PENTAIR Fleck 5800 Sxt Downflow Upflow Owner’s Manual

June 11, 2024
Pentair

PENTAIR Fleck 5800 Sxt Downflow Upflow

PENTAIR-Fleck-5800-Sxt-Downflow-Upflow

PRODUCT INFORMATION

The Fleck 5800 SXT is a water softener system that utilizes a control valve assembly to regulate water flow and regeneration cycles. The system is available in both downflow and upflow configurations. The water softener system is designed to remove hard minerals from water, which can cause damage to pipes and appliances, and create soap scum buildup on surfaces. The system features a user-programmable control panel that allows for customization of backwash, brine and slow rinse, rapid rinse, brinetank refill, and pause time cycles. The system also includes a safety brine valve to prevent overfilling of the brine tank.

PRODUCT USAGE INSTRUCTIONS

Installation:

  1. Determine the job specifications for the system, including job number, model number, water hardness, capacity per unit, mineral tank size, and salt setting per regeneration.
  2. Install the system according to the installation instructions provided in the manual.
  3. Connect the system to the water supply and drain lines.
  4. Connect the control valve assembly to the mineral tank.
  5. Install the brine tank and connect it to the control valve assembly.

Start-Up:

  1. Ensure that the system is properly installed and connected.
  2. Turn on the water supply to the system.
  3. Set the control panel to the desired program settings for backwash, brine and slow rinse, rapid rinse, brine tank refill, and pause time cycles.
  4. Initiate a regeneration cycle by pressing the “Regenerate” button on the control panel.

Control Features:
The control panel includes a variety of features, including: – User- programmable cycles for backwash, brine and slow rinse, rapid rinse, brine tank refill, and pause time. – Master programming mode for advanced customization of system settings. – Diagnostic data viewing to monitor system performance. – System disinfection cycle to remove bacteria and other contaminants.

Control Operation:
The control panel regulates water flow and regeneration cycles for the system. The user can program the control panel to initiate backwash, brine and slow rinse, rapid rinse, brine tank refill, and pause time cycles according to their preferences. The system will automatically regenerate when necessary based on water usage and hardness levels.


Care and Maintenance:

  1. Regularly check the salt level in the brine tank and refill as necessary.
  2. Clean the control valve assembly and mineral tank periodically to ensure optimal performance.
  3. Follow the system disinfection cycle as needed to remove bacteria and other contaminants.

Troubleshooting

If the system is not functioning properly, consult the troubleshooting guide provided in the manual. Common issues may include low water pressure, salt bridging in the brine tank, or malfunctioning control valve assembly components.

IMPORTANT PLEASE READ:

  • The information, specifications and illustrations in this manual are based on the latest information available at the time of printing. The manufacturer reserves the right to make changes at any time without notice.
  • This manual is intended as a guide for service of the valve only. System installation requires information from a number of suppliers not known at the time of manufacture. This product should be installed by a plumbing professional.
  • This unit is designed to be installed on potable water systems only.
  • This product must be installed in compliance with all state and municipal plumbing and electrical codes. Permits may be required at the time of installation.
  • It is established that when daytime water pressure exceeds 80 psi (5.5 bar), the maximum pressure rating of 125 psi (8.6 bar) can be exceeded. A pressure regulator must be installed on this system or warranty is voided.
  • Do not install the unit where temperatures may drop below 32°F (0°C) or above 125°F (52°C).
  • Do not place the unit in direct sunlight. Black units will absorb radiant heat increasing internal temperatures.
  • Do not strike the valve or any of the components.
  • Warranty of this product extends to manufacturing defects. Misapplication of this product may result in failure to properly condition water, or damage to product.
  • A prefilter should be used on installations in which free solids are present.
  • In some applications local municipalities treat water with Chloramines. High Chloramine levels may damage valve components.
  • Correct and constant voltage must be supplied to the controller to maintain proper function.

FLECK 5800 SXT Upflow/Downflow

JOB SPECIFICATION SHEET

Job Number: ___

Model Number: _____

Water Hardness: ___ ppm or gpg

Capacity Per Unit: ___

Mineral Tank Size: __ Diameter: ____ Height: _____

Salt Setting per Regeneration: _____

Regenerant Flow:

Upflow

Downflow

1. Meter Size:

A. 3/4″ Paddle Wheel

B. 3/4″ Turbine

C. 1″ Paddle Wheel (Not Used)

D. 1″ Turbine (Not Used)

E. 1-1/2″ Electronic Inline Plastic Turbine (Not Used)

F. 1-1/2″ Paddle Wheel (Not Used)

G. 2″ Paddle Wheel (Not Used)

H. Generic_____Pulse Count__Meter Size__

2. System Type:

A. System #4: 1 Tank, 1 Meter, Immediate, or Delayed Regeneration

B. System #4: Time Clock

3. Control Program Settings:

A. Backwash: ____ Minutes

B. Brine and Slow Rinse: ___ Minutes

C. Rapid Rinse: ___ Minutes

D. Brine Tank Refill: ___ Minutes

E. Pause Time: ___ Minutes

F. Second Backwash: __ Minutes

4. Drain Line Flow Control:_____ gpm

5. Brine Line Flow Control: ____ gpm

6. Injector Size#: ___

CALIFORNIA PROPOSITION 65 WARNING
WARNING: This product contains chemicals known to the State of California to cause cancer or birth defects or other reproductive harm.

INSTALLATION
Water Pressure
A minimum of 20 psi (1.4 bar) of water pressure is required for the regeneration valve to operate effectively.
Electrical Facilities
An uninterrupted alternating current (120 VAC) supply is required. The control uses a transformer to supply 12 VDC. Please make sure your voltage supply is compatible with your unit before installation.
Existing Plumbing
Condition of existing plumbing should be free from lime and iron buildup. Piping that is built up heavily with lime and/or iron should be replaced. If piping is clogged with iron, a separate iron filter unit should be installed ahead of the water softener.
Location of Softener and Drain
You must have an air gap on the drain line to prevent back flow of drain water into the system. A 2x the drain line pipe diameter air gap is required with a minimum 1″ air gap.
Air Gap
Drain
Figure 1
Outdoor Locations
When the water conditioning system is installed outdoors, several items must be considered.
· Moisture — The system is not designed to withstand extreme humidity or water spray from below. Examples are: constant heavy mist, near corrosive environment, upwards spray from sprinkler.
CAUTION This unit is for dry location use only unless used with a Listed Class 2 power supply suitable for outdoor use.
· Direct Sunlight — The materials used will fade or discolor over time in direct sunlight. The integrity of the materials will not degrade to cause system failures. If it is necessary to locate the system in direct sunlight, a protective outdoor cover (P/N 61882) over the valve and controller is necessary.
· Insects — If installing in an environment that may expose the system to insects or other small animals, a protective cover is required. The protective outdoor cover (P/N 61882) has been designed to keep all but the smallest insects out of the critical areas. The cover should be installed securely in place.
Bypass Valves
Always provide for the installation of a bypass valve if unit is not equipped with one. CAUTION Water pressure is not to exceed 125 psi (8.6 bar),
water temperature is not to exceed 110°F (43°C), and the unit cannot be subjected to freezing conditions. WARNING: The system must be depressurized before
removing any connections for servicing.
Installation Instructions 1. Place the softener tank where you want to install the unit.
Make sure the unit is level and on a firm base.

