Altronix ACMCBJ Series Access Power Controllers with Power Supplies Installation Guide

June 4, 2024
Altronix

ACMCBJ Series Access Power Controllers with Power Supplies

ACMCBJ Series
Access Power Controllers with Power Supplies

Models Include:
AL400ULACMCBJ
– 12VDC @ 4A or 24VDC @ 3A. – PTC Protected Outputs
AL600ULACMCBJ
– 12VDC or 24VDC @ 6A. – PTC Protected Outputs

AL1012ULACMCBJ
– 12VDC @ 10A. – PTC Protected Outputs
AL1024ULACMCBJ
– 24VDC @ 10A. – PTC Protected Outputs

Installation Guide

Rev. 052819

More than just power.TM

Installing Company: ___ Service Rep. Name:


Address: _____ Phone #:


Overview:
Altronix ACMCBJ Series units distribute and switch power to access control systems and accessories. They convert a 115VAC 60Hz input into eight (8) independently controlled 12VDC or 24VDC PTC protected auto-resettable outputs. Outputs are activated by an open collector sink or normally open (NO) dry trigger input from an Access Control System, Card Reader, Keypad, Push Button, PIR, etc. Units will route power to a variety of access control hardware devices including: Mag Locks, Electric Strikes, Magnetic Door Holders, etc. Outputs will operate in both Fail-Safe and/or Fail-Secure modes. The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire alarm disconnect feature is individually selectable for any or all of the eight (8) outputs.
ACMCBJ Series Configuration Reference Chart:

115VAC 60Hz Input (current draw) Power Supply Board Input Fuse Rating Power Supply Board Battery Fuse Rating Maximum Battery Charge Current 12VDC Total Output Current 24VDC Total Output Current Class 2 Rated Power-Limited Outputs Individual Output Rating

Altronix Model Number AL400ULACMCBJ
AL600ULACMCBJ
AL1012ULACMCBJ
AL1024ULACMCBJ
Altronix Model Number AL400ULACMCBJ AL600ULACMCBJ AL1012ULACMCBJ AL1024ULACMCBJ

Agency Listings

UL Listings and
File Numbers

3.5A

5A/ 250V

15A/ 32V

0.7A

4A

3A

8 2.5A

Altronix Corp. 140 58th St. Brooklyn, NY

UL File # BP6714 UL 294*

3.5A

5A/ 250V

­

0.7A 6A

6A

8 2.5A

NYC Dept. of Buildings

California State Fire Marshal

UL Listed for Access Control

System Units.

2.6A

5A/ 250V

15A/ 32V

0.7A

10A

­

8 2.5A

4.2A

5A/ 250V

15A/ 32V

3.6A

­

10A

8

LISTED
2.5A

“Signal Equipment” Evaluated to CSA Standard C22.2 No.205-M1983

  • ANSI/UL 294 7th Ed. Access Control Performance Levels

Destructive Attack

Endurance Test

Line Security

Stand-by Power

I

IV

I

I

I

IV

I

I

I

IV

I

I

I

IV

I

12AH – II, 40AH – III, 65AH – IV

Output Voltage and Stand-by Specification Charts: AL400ULACMCBJ

Voltage 12VDC 24VDC

Switch Position SW1 – ON SW1 – OFF

Stand-by Battery 4 hr. Stand-by / 5 mins. Alarm 24 hr. Stand-by / 5 mins. Alarm

40AH

3.5A / 3.5A

1A / 4A

40AH

2.75A / 2.75A

1A / 3A

AL600ULACMCBJ

Voltage Switch Position

12VDC

SW1 – ON

24VDC

SW1 – OFF

Stand-by Battery 4 hr. Stand-by / 5 mins. Alarm 24 hr. Stand-by / 5 mins. Alarm

40AH

5.5A / 5.5A

0.5A / 5.5A

40AH

5.75A / 5.75A

0.75A / 5.75A

AL1012ULACMCBJ

Voltage 12VDC

Switch Position N/A

Stand-by Battery 4 hr. Stand-by / 5 mins. Alarm 24 hr. Stand-by / 5 mins. Alarm

40AH

9.5A / 9.5A

0.5A / 9.5A

AL1024ULACMCBJ (refer to AL1024ULACMCBJ Battery Size Calculation Worksheet, pg. 11).

Voltage
24VDC 24VDC

Stand-by Battery
12AH 65AH

15 mins. Stand-by / 5 mins. Alarm
7.7A / 9.7A ­

4 hr. Stand-by / 5 mins. Alarm
1.2A / 9.7A 7.7A / 9.7A

24 hr. Stand-by / 5 mins. Alarm
­ 1.2A / 9.7A

60 hr. Stand-by / 5 mins. Alarm
­ 200mA / 9.7A

– 2 –

ACMCBJ Series Installation Guide

Specifications:

Input: · Power input 115VAC, 60Hz
(see ACMCBJ Series Power Supply Configuration Reference Chart, pg. 2). · ACM8CB Power Input Options: a) One (1) common power input for ACM8CB and
lock power (factory installed). b) Two (2) isolated power inputs
(external power supply is required). Current is determined by the power supply connected, not to exceed a maximum of 10A total. · Eight (8) Access Control System trigger inputs. Input options: a) Eight (8) normally open (NO) inputs. b) Eight (8) open collector inputs. c) Any combination of the above.
Outputs: · Eight (8) independently controlled outputs.
Output Options: Eight (8) Fail-Safe and/or Fail-Secure power outputs. · Eight (8) auxiliary power outputs (unswitched). · ACM8CB output PTCs are rated 2.5A. · ACM8CB board main fuse is rated at 10A. · Fire Alarm disconnect (latching or non-latching) is individually selectable for any or all of the eight (8) outputs. · Fire Alarm disconnect input options: a) Normally open (NO) or normally closed (NC)
dry contact input. b) Polarity reversal input from
FACP signaling circuit.

Outputs (cont’d): · Alarm output relay indicates that FACP input is
triggered (form “C” contact rated @ 1A 28VDC, not evaluated by UL). · Filtered and electronically regulated outputs. · Thermal and short circuit protection with auto reset.
Visual Indicators: · Green LED indicates when FACP disconnect
is triggered. · Red LEDs indicate outputs are triggered
(relays energized). · AC input and DC output LED indicators.
Battery Backup: · Built-in charger for sealed lead acid or
gel type batteries. · Automatic switch over to stand-by battery when
AC fails. · Zero voltage drop when switching over to
battery backup.
Supervision: · AC fail supervision (form “C” contact). · Low battery supervision (form “C” contact). · Battery presence supervision (form “C” contact). · Power fail supervision relay
(form “C” contact rated 1A @ 28VDC).
Enclosure Dimensions: 18″ x 14.5″ x 4.625″ (457.2mm x 368.3mm x 117.5mm). Enclosure accommodates up to two (2) 18AH batteries.

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all

local codes and authorities having jurisdiction. Product is intended for indoor use only.

1. Mount unit in desired location. Mark and predrill holes in the wall to line up with the top two keyholes in

the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the

enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower

two holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s

upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all

screws (Enclosure Dimensions, pg. 12). Secure enclosure to earth ground.

It is recommended to first review the following tables to facilitate installation:

Output Voltage and Stand-by Specifications Charts

(pg. 2)

Typical Application Diagram

(pg. 7)

LED Diagnostics

(pg. 7)

Terminal Identification Tables

(pg. 6)

Hook-up Diagrams

(pg. 9-10)

2. Set output voltage:

AL400ULACMCBJ and AL600ULACMCBJ: set desired DC output voltage by setting switch SW1 to the

appropriate position on the power supply board. AL1012ULACMCBJ is factory set at 12VDC and

AL1024ULACMCBJ is factory set at 24VDC (Output Voltage and Stand-by Specification Charts, pg. 2)

3. Connect AC (Fig. 2, pg. 8):

Connect unswitched AC power (115VAC 60Hz) to terminals marked [L, N]. Use 14 AWG or larger for all

power connections. Secure green wire lead to earth ground. Green “AC” LED on power supply board will

turn on. This light can be seen through the LED lens on the door of the enclosure.

ACMCBJ Series Installation Guide

– 3 –

Keep power-limited wiring separate from non power-limited wiring (115VAC 60Hz Input, Battery Wires). Minimum 0.25″ spacing must be provided. CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel. 4. Measure voltage before connecting devices. This helps avoiding potential damage. 5. Output options (Fig. 1, pg. 7): The unit will provide eight (8) switched power outputs or eight (8) unswitched auxiliary power outputs. (a) Switched Power outputs: Connect the negative (­) input of the device being powered to the terminal marked [COM]. For Fail-Safe operation connect the positive (+) input of the device being powered to the terminal marked [NC]. For Fail-Secure operation connect the positive (+) input of the device being powered to the terminal marked [NO]. (b) Auxiliary Power outputs (unswitched): Connect positive (+) input of the device being powered to the terminal marked [C] and the negative (­) of the device being powered to the terminal marked [COM]. Output can be used to provide power for card readers, keypads, etc. 6. Input trigger options (Fig. 1, pg. 7): (a) Normally Open [NO] input trigger: Inputs 1-8 are activated by normally open or open collector sink inputs. Connect devices (card readers, keypads, request to exit buttons etc.) to terminals marked [IN] and [GND]. (b) Open Collector Sink inputs: Connect the access control panel open collector sink positive (+) to the terminal marked [IN] and the negative (­) to the terminal marked [GND]. 7. Fire Alarm Interface options (Figs. 4 through 8, pg. 9): A normally closed [NC], normally open [NO] input or polarity reversal input from FACP signaling circuit will trigger selected outputs. To enable FACP Disconnect for an output turn the corresponding switch [SW1-SW8] OFF. To disable FACP disconnect for an output turn the corresponding switch [SW1-SW8] ON. (a) Normally Open [NO] input:
For non-latching hook-up see Fig. 5, pg. 9. For latching hook-up see Fig. 6, pg. 10. (b) Normally Closed [NC] input:
For non-latching hook-up see Fig. 7, pg. 10. For latching hook-up see Fig. 8, pg. 10. (c) FACP Signaling Circuit input trigger:
Connect the positive (+) and negative (­) from the FACP signaling circuit output to the terminals marked [+ INP ­]. Connect the FACP EOL to the terminals marked [+ RET ­] (polarity is referenced in an alarm condition). Jumper located next to TRG LED must be cut (Fig. 1a, pg. 7). 8. FACP Dry form “C” output (Fig. 1a, pg. 7): Connect desired device to be triggered by the unit’s dry contact output to the terminals marked [NO] and [C] FACP for normally open output or the terminals marked [NC] and [C] FACP for normally closed output. 9. Battery Connections (Fig. 2, pg. 8): For Access Control applications batteries are optional. If batteries are not used, a loss of AC will result in the loss of output voltage. Batteries must be lead acid or gel type. Connect one (1) 12VDC battery to the terminals marked [+ BAT ­] for 12VDC operation. Use two (2) 12VDC batteries wired in series for 24VDC operation. 10. Battery and AC Supervision output (Fig. 2, pg. 8): It is required to connect supervisory trouble reporting devices to outputs marked [AC Fail, BAT Fail] supervisory relay outputs marked [NC, C, NO] to appropriate notification devices. Use 22 AWG to 18 AWG for AC Fail and Low/No Battery reporting. Cut “AC delay” jumper to delay report for 6 hours. Note: A tamper switch must be installed and connected to the appropriate notification device to report a
trouble condition when the enclosure door is open.

– 4 –

ACMCBJ Series Installation Guide

11. Multiple power supply inputs (Fig. 1, pg. 7): When using two (2) power supplies jumpers J1 and J2 (located to the left of the power/control terminals) must be cut (Fig. 1c, pg. 7 & Fig. 3, pg. 9). Connect power for the ACM8CB to the terminals marked [­ Control +] and connect power for the locking devices to the terminals marked [­ Power +]. When using DC power supplies polarity must be observed. When using AC power supplies polarity need not be observed (Fig. 1d, pg. 7). Note: For UL compliance the additional power supply must be power-limited, UL Listed for Access Control Systems and accessories.

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper

voltage level (Output Voltage and Stand-by Specification Charts, pg. 3).

Battery Test:

Under normal load conditions check that the battery is fully charged, check specified

voltage at the battery terminals and at the board terminals marked [+ BAT ­] to

ensure that there is no break in the battery connection wires.

Note: AL400ULXB2, AL600ULXB, AL1012ULXB (Power Supply Board) maximum charge current is 0.7A.

AL1024ULXB2 (Power Supply Board) maximum charge current is 3.6A.

Expected battery life is 5 years, however it is recommended to change batteries within 4 years or less if necessary.

ACMCBJ Series Installation Guide

– 5 –

Terminal Identification Tables: Power Supply Board

Terminal Legend Function/Description

L, G, N

Connect 115VAC 60Hz to these terminals: L to hot, N to neutral.

+ DC ­

AL400ULACMCBJ – 12VDC @ 4A or 24VDC @ 3A to ACM8CB board (power-limited). AL600ULACMCBJ – 12VDC/24VDC @ 6A to ACM8CB board (power-limited). AL1012ULACMCBJ – 12VDC @ 10A to ACM8CB board (power-limited). AL1024ULACMCBJ – 24VDC @ 10A to ACM8CB board (power-limited).

AC FAIL NC, C, NO

Used to notify loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized when AC power is present. Contact rating 1A @ 28VDC. AC or brownout fail is reported within 1 minute of event. To delay reporting of up to 6 hrs. cut “AC delay” jumper and reset power to unit.

BAT FAIL NC, C, NO

Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power is present. Contact rating 1A @ 28VDC. A removed battery is reported within 5 minutes. Battery reconnection is reported within 1 minute. Low battery threshold: 12VDC output threshold set @ approximately 10.5VDC (N/A for AL1024ULACMCBJ), 24VDC output threshold set @ approximately 21VDC (N/A for AL1012ULACMCBJ).

+ BAT ­

Stand-by battery connections. AL400ULXB2, AL600ULXB and AL1012ULXB (Power Supply Board) maximum charge current is 0.7A. AL1024ULXB2 (Power Supply Board) maximum charge current is 3.6A.

ACM8CB Access Power Controller

Terminal Legend Function/Description

­ Power +

12VDC or 24VDC input from power supply board.

­ Control +

These terminals can be connected to a separate power limited, UL listed power supply to provide isolated operating power for the ACM8CB (jumpers J1and J2 Must be removed).

TRIGGER INPUT 1 – From normally open and/or open collector sink trigger inputs INPUT 8 IN, GND (request to exit buttons, exit pir’s, etc.).

12 to 24 volts AC/DC trigger controlled outputs:

OUTPUT 1 – OUTPUT 8 NC, C, NO, COM

Fail-Safe [NC positive (+) & COM Negative (­)], Fail-Secure [NO positive (+) & COM Negative (­)], Auxiliary output [C positive (+) & COM Negative (­)]. When using AC power supplies polarity need not be observed.

Contacts shown in a non-triggered state.

FACP INTERFACE Fire Alarm Interface trigger input from FACP. Trigger inputs can be normally open,

T, + INPUT ­

normally closed from an FACP output circuit (Fig. 4 through 8, pgs. 8-9).

FACP INTERFACE Form “C” relay contact rated @ 1A 28VDC for alarm reporting.

NC, C, NO

(This output has not been evaluated by UL).

– 6 –

ACMCBJ Series Installation Guide

Typical Application Diagram:

Fig. 1
Access Control Panel C
Output Relay NO
NC
F1
LED1
Mag. Lock

Normally Open (N.O.) Door Releasing Device

Keypad

Fig. 1a
Intact = Dry Input Cut = Wet Input
FACP
TRG

FACP (Fire Alarm
Control Panel)

Fig. 1b

FACP Dry Form “C” Output

NO C NC FACP

NO C NC + INP — T + RET –

IN GND IN GND IN GND IN GND

1

2

3

4

IN GND IN GND IN GND IN GND

5

6

7

8

F2

F3

F4

F5

F6

F7

FACP

F8

ON

ON

1 2 3 4

1 2 3 4

LED2

LED3

LED4

LED5

LED6

LED7

LED8

MAIN 10A 250V

FACP

INTERFACE

ON

ON

1

1

SW1-SW8 FACP Interface
Disabled
Enabled

J3

J2 J1

— + — + Power Control

NC C NO COM NC C NO COM

OUTPUT 1

OUTPUT 2

NC C NO COM NC C NO COM

OUTPUT 3

OUTPUT 4

NC C NO COM NC C NO COM

OUTPUT 5

OUTPUT 6

NC C NO COM NC C NO COM

OUTPUT 7

OUTPUT 8

Electric Strike
Electromagnetic Door Holders

UL Listed Power Supply For this application corresponding fuse F8 must be removed.

MAG. LOCK

Fig. 1d

J3

Intact = DC Input Cut = AC Input

NC C NO COM OUTPUT 8

AC or DC Power Supply (req’d.)

AC or DC Power Supply
(optional)

Fig. 1c
Intact = One P/S Input Cut = Dual P/S Input
J2 J1

— + Control

Power Supply Board

LED

Red (DC)

Green (AC)

ON

ON

ON

OFF

OFF

ON

OFF

OFF

LED Diagnostics:
Power Supply Status Normal operating condition. Loss of AC. Stand-by battery supplying power. No DC output. Short circuit or thermal overload condition. No DC output.

Red (Bat) ON OFF

Battery Status Normal operating condition. Battery fail/low battery.

ACM8CB Access Power Controller

LED

ON

LED 1 – LED 8 (Red)

Output relay(s) energized.

Trg (Green)

FACP input triggered (alarm condition).

OFF Output relay(s) de-energized. FACP normal (non-alarm condition).

ACMCBJ Series Installation Guide

– 7 –

MAIN 10A 250V

-+-+ Power Control

DC Output to devices (power-limited)

OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8

NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM

Fig. 2 – ACMCBJ Series Configuration

Green Flying Lead
Unswitched 115VAC power mains (non power-limited)

L GN

AC DC BAT BAT FAIL NC C NO NC C NO AC FAIL

Battery and AC Supervision Circuit (power-limited)

+BAT-

+ DC –

OFF – 24V ON – 12V

ON

Observe polarity

Input (power-limited)

FACP TRG

TRIGGER INPUT

IN GND IN GND IN GND IN GND IN GND IN GND IN GND IN GND

1

2

3

4

5

6

7

8

F 2

F 3

F 4

F 5

F 6

F 7

F8

NO C NC +INP- T + RET-

INTERFACE

Fire Alarm Interface

ON

ON

FACP

1234 1234

OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4

F 1

Optional Rechargeable Stand-by Battery

Optional Rechargeable Stand-by Battery

CAUTION: De-energize unit prior to servicing. For continued protection against fire hazard replace fuse with the same type and rating.
CAUTION: Optional rechargeable stand-by batteries must match the power supply output voltage setting.
Keep power-limited wiring separate from non power-limited. Use minimum 0.25″ spacing.

– 8 –

ACMCBJ Series Installation Guide

Hook-Up Diagrams:
Fig. 3 Optional hook-up using two (2) isolated power supply inputs:
CUT JUMPERS J1 AND J2

J2 J1

ISOLATED POWER INPUT 12 OR 24 VAC OR VDC
(ACM8 POWER)
ISOLATED POWER INPUT 12 OR 24 VAC OR VDC
(LOCK POWER)

Fig. 4 Polarity reversal input from FACP signaling circuit output (polarity is referenced in alarm condition):

FACP TRG

CUT JUMPER

FACP OUTPUT EOL

INTERFACE

— FROM FACP

OUTPUT CIRCUIT

NO C NC FACP

Fig. 5 Normally Open: Non-Latching FACP trigger input: FACP TRG
N.O. TRIGGER INPUT

INTERFACE

NO C NC FACP

ACMCBJ Series Installation Guide

– 9 –

Hook-Up Diagrams:
Fig. 6 Normally Open FACP Latching trigger input with reset (This output has not been evaluated by UL): FACP TRG

N.O. TRIGGER
INPUT
JUMPER

N.C. RESET SWITCH

NO C NC

INTERFACE

Fig. 7 Normally Closed: Non-Latching FACP trigger input:
FACP
TRG N.C. DRY TRIGGER INPUT
JUMPER

NO C NC FACP

Fig. 8 Normally Closed: Latching FACP trigger input with reset (This output has not been evaluated by UL):

FACP

TRG

N.C. RESET SWITCH

JUMPER

N.C. TRIGGER INPUT

– 10 –

ACMCBJ Series Installation Guide

AL1024ULACMCBJ Battery Size Calculation Worksheet:

A. AL1024ULACMCBJ internal current consumption

(stand-by)

__ 0.35A

B. Load current consumption

(stand-by)

__ A

C. Stand-by time required (Hours)

__ H

D. Battery capacity required for stand-by

(A+B)*C

__ AH

E. AL1024ULACMCBJ internal power consumption

(Alarm)

__ 0.35A

F. Load current consumption

(Alarm)

__ A

G. Alarm duration (Hours, example: 15 Min. = 0.25 Hour) (Alarm)

__ H

H. Battery capacity required for Alarm

(E+F)*G

__ AH

I. Total calculated battery capacity

D+H

__ AH

J. Battery capacity required

I*1.8 (safety factor) __ AH

Note: AL1024ULACMCBJ power supply is designed to work with batteries up to 65AH. Please note, line [I] must not exceed 36AH. You have to reduce either stand-by current consumption or stand-by time in order to comply with requirement.

To determine actual battery size please round line [J] to the nearest larger standard battery size.

ACMCBJ Series Installation Guide

– 11 –

Enclosure Dimensions: 18″ x 14.5″ x 4.625″ (457.2mm x 368.3mm x 117.5mm)

1.5″ (38.1mm)

14.5″ (368.3mm) 2.5″
(63.5mm)

2.5″ (63.5mm)

1.5″ (38.1mm)

4.5″ (114.3mm)

1.25″ (31.75mm)

1.0″ (25.4mm)

1.0″ (25.4mm)

1.5″ (38.1mm)

1.0″ (25.4mm) 1.25″ (31.75mm)

1.5″ (38.1mm)

2.5″ 1.5″ (63.5mm) (38.1mm)

6.0″ (152.4mm) 18.0″ (457.2mm)

18.0″ (457.2mm) 8.5″ (215.9mm)

18.0″ (457.2mm)

1.0″ (25.4mm)

1.0″ (25.4mm)

1.5″ (38.1mm)

14.5″ (368.3mm)

1.0″ (25.4mm)

2.75″ (69.9mm)

4.5″ (114.3mm)

4.5″ (114.3mm)

14.5″ (368.3mm)

2.75″ (69.9mm)

Altronix is not responsible for any typographical errors. ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­ 140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056

website: www.altronix.com | e-mail: info@altronix.com | Lifetime Warranty

IIACMCBJ Series

F28U

MEMBER

– 12 –

ACMCBJ Series Installation Guide