EACH ENERGY EET18KPro-M1 Series Solar Inverter User Manual

June 9, 2024
EACH ENERGY

EET18KPro-M1 Series Solar Inverter

User Manual

Version: 1-01

Each Energy Technology (Suzhou) Co., Ltd.
www.eachenergy.com

Each Energy Technology (Suzhou) Co., Ltd.
Address: No.8 Building, No. 38 of Beiguandu Road, Yuexi Street, Wuzhong District, Suzhou, Jiangsu Province, China Tel: +8651266581088 Email: service@eachenergy.com Web: www.eachenergy.com
Copyright © Each Energy Technology (Suzhou) Co., Ltd.

Copyright © Each Energy Technology (Suzhou) Co., Ltd.
Without written permission, any information of this document (partly or entirely) cannot be extracted, copied or transmitted in any form or by any means. All right reserved.
Notice
The information in this document is subject to change without notice. Please adhere to the actual products in case of any discrepancy. Any statements, description, and recommendations in this manual do not constitute a guarantee or warranty of any kind, explicitly or implicitly.
Warranty
Warranty terms and conditions can be downloaded from the Internet at www.eachenergy.com.

Contents
1. About the Manual ……………………………………………………………………………………………….. 3 2. Product Overview …………………………………………………………………………………………………4 3. Safety ………………………………………………………………………………………………………………….7 4. Mounting …………………………………………………………………………………………………………….8
4.1 Installation Location …………………………………………………………………………………….8 4.2 Inverter Mounting ……………………………………………………………………………………….9 5. Electrical Connection …………………………………………………………………………………………. 11 5.1 DC Side Connection of Inverters ………………………………………………………………….11 5.2 AC Side Connection of Inverters …………………………………………………………………. 13 5.3 External Grounding Connection …………………………………………………………………. 14 5.4 Earth Fault Alarm ……………………………………………………………………………………… 14 5.5 Over Current Protection Device …………………………………………………………………..15 5.6 Communications Connection …………………………………………………………………….. 16 5.7 Electrical Connection Overview …………………………………………………………………..17 5.8 Meter and CT Installation (optional) …………………………………………………………… 17 5.9 Residual Current Device (RCD) …………………………………………………………………….19 5.10 DRM (Demand Response Mode) ………………………………………………………………. 19 6. Operation …………………………………………………………………………………………………………. 20 6.1 Start and Stop Inverters …………………………………………………………………………….. 20 6.2 LCD Operation ………………………………………………………………………………………….. 21
6.2.1 Main Menu ……………………………………………………………………………………..21 6.2.2 Basic Info. ……………………………………………………………………………………….22 6.2.3 Basic Setup ……………………………………………………………………………………..24 6.2.4 Detail Info – Maintenance Personnel Only …………………………………………. 25 6.2.5 Technical Set ­ Maintenance Personnel Only …………………………………….. 30 7. Maintenance and Troubleshooting ……………………………………………………………………….42 8. Specification ……………………………………………………………………………………………………… 49

1

2

1. About the Manual

2. Product Overview

The manual describes product information, mounting, installation, operation, maintenance, troubleshooting and specification of Each Energy inverters. Validity The document is valid for the following inverter models: EET15KPro-M1, EET18KPro-M1, EET20KPro-M1, EET22K-M1, EET25K-M1, and EET30K-M1. Target Group The target group of this manual are end users and qualified persons who have knowledge of inverters or skills of inverter installation, maintenance, etc. Only qualified persons are allowed to perform the installation and activities marked in this document under the guidance of safety instructions. Please read this manual carefully before conducting any kind of work on the inverters. Valid Region This manual applies to the operation of Each Energy inverters in Australia, New Zealand, the UK, EU, South America, North America, and Southeast Asia.

2.1 Product Description Each Energy EET15KPro-M1, EET18KPro-M1, EET20KPro-M1, EET22K-M1, EET25K-M1, and EET30K-M1 three phase on-grid inverters convert DC power generated by photovoltaic panel arrays into AC power and feed the converted AC power into utility grid. Product Appearance:

No. Name

1 PV Input Ports

2

3

DC CT

Switch Port

4 Wifi Stick
Logger Port

5 Grounding
Port

6 COM/Met er/DRM
Port

7 AC Output Port

3

4

2.2 Front Panel Operation Panel

2.3 Scope of Delivery

No.

1

2

3

4

56

7

8

Name Communications Power Alarm LCD ESC Up Down Enter

Light

Light Light

LED Light

Light POWER COMMUNICATIONS
ALARM

Status ON OFF ON
OFF
ON OFF

Explanation The inverter is generating power The inverter is not generating power The inverter has been connected to the Internet The inverter has not been connected to the Internet Alarm or fault has been detected The inverter is operating normally

5

No.

Description

Quantity

1

Inverter

1

2

Wall Bracket

1

3

Expansion Screws

4

4

Fastening Screws(M4)

3

Fastening Screws(M3)

4

5

DC Connectors

6 (pairs)

6

AC Connectors

1

7

WiFi/GPRS logger

1

8

Documents

1

6

3. Safety

3.1 Safety Symbols

Symbol

Explanation

DANGER WARNING CAUTION NOTE ELECTRIC SHOCK HOT SURFACE
WAIT

Indicates a high level of risk which, if not avoid, may result in death or serious injury Indicates a medium level of risk which, if not avoid, may result in death or serious injury Indicates a low level of risk which, if not avoid, may result in minor or moderate injury Indicates a situation which, if not avoided, may result in device damage or property damage Indicates a danger of electric shock or high voltage
Indicates hot surface, do not touch
Notice of waiting at least 5 minutes before operation

3.2 Safety Instructions and Notice for Use The inverters involved in this manual comply with applicable safety and technical regulations in design and test. To avoid personal injury and property damage and to ensure longer service life of the machines, please read this manual carefully and observe all safety information during operation. Improper operation may result in risk of person injury or damage to the machine and to other property, so please ensure that the following requirements are met before or during operation.
Installation of inverters must be performed by qualified technicians, and be in compliance with applicable electrical standards, regulations and the
7

requirements of local power authorities. Wear protective equipment for all work on the machines: helmet,
insulated footwear, gloves, etc. Ensure that unauthorized persons and children have no access to the
machines. Do not open the housing of the machines at any time. Unauthorized
opening will void guarantee and warranty and may damage the machines. Do not touch non-insulated parts or cables, disconnect the machines from voltage sources and guarantee no possible re-connection before working on the machine. Use measuring devices with a DC input voltage range of 600 V or higher only. High voltage is present in the live parts and cables inside the product during operation, wait at least 5 minutes after disconnecting voltage sources. The temperature of some parts of the inverter may exceed 60 during operation. To avoid being burnt, do not touch the inverter during operation. Pack inverters properly during transportation, and do not transport them together with flammable material. The inverter has not been tested to section 5 of AS/NZS 4777.2:2020 for multiple inverters combinations.
4. Mounting
4.1 Installation Location
WARNING Do not select locations storing flammable material which may cause fire or explosion!
8

The following points should be considered when selecting an installation location. The wall bearing inverters shall be able to hold the weight of at least 4
times of the weight of the inverters. The location shall be convenient for electrical connection, operation and
maintenance. The ingress protection of the inverter is IP66, so it can be installed both
indoors and outdoors.
The temperature of the cooling fin may exceed 75 , so select safe
locations. The location must be well ventilated and sheltered from direct sunlight,
rain or snow. Ensure the visibility of the LED lights and LCD display on the front panel
of inverters. Install inverters vertically or with a backward tilt within 15 degrees. No
lateral tilt is allowed. If more than one inverter are installed in one location, a minimum 150
mm clearance should be kept between two inverters and a minimum 300 mm clearance between inverters and the ground.

Procedures: 1) Ensure that the bracket is horizontal. Mark the position of the drill holes. For brick walls, the position of the holes should suit expansion screws. 2) Use a 10 mm drill bit to drill mounting holes of 40 mm deep. 3) Insert the expansion tubes into holes. 4) Screw the expansion screws into expansion tubes with a cross screwdriver to fix the bracket on the wall.

  1. Lift up the inverter, and hang it on the mounting bracket securely. 6) Lock the inverter to the mounting bracket with screws.

The Inverter is to be installed in a high traffic area where the fault is likely to be seen.
4.2 Inverter Mounting
Dimension of the mounting bracket:
Unit: mm
9

NOTE: To protect your hands from scratch, please wear gloves!
10

5. Electrical Connection
5.1 DC Side Connection of Inverters 5.1.1 PV Array Configuration This inverters are compatible with monocrystalline silicon, polycrystalline silicon, and thin-film PV panels. The recommended PV array matching the inverters are listed below: 1.25 × Isc of each PV string PCE(Inverter) DC input Isc (18A) Voc of each PV string 1100 V.

NOTE: Use DC cables specialized for photovoltaic systems Only!
Assemble DC cables to DC connectors: 1) Strip the insulation layer off the DC Cable for a little length. 2) Insert the wire into the Crimp Contact and crimp them with an electrical
crimp-er.

NOTE: PV arrays should be under the protection of over voltage class. For the grounding of the PV array, the frame of panels should contact the rail, and the the grounding cable connect the rail.
DANGER ELECTRICAL SHOCK Lethal high voltage will be generated by PV arrays under sunlight, so please disconnect DC and AC breakers and ensure no possibility of re-connection before conduct electrical connection!

  1. Thread the cable through the Cable Gland, insert it into the insulator, and gently pull backward the cable to ensure firm connection. Then screw up the Cable Gland to the Insulator.

DANGER ELECTRICAL SHOCK The inverter cannot be used with functionally earthed PV Arrays. PV strings should be connected to the inverter through special PV connectors that are in the scope of delivery.
NOTE: Use only the supplied connector or the connector with IP 65 or above to guarantee that the protection ingress of the whole inverter is IP66! It is recommended to use the DC cable of 4 mm2 or 6 mm2.

Install the DC connectors to the Inverter: 1) Turn the Grid Supply Main Switch OFF. 2) Turn the DC switch OFF. 3) Connect the DC connectors to the Inverter, small click confirms connection. Please guarantee the correct polarity of the connection.
WARNING Ensure that the open circuit voltage of PV array is within the max. input voltage of the inverter!

11

12

WARNING:Do not turn off DC switch directly for accident reverse
connection of DC inputs or any fault of inverters as it may damage inverters. In that case, turn off the DC switch only when the DC current is below 0.5 A.

5.2 AC Side Connection of Inverters For the sake of safety, it is recommended to use the AC cable of 6 mm2 for the models of EET15KPro-M1, EET18KPro-M1 and EET20KPro-M1, 10 mm2 for EET22K-M1 and EET25K-M1, and 16 mm2 for EET30K-M1.
An AC Connector is supplied together with the inverter.

5.3 External Grounding Connection The external grounding port is located beside the AC connection terminal of the inverter. The parameters of designed external protective earthing conductor and screw are as below: M4 screw with the cross-sectional area of 6.1 mm2; AWG8 conductor with the cross-sectional area of 8.4 mm2. Procedures Prepare an OT terminal M4, crimp a grounding cable to the terminal, insert a fastening screw into the OT terminal, insert them to the grounding port on the inverter, and screw them tightly (the torque is 1.1 N.m.).

AC Connector

Procedures: 1) Strip the insulation layer off the AC cable about 25 to 30 mm.

  1. Insert the stripped wires to the corresponding crimp contacts on the terminal block which is already installed in the AC port of the inverters by the manufacturer, and crimp the wires and crimp contacts together with a crimping plier.
  2. Thread the AC cable through the Nut and the Housing, and fasten the housing to the inverters with screws.

WARNING: The external grounding connection cannot replace the connection of PE terminal in AC connection. Ensure that both the external grounding connection and the PE connection are done properly!
5.4 Earth Fault Alarm The inverters are designed with an earth fault alarm function. If an earth fault occurs, the inverters will stop generating power, the red alarm light will be on

13

14

and the LCD will display ISO Out Range’ orPEN No Connect’. In that case, please refers to Chapter 7 for troubleshooting or contact Each Energy for help.
5.5 Over Current Protection Device

5.6 Communications Connection 5.6.1 Communications overviews

It is recommended to install a breaker (over current protection device (OCPD)) to protect the AC grid connection conductors. The table below is the recommended parameter of an OCPD ratings for the Inverter.

Inverter

Rated output Rated output

voltage (V)

current (A)

EET15KPro-M1 230/400

21.7

EET18KPro-M1 230/400

26.1

EET20KPro-M1 230/400

29.0

EET22K-M1 230/400

31.9

EET25K-M1 230/400

36.2

EET30K-M1 230/400

43.5

Current for protection device (A) 32 32 40 40 50 63

5.6.2 WiFi/GPRS Stick Installation
Assemble WiFi/GPRS stick to the corresponding port on inverter as shown in the diagram.

15

16

  1. Plug the stick to the Wifi port on the inverter 2) Rotate the front operative part of the stick clockwise till the secure connection of the stick More detailed information about communications can be found in corresponding manuals.

Max measuring current for CT: 100A Detail specifications of meter and CT can be found on Each Energy Website and a customer can purchase a suitable meter and CT for inverters on the website.

5.7 Electrical Connection Overview
The following is a diagram of a typical solar system for your reference to install inverters.

NOTE No need to change any parameter of the meter as it has been preset in the factory!
Meter and CT connection: For more information about meter and CT connection, please refer to corresponding manuals on Each Energy website. The following is schematic diagrams for reference.

5.8 Meter and CT Installation (optional)
A meter and CT(current transformer) can be connect to corresponding ports on inverter to monitor electricity parameter such as current, voltage, power, etc. and to realize export power management.
The suggested parameter: Max input current for meter: 80A
17

CT Installation Electrical Diagrams
DANGER ELECTRICAL SHOCK Turn off upSstinregalemPhaansde MdoewtenrsItnrsetaamllateiolencEtrleiccatlriccaolnDnieacgtriaomn sbefore the meter installation!
18

5.9 Residual Current Device (RCD)
An internal residual current device is integrated in the inverter to protect against any potential residual current. If the residual current that exceeds a set limit is detected, the inverter will stop working, the warning light will be on and the LCD will display GFCI Device Fault’ orGFCI Out Range’. If you need to install an external RCD as required by local grid company, we suggest a Type-A RCD with a threshold current higher than 100 mA.

When a DRED is connected to an inverter, the inverter will receive and response to the outside signal directly. And the DRM working mode will be shown in the BASIC INFO in the LCD menu.
6. Operation
6.1 Start and Stop Inverters

5.10 DRM (Demand Response Mode)

6.1.1 Inverter Turning-on

The DRM port is only applicable to installations in Australia and New Zealand as requires by the standard of AS/NZS 4777.2:2020. The inverter detects and initiates a response to the demand response modes listed in the following table.
Mode Functions
DRM 0 Operate the disconnection device DRM 5 Do not generate power DRM 6 Do not generate at more than 50 % of rated power DRM 7 Do not generate at more than 75 % of rated power AND absorb reactive
power if capable DRM 8 Increase power generation (subject to constraints from other active
DRMs)
Ways to connect a DRED (demand response enabling device) to inverters 1) Assemble a RJ45 connector by connecting a network cable to the RJ45 according to the international conventional method; 2) Plug the RJ45 connector to the DRM port of the inverter.
Power rate limit modes as required by AS/NZS 4777.2:2020 is supported in this inverters. When a demand response mode (except for DRM 0) is asserted or unasserted the power rate limit will apply to the increase or decrease in power generation or consumption and the transitions between power levels.
19

The following procedures have to be followed exactly to start an inverter. 1) Turn on the AC breaker. 2) Turn on the DC Switch. 3) After a compulsory delay of 30 to 300 seconds, the inverter will start to
work and the POWER light will be on.
WARNING Ensure that the open circuit voltage of PV array is within the max. input voltage of the inverter!
DANGER ELECTRIC SHOCK High voltage may present, please beware of the risk of electric shock and take protection precautions! 6.1.2 Inverter Turning-off
The following procedures have to be followed exactly when stop an inverter. 1) Switch off the AC Main Switch. 2) Wait around 30 seconds for the capacitor to dissipate energy. Then turn
the DC switch OFF. 3) Be sure that all LED light is OFF (around 1 minute).
20

CAUTION WAIT Beware of the risk of electrical shock! Wait at least 5 minutes before touching the machine although the DC switch has been turn off!

6.2.2 Basic Info.
The table below explains the meaning of information displayed in the sub-menu of Basic Info.

6.2 LCD Operation
6.2.1 Main Menu
When the inverter has been started, the LCD screen shows operation status and power of the inverter alternately every 10 seconds (refer to below figure). You can press UP and DOWN keys to scroll the screens and press ENTER key to access the main menu. The main menu includes four sub-menus: BASIC INFO, BASIC SETUP, DETAIL INFO, and TECHNICAL SET.

No.

Displays

1

TOTAL

ENERGY

50000 Kwh

ThisMon: 255Kwh 2 LastMon: 254Kwh

3 TODAY: 52 Kwh PRE_DAY : 54Kwh

DC VOL1: 401.5V

4

DC CUR1: 18.6A

DC VOL2: 408.5V 5 DC CUR2: 18.6A
DC VOL3: 401.5V 6 DC CUR3: 18.6A

Duration

Explanation

10 S Total energy: total energy generated

This Month: total energy generated

10 S

this month Last Month: total energy generated

last month

This Day: total energy generated today

10 S Previous Day: total energy generated

yesterday

DC voltage1: the DC voltage of the PV

10 S

input 1 DC current1: the DC current of the PV

input 1

DC voltage2: the DC voltage of the PV

10 S

input 2 DC current2: the DC current of the PV

input 2

DC voltage3: the DC voltage of the PV

10 S

input 3

DC current3: the DC current of the PV

input 3

21

22

7

DC VOL4: 40DC

CUR4: 18.6A

DC VOL5: 40DC 8 CUR5: 18.6A

DC VOL6: 40DC 9 CUR6: 18.6A

AC VOL A: 230.6V 10 AC CUR A: 38.8A

AC VOL B: 230.6V

11

AC CUR B: 38.8A

12

AC VOL C: 230.6V AC CUR C: 38.8A

13

FREQ A :50.2Hz

POWER A: 1200 W

14

FREQ B :50.2Hz POWER B: 1200 W

15 FREQ C :50.2Hz POWER C: 1200 W

DC voltage4: the DC voltage of the PV

10 S

input 4 DC current4: the DC current of the PV

input 4

DC voltage5: the DC voltage of the PV

10 S

input 5

DC current5: the DC current of the PV

input 5

DC voltage6: the DC voltage of the PV

10 S

input 6 DC current6: the DC current of the PV

input 6

AC voltage A: the voltage of the utility

10 S

grid live line A AC current A: the current of the utility

grid live line A

AC voltage B: the voltage of the utility

10 S

grid live line B AC current B: the current of the utility

grid live line B

AC voltage C: the voltage of the utility

10 S

grid live line C AC current C: the current of the utility

grid live line C

10 S

the frequency of phase A: 50.2 Hz Output Power: 1200 W

10 S

the frequency of phase B: 50.2 Hz Output Power: 1200 W

10 S

the frequency of phase C: 50.2 Hz Output Power: 1200 W

23

16

TOTAL POWER 3600 w

10 S

The total output power 3600W

17 TOTAL RUNTIME: 152 H

10 S Cumulative energy generation time

18 INVERTER SN EE00S005000001A1

10 S

Inverter SN: The SN of the Inverter EE00S005000001A1

19 MODEL:Volt-Watt DRM : DRM5
20 Standard cAusas4777_2A

10 S

Working Mode: Volt-Watt

DRM NO. :

DRM5

This menu indicates the current 10 S country grid code or safety standards
selected

Customers are able to view those info without password including country grid code. cAUSAS4777_2A, cAUSAS4777_2B, cAUSAS4777_2C and cNZS4777_2 represent Australia A, Australia B, Australia C and New Zealand standard respectively. Another standards such as cEN50549_1 and cABNT_NBR_16149 are also included in the menu.

6.2.3 BASIC SETUP

You can set time and address in this sub-menu.

No.

Display

Explanation

1

SET TIME

To set up time

2

SET RS485 ADDR

To set up RS485 address

24

3

To set up language

SET LANGUAGE

6.2.3.1 Time Setting-up When the sub-menu of SET TIME’ is selected, the LCD will display the screen as below. NEXT = ENT OK = ESC 25-01-2022 18:23 Press ENT to move the cursor from left to right, Press UP/DOWN to select a number for a selected digit. Press ESC to save the setting and return to the main menu. 6.2.3.2 Address Setting-up The inverter RS 485 address communicating with a monitoring platform can be set here, the address ranges from01′ to 99′, and the default address is01′.

YES = ENT EXIT = ESC Slave Add: 01
Press UP/DOWN to scroll through numbers for a selected digit, press ENT to save the setting and return to the main menu, and press ESC to return to the main menu without saving the setting. 6.2.3.3 Language Setting-up Working language of the inverter can be set here, and the default language is English.