2. During cold weather, the installer should warm the valve to room temperature before operating.
3. All plumbing should be done in accordance with local plumbing codes. The pipe size for a residential drain line should be a minimum of 1/2″ (13 mm). Backwash flow rates in excess of 7 gpm (26.5 Lpm) or drain line length in excess of 20′ (6 m) require 3/4″ (19 mm) drain line. Commercial drain lines should be the same size as the drain line flow control.
NOTE: The tank should have the distributor tube installed and have the proper amount of regenerant in place.
4. Refer to the dimensional drawing for cutting height of the distributor tube. If there is no dimensional drawing, cut the distributor tube flush with the top of the tank.
5. Lubricate the distributor O-ring seal and tank O-ring seal. Place the main control valve on tank. Note: Only use silicone lubricant.
6. Soldering of joints near the drain port must be done prior to connecting the Drain Line Flow Control fitting (DLFC). Leave at least 6″ (15 cm) between the DLFC and solder joints when soldering pipes that are connected on the DLFC. Failure to do this could cause interior damage to the DLFC.
7. PTFE plumbing tape is the only sealant to be used on the drain fitting.
8. Make sure that the floor is clean beneath the salt storage tank and that the tank is level.
9. Place approximately 1″ (25 mm) of water above the grid plate. If a grid is not utilized, fill to the top of the air check (Figure 1) in the salt tank. Do not add salt to the brine tank at this time.
CAUTION If grid plate is used, cut air check height even with grid plate. This is critical on 6″, 7″, 8″ and 9″ tanks. The brine refill water must come above the grid plate and make contact with the salt.
10. On units with a bypass, place in bypass position. Turn on the main water supply. Open a cold soft water tap nearby and let run a few minutes or until the plumbing is free from foreign material (usually solder) that may have resulted from the installation. Once clean, close the water tap.
11. Slowly place the bypass in service position and let water flow into the mineral tank. When water flow stops, slowly open a cold water tap nearby and let water run until the air is purged from the unit.
12. Plug the transformer into an electrical outlet. NOTE: All electrical connections must be connected
according to local codes. Be certain the outlet is uninterrupted.
Figure 2 Residential Air Check Valve
Electrical Connection
The controller operates on 12-volt DC power supply. This requires use of the supplied power adapter included with your system. NOTE: The power source should be constant. Be certain
the AC adapter is not on a switched outlet. Power interruptions longer than 8 hours may cause the controller to lose the time setting. When power is restored, the time setting must then be re-entered.
FLECK 5800 SXT Upflow/Downflow · 3

START-UP INSTRUCTIONS
The water softener should be installed with the inlet, outlet, and drain connections made in accordance with the manufacturer’s recommendations, and to meet applicable plumbing codes.
1. Program the valve control according to instructions shown in this manual.
2. Start an immediate regeneration by holding the Extra Cycle button for five seconds. Position the valve to backwash. Ensure the drain line flow remains steady for 10 minutes or until the water runs clear.
3. Position the valve to the brine / slow rinse position. Ensure the unit is drawing water from the brine tank (this step may need to be repeated).
4. Position the valve to the rapid rinse position. Check the drain line flow, and run for five minutes or until the water runs clear.
5. Position the valve to the start of the brine tank fill cycle. Ensure water goes into the brine tank at the desired rate. The brine valve drive cam will hold the valve in this position to fill the brine tank for the first regeneration.
6. Replace control cover.
7. Put salt in the brine tank.
NOTE: Do not use granulated or rock salt.
CONTROL FEATURES

Features of the SXT:
· Power backup that continues to keep time and the passage of days for a minimum of 8 hours in the event of power failure. During a power outage, the control goes into a power-saving mode. It does not monitor water usage during a power failure, but it does store the volume remaining at the time of power failure.
· Settings for both valve (basic system) and control type (method used to trigger a regeneration).
· Day-of-the-Week controls.
· While in service, the display alternates between time of day, volume remaining or days to regeneration.
· The Flow Indicator flashes when outlet flow is detected.
· The Service Icon flashes if a regeneration cycle has been queued.
· A Regeneration can be triggered immediately by pressing the Extra Cycle button for five seconds.
· The Parameter Display displays the current cycle step (BW, BF, RR etc) during regeneration, and the data display counts down the time remaining for that cycle step. While the valve is transferring to a new cycle step, the display will flash. The parameter display will identify the destination cycle step (BW, BF, RR, etc.) and the data display will read “——“. Once the valve reaches the cycle step, the display will stop flashing and the data display will change to the time remaining. During regeneration, the user can force the control to advance to the next cycle step immediately by pressing the Extra Cycle button.
Setting the Time of Day
1. Press and hold either the Up or Down buttons until the programming icon replaces the service icon and the parameter display reads TD.
2. Adjust the displayed time with the Up and Down buttons.
3. When the desired time is set, press the Extra Cycle button to resume normal operation. The unit will also return to normal operation after five seconds if no buttons are pressed.

Figure 3

Figure 4
Queueing a Regeneration 1. Press the Extra Cycle button. The service icon will flash to
indicate that a regeneration is queued. 2. To cancel a queued regeneration, press the Extra Cycle
button.
Regenerating Immediately Press and hold the Extra Cycle button for five seconds.

4 · FLECK 5800 SXT Upflow/Downflow

USER PROGRAMMING
The 5800 SXT control was designed to operate under most conditions with minimal programming. Follow the procedure below to set up the control for normal operation. For more indepth programming information, see the Master Programming section.

Abbreviation

Parameter

Description

DO

Day Override

The control’s day override

setting.

RT

Regeneration Time The time of the day that

the system will regenerate

(meter delayed, time clock,

and day-of-week systems)

H

Feed Water Hardness The hardness of the inlet

water – used to calculate

system capacity for

metered systems.

RC or SF

Reserve Capacity

The fixed reserve capacity of the system in gallons to maintain before the next scheduled regeneration. Can also be set as a percentage of total capacity. See Master Programming section..

CD

Current Day

The current day of week.

NOTE: Some items may not be shown depending on control configuration. The control will discard any changes and exit User Programming Mode if a button is not pressed for 60 seconds.

NOTE: When variable reserve (cr) is selected from Master Programming, User Programming will display SF. However, changing the value of SF will have no effect when variable reserve is selected in Master Programming.

User Programming Mode Steps
1. Press the Up and Down buttons for five seconds while in service, and the time of day is NOT set to 12:01 PM.
2. Use this display to adjust the Day Override. This option setting is identified by “DO” in the upper left corner of the screen.

4. Press the Extra Cycle button. Use this display to adjust the Feed Water Hardness. This option setting is identified by “H” in the upper left corner of the screen.
Figure 7 Range: 1-199 hardness 5. Press the Extra Cycle button. Use this display to adjust the
Fixed Reserve Capacity. This option setting is identified by “RC” or “SF” in the upper left corner of the screen. NOTE: This setting is dependent upon Reserve Selection
setting in Master Programming. Default is RC Reserve Capacity (Gallons). See Master Programming section for more information.
Figure 8 6. Press the Extra Cycle button. Use this display to set the
Current Day of the Week. This option setting is identified by “CD” in the upper left corner of the screen.
Figure 9 7. Press the Extra Cycle button to end User Programming.

Figure 5
3. Press the Extra Cycle button. Use this display to adjust the Regeneration Time. This option setting is identified by “RT” in the upper left corner of the screen.

Figure 6

FLECK 5800 SXT Upflow/Downflow · 5

CONTROL OPERATION
Meter Immediate Control
A Meter Immediate control measures water usage and regenerates the system as soon as the calculated system capacity is depleted. The control calculates the system capacity by dividing the unit capacity (typically expressed in grains/ unit volume) by the feed water hardness and subtracting the reserve. Meter Immediate systems generally do not use a reserve volume. The control will also start a regeneration cycle at the programmed regeneration time if a number of days equal to the regeneration day override pass before water usage depletes the calculated system capacity.
Meter Delayed Control
A Meter Delayed Control measures water usage. The system regenerates at the programmed regeneration time after the calculated system capacity is depleted. As with Meter Immediate systems, the control calculates the system capacity by dividing the unit capacity by the feed water hardness and subtracting the reserve. The reserve should be set to ensure that the system delivers treated water between the time the system capacity is depleted and the actual regeneration time. A Meter Delayed control will also start a regeneration cycle at the programmed regeneration time if a number of days equal to the regeneration day override pass before water usage depletes the calculated system capacity.
Time Clock Delayed Control
A Time Clock Delayed Control regenerates the system on a timed interval. The control will initiate a regeneration cycle at the programmed regeneration time when the number of days since the last regeneration equals the regeneration day override value.
Day of the Week Control
This control regenerates the system on a weekly schedule. The schedule is defined in Master Programming by setting each day to either “off” or “on”. The control will initiate a regeneration cycle on days that have been set to “on” at the specified regeneration time.
Control Operation During Regeneration
During regeneration, the control shows the current regeneration step number the valve is advancing to, or has reached, and the time remaining in that step. The step number that displays flashes until the valve completes driving to this regeneration step position. Once all regeneration steps are complete the valve returns to service and resumes normal operation.
Pressing the Extra Cycle button during a regeneration cycle immediately advances the valve to the next cycle step position and resumes normal step timing.
Control Operation During Programming
The control only enters the Program Mode with the valve in service. While in the Program Mode, the control continues to operate normally monitoring water usage and keeping all displays up to date. Control programming is stored in memory permanently.

Manually Initiating a Regeneration
1. When the system is in service, press the Extra Cycle button for five seconds on the main screen.
2. The control advances to Regeneration Cycle Step #1 (backwash), and begins programmed time count down.
3. Press the Extra Cycle button once to advance valve to Regeneration Cycle Step #2 (brine draw and slow rinse).
4. Press the Extra Cycle button once to advance valve to Regeneration Cycle Step #3 (rapid rinse).
5. Press the Extra Cycle button once to advance valve to Regeneration Cycle Step #4 (brine refill).
6. Press the Extra Cycle button once more to advance the valve back to in service.
NOTE: If the unit is a filter or upflow, the cycle step order may change.
NOTE: A queued regeneration can be initiated by pressing the Extra Cycle button. To clear a queued regeneration, press the Extra Cycle button again to cancel. If regeneration occurs for any reason prior to the delayed regeneration time, the manual regeneration request will be cleared.
Control Operation During a Power Failure
The SXT includes integral power backup. In the event of power failure, the control shifts into a power-saving mode. The control stops monitoring water usage. The display and motor shut down, but it continues to keep track of the time and day for a minimum of 8 hours.
The system configuration settings are stored in a non-volatile memory and are stored indefinitely with or without power. The Time of Day flashes when there has been a power failure. Press any button to stop the Time of Day from flashing.
If power fails while the unit is in regeneration, the control will save the current valve position before it shuts down. When power is restored, the control will resume the regeneration cycle from the point where power failed.
CAUTION If power fails during a regeneration cycle, the valve will remain in it’s current position until power is restored. The valve system should include all required safety components to prevent overflows resulting from a power failure during regeneration.
The control will not start a new regeneration cycle without power. If the valve misses a scheduled regeneration due to a power failure, it will queue a regeneration. Once power is restored, the control will initiate a regeneration cycle the next time that the Time of Day equals the programmed regeneration time. Typically, this means that the valve will regenerate one day after it was originally scheduled. If the treated water output is important and power interruptions are expected, the system should be set up with a sufficient reserve capacity to compensate for regeneration delays.

6 · FLECK 5800 SXT Upflow/Downflow

MASTER PROGRAMMING MODE CHART
CAUTION Before entering Master Programming, please contact your local professional water dealer.

Master Programming Options

Abbreviation

Parameter

Option Abbreviation

Options

DF

Display Format

GAL

Gallons

Ltr

Liters

VT

Valve Type

5800

5800 Control Valve 5810 Control Valve 5812 Control Vavle

RF

Regenerant Flow

dF1b

Standard Downflow Single Backwash

dF2b

Standard Downflow Double Backwash

Fltr

Filter

dFFF

Downflow Fill First

UFbd

Upflow Brine Draw First

UFFF

Upflow Brine Fill First

UFlt

Upflow Filter (5800 Control Valve Only)

O-dF

Other Downflow

O-UF

Other Upflow

CT

Control Type

Fd

Meter (Flow) Delayed

FI

Meter (Flow) Immediate

tc

Time Clock

dAY

Day of Week

C

Unit Capacity

Unit Capacity (Grains)

H

Feed Water Hardness

Hardness of Inlet Water (Grains)

RS

Reserve Selection

SF

Percentage Safety Factor

rc

Fixed Reserve Capacity

cr

Variable Reserve Capacity

SF

Safety Factor

Percentage of the system capacity to be used as a reserve

RC

Fixed Reserve Capacity

Fixed volume to be used as reserve

DO

Day Override

The system’s day override setting

RT

Regen Time

The time of day the system will regenerate

BW, BD, RR, BF Regen Cycle Step Times

The time duration for each regeneration step. Adjustable from OFF and 0-199 minutes.
NOTE: If “Othr” is chosen under “Valve Type”, then C1, C2, …, C20 will be displayed along with available cycle steps RR, BD, SR, BW, RF, SP. LC denotes the Last Cycle.

D1, D2, D3, D4, D5, D6, D7

Day of Week Settings

Regeneration setting (On or Off) for each day of the week on day-of-week systems.

CD

Current Day

The Current day of the week

FM

Flow Meter Type

P0.7

3/4″ Paddle Wheel Meter

Gen

Generic or Other Non-Fleck Meter

P2.0

2″ Paddle Wheel Meter

t1.5

1.5″ Turbine Meter

P1.5

1.5″ Paddle Wheel Meter

t1.2

1.25″ Turbine Meter

t1.0

1″ Turbine Meter

P1.0

1″ Paddle Wheel Meter

t0.7

3/4″ Turbine Meter

K

Meter Pulse Setting

Meter pulses per gallon for generic/other flow meter

RE

Relay

tb

Time Based (tb), start time (ST), end time (ET)

VR

Relay

Fb

NOTE: Some items may not be shown depending on control configuration. The control will discard any changes and exit Master Programming Mode if any button is not pressed for five minutes.

Flow Based (Fb), volume interval (VO), time on (TO) FLECK 5800 SXT Upflow/Downflow · 7

MASTER PROGRAMMING MODE
When Master Programming Mode is entered, all available option setting displays may be viewed and set as needed. Depending on current option settings, some parameters cannot be viewed or set.
Setting the Time of Day
1. Press and hold either the Up or Down buttons until the programming icon replaces the service icon and the parameter display reads TD.
2. Adjust the displayed time with the Up and Down buttons.
3. When the desired time is set, press the Extra Cycle button to resume normal operation. The unit will also return to normal operation after five seconds if no buttons are pressed.

1. Display Format (Display Code DF)
This is the first screen that appears when entering Master Programming Mode. The Display Format setting specifies the unit of measure that will be used for volume and how the control will display the Time of Day. This option setting is identified by “DF” in the upper left corner of the screen. There are two possible settings.

Display Format Setting

Unit of Volume

Time Display

GAL

U.S. Gallons

12-Hour AM/PM

Ltr

Liters

24-Hour

Figure 10
Entering Master Programming Mode
Set the Time of Day display to 12:01 P. M. Press the Extra Cycle button (to exit Setting Time of Day mode). Then press and hold the Up and Down buttons together until the programming icon replaces the service icon and the display format screen appears.
Exiting Master Programming Mode
Press the Extra Cycle button to accept the displayed settings and cycle to the next parameter. Press the Extra Cycle button at the last parameter to save all settings and return to normal operation. The control will automatically disregard any programming changes and return to normal operation if it is left in Master Programming mode for 5 minutes without any keypad input.
Resets
Soft Reset
Press and hold the Extra Cycle and Down buttons for 25 seconds while in normal Service mode. This resets all parameters to the system default values. Not reset are the volume remaining in meter immediate or meter delayed systems and days since regeneration in the time clock system.
Master Reset
Hold the Extra Cycle button while powering up the unit. This resets all of the parameters in the unit back to factory defaults. Check and verify the choices selected in Master Programming Mode.

Figure 11

2. Valve Type (Display Code VT)
Press the Extra Cycle button. Use the display to set the Valve Type.

3. Regenerant Flow (Display Code RF)
Press the Extra Cycle button. The Regenerant Flow Setting specifies the type of cycle that the valve follows during regeneration. Note that some valve configurations are built with specific subcomponents. Ensure the valve is configured properly before changing the Regenerant Flow setting. This option setting is identified by “RF” in the upper left corner of the screen. There are eight possible settings.

Abbreviation dF1b dF2b Fltr UFbd dFFF UFFF UFlt O-dF O-UF

Parameter Standard Downflow Single Backwash Standard Downflow Double Backwash
Filter Upflow Brine Draw First
Downflow Fill First Upflow Brine Fill First Upflow Filter (5800 Control Valve Only)
Other Downflow Other Upflow

Figure 12 4. Control Type (Display Code CT)

8 · FLECK 5800 SXT Upflow/Downflow

MASTER PROGRAMMING MODE continued
Press the Extra Cycle button. Use this display to set the Control Type. This specifies how the control determines when to trigger a regeneration. For details on how the various options function, refer to the Control Operation section of this service manual. This option setting is identified by “CT” in the upper left corner of the screen. There are four possible settings.

Abbreviation Fd FI tc dAY

Parameter Meter (Flow) Delayed Meter (Flow) Immediate
Time Clock Day of Week

7. Reserve Selection (Display Code RS)
Press the Extra Cycle button. Use this display to set the Safety Factor and to select the type of reserve to be used in your system. This setting is identified by “RS” in the upper left corner of the screen. The reserve selection parameter is only available if the control type has been set to one of the metered options. There are three possible settings.

Abbreviation SF rc cr

Parameter Safety Factor Fixed Reserve Capacity Variable Reserve

Figure 13
5. Unit Capacity (Display Code C)
Press the Extra Cycle button. Use this display to set the Unit Capacity. This setting specifies the treatment capacity of the system media. Enter the capacity of the media bed in grains of hardness when configuring a softener system, or desired volume capacity when configuring a filter system. This option setting is identified by “C” in the upper left corner of the screen (or by “V’ if volume capacity for a filter). The Unit Capacity parameter is only available if the control type has been set to one of the metered options. Use the Up and Down buttons to adjust the value as needed.

Figure 16
8. Safety Factor (Display Code SF)
Press the Extra Cycle button. Use this display to set the Safety Factor. This setting specifies what percentage of the system capacity will be held as a reserve. Since this value is expressed as a percentage, any change to the unit capacity or feed water hardness that changes the calculated system capacity will result in a corresponding change to the reserve volume. This option setting is identified by “SF” in the upper left corner of the screen. Use the UP and Down buttons to adjust the value from 0 to 50% as needed.

Figure 14
Range: 1-999.9 x 1000 grains/gallon (mg/liter)
6. Feed Water Hardness (Display Code H)
Press the Extra Cycle button. Use this display to set the Feed Water Hardness. Enter the feed water hardness in grains per gallon or degrees for softener systems. This option setting is identified by “H” in the upper left corner of the screen. The feed water hardness parameter is only available if the control type has been set to one of the metered softener options. Use the Up and Down buttons to adjust the value as needed.

Range: 0-50%

Figure 17

9. Fixed Reserve Capacity (Display Code RC)
Press the Extra Cycle button. Use this display to set the Reserve Capacity. This setting specifies a fixed volume that will be held as a reserve. The Reserve Capacity cannot be set to a value greater than one-half of the calculated system capacity. The Reserve Capacity is a fixed volume and does not change if the unit capacity or feed water hardness are changed. This option setting is identified by “RC” in the upper left corner of the screen. Use the Up and Down buttons to adjust the value as needed.

Figure 15 Range: 1-199 grains (degrees)

Figure 18 Range: 0-half of the calculated system capacity
FLECK 5800 SXT Upflow/Downflow · 9

MASTER PROGRAMMING MODE continued
10. Day Override (Display Code DO)
Press the Extra Cycle button. Use this display to set the Day Override. This setting specifies the maximum number of days between regeneration cycles. If the system is set to a timertype control, the day override setting determines how often the system will regenerate. A metered system will regenerate regardless of usage if the days since last regeneration cycle equal the day override setting. Setting the day override value to “OFF” disables this function. This option setting is identified by “DO” in the upper left corner of the screen. Use the Up and Down buttons to adjust the value as needed.

Abbreviation RR BD SR BW RF SP LC

Cycle Step Rapid Rinse Brine Draw Slow Rinse Backwash
Refill Service Position
Last Cycle

Range: Off-99 days

Figure 19

11. Regeneration Time
Press the Extra Cycle button. Use this display to set the Regeneration Time. This setting specifies the time of day the control will initiate a delayed, manually queued, or day override regeneration. This option setting is identified by “RT” in the upper left corner of the screen. Use the Up and Down buttons to adjust the value as needed.

Range: 0-199 minutes

Figure 21

13. Day of Week Settings
Press the Extra Cycle button. Use this display to set the regeneration schedule for a system configured as Day of Week control. The different days of the week are identified as D1, D2, D3, D4, D5, D6, and D7 in the upper left corner of the display. Set the value to “ON” to schedule a regeneration or “OFF” to skip regeneration for each day. Use the Up and Down buttons to adjust the setting as needed. Press the Extra Cycle button to accept the setting and move to the next day. Note that the control requires at least one day to be set to “ON” If all 7 days are set to “Off”, the unit will return to Day 1 until one or more days are set to “ON”.

Figure 20

12. Regeneration Cycle Step Times
Press the Extra Cycle button. Use this display to set the Regeneration Cycle Step Times. The different regeneration cycles are listed in sequence based on the valve type selected for the system, and are identified by an abbreviation in the upper left corner of the screen. The abbreviations used are listed below.

Abbreviation

Cycle Step

BD

Brine Draw

BF

Brine Fill

BW

Backwash

RR

Rapid Rinse

SV

Service

Cycle steps can be programmed in any order using the Up or Down buttons with the following selections. Up to 20 individual cycles can be set. Time for each cycle can be set from 0 to 199 minutes. Setting a cycle step time to 0 will cause the control to skip that step during regeneration, but keeps the following steps available. Use the Up and Down buttons to adjust the value as needed. Press the Extra Cycle button to accept the current setting and move to the next parameter. Program the last cycle step as LC which forces the valve back to the service position.

10 · FLECK 5800 SXT Upflow/Downflow

Figure 22 14. Current Day (Display Code CD) Press the Extra Cycle button. Use this display to set the current day on systems that have been configured as Day of Week controls. This setting is identified by “CD” in the upper left corner of the screen. Use the Up and Down buttons to select from Day 1 through Day 7.
Figure 23 15. Flow Meter Type (Display Code FM) Press the Extra Cycle button. Use this display to set the type of flow meter connected to the control. This option setting is identified by “FM” in the upper left corner of the screen. Use the Up and Down buttons to select one of the eight available

MASTER PROGRAMMING MODE continued
settings.

Abbreviation P0.7 t0.7 P1.0 t1.0 P1.5 t1.5 P2.0 Gen t1.2

Description 3/4″ Paddle Wheel Meter
3/4″ Turbine Meter 1″ Paddle Wheel Meter
1″ Turbine Meter 1.5″ Paddle Wheel Meter
1.5″ Turbine Meter 2″ Paddle Wheel Meter Generic or Other non-Fleck Meter
1.25″ Turbine Meter

17. Relay Setting (Display Code RE) Press the Extra Cycle button. Use this display to enable the relay output. This option setting is identified by “RE” in the upper left corner of the screen. Use the Up and Down buttons to enable the relay using either time based (tb) or flow based (Fb). Only one method can be used at a time. For time based, set the desired Start Time (ST) and End Time (ET). Time ranges available are determined by the Regen Cycle Step Times. For flow based, set the desired Volume Interval (VO) and Time On (TO).
Figure 26

Figure 24
16. Meter Pulse Setting (Display Code K)
Press the Extra Cycle button. Use this display to specify the meter pulse setting for a non-standard flow meter. This option setting is identified by “K” in the upper left corner of the screen. Use the Up and Down buttons to enter the meter constant in pulses per unit volume.

Figure 27 ST Range: 0 to total number of cycles minus 1
Figure 28 ET Range: Start time to total of all cycles

Figure 25 K Range: 0.1 to 999.9 pulses per gallon.

Figure 29

Figure 30 VO Range: 1 to Total Gallon Capacity

Figure 31 TO Range: 1 to 7200 (minutes) 18. End of Master Programming Mode Press the Extra Cycle button to save all settings and exit Master Programming Mode.
FLECK 5800 SXT Upflow/Downflow · 11

VIEWING DIAGNOSTIC DATA
The SXT control records and maintains diagnostic data to assist with servicing and troubleshooting the water treatment system.

Abbreviation

Parameter

Description

FR

Flow Rate

Displays the current outlet

flow rate.

PF

Peak Flow Rate

Displays the highest flow

rate measured since last

regeneration.

HR

Hours in Service

Displays the total hours

that the unit has been

in service since last

regeneration.

VU

Volume Used

Displays the total volume

of water treated by the unit

since last regeneration.

RC

Reserve Capacity

Displays the system’s

reserve capacity calculated

from the system capacity,

feed water hardness, and

safety factor.

TV

Totalizer Volume Displays the total volume

of water used by the unit

since last installation or

last reset.

SV

Software Version

Displays the software

version installed on the

controller.

NOTE: Some items may not be shown depending on control configuration. The control will discard any changes and exit the Diagnostics View if a button is not pressed for 60 seconds.

Diagnostics View Steps
1. Press the Up and Extra Cycle buttons for five seconds while in service.
2. Use this display to view the current Flow Rate. This option setting is identified by “FR” in the upper left corner of the screen.

4. Press the Up button. Use this display to view the Hours in Service since the last regeneration cycle. This option setting is identified by “HR” in the upper left corner of the screen.
Figure 34 5. Press the Up button. Use this display to view the Volume
Used since the last regeneration cycle. This option setting is identified by “VU” in the upper left corner of the screen.
Figure 35 6. Press the Up button. Use this display to view the Reserve
Capacity. This option setting is identified by “RC” in the upper left corner of the screen.
Figure 36 7. Press the Up button. Use this display to view the Total
Volume data. This option is identified by “TV” in the upper left corner of the screen.

Figure 32
3. Press the Up button. Use this display to view the Peak Flow Rate since the last regeneration cycle. This option setting is identified by “PF” in the upper left corner of the screen.

8. Press the Up button. Use this display to view the Software Version. This option setting is identified by “SV” in the upper left corner of the screen.

Figure 33

Figure 37
9. Press the Extra Cycle button to end Diagnostic Programming Mode.

12 · FLECK 5800 SXT Upflow/Downflow

SYSTEM DISINFECTION
Disinfection Of Water Softeners
The materials of construction of the modern water softener will not support bacterial growth, nor will these materials contaminate a water supply. During normal use, a softener may become fouled with organic matter, or in some cases with bacteria from the water supply. This may result in an off-taste or odor in the water.
Some softeners may need to be disinfected after installation and some softeners will require periodic disinfection during their normal life.
Depending upon the conditions of use, the style of softener, the type of ion exchanger, and the disinfectant available, a choice can be made among the following methods.
Sodium or Calcium Hypochlorite
Application These materials are satisfactory for use with polystyrene resins, synthetic gel zeolite, greensand and bentonites.
5.25% Sodium Hypochlorite These solutions are available by various sellers of household bleach. If stronger solutions are used, such as those sold for commercial laundries, adjust the dosage accordingly.
1. Dosage
A. Polystyrene resin; 1.2 fluid ounce (35.5 ml) per cubic foot.
B. Non-resinous exchangers; 0.8 fluid ounce (23.7 ml) per cubic foot.
2. Salt tank softeners
A. Backwash the softener and add the required amount of hypochlorite solution to the well of the salt tank. The salt tank should have water in it to permit the solution to be carried into the softener.
B. Proceed with the normal recharge.
Calcium Hypochlorite Calcium hypochlorite, 70% available chlorine, is available in several forms including tablets and granules. These solid materials may be used directly without dissolving before use.
1. Dosage
A. Two grains (approximately 0.1 ounce [3 ml]) per cubic foot.
2. Salt tank softeners
A. Backwash the softener and add the required amount of hypochlorite to the well of the salt tank. The salt tank should have water in it to permit the chlorine solution to be carried into the softener.
B. Proceed with the normal recharge.

INSTALLATION CHECKLIST
Read the owner’s/installation manual?
Follow all safety guidelines in the manual?
If metal pipe was used, did you restore the electrical ground?
Securely install both drain hoses to an approved drain?
Perform a leak test?
Move the bypass valve to service?
Sanitize the softener?
Add salt pellets to the salt storage tank?
Program the control correctly to meet your needs?
Start a recharge?
CARE AND USE OF YOUR BRINE TANK
Each time the softener recharges, salty water (brine) is needed to recondition the media in the water tank. The brine is pulled from the salt tank at a controlled amount. If the salt tank does not contain enough salt, the brine is weak, the media will not fully recondition and untreated water will pass through.
You must keep salt in the tank.
The salt tank operates best when the salt level is below halffull. If the tank is filled more than that the salt pellets may “bridge”. The salt pellets wedge against each other and do not fall into the water at the bottom. Bridging will eventually provide no salt to make brine. The softener will recharge but not recondition the media. A salt bridge can be broken up using a broom handle or similar rod. Carefully pound it into the salt and the pellets will collapse. After loosening the salt pellets wait 2 hours and start a regeneration. A second recharge may be needed to fully recondition the media.
You should only use sodium chloride pellet salt for water softeners. Other types of salt (rock or snow melting) will contain dirt and chemicals that will affect your water softener.
Keep the brine tank covered.
Empty and clean the tank every three years.

FLECK 5800 SXT Upflow/Downflow · 13

TROUBLESHOOTING

Error Codes NOTE: Error codes appear on the In Service display. NOTE: To enter Master Programming while in an error condition, press and hold the Up and Down buttons for 4 seconds.

Error Code —0

Error Type
Motor Stall /Cam Sense Error

—1

Motor Run-On Error

/Cycle Sense Error

—2

Regen Failure

—3

Memory Error

—4

Fail Safe Error

Cause No state changes in the optical
sensor are detected for six seconds.
An undesired optical sensor state change occurred.
The system has not regenerated for more than 99 days (or 7 days if the Control Type has been set to
Day-of-Week).
Control board memory failure.
Valve has failed to find position in one minute.

Reset and Recovery
Unplug the unit and plug back in. Allow the control to attempt to find position again.
Verify the optical sensor is in place with the wires connected to the circuit board. Verify the motor and drive train components are in good condition and assembled properly. Check the valve and verify that the piston travels freely. Replace/reassemble the various components as necessary.
Plug the unit back in and observe its behavior. If the error reoccurs, unplug the unit, put it into bypass and contact technical support.
Non-critical error. Extra optical sensor pulse detected. Press any button to clear the error. Press extra cycle button to advance motor to clear error.
Perform a Manual Regeneration to reset the error code.
If the system is metered, verify that it is measuring flow by running service water and watching for the flow indicator on the display. If the unit does not measure flow, verify that the meter cable is connected properly and that the meter is functioning properly.
Enter Master Programming Mode and verify that the unit is configured properly, For the valve configuration. Check that the correct system capacity has been selected, that the day override is set properly, and that meter is identified correctly. If the unit is configured as a Day-ofWeek system, verify that at least one day is set ON. Correct the setting as necessary.
Perform a Master Reset and reconfigure the system via Master Programming Mode. After reconfiguring the system, step the valve through a manual regeneration. If error continues, call technical support.
Unplug the unit and plug it back in. If error continues, call technical support.

14 · FLECK 5800 SXT Upflow/Downflow

POWERHEAD ASSEMBLY
1
8 6

4 2
3
7

BR61501-5800 Rev A

Item No. QTY Part No.

Description

1……………..1…….. 61832-01…………Cover Assembly, Black/Black

5

2……………..1…….. 61836 ……………..Panel Gear Assembly, Upflow/ Downflow

3……………..1…….. 62076 ……………..Timer Assembly, SXT, Downflow

…….. 62076-01…………Timer Assembly, SXT, Upflow

4……………..1…….. 61835 ……………..Motor Assembly

5……………..1…….. 61882 ……………..Cover Assembly, Environmental

6……………..1…….. 44161 ……………..Transformer, 12V UL

7……………..1…….. 44162 ……………..Transformer, Intl, 12V UL

8……………..1…….. 43715 ……………..Cover, Lower, 5800 Series

BR61882 Rev B FLECK 5800 SXT Upflow/Downflow · 15

5800 CONTROL VALVE ASSEMBLY
8
13

14 16 18

7

34

15 2

5

6
17 12

19 1

10

Item No. QTY Part No.

Description

1………………. 1 ……… 61857-01…………… Valve Body Assy, Downflow/Upflow (Includes Items 9, 10, 11, 12)

…………………………… 61857-20…………… Valve Body Assy, Mixing, Downflow/ Upflow (Includes Items 9, 10, 11, 12)

2………………. 1 ……… 18271 ……………….. Screen Injector, 5000

3………………. 1 ……… 40064 ……………….. Seal Injector

4………………. 1 ……… 18277 ……………….. Cap Injector

………. 18278-20…………… Injector Cap Assy, 1610 Regulated, 5000, 20 psi, Black, Upflow

………. 18278-30…………… Injector Cap Assy, 1610 Regulated, 5000, 30 psi, Black, Upflow

5………………. 2 ……… 18262 ……………….. Screw, Hex Washer Head, #10-24 x 1.00

6………………. 1 ……… 19654 ……………….. Label, 0.125 gpm Brine Flow

………. 12128 ……………….. Label, 0.25 gpm BLFC

………. 10759 ……………….. Label, 0.5 gpm 1.5 lbs Salt/Min

………. 10760 ……………….. Label, 1.0 gpm 3 lbs Salt/Min

7………………. 1 ……… 13333 ……………….. Label, Injector, Blank

8………………. 3 ……… 18261 ……………….. Screw, Hex Washer Head, #10-24 0.81

9………………. 1 ……… 13304 ……………….. O-ring, -121

10…………….. 1 ……… 18303-01…………… O-ring, -336, 560CD

11…………….. 1 ……… 13030 ……………….. Retainer, Distributor Tube O-ring

12…………….. 1 ……… 18312 ……………….. DLFC Housing Retainer Clip

13……………………….. 61837 ……………….. Piston and Seal Kit Assy, Downflow, 5800

………. 61838 ……………….. Piston and Seal Kit Assy, Upflow, 5800

14…………….. 1 ……… 60032 ……………….. Brine Valve, 4600/5600

15…………….. 1 ……… 13302 ……………….. O-ring, -014

16……………………….. 60022-12…………… BLFC, 0.125 gpm

………. 60022-25…………… BLFC, 0.25 gpm

………. 60022-50…………… BLFC, 0.5 gpm

………. 60022-100…………. BLFC, 1.0 gpm

17……………………….. 60705-00…………… DLFC, Plastic, Blank

………. 60705-06…………… DLFC, Plastic, 0.60 gpm

………. 60705-08…………… DLFC, Plastic, 0.80 gpm

………. 60705-10…………… DLFC, Plastic, 1.0 gpm
16 · FLECK 5800 SXT Upflow/Downflow

9

11

BR61500-5800 Rev A

………. 60705-12…………… DLFC, Plastic, 1.2 gpm ………. 60705-13…………… DLFC, Plastic, 1.3 gpm ………. 60705-15…………… DLFC, Plastic, 1.5 gpm ………. 60705-17…………… DLFC, Plastic, 1.7 gpm ………. 60705-20…………… DLFC, Plastic, 2.0 gpm ………. 60705-24…………… DLFC, Plastic, 2.4 gpm ………. 60705-30…………… DLFC, Plastic, 3.0 gpm ………. 60705-35…………… DLFC, Plastic, 3.5 gpm ………. 60705-40…………… DLFC, Plastic, 4.0 gpm ………. 60705-45…………… DLFC, Plastic, 4.5 gpm ………. 60705-50…………… DLFC, Plastic, 5.0 gpm ………. 60705-60…………… DLFC, Plastic, 6.0 gpm ………. 60705-20…………… DLFC, Plastic, 2.0 gpm ………. 60705-70…………… DLFC, Plastic, 7.0 gpm ………. 60706-8.0………….. DLFC, AC x 3/4″F, 8 gpm ………. 60706-9.0………….. DLFC, AC x 3/4″F, 9 gpm ………. 60706-10…………… DLFC, AC x 3/4″F, 10 gpm ………. 60706-12…………… DLFC, AC x 3/4″F, 12 gpm ………. 60706-15…………… DLFC, AC x 3/4″F, 15 gpm 18……………………….. 18272-000…………. Injector Assy, 1610, #000, Brown ………. 18272-00…………… Injector Assy, 1610, #00, Violet ………. 18272-0…………….. Injector Assy, 1610, #0, Red ………. 18272-1…………….. Injector Assy, 1610, #1, White ………. 18272-2…………….. Injector Assy, 1610, #2, Blue ………. 18272-3…………….. Injector Assy, 1610, #3, Yellow 19……………………….. 18276-01…………… Injector Assy, Plug, w/O-rings Not Shown: ………. 40947-01…………… Plug, Brine Valve, w/O-ring, 560CD ………. 13918-01…………… BLFC Module Plug Assy, w/O-ring NOTE: In upflow units, the Injector Plug and Injector Assy are put in the reverse holes. In filter units, both injector holes are plugged with 18276-01.

CAUTION

Excessive side load on piston rod may cause premature damage. If seal/spacer stack is stuck in valve bore during

disassembly, rotate stack prior to removal.

TURBINE METER ASSEMBLY – P/N 60626

PADDLE METER ASSEMBLY P/N 60086-50

1 2

4 5

3

BR60626

Item No. QTY Part No.

Description

1……………..1…….. 19797 ……………..Meter Assy, 3/4″ Dual Port, SLP

2……………..2…….. 19569 ……………..Clip, Flow Meter

3……………..2…….. 13314 ……………..Screw, Slot Ind Hex, 8-18 x 0.60

Not Shown:

……… 14613 ……………..Flow Straightener

……… 19791-01…………Meter Cable Assy, Turbine/SXT

8 2
9

1 3
7

10
11 6

BR60086 Rev E

Item No. QTY Part No.

Description

1……………..1…….. 14716 ……………..Meter Cap Assy, NT (includes items 2, 3, and 4)

2……………..1…….. 13874 ……………..Cap, Meter, Electronic

3……………..1…….. 13847 ……………..O-ring, -137, Std, Meter

4……………..1…….. 17798 ……………..Screw, Slot Hex Washer Head

5……………..1…….. 19121-01…………Meter Cable Assy, SXT, Paddle (not included in P/N 60086-50)

6……………..1…….. 13821 ……………..Body, Meter, 5600

7……………..1…….. 13509 ……………..Impeller, Meter

8……………..4…….. 12473 ……………..Screw, Hex Wsh, 10-24 x 5/8

9……………..4…….. 13255 ……………..Clip, Mounting

10……………4…….. 13314 ……………..Screw, Slot Ind Hex, 8-18 x 0.60

11……………4…….. 13305 ……………..O-ring, -119

12……………1…….. 14613 ……………..Flow Straightener

FLECK 5800 SXT Upflow/Downflow · 17

BYPASS VALVE ASSEMBLY (METAL)
9 8

BYPASS VALVE ASSEMBLY (PLASTIC)
6

6 5

4 3
2 10
1
7

6
60040SS Rev Y 60041SS Rev AA

Item No. QTY Part No.

Description

1……………..1…….. 40614 ……………..Bypass Body, 3/4″

……… 40634 ……………..Bypass Body, 1″, SS

2……………..1…….. 14105 ……………..Seal, Bypass, 560CD

3……………..1…….. 11972 ……………..Plug, Bypass

4……………..1…….. 11978 ……………..Side Cover

5……………..1…….. 13604-01…………Label

6……………..8…….. 15727 ……………..Screw, 10-24 x 0.5″

7……………..1…….. 11986 ……………..Side Cover

8……………..1…….. 11979 ……………..Lever, Bypass

9……………..1…….. 11989 ……………..Screw, Hex Head, 1/4-14 x 1.5″

10……………1…….. 60040SS………….Bypass Valve, 5600, 3/4″ NPT Black Grip Lever, SS

……… 60041SS………….Bypass Valve, 5600, 1″ NPT Black Grip Lever, Stainless Steel

Not Shown:

2…….. 19228-01…………Adapter Assy, Coupling, w/O-rings

1 2 3 BR60049 Rev H
4

5 BR41027 Rev G

BR18706 Rev J

Item No. QTY Part No.

Description

1……………..2…….. 13305 ……………..O-ring, -119

2……………..2…….. 13255 ……………..Clip, Mounting

3……………..2…….. 13314 ……………..Screw, Slot Ind Hex, 8-18 x 0.60

4……………..1…….. 18706 ……………..Yoke, 1″, NPT, Plastic

……… 18706-02…………Yoke, 3/4″, NPT, Plastic

5……………..1…….. 13708-40…………Yoke, 1″, Sweat

……… 13708-45…………Yoke, 3/4″, Sweat

……… 19275 ……………..Yoke, Angle 90 Deg, 3/4″, NPT

……… 19275-45…………Yoke, Angle 90 Deg, 3/4″, Sweat

……… 19620-01…………Yoke, Assy, 3/4″, R/Angle 90 Deg, w/O-rings, Clips & Screws

……… 40636 ……………..Yoke, 1-1/4″, NPT

……… 40636-49…………Yoke, 1-1/4″, Sweat

……… 41027-01…………Yoke, 3/4″, NPT, Cast, Machined

……… 41026-01…………Yoke, 1″, NPT, Cast, Machined, SS

……… 41026-02…………Yoke, 1″, BSP, Cast, Machined, SS

……… 18706-10…………Yoke, 1″, BSP, Plastic

……… 41027-02…………Yoke, 3/4″, BSP, Cast, Machined

……… 18706-12…………Yoke, 3/4″, BSP, Plastic

……… 19620-01…………Yoke Assy, 3/4″, R/Angle, 90 Deg

6……………..1…….. 60049 ……………..Bypass Plastic

Not Shown:

2…….. 19228-01…………Adapter Assy, Coupling, w/O-rings

18 · FLECK 5800 SXT Upflow/Downflow

SAFETY BRINE VALVE
11
6 9
5
10 2

8 7
1

11
13 12

4
3 9
14

Item No. QTY Part No.

Description

1……………..1…….. 19645 ……………..Body, Safety Brine Valve, 2310

2……………..1…….. 19803 ……………..Safety Brine Valve Assy

3……………..1…….. 19804 ……………..Screw, Sckt Hd, Set, 10-24 x 0.75

4……………..1…….. 19805 ……………..Nut, Hex, 10-24, Nylon Black

5……………..1…….. 19652-01…………Poppet Assy, SBV w/O-ring

6……………..1…….. 19649 ……………..Flow Dispenser

7……………..1…….. 11183 ……………..O-ring, -017

8……………..1…….. 19647 ……………..Elbow, Safety Brine Valve

9……………..2…….. 19625 ……………..Nut Assy, 3/8″ Plastic

10……………1…….. 18312 ……………..Retainer, Drain

11……………1…….. 60014 ……………..Safety Brine Valve Assy, 2310

12……………2…….. 10150 ……………..Grommet, 0.30 Dia

13……………1…….. 60068-10.5………Float Assy, 2310, w/10.5″ Rod

……… 60068-11.5………Float Assy, 2310, w/11.5″ Rod

……… 60068-20…………Float Assy, 2310, w/20″ Rod

……… 60068-30…………Float Assy, 2310, w/30″ Rod

14……………1…….. 60002-11.38…….Air Check, #500, 11.38″ Long

……… 60002-27…………Air Check, #500, 27″ Long

……… 60002-32…………Air Check, #500, 32″ Long

……… 60002-34…………Air Check, #500, 34″ Long

……… 60002-36…………Air Check, #500, 36″ Long

……… 60002-48…………Air Check, #500, 48″ Long

……… 60002-26.25…….Air Check, #500, 26.25″ Long

……… 60002-33.25…….Air Check, #500, 33.25″ Long

42112 Rev A

FLECK 5800 SXT Upflow/Downflow · 19

WATER CONDITIONER FLOW DIAGRAMS
Upflow
1. Service Position

4. Rapid Rinse Position

2. Brine/Slow Rinse Position

5. Brine Tank Refill Position

3. Backwash Position

20 · FLECK 5800 SXT Upflow/Downflow

WATER CONDITIONER FLOW DIAGRAMS continued
Downflow
1. Service Position

4. Rapid Rinse Position

2. Backwash Position

5. Brine Tank Refill Position

3. Brine/Slow Rinse Position

FLECK 5800 SXT Upflow/Downflow · 21

DIMENSIONAL DRAWINGS

232.3 9.15

70.2 2.77

1.53

38.7

73.7 2.90

.85

21.5

12.7 .50

53.8

111.3

2.12

4.38

91.4 3.60
182.9 7.20

7.6 .30
BR61500-5800LNE Rev A

22 · FLECK 5800 SXT Upflow/Downflow

INJECTOR FLOW DATA
TR18755 Rev B FLECK 5800 SXT Upflow/Downflow · 23

SXT WIRING DIAGRAM
N.C. N.O. COM

GND +24V

+ –

+24V

(do

NOT

use

for

5800/5810/5812)

OPTICAL ENC SIGNAL

GND –

OPTICAL ENC INPUT +

MOTOR R MOTOR L

m

FLOW METER INPUT +12V
GND

+12V GND

+ –

+12V

(use

for

5800/5810/5812)

44060U REV G

24 · FLECK 5800 SXT Upflow/Downflow

FLECK 5800 SXT Upflow/Downflow · 25

26 · FLECK 5800 SXT Upflow/Downflow

FLECK 5800 SXT Upflow/Downflow · 27

} For Fleck Product Warranties visit:
Fleck para las garantías de los productos visite: waterpurification.pentair.com Pour Fleck garanties produit visitez le site :
104 Ambrogio Drive, Gurnee, IL 60031 Customer Care: 800.462.6478 / www.corriganmist.com / service@corriganmist.com
WATER QUALITY SYSTEMS 5730 NORTH GLEN PARK ROAD, MILWAUKEE, WI 53209 P: 262.238.4400 | WATERPURIFICATION.PENTAIR.COM | CUSTOMER CARE: 800.279.9404 | tech-support@pentair.com §For a detailed list of where Pentair trademarks are registered, please visit waterpurification.pentair.com/brands. Pentair trademarks and logos are owned by Pentair plc or its affiliates. Third party registered and unregistered trademarks and logos are the property of their respective owners. 43359-01 REV D OC16 © 2016 Pentair Residential Filtration, LLC All Rights Reserved.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Pentair User Manuals

Related Manuals