Assurance Emergency Lighting ALCR-D10L Emergency Automatic Load Control Relay Instruction Manual

June 9, 2024
Assurance Emergency Lighting

Assurance Emergency Lighting logo

Assurance Emergency Lighting ALCR-D10L Emergency Automatic Load Control

Relay

Assurance Emergency Lighting ALCR-D10L Emergency Automatic Load Control
Relay Instruction Manual-product

Product Information

The Assurance Emergency Lighting Control Device is designed to be used with grounded, UL Listed, indoor fixtures for emergency lighting purposes. There are two models available: ALCR-D20L and ALCR-D10L with a maximum current of 20A and 10A respectively. The device is not suitable for outdoor use, heated air outlets or hazardous locations. It is compatible with lighting loads wired on a 20A or 10A circuit and can be used in standard switching and 0-10 volt dimming applications. The maximum current of the dimming circuit must not exceed 110 mA. The device should be installed in accordance with the National Electrical Code and local regulations.

Product Usage Instructions

  1. Before installing, make sure that the AC power is off for both normal and emergency circuits.

  2. Mounting: The device can be mounted using the following steps:

    • For ALCR-D20L & ALCR-D10L: Use
      Illustration 1 to mount the device on the bottom.

    • For ALCR-D20L-C & ALCR-D10L-C: Use
      Illustration 2 to mount the device on the bottom and single flex. Remove junction box lid and drill holes for mounting studs and lead wire feed. Re- attach cover plate after wiring. An additional single gang junction box for the test switch/normal power indicator light will need to be provided by others. See mounting template on.

  3. Wiring: Refer to the wiring diagram on the back page and install in accordance with the National Electrical Code and local regulations. For additional wiring diagrams, consult customer service.

  4. Installing the AC Indicator: Follow the instructions on Page 2 to install the AC indicator.

  5. Wiring the AC Input: Refer to the wiring diagram on Page 4 for the proper wiring configurations. For wiring diagrams not shown, consult customer service.

  6. Operation: A device is a maintenance-free unit; however, periodic inspection and testing are required. Insure that the AC Indicator light is illuminated monthly. Written records of testing shall be kept by the owner for inspection by the authority having jurisdiction.

IMPORTANT SAFEGUARDS

When using electrical equipment, basic safety precautions should always be followed, including the following:

READ AND FOLLOW ALL SAFETY INSTRUCTIONS
  1. CAUTION This fixture provides more than one power supply output source. To reduce the risk of electrical shock, disconnect both normal and emergency sources by turning off the AC branch circuits.

  2. CAUTION This is a sealed unit. Replace the entire unit when necessary.

  3. DO NOT USE OUTDOORS.The ALCR-D20(10)L & ALCR-D20(10)L-C are used with grounded, UL Listed, Indoor fixtures. Not for use in heated air outlets or hazardous locations.

  4. Do not mount near gas or electric heaters.

  5. The ALCR-D20L (-C) & ALCR-D10L (-C) should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel.

  6. The ALCR-D20L (-C) is compatible with lighting loads wired on a 20A (max.) circuit.
    The ALCR-D10L (-C) is compatible with lighting loads wired on a 10A (max.) circuit.

  7. The ALCR-D20L (-C) & ALCR-D10 (-C) are for use in standard switching and 0-10 volt dimming applications, and are NOT designed for use with 3-wire dimming or step dimming ballasts. The maximum current of the
    dimming circuit must not exceed 110 mA.

  8. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.

  9. Do not use this equipment for other than intended use.

  10. Install in accordance with the National Electrical Code and local regulations.

  11. Installation and servicing should be performed by qualified personnel.

  12. Lighting fixture manufacturers, electricians, and end-users need to ensure product system compatibility before final installation.

SAVE THESE INSTRUCTIONS

INSTALLATION INSTRUCTIONS

CAUTION: Before installing, make certain the AC power is off for both normal and emergency circuits.

  1. MOUNTING THE ALCR-D20L & ALCR-D10L ( Illustration 1)
    Integral (No Flex) – Remove the driver channel cover. Mount in the ballast/driver channel at least ½″ away from the AC driver(s).

  2. MOUNTING THE ALCR-D20L-C & ALCR-D10L-C ( Illustration 2)
    BottomMounting and Single Flex – Remove the Junction Box lid and drill holes for mounting studs and lead wire feed Re-attach the cover plate after wiring. An additional single gang junction box for the test switch/normal power indicator light will need to be provided by other. See the mounting template on Page 3.Assurance Emergency Lighting ALCR-D10L Emergency Automatic Load
Control Relay Instruction Manual-fig-2

WIRING
Refer to the wiring diagram on the back page. Install in accordance with the National Electrical Code- and local regulations. For additional wiring diagrams consult Customer Service.

INSTALLING THE AC INDICATOR

Mount the supplied 4-wire illuminated test switch in a location that is visible and accessible by maintenance personnel. The switch mounts through a 1/2″ hole which may need to be added to the luminaire or could come pre- punched by the luminaire supplier. For the single conduit (-C) models, add an additional single junction box for the test switch indicator light wall plate. Wire the test switch per wiring diagrams provided on these instructions. If wired correctly, the test switch indicator light should be “ON” when normal AC power is supplied to the fixture. Pushing the test switch in normal power condition will turn on the emergency luminaire(s) whether the wall switch is on or off.

WIRING THE AC INPUT
Refer to wiring diagram on Page 4 for the proper wiring configurations.For wiring diagrams not shown, consult Customer Service.

OPERATION

Normal Mode – AC power is present.The AC driver or ballast operates the lamp(s) as intended. The closed dimming relay allows operation of the luminaire(s) at the desired setting of the connected 0-10 Vdc dimming signal (if provided).
Emergency Mode – Failure of normal AC (utility) power.The ALCR device senses the AC power failure and automatically bypasses the wall switch with an internal relay controlling the AC Driver/Ballast, ensuring the flow of emergency power to the controlled emergency lighting load regardless of the wall switch’s “on” / “off” state. The ALCR Device dimming relay contacts open and forces the emergency lighting load to operate at full lumen output regardless of the dimmer setting. This light level will continue for the duration of the provided emergency or auxiliary power or until normal power is restored.

TESTING & MAINTENANCE

The ACLR Device is a maintenance-free unit, however, periodic inspection and testing is required. NFPA 101, Life Safety Code, outlines the following schedule: Insure that the AC Indicator light is illuminated monthly “Written records of testing shall be kept by the owner for inspection by the authority having jurisdiction.”

SERVICINGSHOULDBEPERFORMED BY QUALIFIED PERSONNEL.
ALCR-D20L-C & ALCR-D10L-C Bottom Mount with studsAssurance Emergency
Lighting ALCR-D10L Emergency Automatic Load Control Relay Instruction Manual-
fig-3

TYPICAL WIRING DIAGRAMS
For wiring diagrams of ballast/drivers not shown, consult our Customer Service.
0-10 vdc Dimming Wiring Diagram (Typical)Assurance Emergency Lighting ALCR-
D10L Emergency Automatic Load Control Relay Instruction Manual-
fig-4

Assurance Emergency Lighting, a division of Assurance Lighting LLC, 357 Cumberland Street, Memphis, TN 38112 877-774-4775 AssuranceLighting.com 01112021

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Assurance Emergency Lighting User Manuals

Related Manuals