology standards. · in the
installation, commissioning and
operation of the device and the components.
When handling electrical currents or voltages, serious personal injuries or
death can occur due to: · Touching live exposed or stripped cores. · Device
inputs that are dangerous to touch. · Disconnect it from the power supply! ·
Secure it against being switched back on! · Verify disconnection from power! ·
Ground and short circuit! · Cover or block off neighboring parts that are
under voltage!
Intended use The device is · intended for installation in switching cabinets
and small installation distributors. The device can be installed in any
mounting position (please observe section 3 “Assembly”). · not intended for
installation in vehicles! Using the device in mobile equipment is considered
an unusual environmental condition and is only permissible by special
agreement. · not intended for installation in areas exposed to harmful oils,
acids, gases, vapors, dust and radiation, etc. · designed as an indoor meter.
Incoming goods inspection The prerequisites for trouble-free and safe
operation of the devices and their components include proper transport,
storage, setup and assembly, as well as careful operation and maintenance.
Exercise caution when unpacking and packing the device, without using force
and only using suitable tools.
Check: · Devices and components by performing
a visual inspection to ensure a flawless mechanical condition. · The scope of
delivery (see user manual) for completeness before beginning the installation
of your devices and components.
If you assume that safe operation is no longer possible, shut down the device
with components immediately and secure it from being unintentionally started
back up again.
It can be assumed that safe operation is no longer possible, when, for
example, the device with components: · Has visible damage, · No longer
functions despite an intact power
supply. · Was subjected to extended periods of
unfavorable conditions (e.g. storage outside of the permissible climate
thresholds without adjustment to the room climate, condensation, etc.) or
transport stress (e.g. falling from an elevated position, even without visible
external damage, etc.).
3
Device short description and assembly
4
The device is a multifunctional power analyzer that · measures and calculates
electrical parameters,
such as voltage, current, frequency, power, energy and harmonics, etc. in
building installations, on distributors, circuit breakers and busbar trunking
systems. · displays and saves measurement results and transfers them via
interfaces.
ATTENTION
Property damage due to noncompliance with the assembly instructions
Noncompliance with the assembly instructions can damage or destroy your
device. · Ensure sufficient air circulation in your installation
environment and, where applicable, sufficient cooling with high ambient
temperatures. · You can find more detailed information about the device
functions, data, assembly and the battery used in the device in the user
manual.
Mount the measurement device in switch cabinets or small distribution boards
according to DIN 43880 (any installation position) on a 35 mm (1.38 in) DIN
rail (for type, see technical data), as follows: 1. Insert the bus connector
included in the scope
of delivery in the socket on the bottom of the measurement device. 2. Slide
your measurement device with the bus connector laterally on the DIN rail or
press it frontally onto the DIN rail until the bottom latch engages.
INFORMATION
Before starting with the DIN rail assembly and wiring for your UMG 801, make
sure that the bus connector is mounted on the bottom of your UMG 801. Up to 10
modules are connected via the bus connector.
DIN rail
Bottom latch
1. 2.
Bus connector
Fig. Device with bus connector on DIN rail.
10 / 16
Connecting the supply voltage
The supply voltage level for your device can be found on the rating plate or
in the technical data. After connecting the supply voltage, a display appears.
If no display appears, check whether the supply voltage is within the rated
voltage range.
ATTENTION
Noncompliance of the connection conditions or exceeding the permissible
voltage range can damage or destroy your device.
· The voltage and frequency must comply with the specifications on the rating
plate. Observe the limit values as described in the user manual.
· In building installations, secure the supply voltage with a UL/IEC-listed
circuit breaker/fuse.
· The circuit breaker – must be easily accessible for the user and located in
the vicinity of the device. – must be labeled for the respective device.
· Do not tap the supply voltage at the voltage transformers.
· Provide a fuse for the neutral conductor if the neutral conductor connection
is not grounded to the source.
+PELV 24…48 V DC (grounded low voltage)
230 V AC L1 N
5
Network systems
Suitable network systems and maximum rated voltages (DIN EN 61010-1/A1):
Three-phase 4-conductor systems with grounded neutral conductor
Three-phase 4-conductor systems with ungrounded neutral conductor
(IT networks)
Three-phase 3-conductor systems ungrounded
Three-phase 3-conductor systems with grounded phase
L1
L1
L1
L1
L2
L2
N
N
R
L3
L3
E
E
E
E
E
IEC UL-N / UL-L: 480 VLN / 830 VLL UL UL-N / UL-L: 347 VLN / 600 VLL
UL-L: 690 VLL UL-L: 600 VLL
Application areas of the device: · 3 and 4 conductor networks (TN, TT and IT networks). · Residential and industrial sectors.
INFORMATION
Functional earth · Connection D (UMG 801) in TN, TT and IT
networks must always be connected. · Connection A (UMG 801) only connect in
TN and TT networks (not in IT networks).
L2
L2
L3
L3
E
E
E
UL-L: 830 VLL
UL-L: 600 VLL
6
Voltage measurement
The device has 4 voltage inputs and is suitable for
different connection versions.
WARNING
Risk of injury or damage to the device due to electric voltage and improper
connection! Noncompliance with the connection conditions for the voltage
measurement inputs can damage the device or cause serious injury and even
death. Therefore, please observe the following: · Before starting work on your
system,
disconnect the system from the power supply! Secure it against being switched
back on! Verify disconnection from power! Ground and short circuit! Cover or
block off neighboring parts that are under voltage! · The voltage measurement
inputs – must not be connected to DC current. – must be provided with a
suitable, labeled
fuse and circuit breaker (alternative: miniature circuit breaker) in their
immediate vicinity. – are dangerous to touch. · Voltages that exceed the
allowed nominal network voltages must be connected via voltage transformers. ·
Measured voltages and measured currents must originate from the same network.
L1 L2 L3 N PE
Fuse (UL/IEC listed)
Circuit breaker
Functional earth
Load
Fig. “Voltage measurement” connection example.
The voltage measurement inputs are designed for measurements in low voltage
networks in which rated voltages occur, as described in the “Technical data”.
INFORMATION
The functional earthing is a functional part and essential for the regular
operation of the electrical system.
Load
7
Voltage measurement connection versions
Voltage measurement L1, L2, L3 (baseline measurement)
N V3 V2 V1
N V3 V2 V1
N V3 V2 V1
N V3 V2 V1
L1
L1
L2
L2
L3
L3
N
N
L1
L1
L2
L2
L3
L3
N
N
Three-phase 4-conductor system Three-phase 4-conductor system Three-phase 4-conductor system Three-phase 4-conductor system
without a voltage transformer.
with a voltage transformer.
(symmetrical load)
(assymetrical load)
Three-phase 3-conductor system
N V3 V2 V1
N V3 V2 V1
L1
L1
L2
L2
L3
L3
Three-phase 3-conductor system Three-phase 3-conductor system
(assymetrical load)
with a voltage transformer.
INFORMATION
For a PE/N measurement, connect measuring input A as the functional earth. Do
not use a green-yellow wire for this, as the conductor has no protective
function!
11 / 16
Current measurement
The device · measures current exclusively via a current
transformer. · permits connection of current transformers with
a transformer ratio of ../1 A and ../5 A · has a current transformer ratio of
5/5 A as the
standard setting (I1 to I8). · does not measure DC currents.
The current transformers require basic insulation according to IEC
61010-1:2010 for the rated voltage of the circuit.
WARNING
Risk of injury due to high currents and high electrical voltages! Serious
personal injuries or death can occur due to: · Touching live exposed or
stripped cores. · Device inputs that are dangerous to touch. Therefore, please
observe the following for your system: · Before starting work, disconnect it
from the
power supply! · Secure it against being switched back on! · Verify
disconnection from power! · Ground and short circuit! Use the ground
connection points with the ground symbol for grounding! · Cover or block off
neighboring parts that are under voltage!
S1 S2
L1 L2
S1 S2
L3
S1 S2
N
S1 S2
PE
Fig. “Current measurement” connection example.
WARNING
Electrical currents and voltages! Open current transformers that are operated
on the secondary side (high voltage spikes) can result in serious personal
injuries or even death. Avoid the open operation of the current transformers
and short-circuit unloaded transformers.
Current measurement connection versions
Current measurement I1 to I4 and I5 to I8
I1 I2
I3
I4
30 31 32 33 34 35 36 37
I1 I2
I3
I4
30 31 32 33 34 35 36 37
I1 I2
I3
I4
30 31 32 33 34 35 36 37
L1
L2
L3
N
Current measurement via 3 current transformers in the three-
phase 4-conductor system.
L1
L1
L2
L2
L3
L3
N
N
Current measurement via
Current measurement via 2 current
2 current transformers in systems with transformers (Aron circuit) in the three-
equal loads.
phase 4-conductor system
Three-phase 3-conductor system
I1 I2
I3
I4
30 31 32 33 34 35 36 37
I1 I2
I3
I4
30 31 32 33 34 35 36 37
L1
L1
L2
L2
L3
L3
INFORMATION
You can easily configure the current transformer ratios via · the device menu.
· the GridVis® software. Information on programming the current transformer
ratios can be found in the user manual.
Current measurement via 2 current transformers (Aron circuit) in the three-
phase 3-conductor system
Current measurement via 3 current transformers in the three-phase 3-conductor system
10
Establishing the connection to the PC
Possible connections for the communication between the PC and device. Ex. wiring diagrams/ connections:
1. OPC UA server
PC
UMG 801
Patch cable
Switch/ router
Patch cable
Connection of the device with a patch cable (Ethernet interface) via a switch/router on the OPC UA server and the PC
2. DHCP server
PC
UMG 801
Patch cable
Switch/ router
Patch cable
The DHCP server automatically assigns IP addresses to the device and PC.
3. PC
Patch cable
UMG 801
The PC and device require a fixed IP address.
ATTENTION
Security vulnerabilities can result in data misuse, faults and even cause your
IT infrastructure to shut down. · Notify your network administrator and/or IT
manager. · Always keep the measurement device firmware
up to date and protect the communication to the measurement device with an
external firewall. Close any unused ports. · Take protective measures against
viruses and cyber attacks from the Internet, e.g. through firewall solutions,
security updates and antivirus programs. · Eliminate security vulnerabilities
and update or renew existing protection for your IT infrastructure.
INFORMATION
The device has 2 Ethernet interfaces, which are serially connected (daisy
chain connection).
Patch cable
Ethernet A
Ethernet B
Recommendation: Use at least CAT5 cables!
ATTENTION
Property damage due to incorrect network settings. Incorrect network settings
can cause faults in the IT network! Consult your network administrator for the
correct network settings for your device.
12 / 16
Operation and button functions
The device is operated via 6 function keys for · Selecting measured value
indications. · Navigation within the menus. · Device configuration.
Key Function · Display menu. · 1 step back. · Cancel action (ESC). · Pressing
repeatedly leads to the menu.
· Select menu item or position (up “5”). · Change selection (number +1).
· Confirm selection (Enter).
· Select position (to the left “3”).
· Select menu item or position (down “6”).
· Change selection (number -1).
· Select position (to the right ” “).
Display for measured values
and device configuration
Function keys
Fig. UMG 801 measured values standard display After a return of power, the
device starts with the Home measured value display. By pressing function key 1
(ESC), the menu appears. (For description, see user manual).
INFORMATION
Detailed information about the operation, display and key functions for your
device can be found in the user manual.
INFORMATION
The measurement device has the password 00000 (no password) ex works. Further
information on configuring a password can be found in the user manual.
Configuring the Ethernet connection
After a return of power, the device starts with the Home standard display.
· Press function key 1 ESC to open the menu. · Use keys 2 “5” and 5 “6” to
select the
Configuration menu entry and confirm with key 3 Enter.
Menü Power Energy Multifunctional Channels Configuration System Information
Fig. Configuration menu entry · The Configuration window appears with the
Ethernet (TCP/IP) entry. · In the Configuration window, use keys 2 “5”
and 5 “6” to select the Ethernet (TCP/IP) entry and confirm with key 3 Enter.
· The Ethernet (TCP/IP) window appears.
Ethernet (TCP/IP)
IP Config.
DHCP
IP Address Netmask
192. 168. 3. 177 255. 255. 255. 0
Gateway
192. 168. 3. 4
ESC
Fig. Ethernet window (TCP/IP)
· Select and configure the Ethernet interface.
The device has 2 Ethernet interfaces, which are serially connected (daisy chain connection).
INFORMATION
Detailed information on all menu entries and their settings can be found in
the user manual.
13
Communication via TCP/IP
The device has 2 ways to allocate addresses for the Ethernet interface
(TCP/IP) in the DHCP mode: 1. Static (fixed IP address)
The user selects the IP address, netmask and gateway on the device. Use this
mode for simple networks without a DHCP server. 2. DHCP When starting, the
device automatically receives an IP address, netmask and gateway from the DHCP
server.
The standard setting for the device is DHCP!
INFORMATION
· Consult your network administrator for the correct Ethernet network settings
for your device.
· Descriptions of additional communication interfaces can be found in the user
manual.
· Information on the connection and communication of your device with the
software can be found in the online help for the GridVis® software
Configure your Ethernet (TCP/IP) settings via the function keys as described
in step 11 “Operation and button functions”.
Configuration Ethernet (TCP/IP) Fieldbus Current Transformer Voltage
Transformer Display
ESC
Fig. Configuration window with the Ethernet (TCP/IP) entry
Ethernet (TCP/IP)
IP Config.
DHCP
IP Address Netmask
192. 168. 3. 177 255. 255. 255. 0
Gateway
192. 168. 3. 4
ESC
Fig. Ethernet (TCP/IP)
14 Communication via OPC UA
The data transmission with OPC UA protocol occurs via the Ethernet interfaces
of your device.
The Ethernet interface and data transmission via the OPC UA protocol are
easily configured via the GridVis® software.
INFORMATION
· Consult your network administrator for the correct Ethernet network settings
for your device.
· Descriptions of the communication interfaces can be found in the user
manual.
· Information on the connection and communication of your device with the
software can be found in the online help for the GridVis® software
13 / 16
15 Configuring the current transformer
1. Press function key 1 ESC to open the menu. 2. Use keys 2 “5” and55 “6” to
s6elect the
Configuration menu entry and confirm with key 3 Enter. 3. In the Configuration
window, use keys 2 “5” and55 “6” to s6elect the Current transformer entry and
confirm with key 3 Enter. 4. The Current transformer window appears. 5. In the
Current transformer window, select the Device entry and confirm using key 3
Enter. 6. The Device entry appears in “blue”. In the Device entry, select
between the base unit and up to 10 current measuring modules. 7. Confirm the
Base unit entry with key 3 Enter. 8. Using key 5 “6”, sw6itch to the setting
for the Primary side of the current transformer 1..4 (current measurement
inputs I1..I4) and confirm with key 3 Enter. 9. The entry for the primary side
of the current transformer I1..I4 “flashes”. 10.Use keys 4 (3) and36 () to
change the position of the number to be set and keys 2 (5) and55 (6) to
c6hange the number (-1/+1). 11.Confirm your entries with key 3 Enter or cancel
the action with key 1 ESC. 12.Switch to the configuration for the secondary
side of the current transformer I1..I4 using key 6 ().
13.Configure the secondary side of the current transformer I1..I4 in the same
manner.
14.Confirm your entries with key 3 Enter or cancel the action with key 1 ESC.
15.After completing the entries, press key 1 ESC to return to the Menu window.
Configure the current transformer 5..8 (I5..I8) according to the current
transformer ratios I1..I14.
Current Transformer
Device
Main Device
Primary
Secondary
Transformer 1..4
5 A
5 A
Transformer 5..8
5 A
5 A
ESC
Fig. Current transformer window
INFORMATION
The current transformer ratios are also configured in the device configuration
of the GridVis® software.
0..30 mA 0..30 mA
Load
17
The multifunction channels on the UMG 801 optionally have the functions and
The residual current monitoring and temperature monitoring share the 4
channels (4, 2/2, 3/1 or 1/3 each).
L1 L2 L3 N PE
2x PT100 7 8 9 10 11 12 13 14
Multifunction channels for residual current monitoring (RCM)
The UMG 801 with its multifunction channels, among other things, is suitable
for use as a residual current monitoring device (RCM) for monitoring ·
alternating currents. · direct currents and · pulsing direct currents.
The UMG 801 measures residual currents according to IEC/TR 60755 of:
Type A
Type B and B+ (via corresponding CTs)
Configuring the voltage transformer
1. Press function key 1 ESC to open the menu. 2. Use ke5ys 2 “5” a6nd 5 “6”
to select the
Configuration menu entry and confirm with key 3 Enter. 3. In the Configuration
window, use ke5ys 2 “5” a6nd 5 “6” to select the Voltage transformer entry and
confirm with key 3 Enter. 4. The Voltage transformer window appears. 5. In the
Voltage transformer window, select the entry Transformer 1..4 (voltage
measurement inputs L1 to L4) and press key 3 Enter. 6. The entry for the
primary side of the transformer 1..4 “flashes”. 7. Use k3eys 4 (3) and 6 () to
change the position of the number to be set and keys 5 2 (5) a6nd 5 (6) to
change the number (-1/+1). 8. Confirm your entries with key 3 Enter or cancel
the action with key 1 ESC. 9. Switch to the configuration for the secondary
side of the transformer 1..4 (voltage measurement inputs L1 to L4) using key 6
(). 10.Configure the secondary side of the voltage transformer 1..4 in the
same manner. 11.Confirm your entries with key 3 Enter or cancel the action
with key 1 ESC. 12.After completing the entries, press key 1 ESC to return to
the Menu window.
Voltage Transformer
Primary Secondary
Transformer 1..4 400 V
400 V
ESC
Fig. Voltage transformer window
INFORMATION
The voltage transformer ratios are also configured in the device configuration
of the GridVis® software.
INFORMATION
· The multifunction channels are suitable for the connection of residual
current transformers with a rated current up to 30 mA and have the function
“Check the current transformer connection”.
· The residual current monitoring monitors the residual currents via external
current transformers and, if a threshold value is exceeded, can trigger a
warning signal. The measurement device is not an independent protection device
against electric shock!
Recommendation: To configure the transformation ratio for the residual current
transformer, use the GridVis® software.
ATTENTION
Faulty cross currents, wrong measurements, up to damage to the device and / or
your system due to missing galvanic separations! Failure to galvanically
isolate active external CTs (or other current transmitters) on the
multifunction channels from the device power supply can result in faulty
cross-currents, incorrect measurements, or damage to your device and / or your
system. · Do not remove the auxiliary power supply of
active external current transformers (or other current generators) on the
multifunction channels from the supply voltage of the device! For each active
current transformer, use galvanically isolated power supply units (secondary
side). · Do not ground passive current transformers on the multifunctional
channels! Observe the usage information of the current transformer
manufacturer.
Connection example for multifunction channels for the residual current monitoring and temperature measurement
14 / 16
18
Technical data
5 56 6
Net weight
Device dimensions
5 56
Battery
Service life of the backlight
Installation position
Mounting/assembly suitable DIN rails 35 mm (1.38 in)
Impact resistance
420 g (0.926 lb)
approx. w = 144 mm (5.67 in), h = 90 mm (3.54 in),
dTy=pe766lithmiumm(2C.9R920in3)2, 3 V
(UL1642 approval) 40000 h (50% of the starting brightness)
discretionary
· TS 35/7.5 according to EN 60715 · TS 35/10 · TS 35/15 x 1.5
IK07 according to IEC 62262
Transport and storage
The following informa6tion applie6s to devices which are
transported and stored in the original packaging.
