BOSCH 18 SEER2 Series Inverter Ducted Packaged Heat Pump Instruction Manual
- June 9, 2024
- Bosch
Table of Contents
- BOSCH 18 SEER2 Series Inverter Ducted Packaged Heat Pump
- Product Information
- Table of Contents
- Safety Instructions
- Product Usage Instructions
- Installation Instructions
- Key to Symbols and Safety Instructions
- Dimensions
- Airflow Performance
- Indoor Fan Motor Function
- Air Filter (Not Factory-Installed)
- Electrical Wiring
- Start Up
- System Charge Adjustment
- System Operation and Troubleshooting
- Error Code Troubleshooting (IDU)
- Wiring Diagram
- Maintenance
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
BOSCH 18 SEER2 Series Inverter Ducted Packaged Heat Pump
Product Information
The Inverter Ducted Packaged Heat Pump Bosch IDP Premium is a 3-ton capacity heat pump with 18 SEER2 series and uses R410A refrigerant. The product model number is BTC 761703103 A and the user manual version is 11.2022.
Table of Contents
The user manual contains the following sections:
- Key to Symbols and Safety Instructions
- Component Location
- Dimensions
- Installation
- Airflow Performance
- Indoor Fan Motor Function
- Ductwork
- Condensate Drain Connection
- Air Filter (Not Factory-Installed)
- Electrical Wiring
- Start Up
- System Charge Adjustment
- System Operation and Troubleshooting
- Maintenance
Safety Instructions
The user manual contains safety instructions and warnings that must be read and followed before proceeding with the installation or maintenance of the product. The warnings are identified by a warning triangle printed against a grey background. The following keywords are defined and can be used in this document:
- DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
- WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
- CAUTION indicates a hazardous situation which, if not avoided, could result in minor to moderate injury.
- NOTICE is used to address practices not related to personal injury.
The document also contains important information where there is no risk to people or property. High voltage warning is given in the manual, and it is advised to wait for three (3) minutes after disconnecting power prior to touching electrical components as they may hold a dangerous charge of 380 VDC, then verify DC Voltage is less than 42VDC at inverter TEST POINTS P-N.
Product Usage Instructions
The user manual contains detailed instructions on installation, airflow performance, indoor fan motor function, ductwork, condensate drain connection, air filter (not factory-installed), electrical wiring, start-up, system charge adjustment, system operation and troubleshooting, and maintenance. It is recommended to read and follow the instructions carefully to ensure proper usage of the product.
The manual also contains a wiring diagram and service information that should
be kept with the unit and returned to the
service information pack upon completion of work.
Installation Instructions
Inverter Ducted Packaged Heat Pump Bosch IDP Premium
18 SEER2 Series | 3 Ton Capacity | R410A
BTC 761703103 A | 11.2022
Installation Instructions
2 |
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
Table of Contents
Key to Symbols and Safety Instructions
1.1 Key to Symbols 1.2 Safety
2 Component Location
3 Dimensions 3.1 Unit Dimensions 3.2 Dimensions – Back and Bottom 3.3
Dimensions – Left and Top
4 Installation 4.1 Pre-Installation 4.2 Rigging and Lifting 4.3 Location
Restrictions 4.4 Rooftop Installation – Curb Mounting
5 Airflow Performance
6 Indoor Fan Motor Function
7 Ductwork
8 Condensate Drain Connection 8.1 Install Drain Pipe
9 Air Filter (Not Factory-Installed)
10 Electrical Wiring 10.1 Power Wiring 10.2 Grounding 10.3 Control Wiring
11 Start Up 11.1 System Start Up
12 System Charge Adjustment 12.1 Charging: Weigh-In Method 12.2 Subcooling
Charging and Refrigerant Adjustment In Cooling
(Above 55°F Outdoor Temp.)
Installation Instructions
4 13 System Operation and Troubleshooting
22
4
13.1 Control Logic Description
22
4
13.2 Sensors (Thermistors/Pressure Transducer)
22
13.3 Defrost Description
23
6
13.4 Compressor Crankcase Heater Description
23
13.5 Reversing Valve Operation
23
7
13.6 Protection Functions
24
7
13.7 Fault Code Table
25
8
13.8 Parameter Point Check Table
26
9
13.9 Control Board Overview
27
10
13.10 Error Code Troubleshooting (ODU)
29
10
13.11 Error Code Troubleshooting (IDU)
35
10
13.12 Temperature and Resistance Relationship Tables (for Sensors)
36
10
13.13 Temperature and Resistance Relationship Tables (for T5)
37
12
13.14 Wiring Diagram
38
13 14 Maintenance
39
14.1 Cleaning Precautions
39
14
14.2 Regular Maintenance
39
15
16 16
16
17 17 17 17
19 19
20 20
20
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
| 3
Installation Instructions
1 Key to Symbols and Safety Instructions 1.1 Key to Symbols
Warnings
Warnings in this document are identified by a warning triangle printed against
a grey background. Keywords at the start of a warning indicate the type and
seriousness of the ensuing risk if measures to prevent the risk are not taken.
The following keywords are defined and can be used in this document:
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
WARNING indicates a hazardous situation which, if not avoided, could result in
death or serious injury.
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor to moderate injury.
NOTICE is used to address practices not related to personal injury.
Important information
This symbol indicates important information where there is no risk to people
or property.
1.2 Safety
Please read before proceeding
This document contains a wiring diagram and service information. This is
customer property and is to remain with this unit. Please return to service
information pack upon completion of work.
WARNING: HIGH VOLTAGE Failure to follow this warning could result in property
damage, severe personal injury, or death.
WAIT THREE (3) MINUTES after disconnecting power prior to touching electrical
components as they may hold a dangerous charge of 380 VDC,then verify DC
Voltage is less than 42VDC at inverter TEST POINTS P-N.
NOTICE: This document is customer property and is to remain with
this unit. Please return to service information pack upon completion of work.
These instructions do not cover all variations in systems or provide for every
possible contingency to be met in connection with the installation. Should
further information be desired or should particular problems arise which are
not covered sufficiently for the purchaser’s purposes, the matter should be
referred to your installing dealer or local distributor.
WARNING:
This information is intended for use by individuals possessing adequate
backgrounds of electrical and mechanical experience. Any attempt to repair a
central air conditioning product may result in personal injury and/or property
damage.
WARNING: ELECTRICAL SHOCK
Failure to follow this warning could result in property damage, severe
personal injury, or death.
Disconnect all electric power, including remote disconnects before servicing.
Follow proper lockout/tagout procedures to ensure the power cannot be
inadvertently energized.
4 |
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
WARNING: PERSONAL INJURY/ENVIRONMENTAL HAZARD Any attempt to repair a central
air conditioning product may
result in property damage, severe personal injury, or death. These units use
R-410A refrigerant which operates at 50 to 70% higher pressures than R-22. Use
only R-410A approved service equipment. Refrigerant cylinders are painted a
“Rose” color to indicate the type of refrigerant and may contain a “dip” tube
to allow for charging of liquid refrigerant into the system. All R-410A
systems with variable speed compressors use a POE oil (VG74 or equivalent )
that readily absorbs moisture from the atmosphere. To limit this `hygroscopic”
action, the system should remain sealed whenever possible. If a system has
been open to the atmosphere for more than 4 hours, the compressor oil must be
replaced. Never break a vacuum with air and always change the driers when
opening the system for component replacement.
CAUTION: HOT SURFACE Do not touch top of compressor. May cause minor to
severe burning. Failure to follow this Caution could result in property damage
or personal injury.
CAUTION: HIGH PRESSURE Failure to follow proper procedures can result in
personal
illness or injury or severe equipment damage. System contains oil and
refrigerant under high pressure. Recover refrigerant to relieve pressure
before opening system.
WARNING: GROUNDING REQUIRED Failure to inspect or use proper service tools may
result
in equipment damage or personal injury. Reconnect all grounding devices. All
parts of this product that are capable of conducting electrical current are
grounded. If grounding wires, screws, straps, clips, nuts, or washers used to
complete a path to ground are removed for service, they must be returned to
their original position and properly fastened.
CAUTION: BURN HAZARD Failure to follow this warning will result in abrupt
release
of system charge and may result in personal injury and/ or property damage.
Extreme caution should be exercised when applying gauges to service ports.
Installation Instructions
WARNING: ELECTRICAL SHOCK Failure to follow this warning could result in
property
damage, severe personal injury, or death. Grounding is essential before
connecting electrical supply.
WARNING: This product can expose you to chemicals including Lead and Lead
components, which are known to the State of California to cause cancer and
birth defects or other reproductive harm. For more information go to
www.P65Warnings.ca.gov.
NOTICE: A manufactured (mobile) home installation must conform with the
Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280,
or when this Standard is not applicable, the Standard for Manufactured Home
Installations (Manufactured Home Sites, Communities and Set-Ups), ANSI/NCS
A225.1, and/or MH Series Mobile Homes, CAN/CSA Z240.
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
| 5
Installation Instructions
2 Component Location
Fusible Plug
HPS
T1 EEV Service Valves T5 Th Comp
Outdoor Fan
RV T3 T3L T2 PT Indoor Fan
T4
Figure 1
Component HPS PT T1 T2 T3 T4 T5
Descriptions High pressure switch Pressure transducer Return air temp. sensor Indoor coil temp. sensor Condenser temp. sensor Ambient temp. sensor Comp. discharge temp. sensor
Table 1 Component Descriptions
Component T3L Tf Th EEV RV COMP FP
Descriptions Condensor outlet temp. sensor
Radiator temp. sensor Comp. return temp. sensor Electronic expansion valve
Reversing valve Compressor Fusible Plug
6 |
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
Dimensions
Unit Dimensions
Installation Instructions
Front
Condensate drain connection 3/4″ NPT (Trap required)
K1no-3c/k4o”uDtihaole HLciocgowohnnnvvno.o.l1lt7ta-a1/gg8/ee8″ D” Diaia
Figure 2
Heat Pump Model BRBA-36HWD1N1-M18 Table 2 Unit Dimensions
L 50-11/16″
Heat Pump Model BRBA-36HWD1N1-M18 Table 3 Unit Weights
Net Weight 400 lbs (182 kg)
W 35-1/16″
Gross Weight 420 lbs (191 kg)
H 46-13/16″
A 44-1/16″
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
B 11-3/4″
| 7
Installation Instructions 3.2 Dimensions – Back and Bottom
4-5/16″
OPTIONAL RETURN AIR
OPENING
21-9/16″
Bottom view
OPTIONAL SUPPLY AIR OPENING
7-7/8″ 2-9/16″
Back view
SUPPLY DUCT OPENING
RETURN DUCT OPENING
4-3/16″
Figure 3
Heat Pump Model BRBA-36HWD1N1-M18
C 47-13/16″
Table 4 Dimensions – Back and Bottom
8 |
21-9/16″
D 32-1/4″
E 9-15/16″
F 15-7/8″
G 15-3/4″
H 9-3/4″
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
3.3 Dimensions – Left and Top Top view
Installation Instructions
Left side view
Figure 4
5-1/16″
6-5/8″
11-3/4″
6-5/8″
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
| 9
Installation Instructions
4 Installation 4.1 Pre-Installation
Before installation, carefully check the following: 1. Unit should be
installed in accordance with national and local safety codes, including but
not limited to ANSI/NFPS No. 70, local plumbing and wastewater codes and any
other applicable codes. 2. For rooftop installation, be sure the structure has
enough strength to support the weight of unit. Unit must be installed on a
field supplied roof curb or rack and leveled. 3. For ground level
installation, a field supplied level slab must be used. 4. Condenser airflow
should not be restricted. 5. On applications when a roof curb is used, the
unit must be positioned on the curb so the front of the unit is tight against
the curb. If the unit is to be mounted on a curb in a downflow application,
refer to Figure 14, and convert panels prior to rigging and lifting. The panel
removal process may require the unit to be on the ground.
4.2 Rigging and Lifting
ÙÔÏÚÕÐÛÐÑÖÐ×ÒØÓÒ
ÜÑÐØÿÔÕÐÖ×Ø
Exercise care when moving the unit. Do not remove any packaging until the unit
is near the place of installation. Rig the unit by attaching chain or cable
slings to the lifting holes provided in the base rails. Spreader bars, whose
length exceeds the largest dimension across the unit, MUST be used across the
top of the unit. When rigging/lifting the unit, the minimum height between the
top of the rigging cables’ connection point and top of unit should be 36
inches. Refer to Figure 5.
CAUTION: Before lifting, make sure the unit weight is distributed
equally on the rigging cables so it will lift evenly.
CAUTION: All panels must be secured in place when the unit is lifted.
The condenser coils should be protected from rigging cable damage with plywood
or other suitable material.
4.3 Location Restrictions
Ensure the top discharge area is unrestricted for at least 60 inches above the
unit. Do not locate outdoor unit near bedrooms since normal operational noise
levels may be disturbing to building occupants. Position unit to allow
adequate space for unobstructed airflow, wiring, and serviceability. Do not
restrict outdoor airflow. An air restriction at either the outdoor air inlet
or the fan discharge may be detrimental to compressor life. Do not place the
unit where water, ice, or snow from an overhang or roof will damage or flood
the unit. Do not install the unit on carpeting or other combustible materials.
Slab-mounted units should be at least 2 inches (51 mm) above the highest
expected water and runoff levels. Do not use unit if it has been under water.
Maintain a distance of 24 inches between units. Position unit so water, snow,
or ice from roof or overhang cannot fall directly on unit. See Figure 7 and
Figure 8 for minimum clearance requirements.
Cold climate considerations (heat pump only)
Figure 5
NOTICE:
Precautions must be taken for units being installed in areas where snow
accumulation and prolonged below-freezing temperatures occur.
10 |
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
Units should be elevated 3-12 inches above the pad or rooftop, depending on
local weather. This additional height will allow drainage of snow and will
permit condensate water to drain when the unit is in defrost mode. Ensure that
drain holes in unit base pan are unobstructed, preventing drainage of defrost
water (See Figure 9).
If possible, avoid locations that are prone to snow drifts. If not possible, a
snow drift barrier should be installed around the unit to prevent a build-up
of snow on the sides of the unit.
Ensure that Condensate Drain side is pitched lower than the opposite side (see
Figure 6).
Installation Instructions
Structure
Figure 8
Condensate drain side
Figure 6
Avoid Installs Near Bedrooms
Min 24″ Access Panel
Min. 60″ Unrestricted
Min 24″ Access Panel
Figure 7
A minimum clearance of 24″ should be maintained adjacent to all access/service
panels. Refer to local code requirements for additional clearance
requirements.
7
77
7
7
7
7
7
7 7
Min 24″
Snow barrier
7 7
7
7
7
7
7
7
7
7
77
7
7
7 7
7
7
7
7
7 7
7
7
7
7
7
7
77
7
77
7
7
77
Snow legs
7
3- 12″ Elevation
pad
Figure 9 Insulation Layer
Corrosive Environment
Exposure to a corrosive environment may shorten the life of the equipment,
corrode metal parts, and/or negatively affect unit performance. Corrosive
elements include, but are not limited to: sodium chloride, sodium hydroxide,
sodium sulfate, and other compounds commonly found in ocean water, sulfur,
chlorine, fluorine, fertilizers, and various chemical contaminants from
industry/manufacturing plants. If installed in areas which may be exposed to
corrosive environments, special attention should be given to the equipment
placement and maintenance.
Lawn sprinklers/hoses/waste water should not spray directly on the unit
cabinet for prolonged periods of time.
In coastal areas: locate the unit on the side of the building or roof away
from the waterfront.
Fencing or shrubbery may provide some shielding protection to the unit,
however minimum unit clearances must still be maintained.
Every three months, wash the outdoor coil and any exposed cabinet surfaces.
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
| 11
Installation Instructions
4.4 Rooftop Installation – Curb Mounting
The manufacturer does not supply roof curbs, they must be field supplied.
Refer to Figure 11 for recommended roof curb dimensions. On applications when
a roof curb is used, the unit must be positioned on the curb so the front of
the unit is tight against the curb. The default orientation from the factory
is for horizontal airflow. Convert the unit to downflow using the following
procedure:
1. Remove sheet metal screws from both the supply air and return air panels.
Refer to Figure 14.
2. Add foam tape on the perimeter of the non painted side of each panel. 3.
Move and re-secure the panels to the downflow location using the sheet
metal screws from step 1. For more information, refer to the the Conversion
Kit Manual included with each heat pump unit. Install the field-supplied roof
mounting curb according to the Installation Instructions supplied with the
curb. Install insulation, cant strips, roofing, and flashing. Ductwork must be
attached to curb.
NOTICE: The gasketing of the unit to the roof curb is critical for a water
tight seal. Install gasketing material supplied with the field supplied roof
curb. Improperly applied gasketing also can result in air leaks and poor unit
performance.
CAUTION: The unit must be secured to the curb by installing screws
through the bottom of the curb flange and into the unit base rails.
1″ 2″
14-1/4″ 4-1/4″
Insulation layer
12-5/8″ 30-5/8″
1″ 14″
14″
46-1/16″
2″
Figure 11 Roof Curb Dimensions
For units applied with a roof curb, the minimum clearance may be reduced from
1 inch to 1/2 inch between combustible roof curb material and supply air duct.
NOTICE: UNIT/STRUCTURAL DAMAGE HAZARD
Failure to follow this caution may result in property damage. Ensure there is
sufficient clearance for saw blade when cutting the outer horizontal flange of
the roof curb so there is no damage to the roof or flashing.
A A
A
INSULATION LAYER
B
NOTES: 1. Roof Curb must be set up for unit being installed 2. Seal strip must
be applied, as required, to unit being installed 3. Attach ductwork to curb
(flanges of duct rest on curb) 4. Recommended insulated panels: 1 in. (25.4
mm) thick fiberglass 1 lb. density
C
SUPPLY AIR
1″
Figure 10 Roof Curb Details
CURB
B 14-1/4″
Table 5 Roof Curb Details – inches
C
D
14″
46-1/16″
A
43-1/2″
D
C
RETURN AIR
E 16″
1″ 12-5/8″
E F
F 30-5/8″
12 |
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
Installation Instructions
Airflow Performance
Airflow performance data is based on cooling performance with a coil and no
filter in place. Check the performance table (Table 6) for appropriate unit
size selection.
External static pressure should stay within the minimum and maximum limits
shown in the table below in order to ensure proper operation of both cooling,
heating, and electric heating operation.
Model Number
BRBA-36HWD1N1-M18
Motor Speed *
Tap (1) Tap (2) Tap (3) Tap (4) Tap (5)
SCFM Watts Amps SCFM Watts Amps SCFM Watts Amps SCFM Watts Amps
SCFM
Watts Amps
0[0] 925 114 1.07 1103 162 1.45 1132 193 2.03 1355 296 2.52
1522
426 3.49
0.1[.02] 807 120 1.12 993 169 1.51 1084 201 2.08 1310 301 2.56
1465
432 3.54
SCFM
External Static Pressure-Inches W.C.[kPa]
0.2[. 05] 0.3[.07] 0.4[.10] 0.5[.12] 0.6[.15]
723
658
/
/
/
126
130
/
/
/
1.17
1.19
/
/
/
911
841
776
710
596
175
181
187
193
197
1.56
1.6
1.65
1.69
1.72
1027
972
907
832
762
207
214
221
229
238
2.15
2.17
2.20
2.27
2.31
1270
1180
1049
989
931
307
312
318
323
327
2.6
2.64
2.68
2.71
2.74
1364
1291
1231
1177
1121
438
443
448
452
456
3.58
3.62
3.65
3.68
3.7
0.7[.17] / / / / / / 700 243 2.39 870 331 2.77
1066
460 3.74
0.8[.20] / / / / / / 637 247 2.42 813 336 2.81
1017
466 3.78
Table 6
Bold outlined areas represent airflow outside of the required 300-450 cfm/ton range.
NOTES:
1. This table is only used to select the highest blower speed.
2. The rated airflow of systems without electric heater kits requires between
300 and 450 cubic feet of air per minute (CFM).The rated airflow of systems
with electric heater kits requires between 350 and 450 cubic feet of air per
minute (CFM).
3. The air distribution system has the greatest effect on airflow. Therefore,
the contractor should use only industry-recognized procedures.
4. Duct design and construction should be carefully done. System performance
can be lowered dramatically through poor design or workmanship.
5. Air supplier ducts should be located along the perimeter of the
conditioned space and properly sized. Improper location or insufficient air
flow may cause drafts or noise in the ductwork.
6. Installers should balance the air distribution system to ensure proper
quiet airflow to all rooms in the home. An air velocity meter or airflow hood
can be used to balance and verify branch and system airflow (CFM).
7. 4 Speed Fan default is Tap (1), Tap (2), Tap (3), Tap (4)
For instructions on how to select fan speeds, refer to Section 6 of this manual.
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
| 13
Installation Instructions
Indoor Fan Motor Function
System Operation and Function This unit can run with either 4 Stage Fan
Control or 2 Stage Fan Control. The factory default is 4 Stage Fan Control. To
change the factory default parameters, refer to the information provided
below.
Four Stage Fan Control The IDP 3 Ton supports up to 4 fan speeds. The fan
speed will automatically change according to the temperature difference
between T1 (return air temperature) and Ts (estimated thermostat set point).
Higher differences in temperature between T1 and Ts relate to higher fan
speeds. This fan control is supported by either a single or two stage
thermostat.
The ECM Constant Torque motor has 5 selectable speed taps. The unit can use up
to 4 fan speeds by setting the SW6-4 dip switch to the “ON” position
(default). For determining the required airflow, refer to the Airflow
Performance Table (Table 6). To select the fan speeds, change SW6-1 and SW6-2
dip switches, refer to Table 7 for dip switch speed configuration.
Figure 12
Mid-
SW6-4 SW6-1 SW6-2
High
Mid
Low
high
OFF
OFF
2
2
1
1
OFF
ON
3
2
2
1
ON*
ON*
OFF*
4
3
2
1
ON
ON
5
4
3
2
Table 7 *Note: Default Fan Speed is SW6-4 ON, SW6-1 ON, SW6-2 OFF
Two Stage Fan Control The IDP supports two stage fan control which requires a two stage thermostat (Y1&Y2). When there is a call for Y2, the blower motor will turn to high speed setting. When there is a call for Y1, the blower motor will turn to low speed setting. Unit will run at low speed setting when there is only G call. It will run in high speed setting when there is W/W1/W2 signal (when the electric heat kit is on).
Customers can select two stage fan control by setting the SW6-4 dip switch to the “OFF” position. Select the two fan speeds using the SW6-1 and SW6-2 dip switches, refer to Table 8. Refer to Airflow Performance Table (Table 6) for reference airflow.
If 2 stage thermostat is not available, single stage thermostat may be used, please refer to Wiring Diagram section for wiring instructions. If Y1 and Y2 are jumped, the unit will only run in high stage fan speed.
Mid-
SW6-4 SW6-1 SW6-2
High
Mid
Low
high
OFF
OFF
2
/
1
/
OFF
ON
3
/
1
/
OFF
ON
OFF
4
/
2
/
ON
ON
5
/
3
/
Table 8
Anti-Cold Air Fan Delay The Anti-Cold Air Fan Delay function utilizes a sensor
(T2) located on the indoor coil, which prevents the blower from turning on
until the coil has reached a certain temperature. This feature prevents cold
air blow during heating operation and is activated by setting SW6-3 dip switch
to the “ON” position (default), refer to Figure 12 and Table 9.
1. When SW6-3 dip switch is set to the “ON” position and the unit is in
heating mode, the Anti-Cold Air Fan Delay function will activate based on the
following entry conditions (all 3 conditions must be met):
a. Indoor Coil Temperature (T2) < 82.4 °F b. Electric heat kit is turned off
c. There is a call for Y1 from thermostat to indoor unit
2. This function will deactivate if ONE OF the following exit conditions are
met OR the system has been operating in heating mode for 15 minutes.
a. T2 89.6 °F b. Heater kit is turned on c. The system is NOT running Heat
mode
3. During the heating mode, if one of the exit conditions of Anti-Cold Air is
satisfied, the blower motor will turn on in first stage fan speed.
4. During the heating mode, if all of the entry conditions of Anti-Cold Air
are met and maintained for 120s, the blower motor will change to first stage
speed.
SW6-3
ON OFF
Table 9 Note: Default is ON
Heat: Anti-Cold Air Fan Delay via Temp Sensor Heat: Timed Fan Delay
Heating Fan Delay If SW6-3 dip switch is set to the “OFF” position (refer to Table 9), and the unit is in heating mode, the blower will operate with a 90 second delay with the fan speed dictated by Y1 or Y2 signal.
Passive Dehumidification (Optional) IDP 3 Ton has a Passive Dehumidification function which lowers the fan speed and optimizes the compressor operation with a DH call from the thermostat. This function requires proper DH wiring from the indoor unit to the thermostat (with a humidistat).
If DH wire is not connected, the unit will still function normally, but will not be able to run in dehumidification mode.
14 |
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
Installation Instructions
7 Ductwork
Field ductwork must comply with the National Fire Protection Association NFPA
90A, NFPA 90B and any applicable local ordinance(s).
WARNING: FIRE HAZARD AND CARBON MONOXIDE Do not, under any circumstances,
connect return ductwork
to any other heat producing device such as fireplace insert, stove, etc.
Unauthorized use of such devices may result in fire, carbon monoxide
poisoning, explosion, personal injury or property. damage.
Return Air Supply Air Roof Flashing
Angle Iron Frame
Sheet metal ductwork run in unconditioned spaces must be insulated and covered
with a vapor barrier. Fibrous ductwork may be used if constructed and
installed in accordance with SMACNA Construction Standard on Fibrous Glass
Ducts. Ductwork must comply with National Fire Protection Association as
tested by U/L Standard 181 for Class I Air Ducts. Check local codes for
requirements on ductwork and insulation.
Duct system must be designed within the range of external static pressure the
unit is designed to operate against. It is important that the system airflow
be adequate. Make sure supply and return ductwork, grills, special filters,
accessories, etc. are accounted for in total resistance. See airflow
performance tables in Section 5 of this manual.
Design the duct system in accordance with “ACCA” Manual “D” Design for
Residential Winter and Summer Air Conditioning and Equipment Selection. Latest
editions are available from: “ACCA” Air Conditioning Contractors of America,
1513 16th Street, N.W., Washington, D.C. 20036. If duct system incorporates
flexible air duct, be sure pressure drop information (straight length plus all
turns) shown in “ACCA” Manual “D” is accounted for in system.
If an elbow is included in the plenum close to the unit, it must not be
smaller than the dimensions of the supply duct flange on the unit.
NOTICE:
The front flange on the return duct (if connected to the blower casing) must
not be screwed into the area where the power wiring is located. Drills or
sharp screw points can damage insulation on wires located inside unit.
Figure 13 Rooftop Installation – Frame Mounting
SUPPLY AIR PANEL
SHEET METAL SCREWS
RETURN AIR PANEL
Figure 14 Note: Refer to downflow conversion instructions provided with the unit
Return Air Roof Flashing
Supply Air
Secure all ducts to roof curb and building structure on downflow discharge units. Do not connect ductwork to unit. For horizontal applications, unit is provided with flanges on the horizontal openings. All ductwork should be secured to the flanges using proper fasteners for the type of duct used and tape the duct-to unit joint as required to prevent air leaks.
