Honeywell Home RedLINK Zoning Options Thermostats User Manual
- June 9, 2024
- Honeywell Home
Table of Contents
- Honeywell Home RedLINK Zoning Options Thermostats
- IAQ CONTROL FROM ZONE 1 STAT
- Option B: 2–4 Zones
- Option C: 2–4 Zones
- Option D: More Than 4 Zones
- NO IAQ EQUIPMENT OR ECONOMIZER CONTROL
- ALL PRESTIGE THERMOSTATS WITHOUT IAQ CONTROL
- Option F: 2–4 Zones
- Option G: 2–4 Zones
- Option H: More Than 4 zones
- RedLINK VisionPRO instead of Prestige
- No IAQ Equipment
- EIM to Zone Panel Wiring Diagrams
- To Learn More
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Honeywell Home RedLINK Zoning Options Thermostats
IAQ CONTROL FROM ZONE 1 STAT
Option A: 2–3 Zones
Table 1. 1–2 Stage Furnace + 1–2 Stage Cooling or Single Stage Heat-Pump +
Electric Heat-Strips for Auxiliary Heat.
No Dual Fuel.
Parts list | Description | Quantity |
---|---|---|
1. HZ322K zone panel kit | Includes HZ322 zone panel, C7735A1000 discharge | |
sensor, and AT140A1042 transformer | 1 | |
2. YTHX9421R | Prestige IAQ kit with Thermostat & EIM. (Different kits can | |
also include accessories such as a RedLINK Internet gateway.) | 1 | |
3. YTH6320R1023 | Includes TH6320R1004 wireless programmable FocusPRO | |
thermostat and THM4000R1000 adapter | 1 | |
4. TH6320R1004 | Wireless thermostat for zone 3 _(not needed for 2 zone | |
system)_ | 0–1 | |
5. Appropriate zone dampers and by-pass damper for the application |
Option B: 2–4 Zones
Table 2. 1–3 Stage Furnace + 1–2 Stage Cooling, or 1–2 Stage Heat-Pump + Electric Heat-Strips for Auxiliary Heat.
Parts list | Description | Quantity |
---|---|---|
1. HZ432K zone panel kit | Includes HZ432 zone panel, C7735A1000 discharge | |
sensor, and AT140A1042 transformer | 1 | |
2. YTHX9421R | Prestige IAQ kit with Thermostat & EIM. (Different kits can | |
also include accessories such as a RedLINK Internet gateway.) | 1 | |
3. YTH6320R1023 | Includes: TH6320R1004 wireless programmable FocusPRO | |
thermostat and THM4000R1000 adapter | 1 | |
4. TH6320R1004 | Wireless thermostats for zones 3 and 4 _(not needed for 2 | |
zone system)_ | 0–2 | |
5. Appropriate zone dampers and by-pass damper for the application |
Option C: 2–4 Zones
Table 3. Dual Fuel. 1–2 Stage Heat-Pump + 1–2 Stage Gas Furnace
| |
---|---|---
Parts list| Description| Quantity
1. HZ432K zone panel kit| Includes: HZ432 zone panel, C7735A1000 discharge
sensor, and AT140A1042| 1
2. YTHX9421R| Prestige IAQ kit with Thermostat & EIM. (Different kits can
also include accessories such| 1
3. YTH6320R1023| Includes: TH6320R1004 wireless programmable FocusPRO
thermostat and| 1
4. TH6320R1004| Wireless thermostats for zones 3 and 4 (not needed for 2
zone system)| 0–2
5. C7089R1013| Wireless outdoor sensor for dual fuel changeover| 1
See Fig. 1 below for basic wiring
Option D: More Than 4 Zones
(Cannot use THM4000R Wireless Adapter)
Table 4. 1–3 Stage Furnace + 1–2 Stage Cooling, Heat-Pump with 1–2
Compressor Stages + Auxiliary Heat, or 1–2
Stage Heat-Pump + 1–2 Stage Gas Furnace (Dual Fuel).
| |
---|---|---
Parts list| Description| Quantity
1. HZ432K zone panel kit| Includes: HZ432 zone panel, C7735A1000 discharge
sensor, and AT140A1042 transformer| 1
2. TAZ-4H| Add-A-Zone panel| 1 per each additional 4 zones
3. AT140A1042| 40VA transformer| 1 per TAZ-4H panel
4. YTHX9421R| Prestige IAQ kit with Thermostat & EIM. (Different kits can
also include accessories such as a RedLINK Internet gateway.)| 1
5. YTH6320R1001| Wireless FocusPRO and EIM kit| 1 for each zone other than
the Prestige zone
6. Appropriate zone dampers and by-pass damper for the application|
7. C7089U1006| Wired outdoor sensor (required for dual fuel applications
only)| 1
See Fig. 2 below for basic wiring.
NO IAQ EQUIPMENT OR ECONOMIZER CONTROL
For any of the 2-4 zone applications listed in this document that do not need to control a Humidifier, Dehumidifier, Ventilator, economizer, or Remote Indoor Sensor, you can eliminate the THM5421R1021. You can either enroll the Prestige IAQ thermostat to the THM4000R1000 wireless adapter that is included in the YTH6320R1023 kit or use another TH6320R1004 thermostat for zone 1 in place of the Prestige IAQ. When a TAZ-4H is used for systems over 4 zones, you cannot use a THM4000R1000.
See Fig. 3 below for basic wiring.
- EIMS AND ADAPTORS NEED TO BE AT LEAST 2 FEET APART FROM EACH OTHER.
- THE SUPPLY AND RETURN SENSORS INCLUDED IN THE YTHX9421 2.0 PRESTIGE IAQ KITS ARE NOT USED IN ZONING APPLICATIONS. THE THERMOSTATS CANNOT BE SET FOR DELTA-T DIAGNOSTICS WHEN USED IN ZONING APPLICATIONS.
- PRESTIGE IAQ THERMOSTATS USED WITH A THM4000R ADAPTOR AND THM6000R GATEWAY LOSE THE 2.0 FUNCTIONALITY ONLINE. THIS MEANS YOU WILL BE ABLE TO OVERRIDE THE SET POINT BUT CANNOT PROGRAM THEM OR CONTROL THE FAN SETTING VIA APP. ALSO THEY CANNOT BE USED IN A DEMAND RESPONSE UTILITY PROGRAM. ALSO YOU CANNOT USE THOSE THERMOSTATS WITH AN R EM1000R1003 EXIT/ENTRY CONTROL OR WSK 24 REMOTE SETBACK.
Fig. 3. No IAQ Equipment.
ALL PRESTIGE THERMOSTATS WITHOUT IAQ CONTROL
Option E: 2–3 Zones (If C7189R or C7189U Indoor Sensors are Used, Cannot Use
THM4000R. Need separate EIM for Each Stat).
Table 5. 1–2 Stage Furnace + 1–2 Stage Cooling or Single Stage Heat-Pump +
Electric Heat-Strips for Auxiliary Heat. Not Dual Fuel.
Parts list | Description | Quantity |
---|---|---|
1. HZ322K zone panel kit | Includes: HZ322 zone panel, C7735A1000 discharge | |
sensor, and AT140A1042 transformer | 1 | |
2. YTHX9421R | Prestige IAQ kit with Thermostat & EIM for IAQ zone (usually |
zone 1). Different kits can also include accessories such as a RedLINK
Internet gateway| 1
3. THX9421R5021| Prestige without EIM for zones 2–3| 1–2
4. THM4000R1000| Wireless adapter for zone 2–3 Prestige IAQ thermostats not
controlling IAQ equipment or using an indoor sensor| 1
5. Appropriate zone dampers and by-pass damper for the application|
Option F: 2–4 Zones
(If C7189R or C7189U Indoor Sensors are Used, Cannot Use THM4000R. Need
Separate EIM for Each Stat).
Table 6. 1–3 Stage Furnace + 1–2 Stage Cooling, or 1–2 Stage Heat-Pump +
Electric Heat-Strips for Auxiliary Heat.
Parts list | Description | Quantity |
---|---|---|
1. HZ432K zone panel kit | Includes: HZ432 zone panel, C7735A1000 discharge | |
sensor, and AT140A1042 transformer | 1 | |
2. YTHX9421R | Prestige IAQ kit with Thermostat & EIM for IAQ zone (usually |
zone 1). Different kits can also include accessories such as a RedLINK
Internet gateway| 1
3. THX9421R5021| Prestige without EIM for zones 2–4| 1–3
4. THM4000R1000| Wireless adapter for zone 2–4 Prestige IAQ thermostats not
controlling IAQ equipment or using an indoor sensor| 1
5. Appropriate zone dampers and by-pass damper for the application.|
Option G: 2–4 Zones
(If C7189R or C7189U Indoor Sensors are Used, Cannot Use THM4000R. Need Separate EIM for Each Stat).
Table 7. Dual Fuel. 1–2 Stage Heat-Pump + 1–2 Stage Gas Furnace.
Parts list | Description | Quantity |
---|---|---|
1. HZ432K zone panel kit. | Includes: HZ432 zone panel, C7735A1000 discharge | |
sensor, and AT140A1042 transformer | 1 | |
2. YTHX9421R | Prestige IAQ kit with Thermostat & EIM for IAQ zone (usually |
zone 1). Different kits can also include accessories such as a RedLINK
Internet gateway| 1
3. THX9421R5021| Prestige without EIM for zones 2–4| 1–3
4. THM4000R1000| Wireless adapter for zone 2-4 Prestige IAQ thermostats not
controlling IAQ equipment or using an indoor sensor| 1
5. C7089R1013| Wireless outdoor sensor| 1
6. Appropriate zone dampers and by-pass damper for the application|
See Fig. 4 below for basic wiring.
Option H: More Than 4 zones
(Cannot Use THM4000R Wireless Adapter)
Table 8. 1–3 Stage Furnace + 1–2 Stage Cooling, Heat-Pump with 1–2 Compressor Stages + Auxiliary Heat, or 1–2 Stage Heat-Pump + 1–2 Stage Gas Furnace (Dual Fuel).
| |
---|---|---
Parts list| Description| Quantity
1. HZ432K zone panel kit| Includes HZ432 zone panel, C7735A1000 discharge
sensor, and AT140A1042 transformer| 1
2. TAZ-4H| Add-A-Zone panel| 1 per each additional 4 zones
3. AT140A1042| 40VA transformer| 1 per TAZ-4H panel
4. YTHX9421R| Prestige IAQ thermostat kit with EIM| 1 for each zone
5. Appropriate zone dampers and by-pass damper for the application|
6. C7089U1006| Wired outdoor sensor (required for dual fuel applications
only)| 1
RedLINK VisionPRO instead of Prestige
For any of the A–F applications listed, you could replace the Prestige IAQ thermostats with TH8321R1001 RedLINK VisionPRO models. When the RedLINK VisionPRO models are used, you can link to the THM5421R1021 or THM4000R1000 (same as Prestige) or wire directly from the thermostat sub-base to the zone connection on the zone panel if wires are available.
See Fig. 5 below for basic wiring.
No IAQ Equipment
Any of the above listed 2-4 zone applications that do not need to control a Humidifier, Dehumidifier, Ventilator, Economizer or Remote Indoor Sensor can eliminate the THM5421R1021. You can enroll all Prestige IAQ or RedLINK VisionPRO thermostats to the THM4000R1000 wireless adapter. When a TAZ-4H is used for systems over 4 zone you cannot use a THM4000R1000.
See Fig. 6 below for basic wiring
- THE SUBBASE OF EACH THX9421R5021 THERMOSTAT NEEDS TO BE WIRED TO A 24 VOLT TRANSFORMER. THIS CAN EITHER BE THE TRANSFORMER THAT POWERS THE ZONE PANEL OR A SEPARATE TRANSFORMER.
- EIMS AND ADAPTORS NEED TO BE AT LEAST 2 FEET APART FROM EACH OTHER.
- THE SUPPLY AND RETURN SENSORS INCLUDED IN THE YTHX9421 2.0 PRESTIGE IAQ KITS ARE NOT USED IN ZONING APPLICATIONS. THE THERMOSTATS CANNOT BE SET FOR DELTA-T DIAGNOSTICS WHEN USED IN ZONING APPLICATIONS.
- PRESTIGE IAQ THERMOSTATS USED WITH A THM4000R ADAPTOR AND THM6000R GATEWAY LOSE THE 2.0 FUNCTIONALITY ONLINE. THIS MEANS YOU WILL BE ABLE TO OVERRIDE THE SET POINT BUT CANNOT PROGRAM THEM OR CONTROL THE FAN SETTING VIA APP. ALSO THEY CANNOT BE USED IN A DEMAND RESPONSE UTILITY PROGRAM. ALSO YOU CANNOT USE THOSE THERMOSTATS WITH AN REM1000R1003 EXIT/ENTRY CONTROL OR WSK 24 REMOTE SETBACK.
Fig. 6. No IAQ equipment or remote indoor sensor.
EIM to Zone Panel Wiring Diagrams
To Learn More
For more information regarding zoning, contact 800-468-1502, or for technical literature go to www.pro.resideo.com
Resideo Technologies, Inc.
1985 Douglas Drive North, Golden Valley, MN 55422
1-800-468-1502
33-00642—02 M.S. Rev. 01-23 | Printed in United States
© 2023 Resideo Technologies, Inc. All rights reserved.
The Honeywell Home trademark is used under license from Honeywell
International, Inc. This product is manufactured by Resideo Technologies, Inc.
and its affiliates.
Read User Manual Online (PDF format)