Free fall
1 m (39.37 in)
Temperature
-25 °C (-13 °F) up to +70 °C (158 °F)
Relative humidity
5 to 95% at 25 °C (77 °F) without condensation
3 3
5 56 6
Ambient conditions during operation
The device · must be used in a weather-protected, stationary application. ·
fulfills the operating conditions according to DIN IEC 60721-3-3. · possesses
protection class II according to IEC 60536 (VDE 0106, Part 1),
a ground wire connection is not required!
Measurement temperature range
-10 °C (14 °F) .. +55 °C (131 °F)
Relative humidity
5 to 95% at 25 °C (77 °F) without condensation
Operating height/ overvoltage category
2000 m (1.24 mi) above sea level Voltage measurement: 1000 V CATIII; 600 V
CATIV Current measurement: 300 V CATII
4000 m (2.49 mi) above sea level Voltage measurement: 600 V CATIII; Current
measurement: 300 V CATII
Pollution degree
2
Ventilation
No external ventilation required.
Protection against foreign bodies and water
IP20 according to EN60529
Supply voltage
Nominal range
DC: 24 V – 48 V, PELV
Operating range Power consumption
+/-10% of the nominal range max. 4 W
Maximum power consumption with 10 modules
12 W (UMG 801 with 4 W plus 10 modules with 0.8 W each)
Recommended overcurrent protection device for the line protection
2-6 A (char. B), IEC-/UL approval
Voltage m5easurem5en6t
6
Three-phase 4-conductor systems with rated voltages up to
Tsyhsr6eteem-psh(agsreou36n-dcoednd) wucitthor
rated voltages up to
480 VLN / 830 VLL (+/-10%) acc. IEC 347 VLN / 600 VLL (+/-10%) acc. UL
55
830 VL-L (+/-10%) acc. IEC 600 VL-L (+/-10%) acc. UL
Three-phase 3-conductor systems (ungrounded) with rated voltages up to
690 VL-L (+/-10%) acc. IEC 600 VL-L (+/-10%) acc. UL
Overvoltage category
· 1000 V CAT III acc. IEC · 600 V CAT III acc. UL
Rated surge voltage
8 kV
Fuse for the
1 – 10 A tripping characteristic B
voltage measurement
(with IEC/UL approval)
3 3
Metering range L-N
- .. 720 Vrms
(max. overvoltage 1000 Vrms )
5 Meterin5g r6ange L-L 6
- .. 1000 Vrms (max. overvoltage 1000 Vrms )
Metering range N-PE
up to 100 V
Resolution
16 bit
Crest factor Impedance
1.6 (based on the metering range
600 V L-N)
4 M/phase
Power consumption
Approx. 0.1 VA
Sampling frequency
51.2 kHz
Frequency of the basic oscillation – resolution
40 Hz .. 70 Hz 0.01 Hz
Harmonics
1 .. 127.
- … The device only measures if a voltage L-N of >10 Vrms or a voltage L-L of
18 Vrms is present on at least one voltage measurement input.
Current measurement (../1A) (../5A)
Rated current
Channels
Metering range Crest factor (based on the rated current) Overload for 1 sec.
5 A 8 · 2 systems (L1, L2, L3, N) · Individual channels 0.005 .. 6 Arms
1.98
120 A (sinusoidal)
Resolution
0.1 mA (color graphic display 0.01A)
Overvoltage category
300 V CATII
Rated surge voltage
2,5 kV
Power consumption Sampling frequency
approx. 0.2 VA (Ri = 5 m) 25.6 kHz
Harmonics
1 .. 63.
The device optionally has 4 multifunction channels for use as · residual
current measurement inputs and/or temperature
measurement inputs (mixed), · additional system inputs (L1, L2, L3, N)
Residual current monitoring (RCM)
Rated current Metering range Response current Resolution Crest factor Load Overload for 20 ms
30 mArms 0 .. 40 mArms 50 µA 1 µA (color graphic display 0.01A) 1.414 (based on 40 mA) 4 50 A
Residual current monitoring (RCM)
Overload for 1 s
5 A
Permanent overload Standard
1 A
IEC/TR 60755 (2008-01), type A / type B and B+ (via corresponding CTs)
Temperature measurement
Update time Total burden (sensor and lead)
Lead
Suitable sensor types
1 s
max. 4 k
<= 30 m unshielded > 30 m shielded KTY83, KTY84, PT100, PT1000
Digital inputs 4 digital inputs, semiconductor relays, not short-circuit proof.
Maximum counter frequency 20 Hz
Input signal present Input signal not present
18 V .. 28 V DC (typical 4 mA)
0 .. 5 V DC, current less than 0.5 mA
Digital outputs 4 digital outputs, semiconductor relays, not short-circuit proof.
Switching voltage
max. 60 V DC
Switching current
max. 50 mArms DC
Response time
Approx. 500 ms
Pulse output (energy pulse) Max. 20 Hz
Line length (digital inputs/outputs)
Up to 30 m (32.81 yd.)
Unshielded
Greater than 30 m (32.81 yd.) Shielded
Analog output 1 channel External power supply Current Update time Load Resolution
max. 33 VDC 0/4…20 mA DC 0.2 s Max. 300 10 Bit
RS485 interface 3-wire connection with A, B, GND. Recommended cable types see user manual.
Protocol
Modbus RTU/slave Modbus RTU/gateway
Transmission rate
9.6 kbps, 19.2 kbps, 38.4 kbps, 57.6 kbps, 115.2 kbps
Termination
DIP switch
Ethernet interfaces Connection Function Protocols and services Time synchronization
2 x RJ45
Modbus gateway OPC UA, DHCP, Modbus/TCP, NTP NTP
15 / 16
Potential separation and electrical safety of the interfaces
The interfaces (RS485, Ethernet) have · double insulation to the inputs for
the voltage and current
measurement. · functional insulation against each other to the supply voltage,
the residual current and temperature measurement inputs, the digital
inputs/outputs and the analog output. The interfaces of the connected devices
require a double or reinforced insulation against supply voltages (according
to IEC 61010-1: 2010).
Potential separation and electrical safety of the multifunction channels (RCM,
temp.)
The inputs for the multifunction channels have · double insulation to the
inputs for the voltage and current
measurement. · no insulation among each other and to the supply voltage.. ·
functional insulation to the Ethernet, RS485 interfaces, the
digital inputs/outputs and the analog output. External sensors and/or
measuring transformers require a double insulation to the system parts that
have dangerous contact voltage (according to IEC61010-1:2010).
Potential separation and electrical safety of the digital inputs and outputs
(I/Os) and the analog output
The digital inputs and outputs and the analog output have · double insulation
to the inputs for the voltage and current
measurement. · functional insulation against each other to the supply voltage,
the Ethernet, RS485 interfaces, and the multifunction channels.
Terminal connection capacity
(supply voltage)
Connectable conductors. Only one conductor can be connected per terminal.
Single core, multi-core, fine-stranded
0.2 – 2.5 mm2, AWG 26-12
Cable end sleeve (not insulated) 0.2 – 2.5 mm2, AWG 26-12 – recommended stripping length 10 mm (0.3937 in)
Cable end sleeve (insulated)
0.2 – 2.5 mm2, AWG 26-12
– recommended stripping length 13 mm (0.5118 in)
Cable end sleeve Length of the contact sleeve
10 mm (0.3937 in)
Terminal connection capacity (supply voltage)
Connectable conductors. Only one conductor can be connected per terminal.
Single core, multi-core, fine-stranded
0.2 – 2.5 mm2, AWG 26-12
Cable end sleeve (not insulated) 0.2 – 2.5 mm2, AWG 26-12 – recommended stripping length 10 mm (0.3937 in)
Cable end sleeve (insulated)
0.2 – 2.5 mm2, AWG 26-12
– recommended stripping length 13 mm (0.5118 in)
Cable end sleeve Length of the contact sleeve
10 mm (0.3937 in)
Tightening torque screw flange
0.2 Nm (1.77 lbf in)
Terminal connection capacity (voltage measurement)
Connectable conductors. Only one conductor can be connected per terminal.
Single core, multi-core, fine-stranded
0.08 – 4 mm2, AWG 28-12
Cable end sleeve (insulated/not insulated)
0.25 – 2.5 mm2, AWG 24-14
Stripping length
8-9 mm (0.3150 – 0.3543 in)
Terminal connection capacity (A/D functional ground)
Connectable conductors. Only one conductor can be connected per terminal.
Single core, multi-core, fine-stranded
0.2 – 4 mm2, AWG 24-12
Cable end sleeve (not insulated) 0.2 – 4 mm2, AWG 24-12
Cable end sleeve (insulated)
0.2 – 2.5 mm2, AWG 26-14
Tightening torque
0.4 – 0.5 Nm (3.54 – 4.43 lbf in)
Stripping length
7 mm (0.2756 in)
Terminal connection capacity –
multifunction channels (RCM, temp.) Connectable conductors. Only one conductor
can be connected per terminal.
Single core, multi-core, fine-stranded
0.2 – 1.5 mm2, AWG 24-16
Cable end sleeve (not insulated) 0.2 – 1.5 mm2, AWG 26-16
Cable end sleeve (insulated)
0.2 – 1 mm2, AWG 26-18
Tightening torque
0.2 – 0.25 Nm (1.77 – 2.21 lbf in)
Stripping length
7 mm (0.2756 in)
Terminal connection capacity (digital inputs/outputs, analog output)
Single core, multi-core, fine-stranded
0.2 – 1.5 mm2, AWG 24-16
Cable end sleeve (not insulated) 0.2 – 1.5 mm2, AWG 26-16
Cable end sleeve (insulated)
0.2 – 1 mm2, AWG 26-18
Tightening torque
0.2 – 0.25 Nm (1.77 – 2.21 lbf in)
Stripping length
7 mm (0.2756 in)
Terminal connection capacity (RS485)
Single core, multi-core, fine-stranded
Cable end sleeve (not insulated)
Cable end sleeve (insulated)
0,2 – 1,5 mm2, AWG 24-16
0,2 – 1,5 mm2, AWG 26-16 0,2 – 1 mm2, AWG 26-18
Tightening torque
0.2 – 0.25 Nm (1.77 – 2.21 lbf in)
Stripping length
7 mm (0.2756 in)
INFORMATION
Additional technical data can be found in the user manual for the device at
www.janitza.de.
19
Procedure in the event of errors
Possible error No display
No current display
Cause External fuse for the supply voltage has tripped. Measured voltage is
not connected.
Measurement current is not connected.
Remedy Replace fuse. Connect the measured voltage. Connect measurement current.
Current displayed is too large or too small.
Voltage displayed is too large or too small.
Voltage displayed is too small. Device still does not work despite the above
measures.
Current measurement in the wrong phase.
Check connection and correct if necessary.
Current transformer factor is incorrectly programmed.
Current harmonics exceed the current peak value at the measurement input The
current at the measurement input was not achieved.
Read out and program the current transformer transformation ratio at the
current transformer.
Install current transformer with a larger current transformer ratio.
Install current transformer with a smaller current transformer ratio.
Measurement in the wrong phase.
Check connection and correct if necessary.
Voltage transformer incorrectly programmed.
Read out and program the voltage transformer ratio at the voltage transformer.
Measurement range exceeded.
Install voltage transformers.
The peak voltage value at the measurement input has Attention! Ensure the measurement inputs are not
been exceeded by harmonic components.
overloaded.
Device defective.
Send the device and error description to the manufacturer for testing.
16 / 16
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>