MCZ S2 Teia Comfort Air 10 Pellet Stove Instruction Manual
- June 9, 2024
- MCZ
Table of Contents
INSTALLATION GUIDE SEALED PELLET STOVE
TEIA COMFORT AIR 10 S2
TEIA COMFORT AIR 10 UP! S2
PART 2 – OPERATION AND CLEANING
Instructions in
FIRST START-UP
PRECAUTIONS BEFORE START-UP GENERAL PRECAUTIONS
Remove any objects that may burn from the brazier (manual, various adhesive
labels or any polystyrene).
Check that the brazier is positioned correctly and rests properly on the base.
The first start-up may not be successful as the feed screw is empty and does
not always manage to load the required amount of pellets in time to light the
flame.
CANCEL THE FAILED IGNITION ALARM BY PRESSING AND HOLDING THE ON/OFF KEY FOR A
FEW SECONDS. REMOVE THE PELLET LEFT IN THE BRAZIER AND REPEAT THE START-UP.
SETTINGS TO BE CARRIED OUT BEFORE THE INITIAL START-UP
After connecting the power cable to the back of the product, turn the switch
at the back to position(I). To turn the stove on or off, press button 1 on the
control panel.
The display on the panel will be ON with a flashing flame. When the flame
stops blinking, the stove has reached the operating condition to “supply
power”.
The default target room temperature is set at 20°C. To change this setting,
follow the instructions in the adjustments menu; do the same to set the
heating water temperature and the speed of the ventilation fan (if provided).
To activate an external thermostat, if present, see the dedicated paragraph.
SWITCHING THE EQUIPMENT OFF
To switch the equipment off, press and hold the ON-OFF button on the remote
control or on the APP. The acoustic beep confirms this phase has started.
Alternatively, switch it off from the emergency panel by following the
instructions provided in the dedicated chapter The equipment will start the
shutdown process which involves consuming the residual pellets in the brazier,
the latter being cleaned and the residual heat in the structure being disposed
of.
Technical Dept. – All rights reserved – Reproduction prohibited
13-FIRST START-UP
During the disposal phase of the residual heat, the fans operate at about 80%
of their output and the speed cannot be varied. This is determined by the need
for all the accumulated heat to be evacuated safely and quickly. The switch-
off phase can last 15 – 30 minutes depending on the heat stored in the
structure, determined by the duration and the operating regime of the product
throughout the day. When the internal temperature drops below the set
thresholds, the fans for hot air and exhaust fume extraction will
automatically switch off.
POWER SUPPLY
When start-up is complete, the panel will display ON with a constant flame at
level 3 . The modulation of the flame for higher or lower power is then
controlled autonomously on the basis of reaching the set temperature. (see
also “OPERATING MODE” – “Set Flame”) If the flame fails to ignite, despite a
regular flow of pellets, check that the brazier is seated correctly: it must
rest snugly against the interlocking slot and be clean of any ash
incrustations. If no anomaly is found during this inspection, there may be a
problem with the product components or installation may not be correct.
REMOVE THE PELLETS FROM THE BRAZIER AND CONTACT AN AUTHORISED TECHNICIAN.
Please ensure the brazier is free from ALL pellets and ash build up following
any failed ignitions. Failure to clear out the brazier prior to resetting may
result in further failed ignitions or in certain conditions an explosive
ignition.
It is good practice to ensure effective ventilation in the room during the
initial start-up, as the product will emit some smoke and smell of paint.
Do not stand close to the boiler and ventilate the room as described. The
smell of paint will disappear after about an hour of operation, however, it is
not harmful in any case.
The product will be subject to expansion and contraction during the start-up
and cooling phases, therefore slight creaking noises may be heard.
This is absolutely normal as the structure is made of laminated steel and must
not be considered a defect.
DO NOT EXPECT HEATING EFFICIENCY IMMEDIATELY!!! THE PRODUCT NEEDS SOME
RUNNING-IN TIME.
It is extremely important to make sure the product does not reach high
temperatures straight away, but to increase the temperature gradually using
low power at first.
This will prevent damage to the welds and the steel structure.
Do not touch the product during the first lighting, as it is during this
phase that the paint sets. If you touch the paint, you may expose the steel
surface.
If necessary, touch up the paint with the spray can of the specific colour.
CONTROL PANEL
KEY
- Stove switch-on/switch-off
- Scrolling down through the programming menu
- Menu
- Scrolling up the programming menu
- Decrease set temperature / programming functions.
- Increase set temperature / programming functions.
- Display.
MENU ITEMS AND OPERATION
MAIN MENU
Press key 3 (menu) to access. The options accessed are:
- Date and Time
- Timer
- Sleep (only when stove is on)
- Settings
- Info
Date and time configuration
Configure the time and date as follows:
- Press the “menu” key.
- Select “Date and Time”.
- Press “menu” to confirm.
- Scroll through with the arrow keys and select the variables to be edited one at a time: Day, Hour, Min, Num. day, Month, Year.
- Press “menu” to confirm
- Use the + and – keys to edit.
- Finally, press “menu” to confirm and “esc” to exit.
CONFIGURATION OF PROGRAMMED MODE (TIMER) – Main menu
The current time and date must be configured to ensure correct operation of
the timer.
There are six configurable TIMERS; for each one, the user can select a start
and stop time and the days of the week when it is in use.
When one or more programs are active, the status of the stove and the TIMER
“n” alternate on the display. “n” is the number of timer programs in use,
separated by dashes.Example:
TIMER 1 Timer 1 program active.
TIMER 1-4 Timer 1 and 4 programs active.
TIMER 1-2-3-4-5-6 All timer programs active.
EXAMPLE OF PROGRAMMING
With the stove on or off:
- access the MENU,
- scroll to the TIMER item using the <> arrows,
- press the “Menu” key
- the system shows “P1” (Press the <> keys to move through the timers P2, P3, P4, P5, P6)
- Press the “Menu” key to activate “P1”.
- press + – and select “ON”
- press the “Menu” key to confirm
At this point the start time is 00:00. Press the + – key to set the start time
and press the “menu” key to confirm.
Next, the proposed stop time is 10 minutes later than the configured start
time: press the + key and edit the stop time, and press the “menu” key to
confirm.
Next, you are asked to set the days of the week when the configured timer is
to be enabled or disabled. Press the – or + keys to select the day you want to
activate the time. It will light up white, then confirm with the “menu” key.
If no day is selected for enabling the timer, the timer program is no longer
enabled on the status window.
Next, program the other days or press “ESC” to exit. Repeat this procedure to
program the other timers.
EXAMPLES OF PROGRAMMING
P1 | P2 |
---|---|
on | off |
8:00 | 12:00 |
Stove on between 08:00 and 14:00
P1| P2
---|---
on| off| day| on| off| day
8:00| 11:00| mon| 11:00| 14:00| mon
Stove on between 08:00 and 14:00
P1| P2
---|---
on| off| day| on| off| day
17:00| 0:00| mon| 0:00| 6:00| tue
Stove on between 17:00 on Monday to 06:00 on Tuesday
NOTES ON USE OF THE TIMER
- The timer always starts the boiler with the last temperature and ventilation settings (or with the default settings at 20°C and V3 if they have never been altered).
- The start time can be between 00:00 and 23:50
- If the stop time has not yet been saved, the program proposes a start time at +10 minutes.
- If a timer program turns off the stove at 24:00 on one day and another program starts it up at 00:00 on the next day: the stove remains on.
- A program has a start-up and/or shut-down time that overlap the times of another program: if the stove is already on, the start has no effect while OFF turns off the stove.
- When the stove is on and the timer is active, pressing the OFF key turns off the stove; the stove then restarts automatically at the next time of the timer.
- When the stove is off and the timer is active, pressing the ON key turns on the stove; the stove then stops automatically at the next time of the timer.
SLEEP FUNCTION (main menu)
Sleep may be activated only when the stove is on and allows you to quickly set
a time for the product to turn off.
To set the Sleep function, proceed as follows:
- Enter the MENU
- Scroll to the SLEEP item with the <> arrows
- Press Menu
- Set the turn-off time you want using the + and – keys.
The panel shows a default time of 10 minutes after the current time, which can be adjusted with key 6 up to the following day (i.e. the turn-off can be delayed for a maximum of 23 hours and 50 minutes).
If the SLEEP function is active with the TIMER active, the former has priority, therefore the stove will not turn off at the time set in the timer program but at the time set by the sleep function, even if it comes after the time set by the timer.
OPERATING MODE ADJUSTMENTS MENU
“Adjustments” menu settings determine the operation mode of the stove.
To access the menu, proceed as follows:
- Press the – + keys
- Scroll with the <> arrows and select “Set Amb. T” or “Set Ventilation T” or “Set Flame”
- Press “menu” to enter the option selected.
- Change with the + – keys.
- Press “menu” to confirm and “esc” to exit.
Set Amb T – this function is used to set the temperature to be reached in the
room in which the stove is installed, from a minimum of 5°C to a maximum of
35°C. When this condition is met, the stove setting is equivalent to the
minimum consumption values (the flame and hot air fan speed at minimum), and
then returns to the set values when the room temperature drops below the set
threshold.
PLEASE NOTE: The point to the right of the room temperature on the control
panel display indicates the half degrees (e.g. 23.°C is equivalent to 23.5°C).
Set Vent – this function allows you to select the desired speed of the room
fan from 1 to 5.
Set Flame – this function allows you to set the power of the flame from a
minimum of 1 to a maximum of 5. The power levels correspond to a different
value of fuel consumption, setting 5 heats the room in less time and setting 1
can keep the room temperature stable for a longer period of time. The set
flame is automatically set to a minimum when the set temperature value is
reached.
VIEW WITH STOVE ON
if the bars are all full, the stove is on flame power 5 if only one bar is
full, the stove is on flame power 1 if the bars are flashing, automatic
cleaning is in progress
SETTINGS MENU
The SETTINGS menu is to configure use of the stove:
a. Language.
b. Cleaning (shown only when stove is off).
c. Auger loading (shown only when stove is off).
d. Tones.
e. External thermostat (activation).
f. Auto Eco (activation).
g. Eco Turn-off T (default 10 minutes).
h. Pellet recipe.
i. % of smoke rpm.
j. Component test (shown only when stove is off).
k. “Chimney sweeper” function (can be enabled only when stove is on to check
emissions in field).
l. Technical menu.
a – Language
Select the language as follows:
- Press the “menu” key.
- Use the arrow keys to scroll through and select “Settings”
- Press “menu” to confirm.
- Use the arrow keys to scroll through and select “language”.
- Press “menu” to confirm.
- Use the + – keys to select the required language (IT/EN/DE/FR/ES/NL/PL/DK/SLO)
- Press “menu” to confirm and “esc” to exit.
b – Cleaning
Select “Cleaning” (only with stove off) as follows:
- Press the “menu” key.
- Use the arrow keys to scroll through and select “Settings”
- Press “menu” to confirm.
- Use the arrow keys to scroll through and select ‘’Cleaning’’
- Press “menu” to confirm.
- Use the + – keys to select “On”.
- Press “esc” to exit.
c – Load auger
To select ‘’Load auger’’ (only with stove off), proceed as follows:
- Press the “menu” key.
- Use the arrow keys to scroll through and select “Settings”
- Press “menu” to confirm.
- Scroll with the arrows and select “Load auger”.
- Press “menu” to confirm.
- With the + key “Enable” the load auger.
- Press “esc” to exit.
d – Tones
This function is disabled by default. To enable it proceed as follows:
- Press the “menu” key.
- Use the arrow keys to scroll through and select “Settings”
- Press “menu” to confirm.
- Use the arrow keys to scroll through and select ‘’Tones’’
- Press “menu” to confirm.
- With the + – keys, select “On/Off”.
- Press “menu” to confirm and “esc” to exit.
e – External thermostat (see dedicated chapter)
f – Auto-Eco activation (see dedicated chapter)
To select the Auto-Eco function, proceed as follows:
- Press the “menu” key.
- Use the arrow keys to scroll through and select “Settings”
- Press “menu” to confirm.
- Scroll with the arrows and select “Auto-Eco”.
- Press “menu” to confirm.
- Use the + – keys to select “On”.
- Press “menu” to confirm and “esc” to exit.
g – Eco stop T (see dedicated chapter)
To select the Eco Stop T function, proceed as follows:
- Press the “menu” key.
- Use the arrow keys to scroll through and select “Settings”
- Press “menu” to confirm.
- Scroll with the arrows and select ‘’T Eco off’’.
- Press “menu” to confirm.
- With the + – keys, insert the minutes (from 1 to 30’).
- Press “menu” to confirm and “esc” to exit.
AUTO ECO MODE (see above paragraph activation and switching off)
For activation of the “Auto Eco” mode and time settings, see paragraphs f and
g respectively.
‘’ECO stop T’’ can be adjusted to ensure correct operation in the various
environments in which the stove can be installed and to avoid constant
stopping and starting when the room temperature is subject to sudden change
(drafts, poorly insulated rooms, etc.).
The ECO stop procedure is activated automatically when the power recall device
is satisfied (room probe +1°C or external thermostat with an open contact),
the “ECO stop T” starts to decrease the time (factory default 5 minutes, which
can be changed from the “Settings” menu). During this phase, the panel
alternates between displaying ON with a small flame and Crono (if active) –
Eco active. The minutes counting down to the Eco Stop are shown at the top of
the display. The flame moves to P1 and remains there until the set “T Eco
Stop” time reaches zero, and if the conditions are still satisfied, turns off
the boiler. The ECO stop count is cancelled if one of the devices recalls
power. When the boiler begins to turn off, the panel shows: Off – Eco Active –
flashing small flame.
When the stove turns off, OFF-ECO appears on the display with the flame symbol
off.
The following conditions have to be met simultaneously for the ECO to restart:
- room probe -1°C or external thermostat with a closed contact (for at least 20” in order to prevent false recalls)
- 5 minutes have passed since shut-down.
h – Pellet Recipe
This function is for adapting the stove to the type of pellet in use. As there
are many types of pellet available on the market, operation of the stove can
vary considerably according to the quality of the fuel. When the pellets clog
up the brazier due to excess loading of fuel or when the flames are high even
at low power, or when the flames are low, it is possible to decrease/increase
the amount of pellets in the brazier:
Available values:
-3 = A decrease of 20% on the factory setting.
-2 = A decrease of 13% on the factory setting.
-1 = A decrease of 6% on the factory setting.
0% No changes.
3 = An increase of 10% on the factory setting.
2 = An increase of 6% on the factory setting.
1 = An increase of 3% on the factory setting.
Edit the recipe as follows:
- Press the “menu” key.
- Use the arrow keys to scroll through and select “Settings”
- Press “menu” to confirm.
- Scroll with the arrows and select “Pellet recipe’’
- Press “menu” to confirm.
- Alter the % with the + – keys.
- Press ‘’menu’’ to confirm and ‘’esc’’ to exit.
i – Variation % rpm smoke
In the event the installation presents problems in extracting smoke (lack of
draft or even pressure in the duct), it is possible to increase the smoke and
ash extraction speed. This change resolves all the potential problems related
to pellets clogging in the brazier and deposits forming at the bottom of the
brazier itself caused by poor quality fuel or fuel that produces a lot of ash.
The extraction speed may be altered between -30% to +50%, with increments of
10 percent at a time. Negative variation can be necessary if the flame is too
low.
To alter this parameter, proceed as follows:
- Press the “menu” key.
- Use the arrow keys to scroll through and select “Settings”
- Press “menu” to confirm.
- Scroll with the arrows and select “Fumes rpm Var.”
- Press “menu” to confirm.
- Alter the % with the + – keys.
- Press ‘’menu’’ to confirm and ‘’esc’’ to exit.
j – Components test
This can be done only when the stove is off and allows you to select the
components to be tested:
- Spark plug: it is turned on for a fixed period of 1 minute during which the panel displays the countdown in seconds.
- Feed screw: it is powered for a fixed period of 1 minute during which the panel displays the countdown in seconds.
- Extractor: it is activated at 2500 rpm for a fixed period of 1 minute during which the panel displays the countdown in seconds.
- Exchanger: enables you to conduct the test in V5 for a fixed period of 1 minute during which the panel displays the countdown in seconds.
Enable the “Component test” function (only with stove off) as follows:
- Press the “menu” key.
- Use the arrow keys to scroll through and select “Settings”
- Press “menu” to confirm.
- Use the arrow keys to scroll through and select ‘’Component test’’
- Press “menu” to confirm.
- Use the + – keys to select the test to be carried out.
- Press ‘’menu’’ to confirm and ‘’esc’’ to exit.
k – Chimney sweeper function (for maintenance operators only) –
This function can only be activated when the stove is on and power is
supplied, and it forces operation of the boiler at the parameters P5, with the
ventilator (if present) in V5. Any corrections to the loading/smoke
ventilation percentage must be read. This state lasts 20 minutes, the
countdown is displayed on the panel.
The technician can stop this phase at any moment by quickly pressing the
on/off key.
Enable the “Chimney sweeper” function as follows:
- Press the “menu” key.
- Use the arrow keys to scroll through and select “Settings”
- Press “menu” to confirm.
- Use the arrow keys to scroll through and select ‘’Chimney sweeper function’’
- Press “menu” to confirm.
- Use the + – keys to select “On” (Off by default)
- Press ‘’menu’’ to confirm and ‘’esc’’ to exit.
l – Technical menu
To access the technical menu you must contact the service centre as it
requires a password.
Access the “technical menu” as follows:
- Press the “menu” key.
- Use the arrow keys to scroll through and select “Settings”
- Press “menu” to confirm.
- Use the arrow keys to scroll through and select ‘’Technical menu’’
- Press “menu” to confirm.
- With the + – keys, select “Product Type”, “Service”, “Counter memories”, “Parameters”.
- Press ‘’menu’’ to confirm and ‘’esc’’ to exit.
INFO MENU
- Product type
- Firmware version
- Software info
- Total hours
- No. of start-ups
- Rpm evacuator
- T. smoke
- Heat exchanger voltage
- Feed screw loading
- Flame
EXTERNAL THERMOSTAT CONNECTION (optional)
The room thermostat is not included with the stove and must be installed by a
qualified technician.
ATTENTION!
The electrical wires must not come into contact with the hot parts of the
stove.
The temperature of the stove can also be controlled by an external room
thermostat. It should be positioned centrally in the room where the stove is
installed. It provides a closer match between the heating temperature
requested of the stove and the actual room temperature it provides.
Connect the cables coming from the external thermostat to terminal 14 on the
board on the stove.
Enable the external thermostat (factory settings OFF) as follows:
- Press the “menu” key.
- Scroll with the arrows to “Settings”.
- Press “menu” to select.
- Now use the arrows to scroll to “External thermostat”.
- Press “menu” to select.
- Press the – + keys.
- Select “On” to activate the external thermostat.
- Press the “menu” key to confirm.
- Press the “esc” key to exit.
Once the external thermostat has been enabled, instead of displaying the detected temperature from the probe on the stove, ON or OFF will appear, depending on whether you have requested heat from the external thermostat or not.
ON if the external thermostat contact is closed, OFF if the contact is open.
Remote control (accessory – NOT SUPPLIED)
LEGEND OF BUTTONS
- Increase temperature set-point
- Decrease temperature set-point
- ON/OFF
- Temperature/power switch and vice versa.
- 5/6. Set power and ventilation
PLEASE NOTE Adjusting the temperature with the remote control has no effect if
the external thermostat has been selected.
Attention! Before using, remove the protection from the battery. The batteries
are not included.
Keys 1 and 2: set the room temperature (automatic mode). See paragraph
“Automatic mode”.
Keys 6 and 5: set power and ventilation (manual mode). The values that can be
set are from 1 to 5.
Power does not scale immediately but reaches it at the set time (1 power per
minute) Button 3: On/Off
Button 4: moves on from temperature to flame power; when passing from one
status to another, the following values will be set:
– Temperature 23°C.
– Power 3 ventilation 3
Batteries – type and replacement
The batteries are in the bottom of the remote control. To replace them, pull
out the battery holder and remove or insert the battery in the orientation
marked on the remote control and on the battery itself.
The remote control takes 1 CR2025 lithium battery.
Used batteries contain metals which are harmful to the environment, so they
must be disposed of separately in appropriate containers.
If the remote control is off because it has no battery, the stove can be
controlled with its top-mounted control panel.
While replacing the battery, observe the orientation marked inside the
battery compartment.
SAFETY DEVICES
SAFETY DEVICES
The product is fitted with the following safety devices
PRESSURE SWITCH
Monitors pressure in the smoke duct. It is designed to shut down the pellet
feed screw in the event of an obstructed flue or significant back-pressure
(from the wind).
SMOKE TEMPERATURE PROBE
Detects the temperature of the smoke, thereby enabling start-up or stopping
the product when the temperature drops below the preset value.
CONTACT THERMOSTAT IN THE FUEL TANK
If the temperature exceeds the preset safety level, it immediately shuts down
the running of the stove.
ELECTRICAL SAFETY
The stove is protected against violent changes in current by a general fuse
located in the control panel at the back of the stove. Other fuses that
protect the circuit boards are located on the latter.
SMOKE FAN
If the fan stops, the electronic board shuts off the supply of pellets in good
time, and an alarm message is displayed.
GEAR MOTOR
If the reduction motor stops, the stove will continue to run until the flame
goes out due to lack of fuel and until a minimum level of cooling is reached.
TEMPORARY POWER CUT
When a power cut is less than 10’’ the stove returns to its previous operating
state; if it is more, it executes a cooling/re-ignition cycle.
FAILED START-UP
If during ignition no flame develops, the stove will go into alarm condition.
TAMPERING WITH THE SAFETY DEVICES IS PROHIBITED
If the product is NOT used as described in this instruction manual, the
manufacturer declines all liability for any damage caused to persons and
property. The manufacturer furthermore refuses to accept responsibility for
damage to persons and property arising from the failure to observe all the
rules contained in the manual and in particular:
- All the necessary measures and/or precautions must be adopted when performing maintenance, cleaning and repairs.
- Do not tamper with the safety devices.
- Do not remove the safety devices.
- Connect the product to an efficient smoke expulsion system.
- First, check that the environment where it is to be installed is properly ventilated.
Only after having eliminated the cause of the intervention of the safety system is it possible to relight the product and therefore restore the automatic operation of the probe. This manual will help you understand which anomaly has occurred, and explain how to intervene according to the alarm message displayed on the appliance.
ALARMS
ALARM SIGNALLING
When a condition occurs other than the one expected for regular operation of
the stove, an alarm is triggered.
The reason for the alarm is given on the control panel. The sound signal is
not enabled for alarms A01-A02 in order not to disturb the user when there is
an absence of pellets in the night tank.
Panel signalling | type of problem | Solution |
---|---|---|
A01 | The flame does not light | Check the level of pellets in the hopper. |
Check that the brazier is correctly positioned in its seat and has no build-up
or unburned material.
Make sure the spark plug warms up.
Thoroughly empty and clean the brazier before restarting.
A02The| fire goes out abnormally.| Check the level of pellets in the tank.
A03the
Thermostat alarm| The temperature of the pellet hopper exceeds required safety
threshold.| Wait until the end of the cooling phase, stop the alarm and re-
ignite the stove setting the supply of fuel to minimum (SETTINGS menu – pellet
recipe). If the alarm persists, contact the service centre.
Check whether the room fan is working correctly.
A04| Smoke overtemperature.| Reduce the load of pellets (SETTINGS menu –
Pellet recipe); check cleaning of the brazier.
A05 Safety devices alarm| Smoke pressure switch intervention| Check for
chimney obstructions / door open
Fuel loading hatch| Close the hatch.
Lower the fuel level in the hopper.
Open stove door| Close the door
A08| Anomalous operation of smoke fan.| Delete the alarm and switch the stove
on again. If the alarm persists, contact the service centre.
A09| Fault with the smoke sensor.| Delete the alarm and switch the stove on
again. If the alarm persists, contact the service centre.
Service| Routine maintenance warning (does not seize)| When this blinking
message appears upon start-up, it means it is time to carry out scheduled
maintenance. Call the assistance centre.
ALARM RESET
To reset the alarm, press and hold key 1 (ESC) for a few seconds. The stove
checks whether the cause of the alarm is ongoing.
In the first case, the alarm continues to be displayed, in the second case it
turns OFF.
If the alarm persists, contact a service centre.
NORMAL SHUTDOWN (on the panel: OFF with flashing flame symbol)
When the shutdown key is pressed, or when there is an alarm signal, the stove
enters the thermal extinguishing phase which involves automatic execution of
the following phases.
- Stop pellet loading
- The room fan maintains the set speed until reaching the switch-off temperature
- The smoke extractor fan is activated at maximum speed and remains on for a fixed period of 10 minutes, at the end of which if the smoke T has dropped below the stop threshold, the fan stops, otherwise it will continue to operate at minimum speed until the temperature drops below the threshold.
- If the stove has been shutdown regularly but, due to thermal inertia, the smoke temperature exceeds the threshold again, the shutdown phase will be repeated at minimum speed until the temperature drops.
BLACKOUT WITH STOVE ON
In the event of a blackout, the stove does the following:
- Power failure of less than 10”: continues the work in progress;
- After a loss of power of more than 10’’ which occurred when the stove was on, or during ignition, you can restore the stove to its previous operating condition when power returns as follows:
1. Cool the boiler by activating the smoke extractor at minimum speed for 10’ then proceed to the next step;
2. Restore the stove to the operating condition prior to the blackout.
During phase 1, the panel shows ON BLACK OUT.
During phase 2, the panel shows Start-up.
If during phase 1 the stove receives manual user commands from the control panel, it stops the blackout restoration sequence and begins the start-up or shutdown commanded by the user.
BLACKOUT OF MORE THAN 10’’ DURING EXTINCTION OF STOVE
If the stove experiences a loss of power GREATER THAN 10” while it is shutting
down, when power is restored to the stove, it will automatically turn on in
shutdown mode, even if the smoke temperature has fallen below 45°C in the
meantime. This phase can be skipped by pressing key 1 (esc) (skips to start-
up) and pressing it again (recognises that the stove is off).
BLACKOUT OF MORE THAN 10’’ WITH THE STOVE OFF FROM ECOSTOP
Once power has been restored, a 5-minute timer is set as though the stove were
in switch-off mode; should there be a request for heat in these 5 minutes, the
stove will not start.
SAFETY DEVICES ALARM A05
The safety devices alarm includes the intervention of the smoke pressure
switch, of the fuel loading hatch and of the open stove door.
The alarm will be triggered after 30 seconds, after which the stove will stop
working (e.g. after 30 seconds with the pellet loading hatch open, alarm A05
will be triggered).
In the event that alarm A05 is triggered often, please note that:
A05
Safety devices alarm| Smoke pressure switch intervention| (heck for chimney
obstructions / door open
---|---|---
Fuel loading hatch| (lose the hatch.
Lower the fuel level in the hopper.
Open stove door| (lose the door
you must check some points to verify the cause of the problem and possibly act
on some adjustments and/or safety devices to restore the correct operation of
the product.
However please note that all the adjustments and alterations affecting the
operational safety devices, must only be performed if THE
PRODUCT IS INSTALLED IN COMPLIANCE WITH THE STANDARDS AND LAWS IN FORCE AND IF
IT IS SERVICED PROPERLY BY AUTHORISED AND SPECIALISED PERSONNEL. Alterations
performed randomly, to ensure operation of the product even in the non-
compliant conditions, can cause serious damage to property and injuries to
people.
Attention!
The adjustments must only be carried out by authorised and qualified personnel
under their responsibility and by checking the conformity of the installation
beforehand. The manufacturer declines all liability for damage to property or
injuries to people in the event of altering the safety devices.
All liability for improper use of the product is entirely borne by the user
and relieves the Manufacturer from any civil and criminal liability.
Series of stoves equipped with a pressure switch installed on the hopper with
the sampling point positioned on the bottom, to the right of the gear motor.
This system protects the whole system ensuring tightness of the stove
throughout its duration.
It is important to understand that the pressure switch can intervene with each
significant drop in negative pressure and may be due to:
- The flue clogging.
- The presence of a foreign body in the flue (birds, nests, clogged grates, etc.).
- Wind coming through the flue because it is unprotected or the installation was wall-mounted or required no flue.
- Cold air draught down the flue.
- A damaged pressure switch.
- Blocked membrane inside the pressure switch because soot or pellet dust filtrated.
- The pellet hopper is open or ajar for more than 60 seconds (60 seconds is the estimated time to reload the hopper).
- Pellet trapped between the hopper cover and the hopper, which prevents the gasket to seal.
- Broken/worn hopper cover gasket.
- The gasket between the feed screw and the boiler is damaged or positioned incorrectly.
- Fire door is open or the gasket is worn.
- Clogged lateral smoke exchangers.
- Inspection caps with gaskets installed incorrectly after maintenance.
- Feed screw clogged by a compressed pellet at the top.
- The installation is compliant and the flue/smoke fitting does not generate obvious obstructions which can stop the release of smoke, such as: long horizontal sections (over 3 metres), uninsulated smoke ducts, “wall-mounted” smoke exhaust without proper terminals (installation regulated and permitted in France only [ZONE 3])
- Internal air extraction or recirculation systems (e.g. VMC systems) that generate internal negative pressure exceeding those required by law (not exceeding 4 Pa)
- Installed without combustion air ducting, it is crucial to check that there is an efficient air inlet dedicated to the stove, according to the specifications referred to in chapter 2 of this manual.
The electronic board has also been equipped with an automatic device with a
timer and contactors which increases the RPM of the smoke extractor so as to
restore the negative pressure inside the hopper and therefore the pressure
switch, if the cover is opened for top-up or if there is an immediate or
occasional pressure drop such as gusts of wind outside. If the pressure drop
lasts for more than 60 seconds, the product is set in an alarm statue (A05 or
A18)
Remembering that the draught recommended for the products to work properly is
10 Pa at maximum capacity and 5 Pa at minimum (according to the technical data
sheet found in the user and maintenance manual), adjustments may be required
in worse draught conditions (also due to the position of the flue in areas
that are particularly subject to adverse weather such as prevailing winds,
snow, northern exposure, etc.) so as to always guarantee the required negative
pressure inside the hopper.
To compensate for the lack of internal negative pressure simply adjust the
speed (RPM) of the smoke extractor so as to guarantee the minimum tabular
values.
If the negative internal pressure values are noted to be lower than those
indicated, this can also be due to the internal gaskets not being sealed
properly or by the product being worn over time.
OPERATING INSTRUCTIONS ON NEGATIVE PRESSURE INSPECTIONS AND POSSIBLE
VARIATIONS OF THE RPM
Connect a pressure gauge to the pressure outlet on the hopper:
- In the case of products with a specific pressure outlet in the hopper, access the sampling point and connect the pressure gauge
- In the case of products without a dedicated pressure outlet, disconnect the tube of the pressure switch from the pressure outlet on the hopper, add a “T” on the tube to intercept the circuit, connecting the gauge and reconnect the tube to the pressure outlet on the hopper.
Possible adjustments of the combustion and consequently of the negative
pressure inside the hopper can be implemented in two ways:
A) Change the RPM value of the smoke extractor in the SETTINGS MENU
- The available values are from -3 to +3 which, as a percentage, correspond to:
- RPM: -10% +10% in Active System products
- RPM: -30% +50% in NON Active System products
- The percentage variation affects all the power values (1 to 5) proportionally and as a percentage. The percentage variation does not affect intermediate operating stages such as SWITCH ON, FIRE ON or SWITCH OFF
- As the RPM increase, suction also increases and consequently the internal negative pressure, thereby compensating the phenomena that trigger the alarm.
B) Adjusting the RPM of the gear motor manually in the TECHNICAL PARAMETERS MENU
- The pressure switch has a calibration of 10/20 Pa which means that it disarms when the negative pressure inside the hopper drops below 10 Pa and requires more than 20 Pa negative pressure inside the hopper for it to rearm
- The negative pressure value at the minimum power must always be higher than 10 Pa while also maintaining a reasonable margin that can be used over time due to the gaskets being worn or something similar (at least 12/13 Pa)
- The negative pressure at maximum power must always be above 20 so that the pressure switch can rearm when the pressure switch rearming automated device is activated. The pressure switch rearming procedure (such as after opening the cover to top-up the hopper), requires the electronics to push the RPM of the smoke extraction fan up to POWER 5 (P5) for a few moments. At P5, therefore, the negative pressure inside the hopper must always be > 20 Pa (recommended 22/23 Pa to preserve the margin).
- N.B. = The TECHNICAL PARAMETERS menus are password-protected to prevent the user from accessing them inadvertently
Attention! The factory setting on the product is designed to obtain the
certified technical data. In the event of data discrepancy (as for the pellet
recipe), the settings may be modified as set out above. The adjustments must
only be carried out by authorised and qualified personnel under their
responsibility and by checking the conformity of the installation beforehand.
NEGATIVE PRESSURE INSIDE THE HOPPER WITH FACTORY-SET PARAMETERS AND A
DRAUGHT OF 5 Pa (MINIMUM RECOMMENDED)
POWER | P1 | P2 | P3 | P4 | P5 | VALUES |
---|---|---|---|---|---|---|
6 kW | 13.7/14.2 Pa | 15.1/15.6 Pa | 17.1/17.5 Pa | 19.1/19.5 Pa | 22.0/22.2 Pa |
Draught
95°C| 110°C| 125°C| 141°C| 165°C| Smoke temperature
8 kW| 13.8/14.3 Pa| 15.6/16.1 Pa| 17.8/18.0 Pa| 21.7/22.2 Pa| 26.1/26.6 Pa|
Draught
104°C| 119°C| 145°C| 148°C| 184°C| Smoke temperature
10 kW| 15.9/16.3 Pa| 20.4/20.9 Pa| 25.8/26.3 Pa| 31.8/32.3 Pa| 36.5/37.0 Pa|
Draught
108°C| °C| 150°C| °C| 230°C| Smoke temperature
12 kW| 16.5/17.3 Pa| 20.4/20.9 Pa| 25.8/26.3 Pa| 31.8/32.3 Pa| 36.5/37.1 Pa|
Draught
118°C| 127°C| 155°C| 172°C| 195°C| Smoke temperature
14 kW| 17.6/18.0 Pa| 19.8/20.4 Pa| 23.1/23.7 Pa| 28.9/29.6 Pa| 37.8/38.2 Pa|
Draught
118°C| 131°C| 161°C| 187°C| 210°C| Smoke temperature
PLEASE NOTE The indicated negative pressure readings may differ by ±1Pa based
on flue gas temperature. Likewise, flue gas temperature may differ by ±10°C
based on fuel quality or appliance cleanliness.
Changing the smoke fan revolutions
In the event the installation presents problems in extracting smoke (lack of
draft or even pressure in the duct), it is possible to increase the smoke and
ash extraction speed. This change resolves all the potential problems related
to pellets clogging in the brazier and deposits forming at the bottom of the
brazier itself caused by poor quality fuel or fuel that produces a lot of ash.
The extraction speed may be altered between -30% to +50%, with increments of
10 percent at a time. Negative variation can be necessary if the flame is too
low.
To alter this parameter, proceed as follows:
- Press the “menu” key.
- Use the arrow keys to scroll through and select “Settings”
- Press “menu” to confirm.
- Scroll with the arrows and select “Fumes rpm Var.”
- Press “menu” to confirm.
- Alter the % with the + – keys.
- Press ‘’menu’’ to confirm and ‘’esc’’ to exit.
RECOMMENDATIONS FOR SAFE USE
ONLY CORRECT INSTALLATION AND APPROPRIATE MAINTENANCE AND CLEANING OF THE APPLIANCE CAN GUARANTEE CORRECT OPERATION AND SAFE USE OF THE PRODUCT.
We would like to inform you that we are aware of cases of malfunctioning of domestic pellet-fuelled heating products, mainly due to incorrect installation and inappropriate maintenance. We would like to assure you that all of our products are extremely safe and certified according to European standards of reference. The ignition system has been tested with the utmost attention to enhance ignition efficiency and to prevent any type of problem, even in the worst operating conditions. In any case, like for any other pellet-fuelled product, our appliances must be installed correctly and undergo regular periodical cleaning and maintenance to guarantee safe operation. Our studies show us that malfunctioning is mainly due to the combination of part or all of the following factors:
-
Brazier holes obstructed or brazier deformed, due to lack of maintenance and conditions which can cause delayed ignitions, generating an anomalous production of unburned gases.
-
Insufficient combustion air due to a reduced or clogged air inlet duct.
-
Use of smoke ducts nonconforming to regulatory installation requirements, failing to guarantee an adequate draught.
-
Partially clogged chimney, due to lack of maintenance, reducing the draught and making ignition difficult.
-
End chimneypot nonconforming to the indications of the instruction manual, and therefore not suitable to prevent potential inverse draught.
-
This factor is crucial when the product is installed in especially windy areas, such as coastal regions.
The combination of one or more of these factors could generate important malfunctioning conditions.
To keep this from occurring, it is fundamental to guarantee that the product is installed in compliance with standards in force.
Furthermore it is of the utmost importance to respect the following simple rules: -
Every time the brazier is removed for cleaning, it must always be put back properly in the work position before using the product, completely removing any residual filth left on the support base.
-
Pellets must never be loaded in the brazier manually, either before ignition or during operation.
-
The accumulation of unburned pellets ensuing a failed ignition must be removed before repeating ignition. Also check that they are fed correctly and that the combustion air inlet/smoke outlet are regular.
-
If ignition fails repeatedly, immediately suspend use of the product and contact a qualified technician to check its operation.
Compliance with these indications is absolutely sufficient to guarantee proper operation and to avoid any type of problems with the product.
If the above-mentioned precautions are not taken, and during ignition the brazier is overloaded with pellets thus generating anomalous smoke in the combustion chamber, carefully follow the indications below: -
Do not disconnect electrical power to the product for any reason whatsoever: this would stop the smoke extractor, releasing smoke into the environment.
-
Take the precaution of opening the windows to ventilate the installation room from any smoke in the environment (the chimney might not work properly).
-
Do not open the fire door: this would compromise regular operation of the smoke extraction system to the chimney.
-
Just switch the stove off by acting on the on-off button on the control panel (not the rear power supply socket button!) and move away until smoke has been completely extracted.
-
Before attempting re-ignition, clean the brazier and its air passage holes completely of all deposits and unburned pellets. Put the brazier back in place, removing any residue from its support base. If ignition fails repeatedly, immediately suspend use of the product and contact a qualified technician to check its operation and the chimney.
CLEANING
Only by properly servicing and cleaning the product is it possible to ensure
its safety and correct operation.
ATTENTION!
All the cleaning operations of all parts must be performed with the product
completely cold and the plug disconnected.
Disconnect the product from the 230V power supply before performing any
maintenance operation.
The product requires little maintenance if used with certified good quality
pellets.
DAILY OR WEEKLY CLEANING PERFORMED BY THE USER
Brazier cleaning
Before ignition, always clean the brazier “G” and remove any ash or
incrustation from it that might obstruct the air flow holes, paying attention
to hot ash. In the case of ignition failure, or if fuel in the hopper runs
out, unburned pellets may accumulate in the brazier. Always empty the residue
in the brazier before each start-up. Only if ash is completely cold may a
vacuum cleaner be used to remove it. In this case, use a suitable vacuum
cleaner to remove small sized particles.
**** REMEMBER THAT ONLY A CORRECTLY POSITIONED AND CLEAN BRAZIER CAN
GUARANTEE IGNITION AND OPTIMAL OPERATION OF YOUR PELLET PRODUCT. IN CASE OF
FAILED IGNITION AND AFTER ANY OTHER LOCK STATE OF THE PRODUCT, IT IS ESSENTIAL
TO EMPTY THE BRAZIER BEFORE EVERY RESTART.
For the brazier to be cleaned properly, remove it from its housing completely
and thoroughly clean all the holes and the grate on the bottom. If good
quality pellets are used, you will normally only need to use a brush to
restore the optimal operating conditions of the component.
Cleaning the ash collection compartment
To clean the ash collection compartment, you must raise grille “i” by rotating
until it rests against the firebox. Clean out any residual ash before lowering
the grille “i”. The quality of the pellets used and user experience will
determine the required cleaning frequency.
However, it is recommended not to exceed 2 or 3 days.
CLEANING THE GLASS
It is recommended to clean the ceramic glass with a dry brush, or if it is
very dirty, spray a little specific detergent and clean with a cloth.
ATTENTION!
Do not use abrasive products and do not spray the glass cleaning product on
the painted parts and on the door gaskets (ceramic fibre cord).
CLEANING THE STOVE CLADDING
Below are a few indications to clean the metal cladding of the stove:
- use only water, if necessary with the addition of neutral detergents (pH7) and characterised by light additives.
- use only water on a cloth. There are electrical parts that could be damaged.
- use soft, non-abrasive cloths. Do not rub the surfaces.
- do not use solvents, abrasive or scratching agents. Do not use prepared compounds for cleaning paints as they could be aggressive.
PERIODIC CLEANING PERFORMED BY A QUALIFIED TECHNICIAN CLEANING THE HEAT
EXCHANGER AND THE LOWER COMPARTMENT
Half-way through the winter season, but especially at the end, the compartment
through which the exhaust smoke passes will need to be cleaned.
This cleaning process is mandatory in order to facilitate the general removal
of all combustion residue, before it becomes very difficult to remove it due
to the humidity compacting it over time.
ATTENTION:
Cleaning is mandatory to be performed at the end of the season by an
authorised and skilled technician so that even the seals can be replaced.
CLEANING THE LOWER COMPARTMENT
To remove ash from the lower compartment take the cladding off the stove. Then
take out the four “s” screws and remove cap “M”. Clean all ash residues from
the fan compartment also (refer to the instructions on the next page).
CLEANING THE SMOKE EXTRACTOR
Clean the smoke extractor by loosening the four screws “y” and removing the
plate “n” and the gasket “o”. With the nozzle of the vacuum cleaner remove all
the ash and soot accumulated inside the smoke extractor (area indicated by the
arrow).
Before putting the cap “n” back, it is recommended to change the gasket “o”.
CLEANING THE EXCHANGER
CLEANING THE UPPER COMPARTMENT
Clean the upper exchanger when the stove is cold and without the cladding in
question. After removing the cap to clean the lower compartment “n” (see
previous paragraph), use a stiff rod or a bottle brush to scrape the walls of
the firebox (see arrow) to make the ash fall into the lower compartment.
Then remove the upper calorite plate “H”, to do this open the firebox door, hold the top of the calorite plate “H” and lift it upwards, tilt it to the right or to the left in order to release it from the supports and remove it.
Use a stiff rod or a bottle brush to scrape the walls of the firebox (see arrow – respectively to the right and to the left of the firebox) to make the ash fall into the lower compartment.
Use a vacuum cleaner nozzle to vacuum up any remaining ash and dust on the exchanger (see arrow).
CLEANING THE SMOKE EXPULSION SYSTEM AND GENERAL CHECKS
Clean the smoke extractor system, especially around the “T” joints, elbows and
any horizontal sections of the smoke duct.
For information on periodically cleaning the flue, contact a skilled chimney
sweep.
Check the seal of the ceramic fibre gaskets on the door of the stove. If
necessary, order new replacement gaskets from the retailer or contact an
authorised service centre to carry out the operation.
ATTENTION:
The frequency with which the smoke outlet system is cleaned depends on the use
of the boiler and the type of installation.
We recommend relying on an authorised service centre for end-of-season
cleaning and maintenance, as they will carry out all of the previously
mentioned work and inspect the stove components.
CLEANING TOP OUTLET
When the side panels have been taken down, clean the smoke pipe.
Remove the cap “Q” and the gasket “g”. Then clean the pipe “T”, the cap “Q”
and replace the gasket “g” if necessary.
PERIODICAL CHECK OF THE DOOR CLOSURE
Make sure the door closure ensures a correct sealing action (with the “paper
sheet” test) and that when the door is closed, the closing block (X in the
figure) does not protrude from the sheet metal to which it is secured. For
some products it will be necessary to disassemble the cladding to be able to
assess the anomalous protrusion of the block when the door is closed.
SHUTDOWN (end of season)
At the end of each season, before switching the product off, it is recommended
to remove all the pellets from the hopper with a vacuum cleaner with a long
pipe.
We recommend removing the unused pellets from the hopper because they can
retain moisture. Disconnect any combustion air ducting that can lead to
moisture inside the combustion chamber but, above all, ask the specialised
technician to refresh the paint inside the combustion chamber with the special
silicone spray paints (available at any store or Technical Assistance Centre)
during the necessary annual end of season scheduled maintenance operations.
This way the paint will protect the inner parts of the combustion chamber,
blocking any type of oxidative process.
When not in use the appliance must be disconnected from the mains power
supply. It is recommended to remove the
power cable for additional safety, especially in the presence of children.
The service fuse may have to be replaced if the control panel display does not
switch on when the product is switched on again by pressing the main switch on
its side.
There is a fusebox on the side of the product, near the power socket. Open the
fusebox cover with a screwdriver and replace the fuses if necessary (3.15 A
delayed) – seek assistance from an authorised and qualified technician.
CHECKING THE INTERNAL COMPONENTS ATTENTION!
The internal electromagnetically components must only be checked by qualified
personnel whose technical expertise includes combustion and electricity.
We recommend that an annual maintenance service is carried out (with a
scheduled service contract). This service is essentially a visual and
functional inspection of the internal components. The following is a summary
of the checks and/or maintenance that are essential for the correct operation
of the product.
| PARTS/INTERVAL| 1 DAY| 2-3 DAYS| 15/20 DAYS| 1 YEAR
---|---|---|---|---|---
UNDER THE USER’S RESPONSIBILITY| Brazier| •| | |
Ash compartment| | •| |
Glass| | •| |
Air filter (for the models fitted with it)| | | •|
Remote control battery (optional remote control)| | | | •
BY THE QUALIFIED TECHNICIAN| Upper exchanger| | | | •
Lower exchanger| | | | •
Smoke duct| | | | •
Gaskets| | | | •
Door closure operation| | | | •
FAULTS/CAUSES/SOLUTIONS
ATTENTION!
All repairs must only be carried out by a specialised technician, with the
product switched off and the plug disconnected.
ANOMALY | POSSIBLE CAUSES | SOLUTIONS |
---|---|---|
The pellets are not fed into the combustion chamber. | The pellet hopper is | |
empty | Fill the hopper with pellets. | |
Sawdust has blocked the feed screw | Empty the hopper and remove the sawdust |
from the feed screw by hand.
Faulty gear motor| Replace the gear motor.
Faulty electronic board| Replace the circuit board.
The fire goes out or the boiler stops automatically.| The pellet hopper is
empty| Fill the hopper with pellets.
The pellets are not fed| See the previous anomaly.
The pellet temperature safety probe has been triggered| Let the product cool
down, restore the
thermostat until the lockout is off and switch the product back on. If the
problem persists, contact Technical Assistance.
The door is not closed properly or the gaskets are worn| Close the door and
replace the gaskets with original ones.
Unsuitable pellets| Change the type of pellets with those
recommended by the manufacturer.
Low pellet supply| Check the flow of fuel following the instructions in the
manual.
The combustion chamber is dirty| Clean the combustion chamber, following the
instructions in the manual.
Clogged outlet| Clean the smoke duct.
Faulty smoke extraction motor| Check the motor and replace it, if necessary.
Pressure switch broken or defective.| Replace the pressure switch.
The product works for a few minutes and then switches off.| Start-up phase is
not completed| Repeat start-up.
Temporary power cut| Wait for the automatic restart.
Clogged smoke duct| Clean smoke duct.
Faulty or malfunctioning temperature probes| Check and replace the probes.
Faulty spark plug| Check the spark plug and replace it, if necessary.
Pellets accumulate in the brazier, the glass of the door gets dirty and the
flame is weak.| Insufficient combustion air.| (lean the brazier and check that
all the holes are clear. Perform a general cleaning of the combustion chamber
and the smoke duct. (heck that the entry of air is not obstructed.
Damp or unsuitable pellets.| Change the type of pellets.
Faulty smoke extractor motor.| (heck the motor and replace it, if necessary
The smoke extractor motor does not work.| No electrical supply to the stove.|
(heck the mains voltage and the protection fuse.
The motor is faulty.| (heck the motor and capacitor and replace them, if
necessary.
Defective motherboard.| Replace the electronic board.
The control panel is broken.| Replace the control panel.
The convection air fan never stops.| Faulty or malfunctioning temperature
control probe.| (heck the probe and replace it, if necessary.
In the automatic position, the stove always runs at full power.| Thermostat is
set to minimum.| Reset the temperature of the thermostat.
The room thermostat is in the maximum position.| Reset the temperature of the
thermostat.
Malfunctioning temperature probe.| (heck the probe and replace it if
necessary.
Faulty or malfunctioning control panel.| (heck the panel and replace it, if
necessary
The product does not start.| No power supply.| (heck that the plug is inserted
and the main switch is in the1″ position.
Pellet sensor has seized up.| (heck the recipe parameters.
Blown fuse.| Replace the fuse.
Pressure switch broken (lockout indicated).| Insufficient pressure of water in
stove.
(logged smoke outlet or smoke duct.| (lean the smoke outlet and/or the smoke
duct.
Noisy air fan even though it is set to minimum| High set flame causes
ventilation increase| Lower set flame from Adjustments menu
No increase in temperature with
stove in operation.| Incorrect combustion adjustment.| Check recipe.
Set flame 1 setting (level too low)| Increase power from the settings menu.
Poor pellet quality.| Using pellets from the producer.
CIRCUIT BOARD
LIVE ELECTRICAL CABLES DISCONNECT THE POWER SUPPLY CABLE 230V BEFORE CARRYING
OUT ANY OPERATIONS ON THE ELECTRICAL BOARDS
MOTHERBOARD WIRING KEY
1. FUSE | 10. REAR ROOM FAN (FAN 2) |
---|---|
2. BOARD PHASE | 11. SMOKE SENSOR |
3. BOARD NEUTRAL | 12. EXTERNAL THERMOSTAT CONNECTION (TERMINAL BLOCK) |
4. SMOKE EXTRACTOR FAN | 13. ROOM TEMPERATURE PROBE |
5. FRONT ROOM FAN (FAN 1) | 14. SMOKE EXTRACTOR FAN SPEED CONTROL |
6. PELLET SAFETY THERMOSTAT | 15. EASY CONNECT |
7. GLOW PLUG | 16. MODEM CONNECTION (if applicable) |
8. AIR PRESSURE SWITCH | 17. CONTROL PANEL |
9. FEED SCREW | 18. REAR ROOM FAN (FAN 3) |
PLEASE NOTE The electrical wiring of individual components is fitted with pre-wired connectors of different sizes.
MCZ GROUP S.p.A. Via La Croce n°8
33074 Vigonovo di Fontanafredda (PN) – ITALY
Telephone: 0434/599599 a.s.
Fax: 0434/599598
Website:www.mcz.it
e-mail:mcz@mcz.it
8902247300 REV 0 24/02/2023
Documents / Resources
| MCZ
S2 Teia Comfort Air 10 Pellet
Stove
[pdf] Instruction Manual
S2 Teia Comfort Air 10 Pellet Stove, S2, Teia Comfort Air 10 Pellet Stove,
Comfort Air 10 Pellet Stove, Air 10 Pellet Stove
---|---