Autonics KRN50 Series 50 mm Hybrid Recorder Instruction Manual

June 10, 2024
Autonics

KRN50 Series 50 mm Hybrid Recorder

Product Information

The 50 mm Hybrid Recorder KRN50 Series is a device designed for measuring and recording various types of inputs, such as temperature sensors (TC, RTD), and analogue inputs (voltage, current). It features a fail-safe device that must be installed when using the unit with machinery that may cause serious injury or substantial economic loss. The device also has options for alarm outputs and option outputs for RS485 communication output. The power supply can either be through 100-240 VAC 50/60 Hz or 24 VDC.
The device is equipped with a Lithium battery that should not be disassembled or burned.

Safety Considerations

  • Always install the fail-safe device when using the unit with machinery that may cause serious injury or substantial economic loss.
  • Do not connect, repair, or inspect the unit while connected to a power source.
  • Check connections before wiring.
  • Do not touch the unit during or after operation for a while.
  • Do not use the unit in the place where flammable/explosive/corrosive gas, high humidity, direct sunlight, radiant heat, vibration, impact or salinity may be present.
  • Do not disassemble or modify the unit.
  • Since Lithium battery is embedded in the product, do not disassemble or burn the unit.

Product Usage Instructions

  1. Refer to the manuals and follow the safety considerations in the manuals for proper use of the product.
  2. Use the unit within the rated specifications to avoid fire or product damage.
  3. Clean the unit using a dry cloth and avoid using water or organic solvent to prevent fire or electric shock.
  4. Keep the product away from metal chip, dust, and wire residue that can flow into the unit, causing fire or product damage.
  5. Do not use the load beyond the rated switching capacity contact to avoid fire, relay broken, contact melt, insulation failure, or contact failure.
  6. When connecting the temperature sensor (TC, RTD) or analogue input (voltage, current) as input to the universal input card, set the jumper pin to the correct place for the connected input type.
    If the jumper pin is placed improperly, it may result in product damage or malfunction.

Ordering Information

For selecting the specified model, follow the Autonics website.

The following is only for reference:

  • KRN50 – 01 – 0: 1 CH, None, 100-240 VAC 50/60 Hz
  • KRN50 – 02 – 2: 2 CH, 2, 100-240 VAC 50/60 Hz
  • KRN50 – 02 – 4: 2 CH, 4, 100-240 VAC 50/60 Hz
  • KRN50 – 01 – 4: 1 CH, RS485 communication output, 100-240 VAC 50/60 Hz
  • KRN50 – 02 – 0: 2 CH, None, 100-240 VAC 50/60 Hz
  • KRN50 – 01 – 0: 1 CH, None, 24 VDC
  • KRN50 – 02 – 2: 2 CH, 2, 24 VDC
  • KRN50 – 02 – 4: 2 CH, 4, 24 VDC
  • KRN50 – 01 – 4: 1 CH, RS485 communication output, 24 VDC

Software

Download the installation file and the manuals from the Autonics website. The DAQMaster is a comprehensive device management program for Autonics’ products, providing parameter setting, monitoring and data management.

Thank you for choosing our Autonics product.
Read and understand the instruction manual and manual thoroughly before using the product.
For your safety, read and follow the below safety considerations before using.
For your safety, read and follow the considerations written in the instruction manual, other manuals and Autonics website.
Keep this instruction manual in a place where you can find easily.
The specifications, dimensions, etc. are subject to change without notice for product improvement. Some models may be discontinued without notice.
Follow Autonics website for the latest information.

Product Safety Considerations

  • Observe all ‘Safety Considerations’ for safe and proper operation to avoid hazards.
  • Symbol indicates caution due to special circumstances in which hazards may occur.

Warning: Failure to follow instructions may result in serious injury or death.

  1. Fail-safe device must be installed when using the unit with machinery that may cause serious injury or substantial economic loss. (e.g. nuclear power control, medical equipment, ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster prevention devices, etc.)
    Failure to follow this instruction may result in personal injury, economic loss or fire.

  2. Do not connect, repair, or inspect the unit while connected to a power source. Failure to follow this instruction may result in fire or electric shock.
    Check ‘Connections’ before wiring.
    Failure to follow this instruction may result in fire.

  3. Do not touch the unit during or after operation for a while.
    Failure to follow this instruction may result in burn or electric shock due to high temperature of the surface.

  4. Do not use the unit in the place where flammable/explosive/corrosive gas, high humidity, direct sunlight, radiant heat, vibration, impact or salinity may be present. Failure to follow this instruction may result in explosion or fire.

  5. Install on the device panel, and ground to the F.G. terminal separately.
    When connecting the F.G. terminal, use AWG16 (1.25 mm²) or over.
    Failure to follow this instruction may result in fire or electric shock.

  6. Do not disassemble or modify the unit.
    Failure to follow this instruction may result in fire.

  7. Since Lithium battery is embedded in the product, do not disassemble or burn the unit.
    Failure to follow this instruction may result in fire.

Caution: Failure to follow instructions may result in injury or product damage.

  1. Use the unit within the rated specifications.
    Failure to follow this instruction may result in fire or product damage.

  2. Use a dry cloth to clean the unit, and do not use water or organic solvent.
    Failure to follow this instruction may result in fire or electric shock.

  3. Keep the product away from metal chip, dust, and wire residue which flow into the unit.
    Failure to follow this instruction may result in fire or product damage.

  4. When connecting the power input or measurement input, use AWG20 (0.50 mm²) cable or over, and tighten the terminal screw with a tightening torque of 0.74 N·m to 0.90 N·m.
    Failure to follow this instruction may result in fire or malfunction due to contact failure.

  5. Do not use the load beyond rated switching capacity contact.
    Failure to follow this instruction may result in fire, relay broken, contact melt, insulation failure or contact failure.

  6. When connecting the temperature sensor (TC, RTD) or analogue input (voltage, current) as input to the universal input card, set the jumper pin to the correct place for the connected input type.
    If the jumper pin is placed improperly, it may result in product damage or malfunction.

Cautions during Use

  • Follow instructions in ‘Cautions during Use’. Otherwise, it may cause unexpected accidents.
  • Install a surge absorber at each end of inductive load coil when controlling high-capacity power  relay or inductive load (e.g. magnet).
  • 24VDC power supply should be insulated and limited voltage/current or Class 2, SELV power supply device.
  • Check the polarity of the terminals before wiring the temperature sensor. For RTD temperature sensor, wire it as 3-wire type, using cables in same thickness and length. For thermocouple (CT) temperature sensor, use the designated compensation wire for extending wire.
  • Keep away from high voltage lines or power lines to prevent inductive noise. In case installing power line and input signal line closely, use line filter or varistor at power line and shielded wire at input signal line. Do not use near the equipment which generates strong magnetic force or high frequency noise.
  • This unit may be used in the following environments.
    • Indoors (in the environment condition rated in ‘Specifications’)
    • Altitude max. 2,000 m
    • Pollution degree 2
    • Installation category II

Ordering Information
This is only for reference.
For selecting the specified model, follow the Autonics website.Autonics-
KRN50-Series-50-mm-Hybrid-Recorder-01

  1. No of input channel
    01: 1 CH
    02: 2 CH

  2. Alarm output
    0: None
    2: 2
    4: 4

  3. Option output
    0: None
    4: RS485 communication output

  4. Power supply
    0: 100-240 VAC∼ 50/60 Hz
    1: 24 VDC

Manual
For proper use of the product, refer to the manuals and be sure to follow the safety considerations in the manuals.
Download the manuals from the Autonics website.

Software
Download the installation file and the manuals from the Autonics website..

  • DAQMaster
    It is the comprehensive device management program for Autonics’ products, providing parameter setting, monitoring and data management.

Product Components

  • Product
  • Recording paper × 2
  • Bracket × 2
  • User manual
  • 50 Ω B class (0.1 %) high-accuracy resistor × 2

Specifications

Series KRN50
LCD type LCD dot matrix display
Resolution 128 × 32 pixel
No of input channel 1 / 2 CH model
Input type Refer to ‘Input/Output’ for detailed information.
Alarm output CH1 (AL1, AL2), CH2 (AL1, AL2) relay output
Alarm output adjustment sensitivity Alarm output ON/OFF interval

setting: 1 to 999 digit variable
Communication output| RS485 communication output (Modbus RTU protocol method)
Setting method| Setting with front key
Sampling cycle| 500 ms/CH (2 CH = 1,000 ms)
Recording accuracy| ± 0.5 % F.S.
Graph mode recording speed| 10, 30, 60, 120, 240, 480, 960 mm/H
Graph mode memo speed| 30 s, 1 min, 5 min, 10 min, 15 min, 30 min, 1 hour, 2 hour, 3 hour, 4 hour, 8 hour, 16 hour, 24 hour
TEXT mode recording speed| 00m 05s to 99m 59s
Recording paper| Thermal Direct Receipt Paper (57 mm × 16 m)
Recording paper supply method| Clamshell type
Print method| Direct thermal line print
Print resolution| 80 dot/mm
No. of print dot| 384 dot/Line
Print life cycle| 50 km
Language| Korean, English

| AC voltage type| DC voltage type
---|---|---
Power supply| 100-240 VAC 50/60 Hz| 24 VDC
Allowable voltage range| 85 to 110 % of power supply| 90 to 110 % of power supply
Power consumption| ≤ 34 VA| ≤ 79 W
Dielectric strength| 2300 VAC 50/60 Hz for 1 minute (charging terminal of the different polarity)
Vibration| 0.75 mm amplitude at frequency of 10 to 55 Hz (for 1 min) in each of X, Y, Z directions for 1 hour
Insulation resistance| ≥ 100 MΩ (500 VDC megger)
Noise immunity| Square shaped noise by noise simulator (pulse width 1 ㎲) ±2 kV
Ambient temperature| 0 to 50 ℃, storage: -20 to 60 ℃ (no freezing or condensation)
Ambient humidity| 35 to 85 %RH, storage: 35 to 85 %RH (no freezing or condensation)
Approval| CE EAC
Unit weight| ≈ 700 g

Input / Output
Universal input

  • Input specifications
RTD JPt100Ω, DPt100Ω, DPt50Ω, Cu100Ω, Cu50Ω
Thermocouple K, J, E, T, B, R, S, N, C, G, L, U, PLII

Analog

| Voltage| -50.0-50.0 mV, -199.0-200.0 mV, -1.000-1.000 V, -1.00-10.00 V
Current| 0.00-20.00 mA, 4.00-20.00 mA (external connection of 50 Ω B class (0.1 %) high- accuracy resistor)

If sensor input line is longer, it is recommended to use shield cable to reduce noise.

  • Display accuracy
Input type Temperature Display accuracy
RTD Room temperature range (25 ℃ ± 5 ℃) ± 0.2 % F.S. ± 1 digit
Out of room temperature range ± 0.3 % F.S. ± 1 digit
Thermocouple Room temperature range (25 ℃ ± 5 ℃) ± 0.2 % F.S. ± 1

digit

  • TC-K2 has same accuracy with TC-K1 and -200 to 1350 ℃ range
  • J (-200 ≤ T ≤ -100):
  • (higher one between ± 0.2 % F.S. and ± 2.7 ℃) ± 1 digit
  • R, S, C, G (0 ≤ T ≤ 100):
  • (higher one between ± 0.2 % F.S. and ± 5.2 ℃) ± 1 digit
  • U, T (-200 ≤ T ≤ -100):
  • (higher one between ± 0.2 % F.S. and ± 3.5 ℃) ± 1 digit
  • U, T (-100 ≤ T ≤ 400):
  • (higher one between ± 0.2 % F.S. and ± 2.5 ℃) ± 1 digit
  • Below 400 ℃ of B: there is no accuracy standards.
  • Below -100 ℃ of all thermocouples: ± 0.4 % F.S. ± 1 digit

Out of room temperature range| ± 0.3 % F.S. ± 1 digit
Analog| Room temperature range (25 ℃ ±5 ℃)| ± 0.2 % F.S. ± 1 digit
Out of room temperature range| ± 0.3 % F.S. ± 1 digit

Event input

Non-contact input| ON: residual voltage ≤ 1 V, OFF: leakage current ≤ 0.05 mA
---|---
Contact input| ON: ≤ 1 kΩ , OFF: ≥ 100 kΩ
Outflow current| ≈ 0.3 mA

Alarm output

Relay capacity 250 VAC 3 A, 30 VDC 3 A
Contact type 1 Form A
Mechanical life cycle of relay ≥ 5,000,000 operations
Electrical life cycle of relay ≥ 100,000 operations

Connections

  • Shaded terminals are for the standard model. (power terminal, CH1 input terminal, DI input terminal)
  • Terminals in dotted line are for the option model. (CH2 input terminal, alarm output terminal, communication output terminal)
  • The DC power model does not have F.G.
  • When using 2-wire RTD, short B and b terminals.
  • For current input, connect external 50Ω B class (0.1 %) high-accuracy resistor.

Autonics-KRN50-Series-50-mm-Hybrid-Recorder-02

Dimensions

  • Unit: mm, For the detailed drawings, follow the Autonics website

Autonics-KRN50-Series-50-mm-Hybrid-Recorder-03

Bracket

Autonics-KRN50-Series-50-mm-Hybrid-Recorder-04

Panel cut-out Autonics-KRN50-Series-50-mm-Hybrid-
Recorder-05

Unit Descriptions

Autonics-KRN50-Series-50-mm-Hybrid-Recorder-06

  1. Channel 1 alarm (AL1) output indicator: Turns ON when AL1 of input channel 1 operates.
  2. Channel 1 alarm (AL2) output indicator: Turns ON when AL2 of input channel 1 operates.
  3. Channel 2 alarm (AL1) output indicator: Turns ON when AL1 of input channel 2 operates.
  4. Channel 2 alarm (AL2) output indicator: Turns ON when AL2 of input channel 2 operates.
  5. Recording start / stop indicator:>>> turns ON when recording starts and turns ON when recording stops.
  6. Digital input indicator: Turns ON when setting digital input.
  7. Recording reservation indicator: RE   turns ON when recording reservation operates.
  8. Recording paper status indicator: PED turns ON in running out of recording paper during recording.
  9. Channel display part: Displays input channel of currently displayed PV on the PV display part.
  10. PV display part: In RUN mode, displays PV of the current channel and in setting mode, displays parameters and mode setting values.
  11. Unit display part: Displays unit of relevant channel
  12. [MODE] key: Used to enter setting mode and changing SV mode.
  13. ∧, ∨ key: Used to move parameters or increase/decrease digits.
    • ∧ key: Digital memo key
    • ∨ key: Recording Run/Stop key
  14. < key: Used to move parameters to upper group or move digits.
    • Paper feeding key (STOP), printing parameter setting information key (RUN)
  15. PC loader port: It is a PC loader port for serial communication to set or monitor parameters by PC. Used to connect SCM-US (USB to Serial converter, sold separately).