Autonics MX4W Series LCD Multi Panel Meters Instruction Manual

June 10, 2024
Autonics

Autonics MX4W Series LCD Multi Panel Meters

Safety Considerations

It is important to follow the safety considerations provided in the user manual to avoid serious injury or death. The fail-safe device must be installed when using the unit with machinery that may cause serious injury or substantial economic loss, such as nuclear power control, medical equipment, ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster prevention devices, etc. The unit should not be used in the place where flammable/explosive/corrosive gas, high humidity, direct sunlight, radiant heat, vibration, impact, or salinity may be present. It should be installed on a device panel to use and not connected, repaired or inspected while connected to a power source.

Cautions

It is important to follow the cautions provided in the user manual to avoid injury or product damage. When connecting the power/measurement input and relay output, use AWG 24 (0.20 mm2) to AWG 15 (1.65 mm2) cable or over and tighten the terminal screw with a tightening torque of 0.78 to 0.98 N m. The unit should be used within the rated specifications and cleaned with a dry cloth without using water or organic solvent. The product should be kept away from metal chip, dust, and wire residue which flow into the unit.

Cautions During Use

When installing power line and input signal line closely, use line filter or varistor at power line and shielded wire at input signal line. Do not use near the equipment which generates strong magnetic force or high frequency noise.

Ordering Information

The MX4W series supports the following input types: V: DC/AC voltage and A: DC/AC current, with power supply F: 24-240 VAC/VDC, and preset output N: Indicator 1: NPN open collector 2: PNP open collector. The actual product may not support all combinations. For selecting the specified model, follow the Autonics website.

Product Components

The product components include a bracket, panel cut-out, terminal cover, option output and hold/zero, ADC input circuit, and display part.

Dimensions

The dimensions of the product are as follows:

  • Panel cut-out: 45+00.6 x 93.7 mm
  • Terminal cover: 48 x 116 x 15.5 mm
  • Bracket: 36 x 92+00.8 x 44.4 mm

Product Usage Instructions

To use the LCD Multi Panel Meters MX4W Series:

  1. Ensure to follow the safety considerations provided in the user manual to avoid serious injury or death.
  2. Follow the cautions provided in the user manual to avoid injury or product damage during installation.
  3. Select the specified model by following the Autonics website.
  4. Install the unit on a device panel.
  5. Use the correct cable size and tightening torque when connecting the power/measurement input and relay output.
  6. Use within the rated specifications provided in the user manual.
  7. Clean the unit with a dry cloth without using water or organic solvent.
  8. Keep the product away from metal chip, dust, and wire residue, which may flow into the unit.
  9. Ensure to follow the cautions provided in the user manual during use to avoid injury or product damage.

WELCOME

  • Thank you for choosing our Autonics product.
  • Read and understand the instruction manual and manual thoroughly before using the product.
  • For your safety, read and follow the below safety considerations before using.
  • For your safety, read and follow the considerations written in the instruction manual, other manuals and Autonics website.
  • Keep this instruction manual in a place where you can find easily.
  • The specifications, dimensions, etc. are subject to change without notice for product improvement. Some models may be discontinued without notice.
  • Follow Autonics website for the latest information.

Safety Considerations

  • Observe all ‘Safety Considerations’ for safe and proper operation to avoid hazards.

  • symbol indicates caution due to special circumstances in which hazards may occur.

  • Warning Failure to follow instructions may result in serious injury or death.

    1. Fail-safe device must be installed when using the unit with machinery that may cause serious injury or substantial economic loss. (e.g. nuclear power control, medical equipment, ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime / disaster prevention devices, etc.)
      Failure to follow this instruction may result in personal injury, economic loss or fire.

    2. Do not use the unit in the place where flammable / explosive / corrosive gas, high humidity, direct sunlight, radiant heat, vibration, impact or salinity may be present.
      Failure to follow this instruction may result in explosion or fire.

    3.  Install on a device panel to use.
      Failure to follow this instruction may result in fire or electric shock.

    4. Do not connect, repair, or inspect the unit while connected to a power source.
      Failure to follow this instruction may result in fire or electric shock.

    5. Check ‘Connections’ before wiring.
      Failure to follow this instruction may result in fire.

    6. Do not disassemble or modify the unit.
      Failure to follow this instruction may result in fire or electric shock.

  • Caution Failure to follow instructions may result in injury or product damage.

    1. When connecting the power / measurement input and relay output, use AWG 24 (0.20 mm2) to AWG 15 (1.65 mm2) cable or over and tighten the terminal screw with a tightening torque of 0.78 to 0.98 N m.
      Failure to follow this instruction may result in fire or malfunction due to contact failure.