6.2.4 Detail Info – Maintenance Personnel Only

Select `Detail Info’ from the main menu and the LCD screen will display the following information:
NEXT = ENT EXIT = ESC Password: 1000

Steps to view the menu of the Detail Info.:

  1. Enter the password: The default password is1000. When finishing password entering, press ENT to verify the password. If the password is correct, the sub-menu will be displayed, and if wrong, the LCD will display `Wrong Password’ and return to the previous menu. Press ESC to return to the main menu.

  2. Access the sub-menu: After enter the correct password, the sub-menus will be displayed: 1. Operation Info, 2. Fault Info, 3. Flash Version, 4. Warning Info, 5. SW Version, 6. Rated Power, 7. Rated Voltage, 8. Daily Energy, 9. Monthly Energy, 10. Yearly Energy, 11. Export Total, 12. Export Today

Press UP/DOWN to scroll the screen, press ENT to go into the selected sub-menu and press ESC to return to the main menu.

6.2.4.1 Operation Information

This information is for maintenance personnel to get the operation

information, and the information is as below:

No.

Display

Duration

Explanation

1

10 S

This menu indicates:

GFCI RMS: 10 mA

GFCI RMS: Leakage current

ISO : 1.25 k

protection

ISO:

Ground

fault

protection/Insulation Resistance

2 Heatsink

Temp

65.5

10 S

This menu indicates:

The temperature of heat sink of

inverters

3

Inv Inner Temp

45.0

10 S

This menu indicates:

Inverter inner temperature

25

26

4 BusVol:

385.5V

DCI : 0 mA

5
PF:+1.00 ac Pac Limit: 80%

6
BusHalfVol: GridFilter: ON

7

RCD(GFCI):

ON

PVISOGuard: ON

8

AllPVParal:

ON

MPPTShadow:

9 RelayCheck:OFF
DCI Prot : ON

10 Apparent
2000 VA
11 Active 2000 W
12 Reactive 2000 Var
13 Export 4800W

Power Power Power Power

10 S

This menu indicates:

Bus voltage

AC direct component

10 S

This menu indicates:

Power factor ratio

Output power limit

10 S

Half Voltage of Bus

Grid filter grade

The operation info of inverter and part of protection info. can be view after password has been input and all the info. is included in the above table. Press UP/DOWN to scroll the screen to view.
NOTE: This operation is for maintenance personnel only. Password is required to access this part!

6.2.4.2 Fault Info.

10 S

This menu indicates:

When a fault happens, the Alarm Light will be on, and the LCD will display a

Residual current protection

brief description of the fault. Please refer to Chapter 7 for troubleshooting or

Insulation Resistance/Ground

contact after-sales department if a fault info. is displayed.

fault protection

10 S

This menu indicates:

All PV in parallel mode

ACHCT Device Fault

MPPT shadow mode

6.2.4.3 Flash Version

10 S

This menu indicates:

The flash version can be checked here.

Self examination of AC relay

Output direct component

Flash Version

protection

ES 3.0

10 S

This menu indicates the apparent

6.2.4.4 Warning Info.

power

If a adverse condition presents in the inverter, the LCD will display a warning

information. The inverter will work normally with such warning conditions.

10 S

This menu indicates the active

When a warning info. is displayed, please refer to Chapter 7 for

power

troubleshooting.

10 S

This menu indicates the reactive

power

Warning

Info

0x00000400

6.2.4.5 Software Version/Firmware Version

10 S

This menu indicates the power

The software version or firmware version of the inverter is displayed and is

exported to grid

accessible for technicians only.

SW

Version

V01.05

27

28

6.2.4.6 Rated Power The rated power of the inverter is displayed here.

Rated 5KW

Power

6.2.4.7 Rated Voltage The rated voltage of the inverter is displayed here.

Rated 220V

Voltage

6.2.4.8 Daily Energy The energy generated for a specified day can be checked here.

Select

Day

2020-02-22

6.2.4.9 Monthly Energy The energy generated for a specified month can be checked here.

Select 2020-02-22

Month

6.2.4.10 Yearly Energy The energy generated for a specified year can be checked here.

Select

Year

2020-02-22

6.2.4.11 Export Total Total energy exported to grid can be checked here.

Export

Total

500KWh

6.2.4.12 Export Today

29

The energy exported to grid today can be checked here.

Export 500KWh

Total

6.2.5 Technical Set ­ Maintenance Personnel Only

This section is for maintenance personnel only, enter password to access the sub-menu as guided by Chapter 6.2.4. The sub-menu:

No.

Display

1

ALL Set Enable

2

Standard Set

3

Rated VAC Set

Explanation
To enable the setting-up of all functions under the menu of Technical Set To set up safety standard or country grid code for the inverters
To set up the rated voltage

4
VAC H Limit
5
VAC L Limit
6
FAC H Limit

To set up the high limit of AC output voltage
To set up the low limit of AC output voltage
To set up the high limit of AC output frequency

30

7
FAC L Limit

8

Pmax Limit

9
AC Inst Limit

10
Power Control
11
Standard Func

12
Special Func

13
Set Passwords

14

Factory Reset

15
Adjust Total E

16

Reset Total E

To set up the low limit of AC output frequency To set up the max generation power To set up the AC instant voltage limit
To set up the power control
To set up the increase power rate limit and decrease power rate limit
To set up special functions
To set up passwords
To restore factory settings
To adjust the total power generated To clear the power generation record

31

17
Export ON/OFF

To enable the grid connection

18
Export Limit

To set up export power limit

Press UP/DOWN to scroll the menu, press ENT to access the sub-menu, and press ESC to return to the previous menu.

NOTE: This part is accessible for qualified and accredited technicians only!
6.2.5.1 All Set Enable This function is to enable all the setting-up functions under the menu of Technical Set’. Before enabling or setting up any of the function under this menu, please turn theAll Set Enable’ on.
ALL SET Enable ON
6.2.5.2 Standards Set The safety standard for different countries can be selected in this sub-menu.

Standard

Set

cAusas4777_2A

Australia A, Australia B, Australia C and New Zealand grid codes can be selected here. cAUSAS4777_2A, cAUSAS4777_2B, cAUSAS4777_2C and cNZS4777_2 represent Australia A, Australia B, Australia C and New Zealand standard respectively.

Procedures: Step1: go to All Set Enable’ in the menu ofTECHNICAL SET’ and turn the status to ON’. Step2: move toStandard Set’ and get inside
32

Step3: select the country grid code needed.
Press UP/DOWN to scroll through the national standards, press ENT to confirm the safety standard, and press ESC to return to the previous menu.

NOTE: This operation is for maintenance personnel only. Password is required to access this part!

6.2.5.3 Rated VAC Set Rated AC output voltage can be set up here. Only when there are more than one type of applicable voltage will this function be used. 6.2.5.4 AC Output Voltage Limit This section is to set up the high and low limit of AC output voltage as permitted by local grid company if the grid voltage is beyond the range specified by national standards.

VAC H Limit Set 270V

VAC L Limit Set 180V

The detailed procedure is described in a separated document named `Voltage Adjustment’. 6.2.5.5 AC Output Frequency Limit This section is to set up the high and low limit of AC output frequency as permitted by local grid company if the grid frequency is beyond the range specified by national standards.

FAC H Limit Set 52Hz

FAC L Limit Set 47Hz

The method to set up the AC output frequency limit is similar to that of AC voltage adjustment. 6.2.5.6 Max Generation Power Setup The max output power can be set up here.

Pmax

Limit

70% of Prated

33

The detailed procedure to set up the Max generation power is described in a separated document named `Power Generation Limit’.
NOTE: The inverter has generation limit control capability which has yet to be tested according to AS/NZS 4777.2:2020.

6.2.5.7 Power Control

No.

LCD Display

Explanation

1

Q

+60%

2

PF

+80%

3

Q

Set To set up reactive power Set To set up power factor Reset To restore reactive power

YES=ENT EXIT=ESC Are You Sure?

4

PR

Reset To restore power factor

YES=ENT EXIT=ESC Are You Sure ?
Reactive power and power factor can be set up and restored here. The power quality response modes as required by the standard of AS/NZS 4777.2:2020 can be activated or controlled under this menu combined with the menu of special function. The detail procedure will be described in the

34

following part. 6.2.5.8 Standard Function Power increase slope and decrease slope can be set up here.

Pwr

UpSlope Pwr

DownSlope

90%

20%

This part is for the setup of power rate limit modes as required by AS/NZS 4777.2:2020. Soft ramp up after connect, reconnect or soft ramp up/down following a response to frequency disturbance is available in those inverters.

Procedures to set up the gradient of power rate limit: Step1: Go to All Set Enable’ in the menu ofTECHNICAL SET’ and turn the status to ON’. Step2: Go toStandard Func’ and then get inside. Step3: Go to set up the Pwr UpSlope’ orPwr DownSlope’ for the soft ramp up/down
of rated power per minute.
.
NOTE: This operation is for maintenance personnel only. Password
is required to access this part!

6.2.5.9 Special Function Setup

No.

LCD Display

Explanation

1

Set CV MPPT

To set up the constant PV voltage

2

All PV Paral

3

HVRT

To set up the multiple MPPTs parallel mode
To enable the High Voltage Ride Through

4

LVRT

5

1/2BUS Prot

6

DCI Prot

7
GFCI Prot
8
ISO Prot

9
Island Prot

10

Buzzer Enabled

11

Relay Check

12

QU CURVE

13
PF CURVE

To enable the Low Voltage Ride Through To enable the bus mid-point voltage protection To enable the DC component inspection
To enable the GFCI protection To enable the ISO protection To enable the island protection To enable the buzzer To enable the relay To enable the QU curve To enable the PF curve

35

36

14
Q CURVE
15
PU CURVE
16
Shadow MPPT:

To enable the Q curve To enable the PU curve
To enable the shadow MPPT mode

6.2.5.9.1 Island Protection The active anti-islanding protection of the inverters is achieved by shifting the frequency of the inverter away from nominal conditions in the absence of a reference frequency (frequency shift). It is enabled by default. 6.2.5.9.2 Volt-var Response Mode

QU CURVE

ON

The QU Curve is enabled by default. The volt-var response mode changes the reactive power absorbed or supplied by the inverter in response to the voltage at its grid-interactive port. The diagram and table below are the response mode required for the volt­var response according to the standard of AS/NZS 4777.2:2020.

37

Region Australia A
Australia B
Australia C
New Zealand

Default Value Voltage
Inverter reactive power level (Q)% of Srated
Voltage
Inverter reactive power level (Q)% of Srated
Voltage
Inverter reactive power level (Q)% of Srated
Voltage
Inverter reactive power level (Q)% of Srated

VV1 207 V
44% supplying
205 V 30% supplying
215 V 44% supplying
207 V 60% supplying

38

VV2 220 V
0%

VV3 240 V
0%

VV4 258 V 60% absorbing

220 V 0%

235 V 255 V 0% 40% absorbing

230 V 0%

240 V 255 V 0% 60% absorbing

220 V 0%

235 V 244 V 0% 60% absorbing

Procedures to enable or disable the Volt-var Response Mode: Step1: go to All Set Enable’ in the menu ofTECHNICAL SET’ and turn the status to ON’. Step2: go toSpecial Func’ and then go to QU Curve’ Step3: enable or disable the Volt-var Response Mode’ by changing the status to ON’ orOFF’.
NOTE: This operation is for maintenance personnel only. Password is required to access this part!
6.2.5.9.3 Volt-watt Response Mode
PU CURVE ON
The PU Curve is enabled by default. The volt-watt response mode varies the maximum active power output level of the inverter in response to the voltage at its grid-interactive port. The diagram below is the response curve required for the volt­watt response according to the standard of AS/NZS 4777.2:2020.

Australia A Australia B

Voltage
Inverter maximum active power output level (P)% of Srated
Voltage
Inverter maximum active power output level (P)% of Srated

253 V 100%
250 V 100%

Australia C

Voltage
Inverter maximum active power output level (P)% of Srated

253 V 100%

New Zealand

Voltage
Inverter maximum active power output level (P)% of Srated

242 V 100%

260 V 20%
260 V 20%
260 V 20%
250 V 20%

Procedures to enable or disable the Volt-watt Response Mode: Step1: go to All Set Enable’ in the menu ofTECHNICAL SET’ and turn the status to ON’. Step2: go toSpecial Func’ and then go to PU Curve’ Step3: enable or disable the Volt-watt Response Mode’ by changing the status to ON’ orOFF’.

NOTE: This operation is for maintenance personnel only. Password is required to access this part!

6.2.5.9.4 Fixed Power Factor Mode or the Reactive Power Mode

PF CURVE

OFF

Q CURVE

OFF

Region

Default Value

Vw1

Vw2

39

Those modes are disabled by default. The fixed power factor mode or the reactive power mode may be enabled in some situations by the electrical distributor to meet local grid requirements, one of these modes shall be
40

enabled if the volt-var mode is disabled. Procedures to set up the Reactive Power Mode: Step1: go to All Set Enable’ in the menu ofTECHNICAL SET’ and turn the status to ON’. Step2: go toSpecial Func’, then go to Q Curve’ and enable the Q Curve by change the status toON’ Step3: go to Power Control’ and then go toQ Set’. Step 4: Set up the Reactive Power Mode manually.
Procedures to set up the Fixed Power Factor Mode: Step1: go to All Set Enable’ in the menu ofTECHNICAL SET’ and turn the status to ON’. Step2: go toSpecial Func’, then go to PF Curve’ and enable the PF Curve by change the status toON’ Step3: go to Power Control’ and then go toPF Set’. Step 4: Set up the Fixed Power Factor manually.
NOTE: This operation is for maintenance personnel only. Password is required to access this part!

6.2.5.10 Password Set-up The password for Detail Info’ andTechnical Set’ can be reset here.

Password: Confirm:

1000 1000

Press ENT to move the cursor, press UP/DOWN to select a number for a digit selected, and press ENT to confirm the setup after the last digit has been set up. Press ESC to return to previous menu. 6.2.5.11 Factory Reset This function is designed to restore factory defaults.

YES=ENT EXIT=ESC

Are You Sure ?

41

6.2.5.12 Adjust Total E The total energy generated may be cleared or changed after maintenance or translocation, and the previous data can be restored with this function. The total energy generated can be adjusted here.

TOTAL

ENERGY

5700000 KWh

6.2.5.13 Reset Total E The total energy generated record can be cleared here, and after clearing, the energy generation record will be zero.
YES=ENT EXIT=ESC Are You Sure?

Press ENT to clear the energy generation history and press ESC to cancel the previous operation. 6.2.5.14 Inverter On/Off This function is to control the grid connection or disconnection of inverters.

Inverter ON

ON/OFF

Press UP/DOWN to scroll the menu, press ENT to perform the selection, and press ESC to return to the previous menu. 6.2.5.15 Export Limit

->Soft Limit

Mode: Value:

ON 6000

->Hard Limit

Mode: Value:

ON 6000

->Detection Mode

CT Mode Meter Mode

42

The inverter’s export limit can be achieved together with external devices such as a CT or meter. There are two types of limit, soft limit and hard limit. The soft limit means that the limit is controlled by software, and hard limit means that if the generation exceeds the limit, the inverter will stop working. Under the detection mode menu, you can choose CT mode or meter mode. For the normal working of inverters, please use the soft limit only. The hard limit is used only by compulsory requirement of local grid companies.
7. Maintenance and Troubleshooting
7.1 General Maintenance
The Inverters do not need regular maintenance and just ensure that they are free of dust, foliage and other dirt.
NOTE: The use of cleaning agents may damage the machine and its components. Only use a cloth moistened with clear water to clean the machine.
7.2 Disposing of Inverters
If the inverters need to be disposed of, please do that according to the local regulations for electrical equipment waste, and choose the right site for the disposing specified for electrical equipment waste according to local regulations.

7.3 Storage and Transportation
If the inverters will not be installed in a short term, please store them in a dry room with the ambient temperature between -25~60 . For storage and transportation, please pack them in the original package if possible and stack inverters no more than 6 packs.
7.4 Troubleshooting

No.

Events

Explanation

Solutions

1. Check if the input voltage

1

DC Volt Over

High voltage of PV input strings

exceeds the inverter’s upper limit of input voltage

2. Decrease solar panels

quantity in series

DC Over PV current

1. Restart the inverter

exceeds the

2. Decrease solar panels

2

Current Soft

software protection limit

quantity in parallel if it occurs repeatedly

3

DC Over Current
Hard

PV current exceeds the hardware protection limit

1. Restart the inverter 2. Decrease solar panels quantity in parallel if it occurs repeatedly

1. Check if the input voltage

Transient bus

exceeds the inverter’s upper

4

Bus Over Voltage
Soft

voltage exceeds the software protection limit

limit of input voltage 2. If not, restart the inverter 3. If yes, decrease solar panel

quantity in series

43

44

1. Check if the input voltage

5

Bus Over Voltage
Hard

Transient bus voltage exceeds the hardware protection limit

exceeds the inverter’s upper limit of input voltage 2. If not, restart the inverter 3. If yes, decrease solar panel

quantity in series

Transient

6

Over Voltage

Transient over voltage in grid

Restart the inverters

7

Inv Over Current
Soft

Inverter software over current

1. Restart inverters 2. Decrease string in parallel

8

Inv Over Current Hard

Inverter hardware over current

1. Restart inverters 2. Decrease string in parallel

1. Check whether AC circuit

breaker has been triggered off

2. Check AC cables connection

9

Island Protect

Island effect protection

3. Check whether grid is not in service

4. If the above reasons have

been excluded and this fault

still occurs in the LCD screen,

contact the installer

10

Low Temperatu

Low Temperature

Check if the ambient temperature is below normal working temperature of

re Inside Inverters

Inside Inverters

inverters and increase ambient temperature

11

High Temperatu
re Inside Inverters

High temperature inside inverters

1. Check the ventilation of installation environment 2. Avoid direct sunlight

45

Abnormality in

12

Extern Flash

external flash reading and

Restart the inverter

writing

13

Bus Unbalance

Bus Unbalance

Restart the inverter

1. Check if the input voltage is

14

Low bus

too low Low bus voltage 2. If not, restart the inverter

voltage

3. If yes, increase solar panel

quantity in series

15

Over Frequency

Export reduction due to over frequency

Adjust the protection value limit by user-designing function as permitted by grid company

Over

Export reduction 1. Check the ventilation of

16 Temperatu due to over

installation environment

re

temperature

2. Avoid direct sunlight

17

GFCI Device Fault

Fault in current leakage testing device

Restart the inverter or contact the installer

ACHCT 18 Device
Fault

Fault in HCT device on AC side

Restart inverter or contact the installer

19 GFCI Out Range

Current leakage is out of range

Check the AC connection and DC connection, and check internal wire connection

46

20

DCI Out Range

DC component is Restart the inverter or contact

too large

the installer

1. Remove all DC inputs,

21

ISO Out Range

The insulation impedance is too small

reconnect them one by one, and restart the inverter 2. Identify the string that causes the fault and check the

insulation of the string

1. Check the AC breaker

2. Check the connection of AC

No Grid… 22 Pls Turn On No utility grid
AC

plug 3. Check whether the inverter’s L, N, PE line have been connect with the

corresponding grid L, N, E line

correctly

23

Temp is Too High

Temperature is too high

1. Check the ventilation of installation environment 2. Avoid direct sunlight

24

Temp is Too Low

25

PV Over Voltage

Temperature is too low
Over voltage in PV Inputs

Check if the ambient temperature is below normal working temperature of inverters and increase ambient temperature 1. Check if the input voltage exceeds the inverter’s upper limit of input voltage. 2. Decrease solar panel quantity in series

47

1. Wait for the inverter to

recovery

The grid is

2. If the impedance of AC

26

Grid Volt overloaded by Over 110% 10% for over 10

cable is too small, replace it with a larger size cable

minute

3. Adjust the protection value

limit as permitted by the grid

company

1. If the impedance of AC

cable is too small, replace it

27

Grid Volt Grid voltage is Out Range out of range

with a larger size cable 2. Adjust the protection value

limit as permitted by the grid

company

Adjust the protection value

Grid Freq Grid frequency is limit through self-designing

28

Out Range out of range

function as permitted by the

grid company

29

Relay Fault

Fault in grid-connection relay

Restart the inverter or contact the installer

Communication

30

MS Comm Fault

fault between the main CPU and the slave

Restart the inverter or contact the installer

CPU

Power to

31

Grid beyond

Limit

Power exported to Grid exceeds the Hardware Limit

1. Turn on the software limit and set up a software limit that is lower than the hardware limit 2. Turn off the hardware

48

limit if permitted

32

PEN No Connect

Grounding fault as the PE and N line has not been connected well

1. Check the connection of the PE line and the N line 2. Contact the installer

NOTE If any event in the above table is displayed, please turn off the inverter, wait 5 minutes and then restart the inverter.
8. Specification

49

50

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals