steute RF 96 ST Wireless Switch Instruction Manual

June 11, 2024
Steute

steute RF 96 ST Wireless Switch Instruction Manual

steute RF 96 ST Wireless Switch Instruction Manual

Use of the mounting and wiring instructions
Target group: authorised and qualified staff. All actions described in these instructions may only be performed by qualified persons who have been trained and authorised by the operating company.

  1. Read and understand these mounting and wiring instructions.
  2. Comply with the valid occupational safety and accident prevention regulations.
  3. Install and operate the device. Selection and installation of devices and their integration in control systems demand qualified knowledge of all the relevant laws, as well as the normative requirements of the machine manufacturer. In case of doubt, the German language version of these instructions shall prevail.

Scope of delivery

1 device, 1 mounting and wiring instructions, carton.

Intended use

The device essentially comprises three parts: the power supply with a lithium battery, the wireless part with an integrated interface for the external sensors and the connecting part for the external sensors. The power supply is provided by a non-rechargeable 3.6 V lithium thionyl chloride battery and a nominal capacity of 8.5 Ah. Exceeding the threshold triggers a wireless signal. The battery status is transmitted with every signal transmission. The receiver must conform to the sWave® protocol of the steute modules.

Mounting and wiring

Mount the device on an even surface. Install the device according to the mounting and wiring instructions of the receiver. The wireless range depends heavily on the local conditions. Conductive materials may strongly affect the radio signal. This also includes thin foils, e.g. aluminium laminations on insulation materials.

Allocation of locations and radio frequencies:

steute RF 96 ST Wireless Switch Instruction Manual - Allocation of locations
and radio frequencies

External devices

The sensor/switch connection is evident at the M12 plug-in connector. At this plug-in connector the inductive sensors RF IS M8/M12/M18- or M30 or other mechanical switches with gold-plated contacts can be connected. Therefore, the connecting cable Material No. 1189960 can be used that is available as accessory. The mechanical switches must be equipped with a NO/NC contact. It must be connected to plus (pin 1) and to the entry (pin 4). To connect external devices (sensors or switches): see section »Connecting external devices«. When installing the external device, follow its installation instructions.

Connectable devices:

steute RF 96 ST Wireless Switch Instruction Manual - Connectable
devices

Design of wireless range

The radio signal is attenuated on the way from the transmitter to the receiver. In addition, the radio signal is attenuated/influenced by obstacles. The degree of attenuation depends on the material of the obstacle. The following tables serve as a guide.

Penetration of radio signals:
steute RF 96 ST Wireless Switch Instruction Manual - Penetration of radio
signals

Typical ranges:

steute RF 96 ST Wireless Switch Instruction Manual - Typical
ranges

Field strength meter for range test:

steute RF 96 ST Wireless Switch Instruction Manual - Field strength meter
for range test

Radio operation

The transmission of a switching command from the transmitter to the receiver takes about 80 to 100 ms, based on the sWave® data transmission. The switching signal of a transmitter must not be generated at a shorter distance, otherwise this signal will be overlooked. The receiver must support the sWave® protocol of the statue modules. Each switching operation triggers a transmission from the radio unit. This also applies if several channels are activated or deactivated simultaneously. The current value of the battery voltage is transmitted with each transmission.

Safety

Do not use the device in connection with other devices whose direct or indirect purpose is to ensure life or health, or whose operation may pose a threat to humans, animals or material assets.

Maintenance and cleaning

With rough conditions, we recommend routine maintenance as follows:

  1. Removal of all dirt particles.
  2. Remove dust from sensor surfaces. Clean enclosure on the outside only. Clean enclosure with household cleaning agents. Do not use compressed air to clean.

Battery

The remaining capacity of a battery is hard to evaluate, but an empty battery can be assumed in case of doubt and with a battery voltage approx. <3.4 V at 20°C. In order to ensure reliable functioning, the battery must be replaced. To do this, the 5 screws in the housing cover must be opened using a torx-8 screwdriver. The battery should be inserted in the direction shown by the symbols on the cover. Use only the designated battery type or a complementary battery type. Depending on the country the device is supplied to, delivery will include an AA lithium battery SL-760/3.6 V/2.2 Ah in a battery adapter, or a lithium battery SL-2770/3.6 V/8.5 Ah without an adapter or a complementary battery type.

Spare part:
steute RF 96 ST Wireless Switch Instruction Manual - Spare
part

Disposal

– Observe national, local and legal regulations concerning disposal.
– Recycle each material separately. Dispose of possibly contained batteries correctly.

Status signal

A status signal can be set by the user at various intervals with the jumper. To do this, open the enclosure by removing the 5 cover screws using a Torx 8 screwdriver. Take care to ensure sufficient ESD protection. Inside the enclosure a jumper is located on the circuit board. Adjust to the desired interval. For evaluation of status signals, steute provides special receivers.

steute RF 96 ST Wireless Switch Instruction Manual - Status
signal

After successful adjustment replace the enclosure cover and tighten the cover screws with approx. 0.45 Nm. The sealing must not be contaminated by any foreign bodies.

N.B.
The electrical connection may only be carried out by authorised personnel. Subject to technical modifications. Reconstruction and alterations to the device are not allowed. steute does not assume any liability for recommendations made or implied by this description. New claims for guarantee, warranty or liability cannot be hereby derived beyond the general terms and conditions of delivery.

ESD
Ensure adequate ESD protection for all work that requires opening the unit.

Dimensions

steute RF 96 ST Wireless Switch Instruction Manual -
Dimensions

NC = not connected

Sensor

External contact

Technical data
Applied standards EN 60947-5-1; EN 61000-6-2, -6-3;
EN 301 489-1, -3; EN 300 220-1, -2
Enclosure glass-fibre reinforced, shock-proof thermoplastic, self- extinguishing UL 94-V0
Tightening torque mounting screw enclosure M4: max. 1.2 Nm; cover screws M2.5: approx. 0.45 Nm
Connection connector M12 x 1, 4-pole
Connectable devices RF IS M8, RF IS M12, RF IS M18, RF IS M30,
RF RC 20, external switches using the connecting cable 1215497
Degree of protection IP67 to IEC/EN 60529
Protocol sWave®
Ambient temperature -20°C … +65°C
Ambient temperature -20°C … +65°C
Operation cycles SW868, SW915, SW917: max. 12,000 telegrams with repetitions/h,
SW922: max. 1,440 telegrams with repetitions/h
Switching frequency max. 5 Hz
Standby current 15 µA
Voltage supply Lithium battery (replaceable)
Capacity SL 760: 2.2 Ah; SL 2770: 8.5 Ah
Frequency 868.3 MHz (EU) or 915.0 MHz (USA, Canada,
Mexico) or 917.0 MHz (Brazil) or 916.5 MHz (Japan)
Channel bandwidth SW868: 480 kHz, SW915, SW917: 550 kHz,
SW922: 520 kHz
Transmission power SW868, SW915, SW917: <25 mW,
SW922: <1 mW
Data rate 66 kbps
Wireless range SW868, SW915, SW917:
max. 450 m outdoors,
max. 40 m indoors
SW922: max. 150 m outdoors,
max. 20 m indoors
Actuating time min. 80 ms
Battery life depending on operation cycles
SL-760 (AA) – Inductive sensor:
10 s – approx. 1.0 years
100 s – approx. 1.0 years
1,000 s – approx. 1.0 years
SL-760 (AA) – Micro switch:
10 s – approx. 7.2 years
100 s – >10 years
SL-2770 (C) – Inductive sensor:
10 s – approx. 3.7 years
100 s – approx. 3.9 years
1,000 s – approx. 3.9 years
SL-2770 (C) – Micro switch:
10 s – >10 years

Note status signal adjustable with jumper, transmission of battery cell voltage and switching state
Wireless approval EU: RED 2014/53/EU
USA: FCC – XK5-RFRXSW915
Canada: IC – 5158A-RFRXSW915
Mexico: IFT – RCPSTRF17-1886
Brazil: ö 04172-18-06718
Japan: ? ARIB STD-T108: 204-610002

  • max. manufacturer specification of storage life

MODELO: RF RX SW917
steute RF 96 ST Wireless Switch Instruction Manual - Anatel
Logo

EU DECLARATION OF CONFORMITY
As manufacturer, steute Technologies is solely responsible for issuing this Declaration of Conformity.
Type and name of equipment: Wireless universal transmitter RF 96 ST SW868 *

  • for a detailed product list, see Declaration of Conformity on the internet at www.steute.com
    The object(s) of declaration described above is/are in conformity with the following EU harmonisation legislation:

steute RF 96 ST Wireless Switch Instruction Manual - Relevante EU-
Richtlinien

Rechtsverbindliche Unterschrift,
Marc Stanesby (Geschäftsführer) / Legally binding signature,
Marc Stanesby (Managing Director)

Additional information on mounting and wiring instructions
This mounting and wiring instruction is also available in your national language on request.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals