VICONICS VTR835x0A5x Fancoil Unit Thermostat Retrofit Solution Owner’s Manual
- June 11, 2024
- Viconics
Table of Contents
**VICONICS VTR835x0A5x Fancoil Unit Thermostat Retrofit Solution Owner’s Manual
**
Commercial and hospitality
Suitable for both commercial and hospitality markets and systems (VTR8300
Series)
Digital touch screen
Customizable color digital touch screen interface with multi-language support
(VTR8300 Series)
7-day occupancy scheduling
2 to 4 events (VTR8300 Series)
Extremely compact design
(VC3000 Series)
Highly configurable
LUA custom programming available
90 to 277 Vac
Line powered from 90 to 277 Vac, 50 to 60 Hz (VC3000 Series)
Network Ready, BACnet MS/TP, and Wireless Models Available
VTR835x0A5x
VC3xxxE5000
This two component retrofit option consists of the VTR8300 terminal equipment controller and the VC3000 relay pack. Together, they provide an easy solution for retrofitting fan coil unit thermostats without requiring upgrades to other components such as relays, transformers, controllers, sensors, and network wiring. Existing line voltage wiring between the fan coil unit and temperature controller can be reused, further minimizing overall labor and installation costs.
The VC3000 relay pack features an onboard universal voltage power supply and
line-voltage relays that directly drive fractional horsepower fan motors and
valves. The VTR8350 controller features a fully digital multi-language touch
screen display that can be user customized.
The controller’s built-in commissioning and configuration utility, its
temperature sensor, and the optional humidity and occupancy sensor, provide
maximum flexibility. The VTR8350 controller is available in Network Ready,
BACnet® MS/TP or wireless Zigbee networked models.
SPECIFICATIONS
-
Thermostat Power Requirements: 7 Vdc, 2.4 W min. (from VC3000)
-
Operating Conditions: 0 to 50 °C (32 to 122 °F); 0 to 95% RH non-condensing
-
Storage Conditions: -30 to 50 °C (-22 to 122 °F); 0 to 95% RH non-condensing
-
Temperature Sensor: Local 10k NTC type 2 thermistor
-
Temp. Sensor Resolution: ± 0.1 °C (± 0.2 °F)
-
Temp. Control Accuracy: ±0.5 °C (±0.9 °F ) @ 21 °C (70 °F) typical calibrated
-
Humidity Sensor and Calibration: Single point calibrated bulk polymer sensor
-
Humidity Sensor Precision: Reading range from 10 to 90% RH noncondensing 10 to 20% precision is 10%;
20 to 80% precision is 5%;
80 to 90% precision is 10% -
Humidity Sensor Stability: <1.0% annual drift (typical)
-
Dehumidification Setpoint Range: 30 to 95% RH
-
Occupied and Unoccupied Setpoint Range Cooling: 12 to 38 °C (54 to 100 °F)
-
Occupied and Unoccupied Setpoint Range Heating: 5 to 32 °C (40 to 90 °F)
-
Room and Outdoor Air Temperature Display: -40 to 50 °C (-40 to 122 °F)
-
Proportional Band for Room Temperature Range Control: Cooling & Heating: 1.8 °C (3.2 °F )
-
Binary Inputs: Dry contact across terminal BI1, BI2 & UI3 to Scom
-
Economizer Analog Output Rating: 0 to 10 Vdc into 2k Ω resistance min.
-
Economizer Analog Output Accuracy: ±3% typical
-
Wire Gauge: 18 gauge maximum, 22 gauge recommended
WARRANTY
- Limited Warranty: 18 months
AGENCY APPROVALS
UL: 61010-1 (2nd edition); CSA: 61010-1 (3rd edition); IEC: 61010-1 (3rd edition), EN 60950-1: 2006A2: 2013, UL 873, CSA 22.2 No. 24-93; 61326-1:2005; FCC: Part 15, Subpart B
WALL CONTROLLERS
Ordering Information
PART NUMBER | DESCRIPTION | COMM. |
---|---|---|
VTR8350A5000B | Fancoil Terminal Equipment Controller, PIR ready (PIR cover not | |
included), onboard humidity sensor | BACnet | |
VTR8350A5500B | Fancoil Terminal Equipment Controller, PIR factory equipped, | |
onboard humidity sensor | BACnet | |
VTR8350A5500BP | Wireless (Zigbee Pro) |
RELAY PACKS
PART NUMBER | DESCRIPTION |
---|---|
VC3500E5000 | Transformer relay pack, 5 relay fan outputs |
VC3504E5000 | Transformer relay pack, 5 relay fan outputs and 4 outputs |
VC3404E5000 | Transformer relay pack, 4 relay fan outputs, smart Vdc output, |
and 4 inputs
VC3300E5000| Transformer relay pack, 3 slave fan outputs
APPLICATIONS
Wall Control and Relay Pack Applications (BACnet models shown, wireless similar)
APPLICATION| OUTPUTS/ INPUTS 1H/1C with reheat| CONTROLLER PART
NUMBER
VTR8350A5000B| RELAY PACK PART NUMBER
VC3500E5000
---|---|---|---
2 or 4 pipe, up to 3 speed fan, humidity control| 1H/1C with 4 inputs and
reheat| VTR8350A5000B| VC3504E5000
1H/1C with 4 inputs, reheat, and occ. output| VTR8350A5000B| –
2 pipe, up to 3 speed fan| 1H/1C with pulsed reheat| –| VC3500E5000
1H/1C with 4 inputs andpulsed reheat| –| VC3504E5000
2 or 4 pipe, up to 3 speed fan, humidity control| 1H/1C with reheat|
VTR8350A5000B| VC3500E5000
1H/1C with 4 inputs and reheat| VTR8350A5000B| VC3504E5000
1H/1C with 4 inputs, reheat, and occ. output| VTR8350A5000B| –
2 pipe, up to 3 speed fan| 1H/1C with pulsed reheat| –| VC3500E5000
1H/1C with 4 inputs andpulsed reheat| –| VC3504E5000
Slave fan control only| 3 fan outputs| –| VC3300E5000
WIRING EXAMPLES
DIMENSIONAL DRAWING
SELECTABLE COLOR SCHEMES
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>