URBANA LUXURY FIREPLACES U50T Urbana Tall Series Urban Fireplaces Installation Guide
- June 10, 2024
- URBANA LUXURY FIREPLACES
Table of Contents
- URBANA LUXURY FIREPLACES U50T Urbana Tall Series Urban Fireplaces
- Product Information
- Chase Dimensions and Clearances
- Product Usage Instructions
- U50T / U70T DIMENSIONS
- CHASE DIMENSIONS & CLEARANCES
- MINIMUM CHASE FRAMING
- HDTV CLEARANCES
- FLAT WALL MOUNTED
- SHELF / RECESS MOUNTED
- HORIZONTAL TERMINATION CLEARANCES
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
URBANA LUXURY FIREPLACES U50T Urbana Tall Series Urban Fireplaces
Product Information
The U50T and U70T are fireplaces that require installation with both an intake at the bottom of the chase and a heat release at the top of the chase. The physical dimensions of the U50T and U70T differ only in width. They have minimum dimensions, clearances, and areas that must be followed as outlined in the installation guide and owner’s manual to avoid any fire hazards.
U50T / U70T Dimensions
The U70/U70T dimensions are 71 3/4 [1822mm] x 70 3/4 [1797mm], while the U50/U50T dimensions are 51 3/4 [1314mm] x 50 3/4 [1289mm].
Chase Dimensions and Clearances
The chase must be framed beyond minimum framing for taller ceilings or overhangs, but the top of the chase e must be enclosedand cannot be open to joists or rafters above. The minimum clearance to a sidewall constructed or finished with combustible material is 7 inches [178mm]. The minimum clearance to a sprinkler head from the chase heat release in any direction is 5 feet [1.5m].
Table 1 – Dimensions
Letter | Dimension |
---|---|
A | 93 1/8 (2365 mm) |
B | 21 (533 mm) |
C (U50T) | 50 3/4 (1289 mm) |
C (U70T) | 70 3/4 (1797 mm) |
D | 9 15/16 (253 mm) |
E | Minimum 1 1/2 (38 mm) |
F (U50T) | Minimum 170 in2 (1097 cm2) |
F (U70T) | Minimum 210 in2 (1355 cm2) |
G (U50T) | Minimum 135 in2 (871 cm2) |
G (U70T) | Minimum 165 in2 (1064 cm2) |
H | 24 (610mm) |
I | 0 – 1 1/2 (0-38 mm) Maximum |
J | Minimum 2 (51 mm) |
Product Usage Instructions
Installation Guide
Refer to the owner’s manual for specific installation requirements and additional product instructions. The U50T and U70T fireplaces must be installed with both an intake at the bottom of the chase and a heat release at the top of the chase. A variety of installation styles are permitted as shown in the illustrations in the installation guide.
Top Release / Open Chase
The U50T and U70T fireplaces must be installed with both an intake at the bottom of the chase and a heat release at the top of the chase. A variety of installation styles are permitted as shown in the illustrations in the installation guide. The minimum dimensions, clearances, and areas outlined within this guide MUST be followed along with those stated in the owner’s manual.
Clearances | Framing | Venting
The U50T and U70T fireplaces must be installed with both an intake at the bottom of the chase and a heat release at the top of the chase. A variety of installation styles are permitted as shown in the illustrations in the installation guide. The minimum dimensions, clearances, and areas outlined within this guide MUST be followed along with those stated in the owner’s manual.
Alcove / Sidewall Clearance
The minimum clearance to a sidewall constructed or finished with combustible material is 7 inches [178mm]. Note – Side wall clearance not applicable for closed off side if using corner kit(s).
Sprinkler Clearances
The minimum clearance to a sprinkler head from the chase heat release in any direction is 5 feet [1.5m].
Minimum Chase Framing
All chase framing may be wood 2×4 construction or the like.
Combustible material is permitted for any area of the chase and no steel studs
are required. Chase may be framed beyond the minimum framing for taller
ceilings, overhangs, etc. Note – Top of chase must be enclosed and cannot be
open to joists or rafters above. Minimum ceiling height is 95 1/8 inches
[241cm].
U50T / U70T DIMENSIONS
Note – The U50T and U70T physical dimensions only differ in width
TOP RELEASE / OPEN CHASE
- Top only heat release with front & sides intake
FRONT & SIDES W/ FALSE CEILING
CHASE DIMENSIONS & CLEARANCES
The U50T and U70T fireplaces must be installed with both an intake at the bottom of the chase and a heat release at the top of the chase. A variety of installation styles are permitted as shown in the following illustrations. Refer to Table 1 for the required dimensions corresponding to the letters in the illustrations.
WARNING RISK OF FIRE HAZARD – The minimum dimensions, clearances and areas outlined within this guide MUST be followed along with those stated in the Owner’s Manual.
TABLE 1: LETTER DIMENSION
- A U50T & U70T 93 1/8” (2365 mm)
- B 21” (533 mm)
- C (U50T) 50 3/4” (1289 mm)
- C (U70T) 70 3/4” (1797 mm)
- D 9 15/16” (253 mm)
- E Minimum 1 1/2” (38 mm)
- F (U50T) Minimum 170 in2 (1097 cm2)
- F (U70T) Minimum 210 in2 (1355 cm2)
- G (U50T) Minimum 135 in2 (871 cm2)
- G (U70T) Minimum 165 in2 (1064 cm2)
- H 24” (610mm)
- I 0 – 1 1/2” (0-38 mm) Maximum
- J Minimum 2” (51 mm)
Heat release and intake on front & sides, chase false ceiling
FRONT ONLY
Heat release and intake on the front of the chase only.
SIDES ONLY
Heat release and intake on the sides of the chase only.
Note – Installations with only 1 side of the chase utilized for either
intake or heat release are not permitted.
ALCOVE / SIDEWALL CLEARANCE
Minimum clearance to a sidewall constructed or finished with combustible
material.
Note – Side wall clearance not applicable for closed off side if using
corner kit(s).
SPRINKLER CLEARANCES
Minimum clearance to a sprinkler head from the chase heat release in any
direction.
IMPORTANT NOTE: Framing above the fireplace CANNOT BE CONSTRUCTED prior to fireplace installation, the fireplace and its required shielding WILL NOT FIT!
MINIMUM CHASE FRAMING
All chase framing may be wood 2×4 construction or the like. Combustible
material is permitted for any area of the chase and no steel studs are
required. Chase may be framed beyond minimum framing for taller ceilings,
overhangs etc.
Note – Top of chase must be enclosed, cannot be open to joists or rafters
above.
Note – The fireplace is not load bearing and the chase must be
constructed to fully support finishing material.
MINIMUM THIMBLE HEIGHT
As measured from the bottom of the fireplace to the center line of the vent.
The fireplace uses 5” x 8” co-axial rigid or flex venting.
Note – additional adaptors (50-3789) required for flex venting
MINIMUM CHASE ELBOW CLEARANCE
This clearance only applies to an elbow that is located within the chase. Once
outside of the chase standard venting clearances apply.
POWER AND GAS
The incoming gas and power connections are located on the left and right on
the back of the fireplace as shown. The incoming power junction box is located
underneath the left side louver and is removable to aid with wiring.
EXTENDED HEARTH / PLINTH
An extended hearth or plinth may be constructed around the base of the
fireplace up to the bottom tiling edge. Combustible material is permitted for
construction and finishing of the plinth. Alternatively the optional 50-3824
Steel Framing Base Kit can also be used . The finished depth of the plinth
cannot exceed 12” [305 mm] and minimum intake dimensions must be maintained.
If raising the unit is desired a Flush Framing Base Kit (U50 = 50-4008, U70 =
50-4031) may be used to achieve a rise of 6”-11” off the floor.
Note: 50-3824 & 50-4002/50-4031 cannot be used together
OVERHANG / MANTLE CLEARANCES
An overhanging chase or mantle may be constructed above the fireplace
comprised of combustible framing and finishing material. The maximum finished
depth of an overhanging chase or mantle cannot exceed 12” [305 mm]. There is
no minimum height restriction and the finished surface can be flush with the
top tiling edge.
HDTV CLEARANCES
A TV may installed above the fireplace either on a flat wall or within a shelf
or recess as shown below. When flat wall mounting a TV, the minimum permitted
height may need to be increased to prevent the mounting screws from
penetrating the fireplace cabinet.
It is the responsibility of the home owner to confirm that the TV is within
its maximum allowable operating temperature range once installed. Sherwood
Industries is not liable for any TV malfunctions or adverse effects that may
be incurred.
FLAT WALL MOUNTED
SHELF / RECESS MOUNTED
MINIMUM VENTING
The fireplace utilizes 5” x 8” rigid co-axial venting. Alternatively 5” x 8”
flex venting may be used when using additional vent adaptors (50-3789). Refer
to the Owner’s Manual for more detailed venting and restriction information.
HORIZONTAL TERMINATION CLEARANCES
The clearances shown in the illustration must be followed when horizontally terminating the fireplace. Additionally, a termination guard must be used when the termination is installed in an area where it could be contacted. Only high wind terminations are permitted for installation.
Note – Termination clearances not applicable for power vent installations. See power vent manual.
1 Soffit measured from top of the termination
2 Sidewall measured from side of the termination
Manufactured by Sherwood Industries Ltd. ▪ Victoria, BC, Canada
Printed in Canada.