G21 8595627422127 Impact 16 Dehumidifier Instruction Manual

June 4, 2024
G21

G21 8595627422127 Impact 16 Dehumidifier Instruction Manual
G21 8595627422127 Impact 16 Dehumidifier

Thank you for purchasing our product!
Read this manual carefully prior to using the appliance.

Safety instructions

  • Install this appliance on a firm level place to reduce vibration and noise.
  • Do not place in water or other liquids.
  • In order to prevent accidents, please do not use this dehumidifier if wires or other connections are damaged.
  • This appliance can be used by children aged from 8 years and above and people with reduced physical, sensory or mental capabilities or lack of experience or knowledge if they have been given supervision or instruction concerning the use of this appliance in a safe way and understand the hazards invloved. Children shall not play with the appliance, cleaning and user maintenance shall not be made by children without supervision.
  • After you turn the appliance OFF, take the plug out of the socket.
  • Indoors use only.
  • Empty the water tank to prevent overflow and spill before restarting.
  • Do not tilt as it may cause water leakage and damaging the appliance.
  • Do not insert any hard objects into the appliance in case error and damage occur.
  • If the supply cord is damaged, it must be replaced by a qualified person in order to avoid any damage.

Warning:

  • Do not place close to heating devices (flame or heaters, etc.).
  • Do not turn OFF by pulling the power cord out of the socket.
  • Do not use any flammable substances near this appliance.
  • Do not clean with water, use a damp soft cloth.
  • Do not wipe with chemical solvents, use a natural detergent.
  • Do not tilt over 45°or place upside down.

Frequent questions

Why does the appliance store less water in the water tank in winter?

The temeprature is low and air is dry, not a fault.

Why can’t the appliance run or stops running suddenly?

The water tank might be full of water or it is not installed properly – drain the water tank or re-install it. The appliance might be in the „dehumidification mode“, the ambient temperature is lower or higher than requested (it cannot be performed when the ambient temperature is < 5 °C or > 32 °C).

Why is hot air blown out from the air supply outlet?

The appliance extracts air in the room and the dehumidification unit cools the air. The temperature decreases below the condensation point, the air condenses into water drops, which fall into the water tank and the dehumidified air is heated by the temperature running unit. This can reduce energy consumption and also accelerate dehumidification, therefore, hot air is blown out, not a fault.

Installation

  • Please drain the water from the water tank before running the appliance.

  • When the appliance is ON, please do not open doors and windows if possible since it can save energy resources.

  • When the dehumidifier is installed, a certain space must be reserved around the appliance.
    The minimum distance above is 50 cm and 20 cm in any other direction, as shown in the picture below.

  • When big noise is found during operation of this dehumidifier: It is recommended to insert pads or damping rubber sheets below this appliance. It can reduce the vibration and noise and can also reduce damaging wood floor or carpet (due to vibrations or water leakage)
    Installation

Components

Components

back side

Components

Control panel

Control panel 

Timer – 24h timer setup, press this key to set on/off time of the dehumidifier. The setting range is from 0 to 24 h, it will increase by 1 hour per press. Long press to cancel.
Internal drying function – Press this button to start the inside drying function.
Fan – In AUTO mode and Cloth dry mode, press this button to change the fan speed.
Display screen – In AUTO mode or Cloth dry mode, it will indicate the actual room humidity. In timing mode, it indicates the setting time.
Humidity setting – In AUTO mode, press the key to set humidity, humidity range is from 30-80 %, it changes by 5 % with every press.
Mode – When the appliance is on or the timing power is on, press this button to choose auto or continuous dehumidifying (dry cloth function). The lights will flash when you choose the modes.
On/Off – Press the button to turn on/off the appliance.

Operation

Timing off
When the dehumidifier is running, press this button to adjust the time between 0 hour and 24 hours, Press the button once to increase the set time by 1 hour. After the set time exceeds 24 hours, the display returns to 0 to start the cycle again. When the set time is reached, the dehumidifier turns off automatically. After setting is completed, the set time is confirmed after 5 seconds. In the ‘timer off’ state, the button light on the button is lit.

Timing on
When the dehumidifier is in the standby state, the method for adjusting the set time by the button is the same as for timer ‘off’. When setting is completed, the set time is confirmed after 5 seconds. In the ‘time on’ state the light on the button is lit, and the set time is displayed on the control panel.

AUTO mode
Select AUTO dehumidification. If the room humidity is higher than the set humidity or is between + 5 % or – 5 % of the set humidity, the compressor will start and the fan will run at the set speed.
If the room humidity is lower than the set humidity by – 5 %, then the compressor will stop but the fan will run at the set speed. The default set humidity value is 50 %.

Cloth dry mode
Select CONTINUOUS dehumidification. Regardless of the relative humidity in the room, the compressor starts, the fan runs at high speed by default, and the fan speed can be regulated via the fan speed button.

Drying function
Press the DRYING button to start the drying process. The appliance starts at HIGH air speed and releases air continuously for 30 minutes. The appliance turns to run at LOW air speed and lasts for 15 minutes.

To stop, press the DRYING button again to cancel the process and recover to the prior running mode. Or, press the POWER button to stop the process and recover to standby mode.

Water drainage

Manual

  • When the water tank is full, the full water icon on LCD display flashes (the compressor, fan will stop running), the buzzer sounds 10 times to remind the user till the water is drained.

  • Place both hands respectively at the side of the back cover side of the depression, gently remove the water tank and open the tank cover on the right side of the body, then pour the water from the gap between water tank and the cover.

  • Close the tank cover and rotate the water tank handle down, then put the water tank gently back in to restart the appliance.
    Water drainage

  • Attention: when the water tank is full of water, please empty it. Before putting the water tank into the dehumidifier, please confirm whether the floater rotates flexibly or not, then put it in position using both hands.

Continuous drainage (Optional)

  • If you don’t want to drain the water tank frequently, you can connect a drainage pipe (with inner diameter 9 mm) to the drainage mouth to drain the water automatically.
  • Note: Make sure the pipe is attached firmly. Do not use a pipe longer than 60 cm. The height of the drainage cannot surpass the height of the drainage mouth – possible water leakage.
    Water drainage

Maintenance

Precautions:

  • Please disconnect the power plug before maintenance or repair to prevent electric shock.
  • If the dehumidifier is not used for a long time, please disconnect the power supply.
  • Please do not clean the appliance‘s body with chemical solvents such as alcohol, gasoline etc..
  • Please clean the water tank and its cover with soft cloth dipped in cold or warm water at regular time to prevent mould inside the dehumidifer.
  • Wipe the surface of the appliance slightly with wet cloth and do not use detergent or abrasive in case the plastic surface is damaged.
  • Clean the filter at least once per two weeks with cold or warm water. Do not use chemical solvents or hot water.

Troubleshooting

Symptoms

|

Possible reason

|

Solution

---|---|---

The dehumidifier does not run.

|

  • Power plug fell out.

|

  • Insert the plug into socket.

  • Water tank full of water or place dat incorrect position.

|

  • Drain the water tank and place it back in correctly.

  • The ambient temperature is lower than 5 °C or higher than 32 °C.

|

  • Normal phenomenon.

The dehumidification function is not effective.

|

  • Room temperature or humiditiy too low.

|

  • In dry seasons the dehumidification ability will reduce.

  • Air outlet and inlet blocked.

|

  • Clean up the object block the air outlet and inlet.

Air is not blown out.

|

  • Air filter blocked.

|

  • Clean the air strainer.

Noise is abnormal during operation.

|

  • Appliance placed improperly so that it is inclined or unstable.

|

  • Place the appliance on a firm level place.

  • Air strainer blocked.

|

  • Clean the air strainer.

  • „Tittering“ sound.

|

  • The flowing sound of refrigerant, a normal phenomenon.

Water leakage

|

  • Connection of drainage pipe becomes loose.

|

  • Fasten drainage pipe.

  • Drainage system is blocked.

|

  • Remove obstacles and straighten out the waterpipe.

Frosting occurs

|

  • The ambient temperature is low and i tis in the state of waiting to defrost.

|

  • It is a normal phenomenon and the appliance has the automatic defrosting function.

The English version of the manual is an exact translation of the original manufacturer‘s instructions.
Images used in this manual are for illustrational purposes only and may differ from the actual product.

Safety instructions for installing the device using the R290 refrigerant

gas

To avoid damage, place the unit in an upright position for at least 24 hours before initiation.
Make sure that the air outlet and air inlet are never blocked.
Only operate the unit on a horizontal surface to ensure no water leaks out.

Warnings

  • Do not exceed impedance greeter than 0.236ohm in supply the appliance is connected to.

  • Any person who is involved with working on or breaking into a refrigerant a refrigerant circuit should hold a current valid certificate from an industry-accredited assessment authority.

  • Remember the environment when disposing of packaging around the appliance and when the appliance has reached its by date.

  • A warning that the appliance shall be stored in a well-ventilated area where the size corresponds to the room area as specified for operation.

  • The appliance shall be stored so as to prevent mechanical damage from occurring.

  • Information for spaces where refrigerant pipes are allowed, including statements

    • that the installation of pipe-work shall be kept to a minimum;
    • that pipe-work shall be protected from physical damage and, in the case of flammable refrigerants, shall not be installed in an unventilated space;
    • that compliance with national gas regulations shall be observed;
    • that mechanical connections shall be accessible for maintenance purposes;
    • that, for appliances containing flammable refrigerants, the minimum floor area of the room shall be mentioned in the form of a table or a single figure without reference to a formula;
  • A warning to keep any required ventilation openings clear of obstruction;

  • A notice that servicing shall be performed only as recommended by the manufacturer;

  • When the portable air conditioner or dehumidifier is turned on, the fan can work continuously stable under normal conditions to provide the minimum air volume of 100m3/h even when the compressor is closed due to the temperature controller.

  • Use only implements recommended by the manufacturer for defrosting or cleaning

  • Do not perforate any of the components in the refrigerant circuit. Refrigerant gas may be odourless

  • Use care when storing the appliance to prevent mechanical faults.

  • Maintenance and repairs requiring the assistance of other qualified personnel must be carried out under the supervision of specialists in the use of inflammable refrigerants.


CAUTION ON FIRE

READ THE MAUAL CAREFULLY BEFORE USING THE APPLIANCE R290 refrigerant gas complies with European environmental directives.
Appliance shall be installed, operated and stored in a room with a floor area larger than 4 m2.

Additional warning for appliance with R290 refrigerant gas (refer to the

rating plate for the type of refrigerant gas used)

Checks to the area
Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimised. For repair to the refrigerating system, the following precaution shall be completed prior to conducting work on the system.

Work procedure
Work shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present while the work is being performed.

General work area
All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out. Work in confined spaces shall be avoided.

Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially toxic or flammable atmospheres. Ensure that the leak detection equipment being used is suitable for use with all applicable refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe.

Presence of fire extinguisher
If any hot work is to be conducted on the refrigerating equipment or any associated parts, appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or CO2 fire extinguisher adjacent to the charging area.

No ignition sources
No person carrying out work in relation to a refrigerating system which involves exposing any pipe work shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition sources, including cigarette smoking, should be kept sufficiently far away from the site of installation, repairing, removing and disposal, during which refrigerant can possibly be released to the surrounding space. Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks.

Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A degree of ventilation shall continue during the period that the work is carried out.

Checks to the refrigerating equipment
Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the manufacturer’s maintenance and service guidelines shall be followed. If in doubt, consult the manufacturer’s technical department for assistance.

The following checks shall be applied to installations using flammable refrigerants:

  • the actual refrigerant charge is in accordance with the room size within which the refrigerant containing parts are installed;
  • the ventilation machinery and outlets are operating adequately and are not obstructed;
  • if an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant;
  • marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected;
  • refrigerating pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing components, unless the components are constructed of materials which are inherently resistant to being corroded or are suitably protected against being so corroded.

Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures. If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with

Initial safety checks shall include:

  • that capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking;
  • that no live electrical components and wiring are exposed while charging, recovering or purging the system;
  • that there is continuity of earth bonding.

Repairs to sealed components
During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation.

Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not altered in such a way that the level of protection is affected. This shall include damage to cables, excessive number of connections, terminals not made to original specification, damage to seals, incorrect fitting of glands, etc.

Ensure that seals or sealing materials have not degraded to the point that they no longer serve the purpose of preventing the ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer’s specifications.

Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use.

Intrinsically safe components are the only types that can be worked on while live in the presence of a flammable atmosphere. Replace components only with parts specified by the manufacturer.
Other parts may result in the ignition of refrigerant in the atmosphere from a leak.

Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans.

Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.

Removal and evacuation
When breaking into the refrigerant circuit to make repairs – or for any other purpose – conventional procedures shall be used. However, for flammable refrigerants it is important that best practice is followed since flammability is a consideration.

The following procedure shall be adhered to:

  • remove refrigerant;
  • purge the circuit with inert gas;
  • evacuate;
  • purge with inert gas;
  • open the circuit by cutting or brazing.

The refrigerant charge shall be recovered into the correct recovery cylinders. For appliances containing flammable refrigerants the system shall be purged with oxygen-free nitrogen to render the appliance safe for flammable refrigerants. This process may need to be repeated several times. Compressed air or oxygen shall not be used for purging refrigerant systems.

For appliances containing flammable refrigerants, refrigerants purging shall be achieved by breaking the vacuum in the system with oxygen-free nitrogen and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum.
This process shall be repeated until no refrigerant is within the system. When the final oxygenfree nitrogen charge is used, the system shall be vented down to atmospheric pressure to enable work to take place. This operation is absolutely vital if brazing operations on the pipe-work are to take place.

Ensure that the outlet for the vacuum pump is not close to any potential ignition sources and that ventilation is available.

Charging procedures
In addition to conventional charging procedures, the following requirements shall be followed.

  • Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimise the amount of refrigerant contained in them.
  • Cylinders shall be kept in an appropriate position according to the instructions.
  • Ensure that the refrigerating system is earthed prior to charging the system with refrigerant.
  • Label the system when charging is complete (if not already).
  • Extreme care shall be taken not to overfill the refrigerating system.

Prior to recharging the system, it shall be pressure-tested with the appropriate purging gas. The system shall be leak-tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site.

Decommissioning
Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of recovered refrigerant. It is essential that electrical power is available before the task is commenced.

  1. Become familiar with the equipment and its operation.

  2. Isolate system electrically.

  3. Before attempting the procedure, ensure that:

    • mechanical handling equipment is available, if required, for handling refrigerant cylinders;
    • all personal protective equipment is available and being used correctly;
    • he recovery process is supervised at all times by a competent person;
    • recovery equipment and cylinders conform to the appropriate standards.
  4. Pump down refrigerant system, if possible.

  5. If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system.

  6. Start the recovery machine and operate in accordance with instructions.

  7. Do not overfill cylinders (no more than 80 % volume liquid charge).

  8. Do not exceed the maximum working pressure of the cylinder, even temporarily.

  9. When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are removed from site promptly and all isolation valves on the equipment are closed off.

  10. Recovered refrigerant shall not be charged into another refrigerating system unless it has been cleaned and checked.

Labelling
Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant.
The label shall be dated and signed. For appliances containing flammable refrigerants, ensure that there are labels on the equipment stating the equipment contains flammable refrigerant.

Recovery
When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely.

When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge is available. All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure-relief valve and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs.

The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of all appropriate refrigerants including, when applicable, flammable refrigerants. In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak-free disconnect couplings and in good condition. Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt.

The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant waste transfer note arranged. Do not mix refrigerants in recovery units and especially not in cylinders.

If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out prior to returning the compressor to the suppliers. Only electric heating to the compressor body shall be employed to accelerate this process. When oil is drained from a system, it shall be carried out safely.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals