Air Sampling Smoke Detection System
Instruction Manual
XAS Air Sampling Smoke Detection System
The Xtralis XAS Air-sampling Smoke Detection system provides a flexible detection solution to meet unique needs of challenging applications found in typical commercial and industrial sites. The XAS solution is well suited to installations where access to the monitored areas is restricted and provides tamper-proof and unobtrusive detection. The ability to mount the device outside the protected area makes it ideal for use in applications such as correctional facilities, transformer vaults, cable tunnels, elevator machine rooms and HVAC ducts.
How it Works
The XAS systems actively draw air from the protected area through sampling
holes in a pipe network. Sampled air is then filtered before being analyzed by
conventional or analog point detectors incorporated in the systems. The XAS
system is available with one inlet pipe (XAS-1) or two inlet pipes (XAS-2),
and can be used with one or two detectors per system. A number of different
points from a range of leading technology providers may be used.*
The systems utilize a high performance aspirator and programmable flow
monitoring circuitry. Air flow level is displayed on a ten element bar graph
that can be adjusted for high and low flow thresholds, and flow failure is
reported as a device fault via relays to the monitoring system.
Detection Strategies
The systems may be configured for a number of detection strategies including:
- single or dual addressable area detection
- redundant detection
- coincident or double-knock detection
Installer-specifiable point detectors offer benefits in simplicity of configuration and cost effectiveness. In circumstances where the premises are already protected by point detectors, the XAS system is easily introduced onto the existing fire alarm control panel signaling circuit by installing equivalent detectors into the system*.
- Subject to XAS system approval for the installed spot (point) detector
Features
- Single or dual inlet fire detection
- Multiple piping options
- Multiple detection strategies
- 164 ft (50 m) max. per unit
- 50 ft (15 m) max. per flexible tube
- Microprocessor controlled
- High performance aspirator
- Integral display and programmer
- Field serviceable air filter
- Adjustable aspirator speed with airflow monitoring
Listings/Approvals
- UL-268
- UL-268A
- ULC-529
Detector Configuration Options
Several configuration options are available for the XAS-1 and XAS-2 systems:
- XAS-1 system – one or two spot (point) detectors (shared inlet)
- XAS-2 system – two spot (point) detectors (dual inlet)
XAS-1 systems with one spot (point) detector are capable of providing single area detection, but XAS-1 and XAS-2 systems with two detectors are able to provide a number of detection strategies. The table below describes the recommended configuration options to fit the selected detection strategy when two spot (point) detectors are installed into an XAS system.
| XAS-1| XAS-2
---|---|---
Two Detector Strategy| Dual Addressable Areas| |
Redundancy| (OR)| (OR)
Coincident / Double-Knock†| (AND)| (AND)
† Subject to local codes and standards
Note: (OR / AND) represents the suggested Boolean logic for combining two
detectors to achieve detection strategy
Dimensions
Ordering Information
Air-sampling Smoke Detector with 1 inlet | XAS-1-US |
---|---|
Air-sampling Smoke Detector with 2 inlets | XAS-2-US |
Point detectors are ordered from their manufacturer/supplier; while baffles are ordered separately from Xtralis depending on the point detector type.
Specifications
Supported detectors:
- 1 or 2 analog addressable or conventional spot (point) detectors
- 4 in. mounting base (max)
Supply Voltage:
24 VDC nominal
Note that spot (point) detectors are powered from the Signaling Line Circuit
(SLC) or Initiating Device Circuit (IDC).
Current:
350 mA (max)
In-Rush 680 mA
Dimensions (WHD):
10.2 in. x 12.6 in. x 6.5 in.
(259 mm x 321 mm x 166 mm)
Weight:
XAS-1: 7.27 lbs (3.3 kg)
XAS-2: 7.5 lbs (3.4 kg)
Operating Conditions:
Tested to: 14 to 131 °F (-10 to 55 °C)
Recommended Detector Ambient: 32 to 100 °F
(0 to 38 °C)
Sampled Air: 4 to 140 °F (-20 to 60 °C)
Humidity: 10 to 95% RH (non-condensing)| Air Inlet Pipe:
Accepts both metric and American standard pipe sizes.
Metric: 25mm (1.05 in.)
American Pipe: ¾ in. I.D (21mm)
Flexible tubing: ¾ in.O.D (19mm)
Sampling Network:
Pipe Length: Up to 164 ft (50 m) total per device
Flexible Tube Length: Maximum 50 ft (15m)
IP Rating:
IP30 Wiring Enclosure
Detector Enclosure: IP65
Filtration:
Serviceable filter
External filter optional|
Flow Monitoring and Reporting:
High and Low programmable flow limits
Aspirator:
Control: 10 programmable speeds
Pressure: 250 Pa
Relay outputs:
XAS-1: 1 fault relay output
XAS-2: 2 fault relay outputs
Field Wiring:
Screw Terminals
18 to 10 AWG (0.9 to 5.5 sq. mm) solid
20 to 12 AWG (0.6 to 3.5 sq. mm) stranded
---|---|---
www.xtralis.com
UK and Europe +44 1442 242 330 D-A-CH +49 431 23284 1 The Americas +1 781
740 2223
Middle East +962 6 588 5622 Asia +86 21 5240 0077 Australia and New Zealand
+61 3 9936 7000
The contents of this document are provided on an “as is” basis. No
representation or warranty (either express or implied) is made as to the
completeness, accuracy or reliability of the contents of this document. The
manufacturer reserves the right to change designs or specifications without
obligation and without further notice. Except as otherwise provided, all
warranties, express or implied, including without limitation any implied
warranties of merchantability and fitness for a particular purpose are
expressly excluded.
Xtralis, the Xtralis logo, The Sooner You Know, VESDA-E, VESDA, ICAM, ECO,
OSID, HeiTel, ADPRO, Intrusion Trace, Loiter Trace, Client Trace, SmokeTrace,
XOa, XOh, iTrace, iCommand, iRespond, iCommission, iPIR, and FMST are
trademarks and/or registered trademarks of Xtralis and/or its subsidiaries in
the United States and/or other countries. Other brand names mentioned herein
are for identification purposes only and may be trademarks of their respective
holder(s). Your use of this document does not constitute or create a licence
or any other right to use the name and/or trademark and/or label.
This document is subject to copyright owned by Xtralis. You agree not to copy,
communicate to the public, adapt, distribute, transfer, sell, modify or
publish any contents of this document without the express prior written
consent of Xtralis.
Doc. no. 20637_03
Part no. 29877
firealarmresources.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>