Roof Flashing
Angle Iron Frame
NOTICE:
When fastening ductwork to the side duct flanges on the unit, insert the
screws through the duct flanges only. DO NOT insert the screws through the
casing. Outdoor ductwork must be insulated and waterproofed.
Figure 15 Typical Rooftop Downflow Application with Frame
Be sure to note supply and return openings. Refer to Figure 3 for information concerning supply and return air duct dimensions.
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
| 15
Installation Instructions
Unit should be installed in accordance with national and local safety codes,
including but not limited to ANSI/NFPS No. 70, local plumbing and wastewater
codes and any other applicable codes.
8.1 Install Drain Pipe
1. Ensure drain lines do not block access to front of the unit. Minimum
clearance of 24 inches is required for filter, coil or blower removal and
service access.
2. Make sure unit is leveled or pitched slightly towards primary drain
connection so that water will drain completely from the pan.
3. Do not reduce drain line size to less than connection size provided on
condensate drain pan.
4. All drain lines must be pitched downward away from the unit at a minimum
of 1/8″ per foot of line to ensure proper drainage.
5. Do not connect condensate drain line to a closed or open sewer pipe. Run
condensate to an open drain or run line to a safe outdoor area.
6. The drain line should be insulated where necessary to prevent sweating and
damage due to condensate forming on the outside surface of the line.
7. Make provisions for disconnecting and cleaning of the primary drain line
should it become necessary. Install a 2 inch trap in the primary drain line as
close to the unit as possible. Make sure that the top of the trap is below
connection to the drain pan to allow complete drainage of pan.
1in.(25mm)min
TRAP OUTLET
2in.(51mm)min
Air Filter (Not Factory-Installed)
Filters and filter racks are not included with the unit and must be field
supplied.
An external filter or other means of filtration must be properly sized for a
maximum of 300 feet/min. air velocity or what is recommended for the type of
filter installed.
Filter application and placement are critical to airflow, which may affect the
heating and cooling system performance. Reduced airflow can shorten the life
of the system’s major components, such as motor, elements, heat relays,
evaporator coil or compressor. Consequently, we recommend that the return air
duct system have only one filter location. For systems without a return air
filter grill, multiple filter grills can be installed at each of the return
air openings.
If adding high efficiency filters or electronic air filtration systems, it is
very important that the air flow is not reduced. If air flow is reduced the
overall performance and efficiency of the unit will be reduced. It is strongly
recommended that a professional installation technician is contacted to ensure
such filtration systems are installed correctly.
Do not double filter the return air duct system. Do not filter the supply air
duct system. This will change the performance of the unit and reduce airflow.
WARNING: FIRE HAZARD Do not operate the system without filters. A portion of
the
dust suspended in the air may temporarily lodge in the duct runs and at the
supply registers. Any circulated dust particles could be heated and charred by
contact with the air handler elements. This residue could soil ceilings,
walls, drapes, carpets and other articles in the house. Soot damage may occur
with filters in place, when certain types of candles, oil lamps or standing
pilots are burned.
Figure 16
Heat Pump Model
No.
BRBA-36HWD1N1-M18
1
Table 10
Size Recommended 16″x10″x1″
When making drain fitting connections to the drain pan, use a thin layer of Teflon paste, silicone or Teflon tape and install by hand tightening.
When making drain fitting connections to drain pan, do not overtighten. Over- tightening fittings can split pipe connections on the drain pan.
16 |
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
Installation Instructions
Electrical Wiring
Field wiring must comply with the National Electric Code (NEC) and any
applicable local ordinance.
WARNING: ELECTRICAL SHOCK Disconnect all power to unit before installing or
servicing.
More than one disconnect switch may be required to de-energize the equipment.
Hazardous voltage can cause severe personal injury or death.
10.1 Power Wiring
1. It is important that proper electrical power is available for connection
to the unit being installed. See the unit nameplate, wiring diagram, and
electrical data in the installation instructions for more detailed
requirements. Voltage tolerance should not be over 10% from rating voltage.
2. If any of the wiring must be replaced, replacement wiring must be the same
type as shown in nameplate, wiring diagram and electrical data sheet.
3. Install a branch circuit disconnect of adequate size to handle starting
current, located within sight, and readily accessible to the unit.
4. Electric Heater: If the optional Electric Heat Kit is installed, the unit
should be equipped with suitable circuit breakers or fuse. Refer to Table 11
and 12 for more information. These breaker(s) protect the internal wiring in
the event of a short circuit and serve as a disconnect. Circuit breakers
installed within the unit do not provide over-current protection of the supply
wiring and therefore may be sized larger than the branch circuit protection.
Supply circuit power wiring must be 221 °F minimum copper conductors only.
Refer to Table 11 and 12 for ampacity, wire size and circuit protector
requirements. Supply circuit protective devices may be either fuses or “HACR”
type circuit breakers.1-3/8″ knockouts inside the cabinet are provided for
connection of power wiring to electric heater. Power wiring is connected to
the power terminal block in unit electric cabinet. See Electric Heater Kit
Installation Instructions for details.
5. See wiring diagram located on inside of control board access panel for
proper wiring instructions.
10.2 Grounding
WARNING: ELECTRICAL SHOCK The unit must be permanently grounded. Failure to do
so
can result in electrical shock causing personal injury or death.
The unit must be electrically grounded in accordance with local codes and the
National Electric Code (NEC).
Grounding may be accomplished by attaching ground wire(s) to ground lug(s)
provided in the unit wiring compartment.
10.3 Control Wiring
WARNING: FIRE HAZARD Low voltage control wiring should not be run in conduit
with high voltage wiring. Keep distance between the two conduits per local
codes.
18 AWG. color-coded low voltage wire should be used for lengths less than 100
ft. For wire lengths longer than 100 ft., 16 AWG. wire should be used.
7/8″ knockout hole should be used to route control wires into the unit. After
installation, ensure separation of low voltage and high voltage
wiring is maintained.
Refer to Figure 18 for thermostat wiring diagrams.
Indoor Control Board
C R Y1 Y2 G B/O DH W2 W1
L1 L2
High voltage power supply
Figure 17
Control wiring
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
| 17
Installation Instructions
Support 3H and 2C thermostat
R C Y Y2 G O/B W/E
H/DH THERMOSTAT
RED
R
BROWN
C
YELLOW
Y1
PURPLE
Y2
GREEN
G
BLUE B
WHITE
W1
W2
GRAY
Dh
UNIT CONTROL BOARD TERMINAL STRIP
Support 3H and 1C thermostat
RED
R
R
BROWN
C
C
Y
YELLOW
Y1
Y2
G
GREEN
G
BLUE
O/B
B
W/E
WHITE
W1
WHITE/BLACK
W2
W2
GRAY
H/DH
Dh
THERMOSTAT
UNIT CONTROL BOARD TERMINAL STRIP
Support 1H and 1C thermostat
R C Y
G O/B
H/DH THERMOSTAT
RED
R
BROWN
C
YELLOW
Y1
Y2
GREEN
G
BLUE
B
W1
W2
GRAY
Dh
UNIT CONTROL BOARD TERMINAL STRIP
Figure 18 Thermostat Wiring Diagrams
Dh wiring is optional and requires a thermostat with a humidistat. Dh functions as Passive Dehumidication and will downstage the indoor fan speed. System will operate according to normal sequence of operations if Dh wiring is absent.
Y2 wiring is optional for 4 speed fan control. For 2 stage fan control Y2 wiring is required.
Support 4H and 2C thermostat
R C Y Y2 G O/B W/E W2 H/DH THERMOSTAT
RED
R
BROWN
C
YELLOW
Y1
PURPLE
Y2
GREEN
G
BLUE B
WHITE
W1
WHITE/BLACK W2
GRAY
Dh
UNIT CONTROL BOARD TERMINAL STRIP
Support 2H and 2C thermostat
R C Y Y2 G O/B
H/DH THERMOSTAT
RED
R
BROWN
C
YELLOW
Y1
PURPLE
Y2
GREEN
G
BLUE
B
W1
GRAY
W2
Dh
UNIT CONTROL BOARD TERMINAL STRIP
Support 2H and 1C thermostat
R C Y
G O/B W/E
H/DH THERMOSTAT
RED
R
BROWN
C
YELLOW
Y1
Y2
GREEN
G
BLUE
B
WHITE
W1
W2
GRAY
Dh
UNIT CONTROL BOARD TERMINAL STRIP
Dashed lines in the above thermostat wiring diagrams refer to optional wiring (wiring for Passive Dehumidification Function and/ OR Electric Heat, and 2 stage fan control). For thermostat wiring please refer to the Owner’s Manual of the thermostat.
B wire must be used with heat pump system only, the valve energizes in heating.
reversing
18 |
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
WARNING: ELECTRICAL SHOCK
Label all wiring prior to disconnection when servicing controls. Wiring errors
can cause improper and dangerous operation. Verify proper operation after
servicing.
Installation Instructions
Start Up
System Start Up
1. Ensure Sections 4, 5, 6, 7, and 8 have been completed. 2. Set System
Thermostat to OFF.
Size (Tons)
Voltage – Phase Frequency
Compressors (each)
RLA LRA
36 (3)
208/2301-60
19A
52A
OD Fan Motors (each)
FLA
2.1A
Supply Blower Motor
FLA
3.8A
Unit Circuit
MCA¹ (Amps)
Max Fuse²/ Breaker³ Size
(Amps)
28.7
45
Table 11 Electrical Data Without Electric Heat
Heater Circuit Dual Point
Single Point
Model
kW 208/ 240
Stages
FLA (Amps)
Max Fuse²/
Max Fuse²/
MCA¹ Breaker³ MCA Breaker³
(Amps) Size (AMPS) Size
(Amps)*
(Amps)**
EHK-05J 3.8/5 1 18.1/20.8 23/26 EHK-08J 5.6/7.5 1 27.1/31.3 34/40 EHK-10J 7.5/10.0 1 36.1/41.7 46/53
25/30 35/40 50/60
52/55 63/68 74/81
60/60 70/70 80/90
EHK-15J 11.3/15 2 54.2/62.5 68/79 70/80 97/107 100/110
Table 12 Electrical Data With Electric Heat
1. Minimum Circuit Ampacity. 2. Maximum Over Current Protection per Standard
UL 1995. 3. Fuse or HACR circuit breaker size field installed.
- Max Fuse/Breaker Sizes are for electric heater ONLY (dual point electric heat). DOES NOT include breaker size for the unit. **Max Fuse/Breaker Sizes include breaker size for the unit AND electric heat (single point electric heat).
Figure 19 3. Turn on disconnect to apply power to the indoor and outdoor
units.
ON O FF
Figure 20 4. Wait one (1) hour before starting the unit if compressor
crankcase heater is used and the outdoor ambient temperature is below 70 °F.
60 MIN.
Refer to Electric Heat Kit Installation Manual, some heater kits include fuses
from the manufacturer.
WARNING: ELECTRICAL SHOCK / FIRE HAZARD Any power supply and circuits must be
wired and
protected in accordance with federal, state and local electrical codes.
Figure 21 5. Set system thermostat to ON.
Figure 22
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
| 19
Installation Instructions
System Charge Adjustment
The unit comes precharged from the factory with 7-8 lb-oz of refrigerant. Follow Section 12 for charge adjustments i.e if components have been replaced, or if there is a suspected leak.
80 ºF 70ºF
12.1 Charging: Weigh-In Method
Weigh-in method is recommended anytime a system charge is being replaced.
Weigh-in method can also be used when power is not available to the equipment
site or operating conditions (indoor/outdoor temperatures) are not in range to
verify with the subcooling charging method.
Heat Pump Model BRBA-36HWD1N1-M18 Table 13
Refrigerant Charge (lb-oz) 8-6
Indoor Temp
Figure 24
2. Stabilize the system.
3. After starting the system in cooling mode, short press “FORCE” button, and
a “|– ” symbol should appear. System may take 10 minutes to ramp up. Operate
the system for a minimum of twenty (20) minutes.
12.2 Subcooling Charging and Refrigerant Adjustment In Cooling (Above 55°F
Outdoor Temp.)
1. Check the outdoor ambient temperatures.
Subcooling (in cooling mode) is the only recommended method of charging above
55°F outdoor ambient temperatures. For outdoor ambient temperatures below
55°F, use weigh-in charge method.
It is important to return in the spring or summer to accurately charge the system in the cooling mode when outdoor ambient temperature is above 55°F.
Outdoor Temperature Above 55ºF
120ºF
55ºF
Outdoor Temperature Below 55ºF
55ºF
Figure 25
SW1 is not used.
After a twenty (20) minute stabilization period operating at 100% capacity (72
Hertz ), maintain continuous operation while adjusting refrigerant charge.
After adjusting, operate system for a minimum of five (5) minutes for system
to stabilize, otherwise repeat step 3.
Outdoor Temp1
Outdoor Temp2
Figure 23 For best results the indoor temperature should be kept between 70°F to 80°F.
20 MIN.
Figure 26 4. Calculate subcooling value on liquid line (According to Table 14)
Measured Liquid Line Temp. = ____ºF Measured Liquid Line Pressure =
___ PSIG Calculate subcooling value = ____ºF
20 |
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
Figure 27 Ensure the temperature sampling position as shown above.
Installation Instructions
Connect gauges to refrigerant bottle and unit as illustrated (Figure 27 and
28).
Purge all hoses. Open tank. Stop adding refrigerant when subcooling matches
the charging chart
(Table 14) Final Subcooling value.
Recover refrigerant if the subcooling reading from Table 14 is higher than the
designed value (Table 15).
If calculated subcooling value is lower than the design subcooling value (Table 15), please add refrigerant. Repeat steps 2 through 4.
Liquid
Final Subcooling(°F)
Line Temp 6
7
8
9
10
11 12
13
(°F)
Liquid Gauge Pressure (PSI)
55 173 176 179 182 185 188 191 195
60 188 191 195 198 201 204 208 211
65 204 208 211 215 218 221 225 229
70 221 225 229 232 236 239 243 247
75 239 243 247 251 255 259 262 266
80 259 262 266 270 275 279 283 287
85 279 283 287 291 295 300 304 309
90 300 304 309 313 318 322 327 331
95 322 327 331 336 341 346 351 355
100 346 351 355 360 365 370 376 381
105 370 376 381 386 391 397 402 407
110 397 402 407 413 418 424 430 435
115 424 430 435 441 447 453 459 465
120 453 459 465 471 477 483 489 496
125 483 489 469 502 508 515 521 528
Table 14 R-410A Refrigerant Chart – Final Subcooling
Heat Pump Model BRB-36HWD1N1-M18 Table 15
Design Subcooling 12°F ± 4°F
5. Adjust refrigerant level to attain proper gauge pressure.
Add refrigerant if the subcooling reading from Table 14 is lower than the designed value (Table 15).
Figure 28 6. Stabilize the system. Wait 5 minutes for the system condition to
stabilize between adjustments.
When the subcooling matches the chart, the system is properly charged.
Remove gauges. Replace service port caps to prevent leaks. Tighten finger
tight plus
an additional 1/6 turn. 7. Record System Information for reference (Table16).
Record system
pressures and temperatures after charging is complete.
The subcooling also can be calculated by pressing check button after getting
T3 and T3L temperatures (refer to table 21).
Description Outdoor model number Measured Outdoor Ambient Measured Indoor
Ambient Check Condenser Outlet Temp.(T3L) Check Condenser Temp.(T3) Calculate
subcooling value =T3-T3L
Table 16
Value
°F °F °F °F °F
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
| 21
Installation Instructions
System Operation and Troubleshooting
13.2 Sensors (Thermistors/Pressure Transducer)
13.1 Control Logic Description
T1 = Return Air Temperature
The variable speed system adopts the same 24VAC control as any conventional
heat pump.
The compressor’s speed is controlled based on coil pressures monitored by the
unit’s pressure transducer. To ensure stable and adequate capacity, the
compressor speed will modulate relative to evaporator pressure during cooling
operation and relative to condensing pressure during heating operation. The
target pressure can automatically adjust based on compressor operation so
optimal capacity can be achieved. Target pressure can be manually adjusted
(SW4) to achieve improved dehumidification and capacity demands.
— Indoor Fan Control T2 = Indoor Coil Temperature
— Anti-cold air function in heating mode T3 = Outdoor Coil Temperature
High/Low temperature protection
— Outdoor fan control (cooling mode) — Defrost control (heating mode)
ON OFF 1 2 3 4
Figure 29
Switch ON
SW4-1 OFF ON
SW4-2 OFF ON
SW4-3 OFF ON
SW4-4 OFF
Table 17 *Factory Default
Description Must be set at “ON” position
Unused Unused Must be set to “OFF” position Adaptive capacity output disabled
Adaptive capacity output enabled Accelerated cooling/heating Normally
cooling/heating
Adaptive capacity function is a “self-learning function” which allows a range
of target coil temperatures to adapt for better unit operation and reduced
short cycling.
Accelerated cooling/heating function changes the initial target coil
temperature to provide “enhanced comfort” by increasing unit capacity.
T4 = Ambient Temperature — Operating condition permission — Defrosting
condition permission — Outdoor fan control (heating mode)
T5 = Compressor Discharge Temperature — High/Low temperature protection —
Electronic Expansion Valve (EEV) (ODU/heating mode only)
Th = Compressor Return Temperature T3L = Liquid Line Temperature TF = Control
Board Module Temperature
— Inverter High Temperature Protection
Pressure transducer — Compressor frequency control — Electronic Expansion
Valve (EEV) control (in both heating and cooling modes) — High pressure
protection (heating mode) — Low pressure protection (cooling mode)
22 |
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
Installation Instructions
13.3 Defrost Description
The Demand Defrost Control (DDC) monitors the ODU coil temperature using
thermistor (T3). A second thermistor (T4) monitors outdoor ambient
temperature. Based on these parameters, as well as accumulative run time and
high pressure, the DDC calculates proper initiation of defrost.
Any one of the below three conditions is required to enter defrost:
1. The calculated temperature difference between the outdoor temperature (T4)
and the coil temperature (T3) is called Delta T. After Delta T is achieved and
continues for 3 minutes. — T4 39°F, Delta T = 18°F
— T4 30°F, Delta T = 16°F
— T4 19°F, Delta T = 14°F
— When T4 < 19°F, T3 < 9°F, accumulative compressor run time 80 minutes.
2. After “Minimum Run Time” (MRT) is achieved. MRT is based on outdoor
ambient temperature (T4), for example: — MRT is 4 hours when: T4 < 23°F
— MRT is 2 hours when: 23°F T4 < 42°F 3. After the high pressure saturation
temperature drops below 82°F
for 20 minutes.
Defrost will terminate once outdoor coil temperature (T3) reaches 64°F for a
period of 1 minute or defrost time has exceeded 8 minutes.
Defrost Termination Settings (SW5) offers different defrost termination
options for enhanced defrost for different geographical and outdoor
conditions.
SW5
ON OFF 1 2
Figure 30
Defrosting Choice
ON
OFF Remarks Table 18
SW5-1
SW5-2
Remarks
Operating time is Defrosting extended for
reduced by 10%
60 seconds
Normal Enter defrost
Normal Quit defrost
Default
Manual Defrost: 1. System must have a call for heat and have been operating
for a minimum of 8 minutes. 2. Press “Force” button on inverter board for 6
seconds to begin forced defrost. 3. Wait approximately 40 seconds for defrost
to initiate. 4. Once defrost initiates, the display will indicate “dF”. 5.
Defrost test will terminate automatically, after which the display will
indicate running speed. 6. If a second defrost test is required, repeat steps
2-5 after 5 minutes.
13.4 Compressor Crankcase Heater Description
Refrigerant migration during the OFF cycle can result in noisy start-ups,
therefore a CrankCase Heater (CCH) is used to minimize refrigerant migration
thereby minimizing start-up noise and/or bearing “wash out”. All CCHs must be
installed on the lower half of the compressor shell. Its purpose is to warm
the compressor during the OFF cycle, driving refrigerant from compressor.
After extended shutdown periods in cold weather, it is recommended to allow
CCH to be energized for at least 12 hours prior to compressor operation by
applying line voltage to heat pump with thermostat OFF.
CCH operation energizes: 1. First time line voltage is applied and compressor
discharge temperature T5 < 53.6°F. 2. Compressor stops running for 3 hours
(outdoor ambient temperature T4 < 41°F OR compressor discharge temperature T5
< 53.6°F).
CCH operation de-energizes: 1. Compressor discharge temperature T5 60.8°F. 2.
Compressor start running.
13.5 Reversing Valve Operation
Reversing valve energizes during heat mode and de-energizes in cool mode.
During a heat call on first time operation the unit will run about 1 minute in
cooling to build up pressure for reversing valve to change.
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
| 23
Installation Instructions
13.6 Protection Functions
Outdoor coil temperature protection (T3) i. If T3 > 143.6°F, compressor is de-
energized. ii. If T3 < 129.2°F, compressor is energized.
Ambient temperature protection (T4) i. If 23°F T4 < 125°F, unit can operate in
cooling. ii. If 4°F T4 < 86°F, unit can operate in heating. iii. If T4 < 4°F,
heat pump will provide 24V control to indoor unit energizing electric heat (if
installed).
See Product Specification for extended performance data.
Discharge Temperature (DT) protection (T5) i. If DT > 230°F during cooling
mode, the compressor will stop. ii. If DT < 212°F during cooling mode, the
compressor will restart. iii. If DT > 230°F during heating mode, the
compressor will stop. iv. If DT < 212°F during heating mode, the compressor
will restart.
High Pressure (HP) protection (mechanical open/close pressure switch) i. High
Pressure Switch opens at P > 580 PSIG, the compressor and outdoor fan stop.
ii. High Pressure Switch closes at P < 435 PSIG, the compressor and outdoor
fan restart.
Low Pressure (LP) protection i. If Low Pressure < 43.5 PSI for 5 minutes
during cooling mode, the compressor and outdoor fan will stop.The system will
attempt to run again after 6 minutes. ii. If condensing temp. Tc < outdoor
ambient temp. T4 during heating mode, the compressor and outdoor fan will
stop.
Module (inverter) protection (TF) i. If TF > 172°F, the compressor and outdoor
fan will stop. ii. If TF < 160°F, the compressor and outdoor fan will restart.
24 |
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
13.7 Fault Code Table
Outdoor Control Board Code Fault Description (Sensor)
C3
The coil sensor is seated fault in cooling (T3)
E4
Temperature sensor fault (T3, T4, T5, Th, T3L)
E5
High/low voltage protection
E6
DC fan motor fault
E7
Compressor discharge sensor is seated fault (T5)
E9
EEPROM
H0
Communication fault in main control chip
H5*
5 times (P2) protection in 100 minutes, system lockup
H8
Pressure transducer fault (PT)
P0
High module radiator temperature protection (TF)
P1
High pressure switch protection (HPS)
P2
Low pressure protection in cooling or heating (PT)
P3
Compressor over current protection
P4
High compressor discharge temperature protection (T5)
P5
Condensor coil temperature protection in cooling (T3)
P8
DC fan motor typhoon protection
PH
Low discharge superheat protection
F1
High pressure switch (HPS) fault
L0-L9
IPM module protection
System Protection Status Codes** Forced operation mode
L
Running indication under T3 limited condition
D
Running indication under T5 limited condition
P
Running indication under compressor ratio limited condition
F
Running indication under TF limited condition
C
Running indication under current limited condition
U
Running indication under low voltage limited condition
A
Running indication under return oil model
dF
Running indication under defrost model
Table 19 * Fault requires hard restart
** If the first digit shown on the control board LED is one of the following protection codes (followed by two numerical digits which show the current compressor frequency in Hz), the unit will continue to run but in a limited condition. The only exception is when the system is in defrost mode, which only displays “dF” (without any numerical digits following).
Indoor Unit Board LED Codes Number of flashes Always ON 1 2 3 4 5 6
Table 20
Description Normal Dehumidification mode active Reserved Anti-cold air function active Temperature sensor fault (T1) Temperature sensor fault (T2) Communication error
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
Installation Instructions | 25
Installation Instructions
13.8 Parameter Point Check Table
To display system parameters, press the “Check” button to index through the
series of parameters available. The first time you press the “Check” button,
it will display the sequence, and after 1 second it will display the value of
the parameter. If you press the “Check” button again, it will display the next
sequence. Refer to Figure 32 for check button location on the control board.
Check button
Normal Status, last two digits will display under the following conditions i.
Unit not operating (Standby Mode); “outdoor ambient temperature”. ii. Unit
operating; displays “compressor operating frequency”.
After 20 seconds on same parameter, the display will revert back to normal
status.
If a system protection is active, first digit will display “status code”.
SW1 is not used. See Figure 31.
Figure 31
No. 0
1
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29
Table 21
Point check content Outdoor unit capacity
Outdoor unit mode
Outdoor unit set compressor speed (Hz) T3 (outdoor coil temp.) (°F) T4
(outdoor ambient temp.) (°F) T5 (compressor discharge temp.) (°F) Th
(compressor suction temp.) (°F) T3L(Condenser outlet temp.) (°F) Tf (module
temp.) (°F ) Pe (evaporating pressure) (PSI) Pc (condensing pressure) (PSI)
Tes ( target of the evaporating temp.) (only use for cooling mode) (°F) Te
(evaporating temp.) (°F) Tcs target of the condensing temp. (only use for
heatling mode) (°F) Tc (condensing temp.) (°F) Target of the compressor
discharge superheat (only use for heating mode) (°F) Compressor discharge
superheat (°F) Openings of EEV Outdoor Fan speed Compressor current (A) Power
AC voltage Input (V) Compressor input dc voltage (V) Continuous running time
of the compressor (min) Last Fault Code Software version T1 (Return air temp)
(°F) T2 (Indoor coil temp) (°F) Indoor blower motor speed Ts (Estimated
thermostat set point) (°F) Remark”–”
Example H3
2
66
Remark
H3=Heat pump 3 ton
0 standby 2 cooling 3 heating
Low Suction Pressure High Head Pressure
see Table 19
Only valid for 3T Only valid for 3T Only valid for 3T Only valid for 3T
26 |
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
13.9 Control Board Overview
Outdoor Unit Control Board for 3 Ton Model
Installation Instructions
No. Function description
23 22 21 20 19 18 17 16 15 14 13
1. Compressor crankcase heater port 2. Reserve 3. Reversing valve port
4. Thermostat wire connections
12
5. Th sensor port
11
6. T3 T4 T3L sensor port
7. Pressure transducer port
10
8. T5 sensor port
9
9. Communication port (to indoor unit)
8
10. Electric expansive valve
24
7
11. Reserve
25
6
12. Reserve
13. High pressure switch port
26
5
14. SW2 FORCE BUTTON
15. SW3 CHECK BUTTON
4
16. Reserve
3
17. USB port
18. Reserve
19. SW5 Dip SWITCH: Defrost logic settings
20. SW4 Dip SWITCH: Control logic settings
21. LED
22. Reserve
23. ECM motor port
24. Compressor: W port
27
25. Compressor: V port
28
26. Compressor: U port
27. Power input
28. Power input
29 30
31 1 2
29. Non-replaceable Fuse 30. Ground port
31. Ground port
Figure 32
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
| 27
Installation Instructions Indoor Unit Control Board for 3 Ton Model
6 7 8 9 10
Figure 33
5
No. Function description
1. Thermostat wire connection terminal
2. Electric Heat Kit E port
3. Thermostat wire port (to ODU board)
4. Transformer port
5. Blower motor port
6. T1, T2 sensor port
4
7. LED
3
8. Communication port (To ODU board)
9. Reserve
2
10. 3 Amp Replaceable Fuse
1
28 |
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
Installation Instructions
13.10 Error Code Troubleshooting (ODU)
Error Code P1 P5 P3
Table 22
Description (Sensor) High pressure switch (HPS) protection Condenser coil temperature (T3) protection in cooling Compressor over current protection
P1 (High pressure switch (HPS) protection)
Diagnosis
Handling
Check whether the high pressure switch wires are seated normally
Yes
No Reseat the wires according to wiring diagram
Check whether high pressure No Replace high pressure switch switch is closed
Yes
Check whether indoor and No outdoor units are normal by filter and airflow
Yes
Exclude all fault reasons and restart
Cooling mode refers to P5
Figure 34
P5 (Condenser coil temperature (T3) protection in cooling)
Diagnosis
Handling
Check whether T3 is normal according toTable 34 (between
No
temperature and resistance)
Yes
Check whether outdoor unit motor is abnormal or whether Yes the outdoor
condenser coil is blocked
No
Replace the T3 sensor
Replace the fan or remove all the blockage
Check whether there is short Yes Do something to avoid air
circuit in air outlet and inlet side
return short circuit
No
Check whether the charge is
correct by subcooling
No
according to installation guide
in charge mode when cooling
Yes
Adjust refrigerant charge
Check whether there is normal throttle
Yes
No Adjust or repair the EEV throttle
Figure 35
P3 (Compressor over current protection)
Diagnosis
Handling
Check whether outdoor unit motor is abnormal and the Yes outdoor condenser
coil is blocked
No
Replace the fan or remove all the barriers
Check whether compressor No wiring is normal
Wire correctly according to the wiring diagram
Yes
Check whether compressor insulation resistance is greater
No
than 100K
Yes
Replace the compressor
Restart system and check whether the difference of high and low
No
pressure is more than 30 PSI after
compressor has run for 10 mins
Yes
Check whether the compressor current is more No than 15A for 2/3 ton when protected
Yes
Replace the compressor Replace the board
Replace the compressor
Figure 36
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
| 29
Installation Instructions
Error Code P0
Table 23
Description High module radiator temperature (TF) protection
P0 (High module radiator temperature (TF) protection)
Diagnosis
Handling
Check for dust or debris Yes blocking radiator
Clean all the dust and debris
No
Check if all screws are properly installed and if thermal paste is properly
applied
Yes
No Follow board replacement instruction for correct steps
Restart system and check whether the fan and motor
No
Replace the fan and motor
can operate normally
Yes
Operate system and check No whether there`s the same fault
Yes
Operate normally
Figure 37
Error Code P2 H5 P4
Table 24
Description Low pressure (PT) Protection in cooling and heating System lockup, 5 times (P2) protection in 100 minutes High compressor discharge temperature(T5) protection
P4 (High compressor discharge temperature (T5) protection)
Diagnosis
Handling
Check whether the T5 is normal according to Table 35 (between
No
temperature and resistance)
Replace the T5 sensor
Yes
Check whether outdoor and indoor unit motor is abnormal Yes or whether coils
(outdoor and indoor) are blocked
No
Check whether the charge is
correct by subcooling
No
according to design subcooling
force mode when in cooling
Yes
Check whether the EEV is
normal for throttle
No
(wire seated coil)
Yes
Replace the fan or remove all the barriers
Adjust the charge
Re-power and check again,if the same, replace the EEV.
Check whether the compressor is normal (abnormal noise,
No
abnormal vibration)
Yes
Replace the compressor
Figure 39
P2 (Low pressure (PT) Protection in cooling) H5 (System lockup, 5 times (P2) protection in 100 minutes)
Diagnosis
Handling
Do superheat and subcooling meet required values? (Refer No to Section 12
system charge adjustment)
Yes
Is the blower fan motor working properly? Is there any No blockage on filter?
Are the EEV and outdoor fan motor working properly?
Yes
Is the pressure transducer working properly? Compare No the data between
pressure measurement and No 9 (cooling) or No 10 (heating) values (by pressing
the check button).
Yes
Adjust charge
Correct these issues and restart the system
Replace the pressure transducer
Figure 38
30 |
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
Error Code E4 H8 F1
Table 25
Description Temperature sensor fault (T3, T4, T5,Th, T3L) Pressure transducer (PT) fault High pressure switch (HPS) fault
E4 (Temperature sensor fault (T3, T4, T5, Th, T3L)
Diagnosis
Handling
Check whether sensor T3/T4/T5/Th/T3L are seated and normal (T4 for Heat Pump
only)
Yes
No Reseat the sensor according to wiring diagram
Unplug the sensor, check
whether the resistance of
No
T3/T4/Th/T3L is in the range
of Table 34
Yes
Replace the fault T3/T4 Th/T3L sensor
Unplug the sensor, Check
No
whether the resistance of T5/Tf
Replace the fault T5/Tf sensor
is in the range of Table 35
Yes
Check whether the display the shows the same error code
No
when re-powered on
Yes
Keep running
Figure 40
H8 (Pressure transducer (PT) fault)
Diagnosis
Handling
Check whether pressure
No
transducer (PT) wiring are
seated and normal
Yes
Is the pressure transducer No working properly? Compare the data between
pressure measurement and No 9 (cooling) or No 10 (heating) check point value
(by pressing check button)
Yes
Wire according to the diagram correctly
Replace the pressure transducer
Check whether there is the No same fault
Yes
Keep running
Figure 41
Installation Instructions
F1 (High pressure switch (HPS) fault)
Diagnosis
Handling
Check whether high pressure No switch (HPS) wiring is seated and normal
Yes
Check whether the
No
resistance of HPS is close to
0K
Yes
Reseat wiring according to thewiring diagram
Replace high pressure switch
Check whether there is the No same fault
Yes
Keep running
Figure 42
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
| 31
Installation Instructions
Error Code C3 E7
Table 26
Description Condenser coil sensor (T3) is seated fault in cooling Compressor discharge sensor (T5) is seated fault
C3 Condenser coil sensor (T3) is seated fault in cooling)
Diagnosis
Handling
Check whether condenser coil sensor (T3) is seated
No
to the condenser coil
Yes
Reseat the sensor to condenser coil
Check whether the T3/T4
sensors are connected
No
according to wiring diagram
Wire according to the wiring diagram correctly
Yes
Check whether the
No
resistance of T3/T4 is in
the range of Table 34
Yes
Check whether there are other heat sources around No T3/T4
Yes
Replace the fault T3/T4 sensor
Remove all the other heat sources
Check whether there is the No same fault
Yes
Keep running
Figure 43
E7 Compressor discharge sensor (T5) is seated fault)
Diagnosis
Handling
Check whether compressor
discharge sensor (T5) is
No
seated to the compressor
discharge line
Yes
Reseat the sensor to discharge tube
Check whether the sensor of T3/T5 are connected accord-
No
ing to wiring diagram
Yes
Wire according to the wiring diagram correctly
Check whether the resistance No
of T3/T5 is in the range of
Replace the fault T3/T5 sensor
Table 34 and Table 35
Yes
Check whether there are other No heat sources around T3/T5
Yes
Remove all the other heat sources
Check whether there is the No same fault
Keep running
Figure 44
Error Code E6
Table 27
Description DC fan motor fault
If the E6 error code appears occasionally, no action is necessary. The system will restart automatically after 6 minutes.
32 |
E6 DC fan motor fault)
Diagnosis
Handling
Check whether DC motor wiring is reliably connected No according to the wiring
diagram
Yes
Reseat the wiring according to wiring diagram
Check whether outdoor coil air return is blocked
No Remove all the barriers
Yes
Check whether there is No
15V DC between the test
Replace the control board
point P & N
Yes
Check whether there is No the same fault
Keep running
Yes
Figure 45
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
Error Code E9 H0 E5
Table 28
Description EEPROM fault Communication fault in main control chip High/low voltage protection
If error codes E9/H0/E5 appear occasionally and after the system restarts and runs normally after the power supply is re-established, no action is necessary. Otherwise the system must be checked.
E9 (EEPROM fault) Diagnosis
Handling
Check whether the wiring is No Reseat the wiring according
connected normally
to wiring diagram
Yes
Restart to power on and check whether it is normal
No Reseat the wiring according to wiring diagram
Yes
No action is necessary. This fault may be caused by strong interference from
the electric grid. The system will recover when the electric supply
stabilizes.
The fault is still present
Replace the control board
Figure 46
Installation Instructions
E5 (High/low voltage protection)
Diagnosis
Handling
Check whether the power supply voltage is between
No
172-270V
Yes
Check whether the power wires are
connected firmly and whether the power supply wires diameter meets
No
the requirements from the
manufacturer
Yes
Make sure the power supply is within correct range
Replace the power supply wires or connect the power supply wires well
Restart to the power supply and check whether the
No
compressor operates normally
Replace the control board
Yes
Gauge and check whether there is 380V DC between the No terminals P & N when
the compressor is running
Yes
Replace the control board
Check whether there is high voltage equipment nearby
No
Yes
Separate high-power equipment and power
supply
Figure 48
H0 (Communication fault in main control chip)
Diagnosis
Handling
Check whether the wiring is No Reseat the wiring according
connected normally
to wiring diagram
Yes
Restart to power on and check whether it is normal
No Replace the control board
Yes
No action is necessary. This fault may
be caused by strong interference from No
the electric grid. The system will recover when the electric supply
stabilizes.
Replace the control board
Figure 47
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
| 33
Installation Instructions
Error Code L0-L9
Table 29
Description IPM module protection
When error codes L0-L9 appears occasionally, no action is necessary. The system will restart automatically after 6 minutes. Please follow the steps below if L0-L9 appears frequently.
Error Code AtL
Table 30
Description Ambient Temperature Limited
When the ambient temperature returns to within the operating range, the system will recover automatically.
L0-L9 ( IPM module protection)
Diagnosis
Handling
Check whether the power supply is stable
No
Correct the power supply
Yes
Check for blockages in refrigerant piping.
Yes
Clean the blockage
No
Check to see if there are any abnormal noises from the
Yes
compressor
Replace the compressor
No
Power off and wait at least 3 minutes before powering on. Yes
Check if the unit can run at
least 1 hour
Check the refrigerant charge and adjust
No L0-L9 issue happen again
No need to replace board
Check the winding resistance: 1. The resistance of two
No
windings (U, V, W) 2
2. The resistance between
compressor winding and
ground 10M
Yes
Replace control board
Replace compressor
Power on and check if the No problem has been resolved.
Yes
Run unit normally
Replace the unit
Figure 49
AtL (Ambient Temperature Limited)
Diagnosis
Handling
Check whether the ambient temperature is beyond the range Yes cooling:
23°F-125°F heating: -4°F-86°F
No
Normal
Check whether sensor T4 is seated normally (T4 for Heat Pump only)
Yes
No Reseat the sensor according to the wiring diagram
Unplug the sensor, and check whether the resistance of T4 is No within the
operational range (Refer to Table 34)
Yes
Replace the faulty T3/T4 sensor
No action is necessary. restart the system.
Figure 50
Error Code /
Table 31
Description No display on control board
No display on ODU control board
Diagnosis
Handling
Restart the system and check if Yes the LED display is working
No
Check if the high voltage No power supply is stable
Yes
Pull out the ODU motor
Yes
connection, check if there is
any display
No
Pull out the pressure
Yes
transducer connection,
check if there is any display
No
Replace ODU board
Working properly
Correct power supply
Replace ODU motor Replace pressure transducer
Figure 51
34 |
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
Error Code Troubleshooting (IDU)
Number of flashes 4 5
Table 32
Description (Sensor) Temperature sensor fault (T1) Temperature sensor fault (T2)
4/5 Flashes (Temperature sensor fault)
Diagnosis
Handling
Check whether T1/T2 sensor No is seated normally
Yes
Unplug the sensor and measure the resistance to
Yes
ensure it’s neither 0 nor
No
Restart the unit to check if Yes the problem is resolved
No
Replace indoor control board
Reseat sensors Replace sensors
Finish
Figure 52
Installation Instructions
Number of flashes 6
Table 33
Description (Sensor) Communication error
6 Flashes (Communication error)
Diagnosis
Handling
Check if the communication wire is connected properly
No
Correct the wire connections
(Refer to Figure 32 and 33)
Yes
Check if ODU control board No LED display is working
Yes
Check if there is 230V power input, if yes, replace ODU board
Restart the system
Figure 53
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
| 35
Installation Instructions
13.12 Temperature and Resistance Relationship Tables (for Sensors)
TEMP F -5 0 5 10 15 20 25 30 40 45 50 55 60 65 70 75 80 85
TEMP C -20.6 -17.8 -15.0 -12.2 -9.4 -6.7 -3.9 -1.1 4.4 7.2 10.0 12.8 15.6 18.3 21.1 23.9 26.7 29.4
RESISTANCE k 107.732 93.535 79.521 67.795 57.948 49.652 42.645 36.710 27.386 23.732 20.610 17.939 15.648 13.681 11.987 10.527 9.265 8.172
Table 34 for T3, T4, Th, T3L, T1, T2
VOLTS DC 4.65 4.60 4.54 4.47 4.39 4.30 4.21 4.10 3.86 3.73 3.59 3.45 3.30 3.15 2.99 2.83 2.67 2.52
TEMP F 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 165 170
TEMP C 32.2 35.0 37.8 40.6 43.3 46.1 48.9 51.7 54.4 57.2 60.0 62.8 65.6 68.3 71.1 73.9 76.7
RESISTANCE k 7.225 6.401 5.683 5.057 4.509 4.028 3.606 3.233 2.902 2.610 2.350 2.119 1.914 1.731 1.574 1.416 1.276
VOLTS DC 2.36 2.21 2.07 1.93 1.79 1.67 1.55 1.43 1.32 1.22 1.13 1.04 0.96 0.88 0.82 0.75 0.68
36 |
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
13.13 Temperature and Resistance Relationship Tables (for T5)
TEMP F -5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105
TEMP C -20.6 -17.8 -15.0 -12.2 -9.4 -6.7 -3.9 -1.1 1.7 4.4 7.2 10.0 12.8 15.6 18.3 21.1 23.9 26.7 29.4 32.2 35.0 37.8 40.6
110
43.3
115
46.1
120
48.9
125
51.7
130
54.4
135
57.2
Table 35 for T5
RESISTANCE k 600.134 505.551 427.463 362.739 308.891 265.398 227.481 195.601 168.707 146.695 127.258 110.707 96.572 84.465 74.411 65.408 57.634 50.904 45.258 40.152 35.699 31.807 28.398 25.506 22.861 20.529 18.47 16.708 15.085
VOLTS DC 4.93 4.92 4.91 4.89 4.87 4.85 4.83 4.80 4.77 4.74 4.70 4.66 4.61 4.56 4.51 4.45 4.39 4.32 4.24 4.16 4.08 3.99 3.89 3.80 3.70 3.59 3.48 3.37 3.26
TEMP F 140 145 150 155 160 165 170 175 180 185 190 195 200 205 210 215 220 225 230 235 240 245 250 255 260 265 270 275 280
TEMP C 60.0 62.8 65.6 68.3 71.1 73.9 76.7 79.4 82.2 85.0 87.8 90.6 93.3 96.1 98.9 101.7 104.4 107.2 110 112.8 115.6 118.3 121.1 123.9 126.7 129.4 132.2 135.0 137.8
Installation Instructions
RESISTANCE k 13.643 12.359 11.214 10.227 9.308 8.485 7.746 7.105 6.504 5.963 5.474 5.032 4.645 4.28 3.949 3.648 3.383 3.133 2.904 2.694 2.503 2.334 2.172 2.024 1.888 1.767 1.651 1.544 1.446
VOLTS DC 3.14 3.03 2.91 2.80 2.68 2.56 2.45 2.34 2.23 2.13 2.02 1.92 1.83 1.73 1.64 1.56 1.48 1.40 1.32 1.25 1.18 1.12 1.06 1.00 0.95 0.90 0.85 0.80 0.76
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
| 37
Installation Instructions
Wiring Diagram
Figure 54
1 2 Reserved 3 4 5 6
SW6-4 ON*
SW6-4 OFF
- H MH M L H MH M L
38 |
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
Maintenance
For continuing high performance and to minimize possible equipment failure,
periodic maintenance must be performed on this equipment.
14.1 Cleaning Precautions
WARNING: Any unit repairs must be performed by qualified service
personnel only.
WARNING: ELECTRICAL SHOCK Always turn off your heat pump and disconnect its
power
supply before cleaning or maintenance.
CAUTION: When removing filter, do not touch metal parts in the unit.
The sharp metal edges can cut you.
Installation Instructions
14.2 Regular Maintenance
Your heat pump must be inspected regularly by a qualified service technician.
- Inspect the air filter every ninety days or as often as needed. If blocked
or obstructed, clean or replace at once.
Your annual system inspection must include: 2. Inspection and/or cleaning of the blower wheel housing and motor.
3. Inspection and cleaning of indoor and outdoor coils as required.
4. Inspection and/or cleaning of the indoor coil drain pan and drain lines, as well as auxiliary drain pan and lines.
5. Check all electrical wiring and connections. Correct as needed, referring to the wiring diagram. (Refer to Figure 54)
Online Help Resources Alternatively, please visit our Service & Support webpage to find FAQs, videos, service bulletins, and more; www.boschheatingcooling.com/service or use your cellphone to scan the code below.
NOTICE: Do not use chemicals or chemically treated cloths to clean
the unit .
Do not use benzene, paint thinner, polishing powder or other solvents to clean
the unit.
Do not operate the system without a filter in place
Bosch 18 SEER2 Series Inverter Ducted Packaged Heat Pump – BTC 761703103 A (11.2022)
| 39
United States and Canada Bosch Thermotechnology Corp. 65 Grove St. Watertown,
MA 02472
Tel: 866-642-3198 Fax:
954-776-5529 www.bosch-
thermotechnology.us
BTC 761703103 A | 11.2022
Bosch Thermotechnology Corp. reserves the right to make changes without notice
due to continuing engineering and technological advances.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>