HALCYON R602 150mm LED Downlight Installation Guide

June 10, 2024
HALCYON

HALCYON LOGO INSTALLATION R602

Installation Directions

HALCYON R602 150mm LED Downlight - Lighting circut

  1. Switch off mains power supply
  2. Connect Dimmable Driver to mains voltage cable (L, N) Do not connect downlight to driver if driver is live. Inrush current from live driver will cause instant downlight failure. Do not switch secondary side.
  3. Carefully install downlight into Precut 130-140mm hole.
  4. Turn on mains power and switch on lighting circuit.

Approved Clearances
Note: Omm required but 25mm always recommended for optimum product lifespan through effective heat dissipation.
Example 1:
Omm Approved Height Clearance. Building element abutting rear, insulation abutting sides of fitting.

HALCYON R602 150mm LED Downlight - Clearance 1

Example 2:
Omm Approved Side Clearance. Building element abutting side of fitting, insulation abutting and covering fitting.HALCYON R602 150mm LED Downlight -
Clearance 2

Driver is designed to be covered and abutted with IC /IC-F / 1C-4 approved insulation.

HALCYON R602 150mm LED Downlight - Insulation

CLASSIFICATION SHEET

Manufacturer I Supplier Halcyon Lighting Ltd
Product Code R602 W3K / R602 B3K

R602 W3KHO / R602 W4KHO
Product Type| LED Recessed Luminaire
Primary Voltage| 220-240V-50/60Hz
Secondary Voltage| 260mA 36VDC Constant Current
500mA 36VDC Constant Current
Wattage| 12W
20W
Ingress Protection Rating| IP54
Classification| | IC-F — building insulation that can safely be continuously exposed to 90°C allowed to abut and cover the luminaire.
---|---|---
HALCYON R602 150mm LED Downlight - IC4| IC-4 — building insulation that can safely be continuously exposed to 90°C allowed to abut and cover the luminaire.

In the vicinity of the recessed luminaire, use an insulation product that:
(a) Maintains its dimensions and structural integrity when exposed to a temperature of 90°C; and
(b) Withstands a 30-second needle flame test carried out in accordance with AS/NZS 60695.11.5 with the flame applied to all surfaces of the sample.

Rear of fitting may abut structural members and building elements.
Do not install through or directly into joist, beam, rafter or ceiling batten.

Side Clearance from heatsink to building element (e.g. timber, joist or batten)| SCB: 0mm
---|---
Height Clearance from heatsink to building element (e.g. timber, joist or batten)| HCB: 0mm
Minimum insulation clearance to building element| MIC: 0mm

Recessed luminaires and their associated equipment may pose a risk of fire or damage to property if not installed and maintained correctly. Halcyon recommends a clearance of 25mm to building elements for optimum lifespan.
Halcyon IC-F rated luminaires are completely safe to install in sarked timber ceiling linings.
Halcyon accepts no responsibility if the timber used is not treated correctly and dries out, crack or warps over time due to the constant low heat from the aforementioned “IC-F Rated” LED recessed lighting.
This data sheet contains information necessary to ensure compliance with the New Zealand Electrical Code of Practice for Installation and Maintenance of Recessed Luminaires and Associated Equipment AS/NZS 60598.2.2:2001

Cutting of holes prior to receiving goods is entirely at the risk of the installer.
10 Basalt Place, East Tamaki, Auckland, PO Box 58-501, Botany, Manukau 2163, Auckland, New Zealand
Ph (0064 9) 273-9177 Fax (0064 9)273 9155 Email: sales@halcyon.co.nz Web: www.halcyonlights.co.nz
56210652 V1.0