    2. Use the unit within the rated specifications.
      Failure to follow this instruction may result in fire or product damage.

    3. Use a dry cloth to clean the unit, and do not use water or organic solvent.
      Failure to follow this instruction may result in fire or electric shock.

    4. Keep the product away from metal chip, dust, and wire residue which flow into the unit.
      Failure to follow this instruction may result in fire or product damage.

Cautions during Use

  • Follow instructions in ‘Cautions during Use’. Otherwise, It may cause unexpected accidents.
  • Power supply should be insulated and limited voltage / current or Class 2, SELV power supply device.
  • Install a power switch or circuit breaker in the easily accessible place for supplying or disconnecting the power.
  • Keep away from high voltage lines or power lines to prevent inductive noise.
    • In case installing power line and input signal line closely, use line filter or varistor at power line and shielded wire at input signal line.
    • Do not use near the equipment which generates strong magnetic force or high frequency noise.

Autonics-MX4W-Series-LCD-Multi-Panel-Meters-fig-2

  • This unit may be used in the following environments.
    • Indoors (in the environment condition rated in ‘Specifications’)
    • Altitude max. 2,000 m
    • Pollution degree 2
    • Installation category II

Ordering Information

This is only for reference, the actual product does not support all combinations.
For selecting the specified model, follow the Autonics webstie.

Autonics-MX4W-Series-LCD-Multi-Panel-Meters-fig-3

  1. Input type

  2. V: DC / AC voltage

  3. A: DC / AC current

  4. Power supply
    F: 24 – 240 VACᜠ / VDCᜡ

  5. Preset output

  6. N: Indicator

  7. 1: NPN open collector

  8. 2: PNP open collector

Product Components

  • Product
  • Bracket × 2
  •  Instruction manual
  • Terminal cover × 1

Dimensions

Unit: mm, For the detailed drawings, follow the Autonics website.

Bracket

Panel cut-out

Autonics-MX4W-Series-LCD-Multi-Panel-Meters-fig-6

Terminal cover

Cautions during Wiring

  • Unit: mm, Use terminals of size specified below.

  • Input and output are insulated from the power.

Connections

Input

  • For using DC power, connect wires regardless of polarity.
  • Indicator model does not have the hold / zero terminal.

Autonics-MX4W-Series-LCD-Multi-Panel-Meters-fig-10

  MX4W- V- F□ MX4W- A- F□

| DC| ± 500 mVDC / ± 200 mVDC /

± 50 mVDC

| ± 20 mA / 4 – 20 mA / ± 5 mA / ± 2 mA
AC| 0 – 500 mVAC / 0 – 200 mVAC /

0 – 50 mVAC

| 0 – 20 mA / 0 – 5 mA / 0 – 2 mA

| DC| ± 20 VDC / ± 5 VDC / 1 – 5 VDC /

± 2 VDC

| ± 500 mA / ± 200 mA / ± 50 mA
AC| 0 – 20 VAC / 0 – 5 VAC / 0 – 2 VAC| 0 – 500 mA / 0 – 200 mA / 0 – 50 mA

| DC| ± 500 VDC / ± 200 VDC / ± 50 VDC| ± 5 A / ± 2 A
AC| 0 – 500 VAC / 0 – 200 VAC /

0 – 110 VAC / 0 – 50 VAC

| 0 – 5 A / 0 – 2 A

Output

Autonics-MX4W-Series-LCD-Multi-Panel-Meters-fig-11

Specifications

Model MX4W- V- F□ MX4W- A- F□
Input type DC / AC voltage DC / AC current
Max. allowable input Dependent on the input type
+DC input ≈ -10 to 110 % F.S. for each measured input range
-DC input ≈ -110 to 110 % F.S. for each measured input range
AC input ≈ 10 to 110 % F.S. for each measured input range

Display method

| 12-segment LCD 01)

– measurement value display part: white, character height: 19 mm

– other display parts: red, green, yellow (indicator: white)

Display accuracy| Dependent on the ambient temperature
23 ± 5 ℃ (DC input)| ± 0.1 % F.S. rdg ± 2-digit| ± 0.1 % F.S. rdg ± 2-digit 02)
23 ± 5 ℃ (AC input)| ± 0.3 % F.S. rdg ± 3-digit| ± 0.3 % F.S. rdg ± 3-digit
0 to 50 ℃| ± 0.5 % F.S. rdg ± 3-digit| ± 0.5 % F.S. rdg ± 3-digit 03)
Display cycle| 0.2 to 5.0 sec (select per 0.1 sec)
Display scale| -9999 to 9999 (4-digit)
A / D conversion method| ΣΔ (Sigma Delta) analog-to-digital converter
Sampling cycle (DC input)| 50 ms
Sampling cycle (AC input)| 16.6 ms
Resolution| 1 / 20,000
Preset output| NPN / PNP open collector output model
Load voltage| ≤ 30 VDC
Load current| ≤ 100 mA
Residual voltage| NPN open collector output: ≤ 1 VDC / PNP open collector output: ≤ 2 VDC
Unit weight (packaged)| ≈ 77 g (≈ 100 g)
Approval|

  1. When using the unit at low temperature (below 0 ℃), display cycle is slow due to charateristics of LCD. Control output operates normally.
  2. 5 A terminal: ± 0.3 % F.S. rdg ± 3-digit
  3. 5 A terminal: ± 1 % F.S. rdg ± 3-digit
    Power supply| 24 – 240 VDCᜡ ± 10 %, 24 – 240 VACᜠ ± 10 % 50 / 60 Hz
    ---|---
    Power consumption| DC: ≤ 3 W, AC: ≤ 5 VA
    Insulation resistance| ≥ 100 MΩ (500 VDCᜡ megger)
    Dielectric strength| Between the charging part and the case: 3,000 VACᜠ 50 / 60 Hz for 1 min
    Noise immunity| ± 2 kV square wave noise (pulse width: 1 ㎲) by the noise simulator
    Vibration| 0.75 mm double amplitude at frequency of 10 to 55 Hz in each X, Y, Z direction for 2 hours
    Vibration

(malfunction)

| 0.5 mm double amplitude at frequency of 10 to 55 Hz in each X, Y, Z

direction for 10 min

Shock| 300 m/s2 (≈ 30 G) in each X, Y, Z direction for 3 times
Shock (malfunction)| 100 m/s2 (≈ 10 G) in each X, Y, Z direction for 3 times
Ambient temperature| -10 to 50 ℃, storage: -20 to 60 ℃ (no freezing or condensation)
Ambient humidity| 35 to 85 %RH, storage: 35 to 85 %RH (no freezing or condensation)
Insulation type| Symbol: , double or reinforced insulation (dielectric strength between the measurement input part and the power part: 1 kV)

Mode Setting

Autonics-MX4W-Series-LCD-Multi-Panel-Meters-fig-12

Parameter Setting

  • Some parameters are activated / deactivated depending on the model or setting of other parameters. Refer to the description of each parameter.
  • If any key is not entered for 60 sec in each parameter, it returns to RUN mode.
  • After returning to RUN mode, press the [MODE] key within 2 sec, it returns to previous parameter.
  • [MODE] key: Saves current setting value and moves to the next parameter.
  • [◀] key: Checks fixed value / Changes setting digits.
  • [▲] key: Changes setting values.

Parameter 1 group

Parameter Display Defaults Setting range Display condition
1-1 Input type DCAC DC DC, -DC, AC

1-2

|

Input range

|

IN-R

|

50)0

|   [MX4W-V-F□]

•  Refer to Input Range and Display Range

| 1-1 Input

type: DC, AC

-50)0| 1-1 Input

type: -DC

%000

|   [MX4W-A-F□]

•  Refer to Input Range and Display Range

| 1-1 Input

type: DC, AC

-%000| 1-1 Input

type: -DC

1-3

|

Display method

|

DISP

|

STND

|

STND: standard, SCAL: scale,

FREQ: frequency*, PF: power factor**

| *1-1 Input

type: AC

**1-1 Input

type: ±DC

1-4| IN-T| RMS| AVG, RMS| 1-1 Input

type: AC

1-5

| High-limit display value gradient correction|

SPAN

|

!000

|

0.100 to 9.999 %

|

1-3

Display method: STND

1-6

| Low-limit display value deviation correction|

ZERO

|

00

|

-99 to 99

1-7

|

Decimal point position

|

DOT

| 00)0| [DC / AC voltage model] 0, 0.0, 0.00, 0.000|

1-3

Display method: SCAL

&

  • 1-7

Decimal point position: 0.0, 0.00,

0.000

)000| [DC / AC current model] 0, 0.0, 0.00, 0.000
1-8| High-limit scale| H-SC| –| Display value against max. measurement input
1-9| Low-limit scale| L-SC| –| Display value against min. measurement input

1-10

| High-limit display value gradient correction|

SPAN

|

!000

|

0.100 to 9.999 %

1-11

| Low-limit display value deviation correction 02)|

ZERO

|

00

|

-99 to 99

1-12

|

Decimal point position 03)

|

DOT

| 00)0| [DC / AC voltage model] 0, 0.0, 0.00, 0.000|

1-3

Display method: FREQ

)000| [DC / AC current model] 0, 0.0, 0.00, 0.000

1-13

| High-limit display value gradient correction|

SPAN

|

!000

|

0.100 to 9.999

1-14| Exponent of SPAN| eSPN| 10-0| 10-0: 100, 10-1: 10-1, 10-2: 10-2, 10 1: 101
1-15| High-limit input value| H-RG| –| Max. value of input range| 1-3

Display method: PF

1-16| Low-limit

input value

| L-RG| –| Min. value of input range

1-17

|

Display unit

|

dUNT

| V| [DC / AC voltage model] V, MV, OFF|

A| [DC / AC current model] A, MA, HZ, OFF

  1. When changing input range, the following parameters are reset.
    • Parameter 1 group: display method, measurement method, decimal point position, high / low-limit scale, high-limit display value gradient correction, exponent of span, high / low-limit input value, display unit
    • Parameter 2 group: OUT1 / 2 output operation mode, OUT1 / 2 hysteresis
    • Parameter 0 group: OUT1 / 2 high-limit output setting value, OUT1 / 2 low-limit output setting value, max. / min. peak value
  2. Low-limit display value deviation correction range is within -99 to 99 for D 0, D-1digit regardless of decimal point position.
  3. Display range is variable according to decimal point position.
    Dot| Display range| Frequency measurement range
    ---|---|---
    0| -9999 to 9999| 1 to 1200 Hz
    )0| -999.9 to 999.9| 0.1 to 999.9 Hz
    )00| -99.99 to 99.99| 0.10 to 99.99 Hz
    )000| -9.999 to 9.999| 0.100 to 9.999 Hz

Parameter 2 group

Parameter Display Defaults Setting range Display condition

2-1

| OUT1

operation mode

|

OU!T

|

OFF

| [Preset output model] OFF, HIGH, LOW, HL, HL-G|

2-2

| OUT2

operation mode

|

OU@T

|

OFF

| [Preset output model] OFF, HIGH, LOW, HL, HL-G|

2-3

|

OUT1

hysteresis

|

HYs1

| 0)1| [DC / AC voltage model]

Within 10 % of max. display range, digit

| 2-1 OUT1

operation mode: except OFF

)001| [DC / AC current model]

Within 10 % of max. display range, digit

2-4

|

OUT2

hysteresis

|

HYs2

| 0)1| [DC / AC voltage model]

Within 10 % of max. display range, digit

| 2-2 OUT2

operation mode: except OFF

)001| [DC / AC current model]

Within 10 % of max. display range, digit

2-5

| Startup compensation time|

STaT

|

0)0

|

00.0 to 99.9 sec

|

2-6

| Peak monitoring delay time|

PEaK

|

00 S

|

00 to 30 sec

|

2-7| Display cycle| DIsT| )2 S| 0.2 to 5.0 sec| –

2-8

| External input terminal|

DI-T

|

HOLD

| [Preset output model] HOLD, ZERO|

2-9

|

Lock

|

LOC

|

OFF

| OFF: unlock,

LOC1: lock parameter 1, LOC2: lock parameter 1, 2,

LOC3: lock parameter 0, 1 and 2

|

Parameter 0 group

Parameter| Display| Defaults| Setting range 01)| Display condition|
---|---|---|---|---|---
 |

OUT1 high-

|  | 50)0| [DC / AC voltage & preset output model]| 2-1 OUT1

operation

|
0-1| limit output| OU!H|  |  | mode:|
%000| [DC / AC current & preset output model]|
 | setting value|  | HIGH, HL,|
 |  |  | HL-G|
 |  |  |  |  | 1-1 Input|
 |  |  | 00)0| [DC / AC voltage & preset output model]| type:

DC, AC

|
 |  |  |  |  | &|
 |  |  |  |  | 2-1 OUT1|
 |  |
 |  |  |  |  | operation|

0-2

|

OUT1 low-

limit output

|

OU!L

| )000| [DC / AC current & preset output model]| mode:

LOW, HL, HL-G

|
 | setting value|  |  |  | 1-1 Input|
 |  |  | -50)0| [DC / AC voltage & preset output model]| type: -DC

&

|
 |  |  |  |  | 2-1 OUT1|
 |  |  |  |  | operation|
 |  |  | -%000| [DC / AC current & preset output model]| mode:

LOW, HL,

|
 |  |  |  |  | HL-G|
 |  |  | 50)0| [DC / AC voltage & preset output model]| 2-2 OUT2|
 | OUT2 high-|  | operation|
0-3| limit output| OU@H| mode:|
%000| [DC / AC current & preset output model]|
 | setting value|  | HIGH, HL,|
 |  |  | HL-G|
 |  |  |  |  | 1-1 Input|
 |  |  | 00)0| [DC / AC voltage & preset output model]| type:

DC, AC

|
 |  |  |  |  | &|
 |  |  |  |  | 2-2 OUT2|
 |  |
 |  |  |  |  | operation|

0-4

|

OUT2 low-

limit output

|

OU@L

| )000| [DC / AC current & preset output model]| mode:

LOW, HL, HL-G

|
 | setting value|  |  |  | 1-1 Input|
 |  |  | -50)0| [DC / AC voltage & preset output model]| type: -DC

&

|
 |  |  |  |  | 2-2 OUT2|
 |  |  |  |  | operation|
 |  |  | -%000| [DC / AC current & preset output model]| mode:

LOW, HL,

|
 |  |  |  |  | HL-G|
 |  |  |  |  | 2-1 OUT1|
 |  |  |  |  | operation|
 |  |  |  |  | mode:|
0-5| Display max. peak value 02)| hPEK| )0| Max. peak value in run mode| except

OFF

or

|
 |  |  |  |  | 2-2 OUT2|
 |  |  |  |  | operation|
 |  |  |  |  | mode:|
except|
 |  |  |  |  |
 |  |  |  |  | OFF|
 |  |  |  |  | &|

0-6

| Display min. peak value 02)|

lPEK

|

)0

|

Min. peak value in run mode

| 2-6 Peak

monitor- ing delay

|
 |  |  |  |  | time:|
 |  |  |  |  | except|
 |  |  |  |  | 00|

  1. Setting range of OUT1 / 2 high / low-limit output setting value
    • 1-1 input type +DC = -10 to 110 % of display range
    • 1-1 input type -DC = -110 to 110 % of display range
    • 1-1 input type AC = 0 to 110 % of display range
  2. Reset: Press [◀] + [▲] key for over 1 sec

Input Range and Display Range

When the max. input value is over the 100 %, it may result in input terminal damage.

DC / AC voltage model (input type: DC)

Autonics-MX4W-Series-LCD-Multi-Panel-Meters-fig-17

DC / AC voltage model (input type: -DC)

Autonics-MX4W-Series-LCD-Multi-Panel-Meters-fig-18

DC / AC voltage model (input type: AC)

Autonics-MX4W-Series-LCD-Multi-Panel-Meters-fig-19

DC / AC current model (input type: DC)

Autonics-MX4W-Series-LCD-Multi-Panel-Meters-fig-20

DC / AC current model (input type: -DC)

Autonics-MX4W-Series-LCD-Multi-Panel-Meters-fig-21

DC / AC current model (input type: AC)

Autonics-MX4W-Series-LCD-Multi-Panel-Meters-fig-22

Output Operation Mode

  • The below describes based on OUT1.
  • OUT1 and OUT2 of output operations are same. It operates individually by the set output operation mode.
  • When changing output operation mode, high-limit / low-limit output setting value, hysteresis are reset.

Autonics-MX4W-Series-LCD-Multi-Panel-Meters-fig-15

Reset

  1. Press the [◀] + [▲] + [▼] keys for over 5 sec. in run mode, INIT and NO flash alternately for 0.5 sec in turn.
  2. Change the setting value as YES by pressing the direction keys.
  3. Press the [MODE] key to reset all parameter values as default and to return to run mode.

Error

Error display is released automatically when it is in the measured and display range.

Display Description Troubleshooting
HHHH Flashes when measurement input is exceeded the

max. allowable input (110 %)

|

Disconnect power supply

and check the cables.

LLLL| Flashes when measurement input is exceeded the

min. allowable input (-DC: -110 % / DC, AC: -10 %)

D-HH| Flashes when measurement input is exceed the

max. display value (9999)

|

Reset within the display

range.

D-LL| Flashes when measurement input is exceed the

min. display value (-9999)

F-HH| Flashes when input frequency is exceeded the max. display value of measured range|

PF-H| Flashes when power factor display value to

measured input is over than LAG 0.50

PF-L| Flashes when power factor display value to

measured input is less than LEAD -0.50

OVER| Flashes twice when it exceeds zero range (±99)

and returns to run mode

| Reset within the zero range.