Lindab IR24-P Passive Infrared Occupancy Sensor Instructions

June 10, 2024
Lindab

IR24-P Passive Infrared Occupancy Sensor
Instructions

IR24-P Passive Infrared Occupancy Sensor

IR24-P **** Read this instruction before installation and wiring of the product.
100º, 15×15 m at 25ºC Plan view

INSTRUCTION

Occupancy sensor
IR24-P is a passive infrared occupancy sensor suitable for use in “on demand” control of ventilation systems or in intrusion alarm circuits.
Installation
For best coverage IR24-P should be placed 6…8 feet above floor level in a location with an unhindered view of the area to be monitored. Avoid exposure to direct sunlight or
other powerful head sources. For corner mounting the two corner mounting holes n the casting may be used. For other wall mounting or for ceiling mounting use the supplied mounting bracket. Fasten the bracket according to the appropriate figure. Fasten the unit to the bracket and lead the cable through the access tube in the bracket and through the cable hole in the housing. Align the unit and llock in position by tightening the locking screw on the bracket. Replace the front cover.
Wiring
Supply voltage:…………………….. 24 V AC/DC +2 V
Power consumption:…………………. 5mA @ 24 V AC
Relay:………………… Form C, 0.2 A, 30 V DC
Functions
IR24-P is equipped with adjustable ON- and OFF-delays. IR24-P is normally in standby mode wtih the output relay unactivated. On detecting a movement the ON-delay is activated. The relayremains unactivated. When the ON-delay time expires the IR24-P enters a 1-minute waiting period. If no movement is detected during the waiting period the IR24-P revers to standby mode. If however a movement is detected during the waiting period, the output relay will be activated and the OFF-delay initiated. Any detection during of OFF- delay will restart the delay time. If for example the OFFdelay will restart the delay timer. If for example the OFF-delay has been set to 5 minutes the relay will remain activated until 5 minuts after the last detection. Thereafter the IR24-P reverts to standby mode. Setting of the delay times is done using two jumpers on the PCboard. Delay times as in table below.

| A| B| C| D| E| F
---|---|---|---|---|---|---
ON| 0 sec.| 10 sec.| 30 sec.| 1 min.| 5 min.| 10 min
OFF| 10 sec.| 1 min| 5 min.| 10 min.| 20 min| 30 min

Function test

On completing the installation a function test should be run. Connect supply voltage and wait for 25 seconds for warm up. The green LED will blink during warm up. Move about over the area to be monitored. the red LED will indicate detection. If detection seems unsatisfactory the unit may need realingment.

EMC emissions & immunity standards

This product conforms with the requirements of European EMC standarards CENELEC EN 50081-1 and EN 50082-1 and carries the CE mark.Lindab IR24-P
Passive Infrared Occupancy Sensor - requirements Lindab reserves the right to make changes without prior notice
2018-06-14

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals