NOTIFIER AFP-400 Analog Fire Panel Instruction Manual
- June 9, 2024
- NOTIFIER
Table of Contents
AFP-400 Analog Fire Panel
12 Clintonville Road Northford, CT 06472 203-484-7161 203-484-7118 (Fax)
Installation Manual
www.PDF-Zoo.com
C
firealarmresources.com
Installation Precautions – Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING – Several different sources of power can be connected to the fire
alarm control panel. Disconnect all sources of power before servicing. Control
unit and associated equipment may be damaged by removing and/or inserting
cards, modules, or interconnecting cables while the unit is energized. Do not
attempt to install, service, or operate this unit until this manual is read
and understood.
CAUTION – System Reacceptance Test after Software Changes: To ensure proper
system operation, this product must be tested in accordance with NFPA 721993
Chapter 7 after any programming operation or change in site-specific software.
Reacceptance testing is required after any change, addition or deletion of
system components, or after any modification, repair or adjustment to system
hardware or wiring.
All components, circuits, system operations, or software functions known to be
affected by a change must be 100% tested. In addition, to ensure that other
operations are not inadvertently affected, at least 10% of initiating devices
that are not directly affected by the change, up to a maximum of 50 devices,
must also be tested and proper system operation verified.
Like all solid state electronic devices, this system may operate erratically
or can be damaged when subjected to lightning induced transients. Although no
system is completely immune from lightning transients and interferences,
proper grounding will reduce susceptibility. Overhead or outside aerial wiring
is not recommended, due to an increased susceptibility to nearby lightning
strikes. Consult with the Technical Services Department if any problems are
anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit
boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or
punching of the enclosure. When possible, make all cable entries from the
sides or rear. Before making modifications, verify that they will not
interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over tightening may damage
threads, resulting in reduced terminal contact pressure and difficulty with
screw terminal removal.
This system meets NFPA requirements for operation at 0-49O C/32-120O F and at
a relative humidity of 85% RH (non-condensing) at 30O C/86O F. However, the
useful life of the system’s standby batteries and the electronic components
may be adversely affected by extreme temperature ranges and humidity.
Therefore, it is recommended that this system and its peripherals be installed
in an environment with a nominal room temperature of 15-27O C/60-80O F.
Verify that wire sizes are adequate for all initiating and indicating device
loops. Most devices cannot tolerate more than a 10% I.R. drop from the
specified device voltage.
This system contains static-sensitive components. Always ground yourself with
a proper wrist strap before handling any circuits so that static charges are
removed from the body. Use static suppressive packaging to protect electronic
assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming
manuals. These instructions must be followed to avoid damage to the control
panel and associated equipment. FACP operation and reliability depend upon
proper installation.
Fire Alarm System Limitations While installing a fire alarm system may make lower insurance rates possible, it is not a substitute for fire insurance!
An automatic fire alarm system – typically made up of smoke detectors, heat
detectors, manual pull stations, audible warning devices, and a fire alarm
control with remote notification capability can provide early warning of a
developing fire. Such a system, however, does not assure protection against
property damage or loss of life resulting from a fire.
Any fire alarm system may fail for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such
as in chimneys, in walls, or roofs, or on the other side of closed doors.
Smoke detectors also may not sense a fire on another level or floor of a
building. A second floor detector, for example, may not sense a first floor or
basement fire. Furthermore, all types of smoke detectors – both ionization and
photoelectric types, have sensing limitations. No type of smoke detector can
sense every kind of fire caused by carelessness and safety hazards like
smoking in bed, violent explosions, escaping gas, improper storage of
flammable materials, overloaded electrical circuits, children playing with
matches, or arson.
IMPORTANT! Smoke detectors must be installed in the same room as the control
panel and in rooms used by the system for the connection of alarm transmission
wiring, communications, signaling, and/or power. If detectors are not so
located, a developing fire may damage the alarm system, crippling its ability
to report a fire.
Audible warning devices such as bells may not alert people if these devices
are located on the other side of closed or partly open doors or are located on
another floor of a building.
A fire alarm system will not operate without any electrical power. If AC power
fails, the system will operate from standby batteries only for a specified
time.
Rate-of-Rise heat detectors may be subject to reduced sensitivity over time.
For this reason, the rate-of-rise feature of each detector should be tested at
least once per year by a qualified fire protection specialist.
Equipment used in the system may not be technically compatible with the
control. It is essential to use only equipment listed for service with your
control panel.
Telephone lines needed to transmit alarm signals from a premise to a central
monitoring station may be out of service or temporarily disabled.
The most common cause of fire alarm malfunctions, however, is inadequate
maintenance. All devices and system wiring should be tested and maintained by
professional fire alarm installers following written procedures supplied with
each device. System inspection and testing should be scheduled monthly or as
required by National and/or local fire codes. Adequate written records of all
inspections should be kept.
FCC Warning
WARNING: This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his own expense.
Canadian Requirements This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital apparatus set out in the
Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n’emet pas de bruits radioelectriques depassant
les limites applicables aux appareils numeriques de la classe A prescrites
dans le Reglement sur le brouillage radioelectrique edicte par le ministere
des Communications du Canada.
Technical Publishing
www.PDF-Zoo.com
firealarmresources.com
Document PRECAULG.PM6 12/31/96
Introduction ………………………………………………………………………………………………..1-1 About this
Manual……………………………………………………………………………………..1-1 Description
……………………………………………………………………………………………….1-1 Standard Features and
Options…………………………………………………………………….1-2 System
Limitations…………………………………………………………………………………….1-2 AFP-300 System Diagram
………………………………………………………………………….1-3 AFP-400 System Diagram
………………………………………………………………………….1-4
Specifications………………………………………………………………………………………………. 1-5 Overview
………………………………………………………………………………………………….1-5 AC Power
…………………………………………………………………………………………………1-5 Battery (sealed lead-acid
only)…………………………………………………………………….1-5 Signaling Line Circuit (SLC)
Loop………………………………………………………………1-5 Notification Appliance and Releasing Circuits
(MPS-400 ICM-4, ICE-4) ………..1-6 Relays
………………………………………………………………………………………………………1-6 Four-wire Smoke Detector
Power………………………………………………………………..1-6 Power Outputs
…………………………………………………………………………………………..1-7 Operating
Power………………………………………………………………………………………..1-7 AC Branch Circuit
…………………………………………………………………………………1-7 Secondary Power Source (Batteries)
………………………………………………………..1-7
System Components …………………………………………………………………………………….1-8 Basic Equipment
Packages …………………………………………………………………………1-8 CPU
…………………………………………………………………………………………………………1-8 Power
Supplies………………………………………………………………………………………….1-9 Audio Amplifiers
…………………………………………………………………………………….1-10 Transformer Assembly and MPS-400PCA
………………………………………………….1-10 Battery Boxes ………………………………………………………………………………………….1-10
Optional Devices ………………………………………………………………………………………..1-11
Intelligent Detectors …………………………………………………………………………………..1-12 Overview
………………………………………………………………………………………………..1-12 Detector
Descriptions……………………………………………………………………………….1-12
Addressable Modules …………………………………………………………………………………1-13 Overview
………………………………………………………………………………………………..1-13 Module Descriptions
………………………………………………………………………………..1-13
End-of-Line Devices …………………………………………………………………………………..1-14
Annunciation Modules ……………………………………………………………………………….1-15 Overview
………………………………………………………………………………………………..1-15 LDM Series Lamp Driver Modules
……………………………………………………………1-15 Annunciator Control System (ACS)
…………………………………………………………..1-16 Annunciator Fixed
Modules………………………………………………………………………1-16
Peripheral Displays and Printers ………………………………………………………………..1-17 Overview
………………………………………………………………………………………………..1-17 LCD-80 Display
………………………………………………………………………………………1-17 PRN-4 Remote Printer
……………………………………………………………………………..1-17 Keltron Remote Printer (Model VS4095)
……………………………………………………1-17 CRT-2 Terminal ………………………………………………………………………………………1-17
Notification Circuit and Control Modules …………………………………………………..1-18 Overview
………………………………………………………………………………………………..1-18 Descriptions of Modules
…………………………………………………………………………..1-18
Voice Alarm Equipment …………………………………………………………………………….1-19 Overview
………………………………………………………………………………………………..1-19 Audio Message Generator (AMG-1)
………………………………………………………….1-19
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
iii
www.PDF-Zoo.com
firealarmresources.com
iv
www.PDF-Zoo.com
2. Installation
Audio Tone Generator (ATG-2) ………………………………………………………………..1-19 Fire Fighters
Telephone FFT-7/FFT-7S………………………………………………………1-19 Voice Control Module (VCM-4)
……………………………………………………………….1-19 Dual Channel Module (DCM-4)
………………………………………………………………..1-19 Cabinet Hardware
……………………………………………………………………………………..1-20 Cabinet
Overview…………………………………………………………………………………….1-20 CHS-4M Chassis/Dress Panel
Assembly…………………………………………………….1-20 CHS-4L Chassis
………………………………………………………………………………………1-20 CAB-X3 Series
Cabinets…………………………………………………………………………..1-21
Overview ……………………………………………………………………………………………. 1-21 CAB-A3
……………………………………………………………………………………………..1-21 CAB-B3
……………………………………………………………………………………………..1-21 CAB-C3
……………………………………………………………………………………………..1-22 CAB-D3
……………………………………………………………………………………………..1-22 CAB-400AA Cabinets
……………………………………………………………………………..1-23 CAB-400AA Overview
………………………………………………………………………..1-23 CAB-400AA
Limitations………………………………………………………………………1-23 CAB-400AA Dimensions
……………………………………………………………………..1-23
Preparing for Installation …………………………………………………………………………….2-1 Installation
Checklist……………………………………………………………………………………2-2 Installing a Cabinet
Door……………………………………………………………………………..2-4
Cabinet Door Mounting Guidelines ……………………………………………………………..2-4 How to Install a
Cabinet Door (CAB-X3 only) ……………………………………………..2-4 Installing the Door
Alignment Tabs……………………………………………………………..2-5 Installing a Chassis (CAB-X3 Series
Cabinets) ……………………………………………..2-6 Overview
………………………………………………………………………………………………….2-6 Installing a CHS-4
Chassis………………………………………………………………………….2-6 Installing a CHS-4L Chassis
……………………………………………………………………….2-6 Mounting a Backbox (SBB-X3 and CAB-400AA)
………………………………………….2-7 Mounting an MPS-400 Power Supply
…………………………………………………………..2-8 Mounting an MPS-400 into a CAB-X3 Cabinet
…………………………………………….2-8 Mounting an MPS-400 into a CAB-
400AA…………………………………………………..2-9 Mounting an Optional AVPS-24 Power Supply
…………………………………………..2-10 Overview ………………………………………………………………………………………………..2-10
Installation ……………………………………………………………………………………………… 2-10 Installing an Auxiliary
Relay Module (ARM-4)…………………………………………..2-11 Overview
………………………………………………………………………………………………..2-11 Mounting the ARM-4 Module to a
CHS-4 Chassis ………………………………………2-11 Wiring the ARM-4
Module……………………………………………………………………….2-12 Connecting the MPS-400 Power Cables
………………………………………………………2-13 MPS-400 Electrical Connections
……………………………………………………………….2-13 Connecting the MPS-400 to AC Power (TB1)
…………………………………………….2-13 Connecting the Batteries (MPS-400, TB1-6, TB1-7)
……………………………………2-13
Connecting Four-Wire Smoke Detector 24 VDC Power (MPS-400, TB2)…..2-14
Notification Appliance Power (24 VDC) ………………………………………………..2-14 Annunciator
Power (24 VDC) ……………………………………………………………….2-14 System Harness
Connections…………………………………………………………………2-14 System Power Connections
…………………………………………………………………..2-14 Installing Expander Row Ribbon Cables for
Panel Modules………………………..2-15 Installing Row Ribbon Cables for CAB-B3, CAB-C3,
and CAB-D3 Cabinets ..2-15 Installing Row Ribbon Cables for CAB-C3 and CAB-D3
Cabinets ……………….2-16 Installing Row Ribbon Cables for a CAB-400AA Cabinet
……………………………2-17 Installing the CPU ……………………………………………………………………………………..2-18
Installing the CPU into a Chassis……………………………………………………………….2-18
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
firealarmresources.com
2. Installation
Connecting the CPU to the MPS-400 …………………………………………………………2-19
Mounting Expander Modules (CRE-4, ICE-4, VCE-4) ………………………………..2-20
Mounting Panel Modules (CRM-4, ICM-4, VCM-4) onto a Chassis…………….2-21
Installing a 4XTM Module (Remote Station Fire Alarm) …………………………….2-22 Mounting
the Module……………………………………………………………………………….2-22 4XTM Electrical Requirements
…………………………………………………………………2-22 Connecting the 4XTM Module
………………………………………………………………….2-23
Installing a UZC-256 Module ……………………………………………………………………..2-24 Overview
……………………………………………………………………………………………. 2-24 CAB-X3 Installation
…………………………………………………………………………….2-24 CAB-400AA Installation
………………………………………………………………………2-24
Field-Wiring the Modules…………………………………………………………………………..2-25 Notification
Appliance Circuit (NAC) Wiring …………………………………………….2-25 MPS-400/ICM-4 NAC
Configurations ……………………………………………………….2-25 Typical Power Supply/Notification
Appliance Circuit Configurations………..2-25 AVPS-24/ICM-4 NAC Configurations
………………………………………………….2-26 Field-Wiring an ICM-4 and an ICE-4 (NFPA Style Y and
Z)………………………..2-27 Field-Wiring a CRM-4 and the CRE-4
……………………………………………………….2-28 CRM-4 and CRE-4 Wiring
Guidelines……………………………………………………2-28 CRM-4 and CRE-4 Connections
……………………………………………………………2-28 Field Wiring an Optional AVPS-24 Power Supply
………………………………………2-29 AVPS-24 Wiring Overview…………………………………………………………………..2-29
AVPS-24 Wiring Diagrams …………………………………………………………………..2-29 Field Wiring Four-Wire
Smoke Detectors (Style B and Style D) …………………..2-30 Field Wiring Overview
…………………………………………………………………………2-30 Field Wiring (Style D)
………………………………………………………………………….2-30 Field Wiring (Style B)
………………………………………………………………………….2-30 Field Wiring the Auxiliary Relay Module
(ARM-4) …………………………………….2-31 Overview ……………………………………………………………………………………………. 2-31
ARM-4 Terminal Assignments………………………………………………………………2-31 Field Wiring the
MPS-400 Power Supply …………………………………………………..2-32 MPS-400 Board
…………………………………………………………………………………..2-32 DC Power Output Connections
(MPS-400)……………………………………………..2-33 AC and Battery Power Connections (MPS-400
……………………………………….2-33 Wiring MPS-400 Output Circuits
…………………………………………………………..2-34
Installing Remote Printers and CRTs …………………………………………………………2-35 Remote Printers
……………………………………………………………………………………….2-35 Setting PRN-4
Options……………………………………………………………………………..2-35 Installing a PRN-4 Remote Printer
…………………………………………………………2-36 Installing a Keltron Printer
……………………………………………………………………2-37 Setting up the Keltron Printer
………………………………………………………………..2-37 Installing a
CRT-2……………………………………………………………………………………2-38 Connecting Multiple Printers, CRTs,
or CRT/PRN Combination…………………..2-38
Wiring a Signaling Line Circuit (SLC) ……………………………………………………….2-39 Overview of
SLC Wiring ………………………………………………………………………….2-39 SLC
Devices……………………………………………………………………………………………2-40 Control Panel Capacity
…………………………………………………………………………….2-40 SLC Performance
…………………………………………………………………………………….2-41 SLC Shield Termination
…………………………………………………………………………..2-42 Wire Requirements for a Two-Wire SLC
……………………………………………………2-43 Measuring Loop Resistance for a Two-Wire SLC
……………………………………2-43 Measuring Total Wire Length for a Two-wire SLC
………………………………….2-43 Wire Requirements for a Four-Wire SLC
……………………………………………………2-45 Measuring Loop Resistance for a Four-Wire SLC
……………………………………2-45 Measuring Total Wire Length for a Four-wire
SLC………………………………….2-45 Style 6 Wiring Overview ………………………………………………………………………2-46
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
v
www.PDF-Zoo.com
firealarmresources.com
3. Testing the System
Style 6 Wiring Diagram ………………………………………………………………………..2-46 Style 7 Wiring Overview ………………………………………………………………………2-47 Style 7 Wiring Diagram ………………………………………………………………………..2-47 Wiring an Isolator Module (ISO-X)……………………………………………………………2-48 ISO-X Overview ………………………………………………………………………………….2-48 Isolating a Branch of a Two-Wire SLC …………………………………………………..2-48 Wiring an IDC with MMX Modules…………………………………………………………..2-49 Overview of Monitor Modules (MMX Series)…………………………………………2-49 Wiring an MMX Module ………………………………………………………………………2-49 Wiring an NFPA Style B IDC with MMX-1s …………………………………………2-50 Wiring an NFPA Style B IDC with MMX-2s …………………………………………2-51 Wiring an NFPA Style B IDC with MMX-1s ………………………………………..2-52 Wiring a NFPA Style D IDC with MMX-2 Modules………………………………..2-53 Wiring a Notification Appliance Circuit (NAC) or Control Circuit ………………..2-54 CMX Module Overview ……………………………………………………………………….2-54 Testing a CMX Module ………………………………………………………………………..2-54 Installing a CMX Module as a Form-C Relay ………………………………………….2-55 SLC Wiring with CMX Modules ……………………………………………………………….2-55 Style Y NAC Circuits (Two-Wire) …………………………………………………………2-56 Wiring Diagram and Instructions……………………………………………………………2-56 Style Z NAC ……………………………………………………………………………………….2-57 Style Z NAC Circuits (Method 1 MPS-400 powers CMX)……………………..2-58 Style Z NAC Circuits (Method 2 MPS-400 powers CMX)……………………..2-59 SLC Wiring with an Intelligent Detector …………………………………………………….2-60 Overview for Wiring Intelligent Detectors ………………………………………………2-60 Wiring a BX-501 Detector to an SLC Loop …………………………………………….2-60 SLC Wiring with a BX-101L Addressable Manual Pull Station …………………….2-61 BX-101L Overview ……………………………………………………………………………..2-61 BX- 101L Wiring Connections……………………………………………………………….2-61
Acceptance Test …………………………………………………………………………………………..3-1
Periodic Testing and Service ………………………………………………………………………..3-1
Operational Checks ……………………………………………………………………………………..3-1
Battery Checks and Maintenance …………………………………………………………………3-2
Section Overview …………………………………………………………………………………………4-1
Installing an AMG ……………………………………………………………………………………….4-2 Configuring the AMG…………………………………………………………………………….4-4 AMG-1 and AMG-E Tone/Message Selections (SW2=Off)………………………..4-5 AMG-1 and AMG-E Tone/Message Selections (SW2=On) ………………………..4-6 ATG-2 Terminal Connections …………………………………………………………………4-7
Installing a Fire Fighter’s Telephone (FFT-7 and FFT-7S) ……………………………4-8 Overview ………………………………………………………………………………………………….4-8 Mounting an FFT-7/FFT-7S ……………………………………………………………………….4-8 Connecting an FFT-7/FFT- 7S……………………………………………………………………..4-9
Installing Audio Amplifiers (AA-30/AA-100/AA-120) ………………………………….4-10 Installing an AA-30………………………………………………………………………………….4-10 Overview ……………………………………………………………………………………………. 4-10 Mounting an AA-30……………………………………………………………………………..4-10 AA-30 Terminals and Connectors ………………………………………………………….4-11 Installing an AA-100/AA-120……………………………………………………………………4-12 Overview ……………………………………………………………………………………………. 4-12 Mounting an AA-100/AA-120……………………………………………………………….4-12 AA-100/AA-120 Terminals and Connectors ……………………………………………4-13 Installing a Backup Amplifier ……………………………………………………………………4-14
vi
www.PDF-Zoo.com
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
firealarmresources.com
4. Voice Alarm System
Overview ……………………………………………………………………………………………. 4-14 Typical Installation
Drawing …………………………………………………………………4-14
Voice Alarm Modules…………………………………………………………………………………4-15 Overview
………………………………………………………………………………………………..4-15 Module Descriptions
………………………………………………………………………………..4-15 Connecting VCM-4 Speaker Circuits
…………………………………………………………4-16 Overview ……………………………………………………………………………………………. 4-16
VCM-4 Speaker Wiring Diagram…………………………………………………………..4-16 Connecting VCM-4
Telephone Circuits ……………………………………………………..4-17 Wiring Diagram
…………………………………………………………………………………..4-17 Setting the VCM-4 to Speaker or
Telephone Mode ………………………………….4-18 Connecting a CMX-2 Module to Speaker
Circuits……………………………………4-18 Connecting Dual Channel Module Circuits
…………………………………………………4-19 Wiring Notes……………………………………………………………………………………….4-19
Wiring Diagram …………………………………………………………………………………..4-19
Voice System Configurations………………………………………………………………………4-20 Voice Systems
Wiring Overview……………………………………………………………….4-20 Internal Power
Distribution……………………………………………………………………….4-21 Wiring Diagram
…………………………………………………………………………………..4-21 Block Diagram
…………………………………………………………………………………….4-21 CPU EIA-485 Connections
……………………………………………………………………….4-22 Wiring Diagram
…………………………………………………………………………………..4-22 Block Diagram
…………………………………………………………………………………….4-22 Wiring an Audio Signal without a Backup
Amplifier …………………………………..4-23 Wiring
Notes……………………………………………………………………………………….4-23 Typical Wiring Diagram
……………………………………………………………………….4-23 Block Diagram
…………………………………………………………………………………….4-23 Audio Signal Wiring Using a Backup
Amplifier ………………………………………….4-24 Wiring
Notes……………………………………………………………………………………….4-24 Wiring Diagram
…………………………………………………………………………………..4-24 Block Diagrams
…………………………………………………………………………………..4-24 CPU-400 Trouble Bus
Connections……………………………………………………………4-25 Wiring
Notes……………………………………………………………………………………….4-25 Wiring Diagram
…………………………………………………………………………………..4-25 Block Diagram
…………………………………………………………………………………….4-25
Wiring Speaker Circuits …………………………………………………………………………….4-26 Wiring Speaker
Circuit Overview………………………………………………………………4-26 30 Watt/Four and Eight Speaker
Circuits ……………………………………………………4-27 Wiring
Notes……………………………………………………………………………………….4-27 Wiring Four Speakers
…………………………………………………………………………..4-27 Wiring Eight Speakers
………………………………………………………………………….4-27 120 Watt/Four and Eight Speaker Circuits
………………………………………………….4-28 Wiring Notes……………………………………………………………………………………….4-28
Wiring Four Speakers …………………………………………………………………………..4-28 Wiring Four Speakers
…………………………………………………………………………..4-28 90 Watt/Eight Speaker Circuit
Configuration………………………………………………4-29 Wiring
Notes……………………………………………………………………………………….4-29 Wiring Diagram
…………………………………………………………………………………..4-29 240 Watt/Eight Speaker Circuit
…………………………………………………………………4-30 Wiring
Notes……………………………………………………………………………………….4-30 Wiring Diagram
…………………………………………………………………………………..4-30 180 Watt/Eight Speaker Circuit
Configuration…………………………………………….4-31 Wiring
Notes……………………………………………………………………………………….4-31 Wiring Diagram
…………………………………………………………………………………..4-31 30 Watt Dual-Channel Configuration
…………………………………………………………4-32 Wiring Notes……………………………………………………………………………………….4-32
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
vii
www.PDF-Zoo.com
firealarmresources.com
!!
viii
www.PDF-Zoo.com
5. Applications
Wiring Diagram …………………………………………………………………………………..4-32 120 Watt Dual-Channel
Configuration (Four AA-30s) …………………………………4-33
Wiring Notes……………………………………………………………………………………….4-33 Wiring Diagram
…………………………………………………………………………………..4-33 120 Watt Dual-Channel Configuration (Two
AA-120s) ……………………………….4-34 Wiring Notes……………………………………………………………………………………….4-34
Wiring Diagram …………………………………………………………………………………..4-34 Voice Message Options
(VROM and VRAM) ……………………………………………..4-35 Overview of VROM and VRAM
……………………………………………………………….4-35 Installing VROM and VRAM
……………………………………………………………………4-35 ACT-1 Audio Coupling Transformer
………………………………………………………….4-36 ACT-1
Overview……………………………………………………………………………………..4-36 Isolating Power
Supplies…………………………………………………………………………..4-36 ACT-1 Installation
…………………………………………………………………………………..4-37 Installation Notes
…………………………………………………………………………………4-37 Installation Diagram
…………………………………………………………………………….4-37 Connecting the
ACT-1………………………………………………………………………….4-37
Applications Overview …………………………………………………………………………………5-1 Central or Remote
Station Fire Alarm System ……………………………………………..5-2
Installation ……………………………………………………………………………………………….. 5-2 Wiring Diagram
………………………………………………………………………………………..5-2 Auxiliary Fire Alarm System
……………………………………………………………………….5-3 Overview
………………………………………………………………………………………………….5-3 Wiring Diagram
………………………………………………………………………………………..5-3 NFPA 72-1993 Remote Station Fire Alarm
System ……………………………………….5-4 Overview ………………………………………………………………………………………………….5-4
Wiring Diagram ………………………………………………………………………………………..5-4 NFPA 72-1993 Proprietary
Fire Alarm Systems ……………………………………………5-5 Overview
………………………………………………………………………………………………….5-5 Wiring Diagram
………………………………………………………………………………………..5-5 Network Interface Board
(NIB-96)……………………………………………………………….5-6 NIB-96
Overview………………………………………………………………………………………5-6 NIB-96
Assembly………………………………………………………………………………………5-6 NIB-96 SLC and EIA-485
Connections ……………………………………………………….5-7 Wiring
Specifications…………………………………………………………………………………5-7 Using the XP Transponder with
the AFP-300/AFP-400 …………………………………5-8 XP Transponder
Overview………………………………………………………………………….5-8 Wiring Diagram
………………………………………………………………………………………..5-8 Combination Fire/Security
Applications……………………………………………………….5-9 Overview
………………………………………………………………………………………………….5-9 General Operation
……………………………………………………………………………………..5-9 Installing a Security Tamper Switch
…………………………………………………………….5-9
Installing a Security Tamper Switch into the CAB-400AA ………………………..5-9
Installing a Security Tamper Switch into the CAB-X3 ……………………………..5-10
Receiving Unit ………………………………………………………………………………………..5-10 Programming
………………………………………………………………………………………….. 5-10 Wiring for Proprietary Security
Alarm Applications…………………………………….5-11 Universal Zone Coder
(UZC-256)……………………………………………………………….5-12 UZC-256
Description……………………………………………………………………………….5-12 UZC-256 Connectors and
Indicators ………………………………………………………….5-12 NAC and EIA-485 Power Connections
………………………………………………………5-13 Installing the UZC-256
…………………………………………………………………………….5-14 Overview
……………………………………………………………………………………………. 5-14 CAB-X3 Installation
…………………………………………………………………………….5-14
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
firealarmresources.com
CAB-400AA Installation ………………………………………………………………………5-14 UZC-256 Electrical
Connections ……………………………………………………………….5-15 Wiring Diagram
………………………………………………………………………………………5-15 Wiring 12 Zone-Coded NACs
…………………………………………………………………..5-16 Wiring 20 Zone-Coded NACs
…………………………………………………………………..5-17
Releasing Applications ……………………………………………………………………………….5-18 Overview
………………………………………………………………………………………………..5-18 Programming Releasing
Applications…………………………………………………………5-18 Wiring for Releasing
Applications……………………………………………………………..5-18 Connecting a Releasing Device to the
MPS-400 ………………………………………….5-19 Overview …………………………………………………………………………………………….
5-19 Typical Connections …………………………………………………………………………….5-19 Connecting a
Releasing Device to an ICM-4/ICE-4 Module …………………………5-20 Overview
……………………………………………………………………………………………. 5-20 Typical Connections
…………………………………………………………………………….5-20 Connecting a Releasing Device to a CMX
Module ………………………………………5-21 Overview ……………………………………………………………………………………………. 5-21
Typical Connections …………………………………………………………………………….5-21 Connecting an N-ARA-10
Agent Release-Abort Station ………………………………5-22 Overview
……………………………………………………………………………………………. 5-22 Typical Connections
…………………………………………………………………………….5-22 Installing a Combination
Waterflow/Supervisory Valve Monitor…………………..5-23 Overview
……………………………………………………………………………………………. 5-23 Typical Connections
…………………………………………………………………………….5-23
!!
“#$
%
Overview……………………………………………………………………………………………………. A-1
Annunciator Interfaces ………………………………………………………………………………. A-1 Terminal Mode
(LCD-80)…………………………………………………………………………. A-1 ACS
Mode………………………………………………………………………………………………. A-1
Annunciator Selection Groups ……………………………………………………………………. A-2 Overview
………………………………………………………………………………………………… A-2 ACS Annunciator Selection Group 2
………………………………………………………….. A-4 ACS Annunciator Selection Group 3
………………………………………………………….. A-5 ACS Annunciator Selection Group 4 (AFP-400 only)
………………………………….. A-6 ACS Annunciator Selection Group 5 …………………………………………………………..
A-7 ACS Annunciator Selection Group 6 ………………………………………………………….. A-8 ACS
Annunciator Selection Group 7 (AFP-400 only) ………………………………….. A-9 ACS
Annunciator Selection Group 8 ………………………………………………………… A-10 ACS Annunciator
Selection Group 9 ………………………………………………………… A-11
Connecting Annunciators …………………………………………………………………………. A-12 Overview
………………………………………………………………………………………………. A-12 LCD-80 Terminal Mode EIA-485
Connection (CPU, TB3) ………………………… A-13 Connection
Guidelines………………………………………………………………………… A-13 Connecting LCD-80s in Terminal
Mode ……………………………………………….. A-13 LCD-80 ACS Mode EIA-485 Connection (CPU, TB4)
………………………………. A-14 Connection Guidelines………………………………………………………………………… A-14
Connecting LCD-80s in ACS Mode …………………………………………………….. A-14 Powering ACS-,
ACM-, and LCD-type Annunciators ………………………………… A-15
Overview…………………………………………………………………………………………… A-15 Power Connections for LCD and
ACS Annunciators………………………………. A-15 Power Connections for LCD-
80s………………………………………………………….. A-15 ACS and LDM Series EIA-485 Connection
………………………………………………. A-16 Connection Guidelines…………………………………………………………………………
A-16 ACS and LDM Series EIA-485 Connections …………………………………………. A-16
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
ix
www.PDF-Zoo.com
firealarmresources.com
!!
“#&$'()%
!!
“# $ !*)%!
!!
“#+$ (,
%
Overview ………………………………………………………………………………………………… D-1 Setting CRT-2
Parameters…………………………………………………………………………. D-1 Uploading or Downloading the
Operating Program ……………………………………… D-2
!!
“#*$
–
General Description……………………………………………………………………………………. E-1
Operating Modes ……………………………………………………………………………………….. E-1 Local Terminal Mode
(LocT) ……………………………………………………………………. E-1 Local Monitor Mode
(LocM)…………………………………………………………………. E-2 Remote Terminal Mode (RemT)
……………………………………………………………. E-3
Using the CRT-2 for Read Status………………………………………………………………… E-4 Overview
………………………………………………………………………………………………… E-4 Accessing Read Status
Options………………………………………………………………….. E-4 Read Point
………………………………………………………………………………………………. E-5 Display Devices in Alarm or Trouble
…………………………………………………………. E-5 Display the Status of all Programmed
Points……………………………………………….. E-5 View the History
Buffer……………………………………………………………………………. E-6 Send the History Buffer to the CRT-2
………………………………………………………… E-6
Using the CRT-2 for Alter Status………………………………………………………………… E-7 Overview
………………………………………………………………………………………………… E-7 Accessing Alter Status
Options………………………………………………………………….. E-7 Enable or Disable Detectors, Modules,
or Panel Circuits ………………………………. E-8 Change Alarm and Pre-Alarm levels
………………………………………………………….. E-9 Clear the Verification Counter
…………………………………………………………………… E-9 Clear the Entire History Buffer
………………………………………………………………….. E-9 Set the Pre-Alarm for Alert or
Action…………………………………………………………. E-9
!!
“#.$/0-,”‘
()%
Overview……………………………………………………………………………………………………. F-1
Power-limited Modules and Circuits …………………………………………………………… F-1 UL Power-
limited Wiring Requirements ………………………………………………………F-2 Power Supply Wiring
…………………………………………………………………………………F-3
!!
“#1$-%!! %
Overview……………………………………………………………………………………………………. G-1
Calculating AC Branch Circuit Current ……………………………………………………… G-1 Calculating
the System Current Draws……………………………………………………….. G-1
How to Use Table G-2 ……………………………………………………………………………… G-2 Calculating the
Maximum Secondary Power Fire Alarm Current Draw ………….. G-4
Calculating the Battery Requirements ………………………………………………………… G-5 Calculating
the Battery Capacity ……………………………………………………………….. G-5 Calculating the Battery
Size………………………………………………………………………. G-5
x
www.PDF-Zoo.com
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
firealarmresources.com
Standards and Other Documents
“”
“+%
This Fire Alarm Control
NFPA 12 CO2 Extinguishing Systems
Panel complies with the fol- NFPA 12A Halon 1301 Extinguishing Systems
lowing NFPA standards:
NFPA 12B Halon 1211 Extinguishing Systems
NFPA 13 Sprinkler Systems
NFPA 15 Water Spray Systems
NFPA 16 Foam/Water Deluge and Foam/Water Spray Systems
NFPA 17 Dry Chemical Extinguishing Systems
NFPA 17A Wet Chemical Extinguishing Systems
NFPA 72-1993 Central Station Fire Alarm Systems (Automatic, Manual and Water-
flow) Protected Premises Unit (requires Notifier UDACT).
NFPA 72-1993 Local (Automatic, Manual, Waterflow and Sprinkler Supervisory) Fire
Alarm Systems.
NFPA 72-1993 Auxiliary (Automatic, Manual and Waterflow) Fire Alarm Systems
(requires 4XTM).
NFPA 72-1993 Remote Station (Automatic, Manual and Waterflow) Fire Alarm Sys-
tems (requires 4XTM or NOTI-FIRE 911A DACT).
NFPA 72-1993 Proprietary (Automatic, Manual and Waterflow) Fire Alarm Systems
(Protected Premises Unit).
NFPA 2001 Clean Agent Fire Extinquishing Systems
The installer should be famil-
iar with the following docu- NFPA 72-1993 Initiating Devices for Fire Alarm Systems
ments and standards:
NFPA 72-1993 Inspection, Testing and Maintenance for Fire Alarm Systems
NFPA 72-1993 Notification Appliances for Fire Alarm Systems
UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detectors, Single and Multiple Station UL 228 Door Closers – Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 268A Smoke Detectors for Duct Applications UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1971 Visual Signaling Appliances UL 1076 Proprietary Burglar Alarm Systems
Standard CAN/ULC-S527-M87
EIA-485 and EIA-232 Serial Interface Standards NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
xi
www.PDF-Zoo.com
firealarmresources.com
Document Title
Document Number
The LDM Series Annunciator
15885
The LCD-80 Liquid Crystal Display
15037
The Device Compatibility Document The NIB-96 Network Interface Board The ACM- 8R Annunciator Control Module
15378 15666 15342
The ACS Series Annunciators
15843
AFP-300/AFP-400 Operations Manual AFP-300/AFP-400 Programming Manual AFP-300/AFP-400 Basic System Connections The AFM-16A Annunciator
50260 50259 50683 15207
The AM2020/AFP1010 Manual
15088
Veri-Fire 400 Product Installation Document
50376
The UDACT Manual
50050
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
xii
www.PDF-Zoo.com
firealarmresources.com
6VWHP2YHUYLHZ
,QWURGXFWLRQ
1RWH 7KURXJKRXW WKLV PDQXDO FRQWURO SDQHO UHIHUV WR DQ $)3$)3 FRQWURO SDQHO DQG &38 UHIHUV WR D &38 RU &38
$ERXWWKLV0DQXDO
This manual contains information for designing, installing, and testing the
AFP-300/ AFP-400 Fire Alarm Control Panel and fire alarm system components.
Table 1-1 contains a list of document sources for supplemental information:
For information on…
Refer to…
Part Number
All features Programming Operation Compatible Devices System Connections
AFP-300/AFP-400 Data Sheet AFP-300/AFP-400 Programming Manual AFP-300/AFP-400 Operations Manual Device Compatibility Document AFP-300/AFP-400 Basic System Drawing
DN-5262 50259 50260 15378 50683
$)3 $)3
Table 1-1 Supplemental Documentation
‘HVFULSWLRQ
The AFP-300 and AFP-400 control panels are modular, intelligent fire alarm
control panels (FACP) with an extensive list of powerful features. The CPU
module, power supply module, mounting chassis, and cabinet combine to create a
complete fire alarm control system with Notifier’s VIEWTM early warning fire
detection and optional voice and telephone, advanced networking. Optional
modules mount to the chassis to provide additional output circuits. This
manual covers the AFP-300 and the AFP-400 control panels, described as
follows:
!
An intelligent fire alarm control panel with a capacity for installing up to
464 intelligent, addressable devices (198 analog detectors and 198
monitor/control modules, and up to 68 internal circuits/relays). Five cabinet
options for the AFP-400 (CAB-400AA, CAB-A3, CAB-B3, CAB-C3, or CAB-D3) for
enclosing system components.
!
A cost-effective, compact, intelligent fire alarm control panel with a capacity of 266 points (99 intelligent detectors, 99 monitor/control modules, and up to 68 internal circuits/relays) using one Signaling Line Circuit (SLC) loop. The AFP-300 mounts into a CAB-400AA cabinet and provides the same features as the AFP-400, including voice and telephone, advanced networking, and Notifier’s VIEWTM early warning fire detection.
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
1-1
www.PDF-Zoo.com
firealarmresources.com
6VWHP 2YHUYLHZ
Introduction
6WDQGDUG)HDWXUHVDQG2SWLRQV
Control panel features and options that affect installation include:
· Four Notification Appliance Circuit (NAC) bell circuits standard, expandable
to 68 total (Class A or B).
· EIA-485 connections for wiring ACS annunciators (including LDM custom
graphic annunciators).
· Optional modules include: 4XTM transmitter, UDACT Universal Digital Alarm
Communicator/Transmitter, ACM-8R remote relay module to increase point
capacity, and audio and voice components.
· Autoprogram feature for faster programming of new devices. · Optional LCD-80
allows monitoring the system–up to 6,000 feet from the control
panel. The control panel provides 6.0 amps of usable output power (standard).
6VWHP/LPLWDWLRQV
System expansion must comply with:
1. The physical limitations of the cabinet configuration.
2. The electrical limitations of the system power supply, including auxiliary
power supplies used for notification appliances.
3. The capacity of the Secondary Power Source (standby batteries).
Refer to System Components, for descriptions of the various optional modules.
Refer to Section 2, Installation for installation information.
1-2
www.PDF-Zoo.com
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
firealarmresources.com
Introduction
6VWHP 2YHUYLHZ
$)36VWHP’LDJUDP
Figure 1-1 shows an AFP-300 system installed in a CAB-400AA with a voice alarm
system and a full complement of installed devices
)LJXUH $)3 6VWHP ‘LDJUDP
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
1-3
www.PDF-Zoo.com
firealarmresources.com
6VWHP 2YHUYLHZ
Introduction
$)36VWHP’LDJUDP
Figure 1-2 shows an AFP-400 system installed in a CAB-C3 with a voice alarm
system and a full complement of installed devices.
8S WR /&’ 5HPRWH ‘LVSOD&RQWURO
56
8S WR IXOO SURJUDPPDEOH RXWSXW FLUFXLWV
6/& ,QWHOOLJHQW /RRS
6′; &3;
)’;
‘HYLFHV %*;/ 00;
&0;
6/& ,QWHOOLJHQW /RRS
‘HYLFHV
6′; &3; )’;
%*;/ 00; &0;
$&6 56
,’&
1$&
DQQXQFLDWRU FRQWURO SRLQWV
;3 7UDQVSRQGHU ;3 7UDQVSRQGHU
!
$&05 5HOD &RQWURO
$&0$(0$7 DQQXQFLDWRU 2SWLRQDO FKDQQHO 8’$&7
/’0 FXVWRP JUDSKLFV
56 WHUPLQDO
‘XDO SKRQH OLQHV WR &HQWUDO 6WDWLRQ
351 SULQWHU
&57 WHUPLQDO
7R RWKHU )$&3
)LJXUH $)3 6VWHP ‘LDJUDP
1-4
www.PDF-Zoo.com
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
firealarmresources.com
Specifications
6SHFLILFDWLRQV
6VWHP 2YHUYLHZ
2YHUYLHZ
This section contains electrical specifications for the control panel.
$&3RZHU
Component MPS-400
AVPS-24 AA-30 AA-100/AA120 Wire size
Values
120 VAC, 50/60 Hz, 3.0 A; or 240 VAC, 50/60 Hz, 1.5 A 120 VAC, 1.0 A each 120
VAC, 1.0 A each 120 VAC, 50/60 Hz, 1.85 A each Minimum 14 AWG with 600 VAC
insulation
Table 1-2 AC Power
%DWWHUVHDOHGOHDGDFLGRQO
Table 1-3 contains specifications for batteries that can be used with the
control panel:
Battery Charger (MPS-400)
Maximum Battery Capacity (MPS-400)
Dual Rate: High Charge Normal Flat Charge Charging Current
55 AH (Batteries larger than 25 AH require Notifier BB-55 or other UL-listed
battery cabinet.)
29.1 VDC 27.6 VDC 2.0 A max 1.5 A typical
CAB-400AA CAB-A3 through CAB-B3
12 AH (17 AH with BB-17) 25 AH (55 AH with BB-55)
Table 1-3 Battery Specifications
1RWH 5HIHU WR $SSHQGL[ % IRU :LUH 5HTXLUHPHQWV
6LJQDOLQJ/LQH&LUFXLW6/&/RRS
Table 1-4 contains specifications for an SLC:
Item
Value
Voltage Maximum length
Maximum loop current Maximum loop resistance
24 VDC nominal, 27.6 VDC maximum 10,000 ft. per channel (NFPA Style 4) or 10,000 ft. total loop length (NFPA Style 6 and 7) 250 mA (max short circuit) or 100 mA (normal) 40 ohms (supervised and power-limited)
Table 1-4 SLC Specifications
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
1-5
www.PDF-Zoo.com
firealarmresources.com
6VWHP 2YHUYLHZ
Specifications
1RWLILFDWLRQ$SSOLDQFHDQG5HOHDVLQJ&LUFXLWV 036,&0,&(
Table 1-5 contains specifications for NACs and releasing circuits available on
the MPS-400:
Item Max. wiring voltage drop Normal operating voltage Current for all
external devices connected to MPS-400 Optional AVPS-24
Maximum signaling current/ circuit (MPS-400) End-of-line resistors
Value
2 VDC (except CMX which is 1.2 VDC)
24 VDC
6.0 A (except devices powered from the AVPS-24 or AA-30 and AA-120, or
FCPS-24)
Additional 3.0 A of NAC power for each AVPS-24 (requires ICM-4 modules)
2.5 A (except CMX which is 2 A)
MPS-400 (TB-7TB-10): 2.2K, 1/2 watt ICM-4, ICE-4, VCM-4, CE-4, and DCM-4:
4.7K, 1/2 watt (2 watts on 70 Vrms audio) CMX Modules: 47K, 1/2 watt
Table 1-5 NACs and Releasing Circuits
5HODV
Relays for Alarm, Trouble, Security, and Supervisory are available on MPS-400
terminals TB3 to TB6. Contact ratings for TB3-TB6 are:
· 2.0 A @ 30 VDC (resistive); · 0.5 A 30 VAC (resistive) when used for a
Form-C relay.
1RWH 7KH 036 SURYLGHV D WRWDO RI $ RI SRZHU VKDUHG E DOO LQWHUQDO PRGXOHV DQG HDFK 036 FLUFXLW )RU SRZHU UHTXLUHPHQWV UHIHU WR WKH SRZHU VXSSO FDOFXODWLRQ WDEOHV LQ $SSHQGL[ *
)RXUZLUH6PRNH’HWHFWRU3RZHU
MPS-400 terminals TB2-5 (+) and TB2-6 () supply filtered, low-noise power for
fourwire smoke detectors. Specifications for TB2-5 and TB2-6 are:
· Max. ripple voltage: 10 mVrms · Up to 1.25 A is available for powering four-
wire smoke detectors.
For 24 VDC detectors, refer to the Device Compatibility Document for
compatible detectors.
1-6
www.PDF-Zoo.com
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
firealarmresources.com
Specifications
6VWHP 2YHUYLHZ
1RWH 7KH 036 SURYLGHV D WRWDO RI $ RI SRZHU VKDUHG E DOO LQWHUQDO PRGXOHV DQG HDFK 036 FLUFXLW )RU SRZHU UHTXLUHPHQWV UHIHU WR WKH SRZHU VXSSO FDOFXODWLRQ WDEOHV LQ $SSHQGL[ *
3RZHU2XWSXWV
There are two power-limited circuits available to power external devices, such
as notification appliances and annunciators. Refer to the Device Compatibility
Document for compatible devices and notification appliances.
Item Terminals
Circuit A TB2-1 (+) and TB2-2 ()
Circuit B TB2-3 (+) and TB2-4 ()
Nominal Voltage
24 VDC
24 VDC
Max rated current
1.25 A DC
1.25 A DC
Max ripple voltage
100 mVrms
100 mVrms
Table 1-6 Power-Limited Circuits
2SHUDWLQJ3RZHU
$& %UDQFK &LUFXLW
This control panel requires connection to a separate dedicated AC branch circuit. Follow these guidelines when connecting the AC branch circuit:
· Label the branch circuit “Fire Alarm”.
· Connect the branch circuit to the line side of the main power feed of the
protected premises.
· Do not power other equipment from the fire alarm branch circuit.
· Run the branch circuit wire continuously, without any disconnect devices,
from the power source to the fire alarm control panel.
· Overcurrent protection for this circuit must comply with Article 760 of the
National Electrical Codes, as well as local codes.
· Use 14 AWG wire with 600 VAC insulation for this branch circuit. Connect the
earth ground terminal (MPS-400, TB1-3) to a solid earth ground (a metallic,
cold water pipe may be suitable in some installations). This connection is
vital to maintaining the control panel’s immunity to unwanted transients
generated by lightning and electrostatic discharge.
6HFRQGDU 3RZHU 6RXUFH The battery charger is current-limited and can recharge sealed lead-acid type batteries.
%DWWHULHV
The charger shuts off when the control panel is in alarm.
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
1-7
www.PDF-Zoo.com
firealarmresources.com
6VWHP 2YHUYLHZ
System Components
6VWHP&RPSRQHQWV
%DVLF(TXLSPHQW3DFNDJHV
Basic Equipment packages for the AFP-300 and AFP-400 include the following:
AFP-300 Basic Equipment Packages
· BE-300AA Base Equipment for use with the CAB-400AA mini cabinet. It is
similar to the BE-300 but for use in CAB-400AA. Includes MPS-400RB and
transformers. Supports one output option module. Order CAB-400AA cabinets
separately.
· BE-300 Base Equipment includes the CPU module (CPU-300), an 80-character
display, programming keypad, MPS-400 main power supply, installation
instructions, chassis and required hardware. Order CAB-X3 cabinets separately.
AFP-400 Basic Equipment Packages
· BE-400 Base Equipment includes the CPU-400 module, an MPS-400 power
supply, a BP-3 Battery Plate, cables, manuals, and a first row chassis. Order
CAB-X3 cabinets separately.
· BE-400AA Base Equipment for a CAB-400AA mini-cabinet–similar to the
BE-400–but for use in the CAB-400AA. The BE-400AA supports one output option
module, and includes an MPS-400PCA and transformers. Order CAB-400AA cabinets
separately.
&38
The CPU provides LED indicators and operational switches. The panel is visible
with the cabinet door closed, except for programming switches, which are
located behind a flip-down door.
&38 RQO
6OLGHLQ ODEHOV XVHG IRU PRVW QRPHQFODWXUH
)LJXUH &38 0RGXOH
1-8
www.PDF-Zoo.com
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
firealarmresources.com
System Components
6VWHP 2YHUYLHZ
3RZHU6XSSOLHV
The control panel can use two types of internally mounted power supplies: the MPS-400 main power supply and an optional Audio Visual Power Supply (AVPS-24).
036 UHTXLUHG The MPS-400 supplies a total of 6 A in alarm, used for the following: (a) powering AFP-300/400 modules; (b) powering a variety of UL- listed 24 VDC notification appliances (refer to the Device Compatibility Document); and (c) providing up to 1.25 A of resettable power for four-wire smoke detectors. The MPS-400 contains an integral battery charger, four NAC/Releasing circuits, and four relay outputs (Alarm, Trouble, Supervisory, and Security).
$ RI UHVHWWDEOH SRZHU
)RXU 5HOD 2XWSXWV
)RXU 1$&5HOHDVLQJ &LUFXLWV
)LJXUH 036 3RZHU 6XSSO
$936 RSWLRQDO The AVPS-24 Audio/Visual Power Supply provides up to 3 A of
additional special purpose power (unregulated, unfiltered) for output modules.
The AVPS-24 mounts to one-fourth of a CHS-4 chassis. In space-critical
applications, mount an AVPS-24 under system modules on a CHS-4 chassis. Refer
to the Device Compatibility Document for a list of compatible, UL-listed
notification appliances.
)LJXUH $936 3RZHU 6XSSO
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
1-9
www.PDF-Zoo.com
firealarmresources.com
6VWHP 2YHUYLHZ
System Components
$XGLR$PSOLILHUV
The control panel uses three types of audio amplifiers with an installed Voice
Alarm System: the AA-30, the AA-100, and the AA-120. · AA-30 The AA-30 Audio
Amplifier provides up to 30 watts of audio power for
driving 25 Vrms speaker circuits. · AA-100 The AA-100 Audio Amplifier
provides 100 watts of audio power for
driving 70 Vrms speakers. · AA-120 The AA-120 Audio Amplifier provides 120
watts of audio power for
driving 25 Vrms speakers. Each AA amplifies the audio signal coming in from an
Audio Message Generator (AMG-1) or Audio Tone Generator (ATG-2).
7UDQVIRUPHU$VVHPEODQG0363&$
Two 100VA transformers and connectors are used with the MPS-400PCA in the CAB-
400AA.
0363&$
9$ 7UDQVIRUPHUV 31 7$
)LJXUH 0363&$ 8VLQJ 7ZR 9$ 7UDQVIRUPHUV
%DWWHU%R[HV
The CAB-400AA cabinet provides space for two 12 ampere-hour (AH) batteries.
CAB-X3 cabinets provide space for two 25 AH (or smaller) batteries. Use
external battery boxes if your installation requires larger capacity
batteries. Battery boxes mount directly below the main cabinet. Models of
battery boxes are:
· BB-17 battery box for batteries up to 17 AH. · BB-55 battery box for
batteries up to 55 AH.
1-10
www.PDF-Zoo.com
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
firealarmresources.com
Optional Devices
6VWHP 2YHUYLHZ
2SWLRQDO’HYLFHV
Table 1-7 contains a list of optional components that can be installed in an
AFP-300 or AFP-400 system:
Option UDACT
Description
A Universal Digital Alarm Communicator/Transmitter (UDACT) transmits system
status to UL-listed Central Station Receivers over a public switched telephone
network. The UDACT mounts in a cabinet or mounts remotely in the ABS-8R. The
UDACT connects to the EIA-485 annunciator port and 24 VDC (nominal) power.
4XTM Transmitter Module
A 4XTM module provides municipal box and remote station transmitters meeting NFPA 72-1993 Auxiliary and Remote Station requirements. The 4XTM also includes a Disable switch and an LED indicator.
Trim Ring
A gray trim ring is available for semi-flush mounting of the CAB-X3 Series cabinet.
UZC-256 Universal Zone Coder
A UZC-256 module is a circuit board–used for NAC coding applications–that provides three output circuits and up to 256 zone codes.
NIB-96 Network Interface Board
A Network Interface Board (NIB) is a microprocessorcontrolled module that connects slave control panels to a master control panel. The NIB-96 module can be installed in each slave FACP. Each slave FACP can contain as many as 96 input/output points, or as few as eight points.
FCPS-24 Field Charger Power Supply
The FCPS-24 is a compact, cost-effective remote power supply and battery charger. This remote power supply consists of a filtered, 24 VDC output that can drive up to four Notification Appliance Circuits (NACs).
Table 1-7 Optional Devices for the AFP-300/400
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
1-11
www.PDF-Zoo.com
firealarmresources.com
6VWHP 2YHUYLHZ
Intelligent Detectors
,QWHOOLJHQW’HWHFWRUV
2YHUYLHZ
Intelligent, addressable detectors provide analog information to the control
panel. This allows the control panel to continually process this information
to determine the status of each detector (alarm, trouble, maintenance, or
normal). Each detector responds to an address that is set in the detector head
using built-in rotary decimal switches. You can program the sensitivity of
each intelligent detector. (Refer to Appendix C in the AFP-300/AFP-400
Programming Manual for details.)
‘HWHFWRU’HVFULSWLRQV
Table 1-8 contains a list of the intelligent detectors that you can use with
an AFP-300 or AFP-400 system:
Option BX-501 B710L B501BH B524RB B524BI SDX-551/SDX-551TH/ SDX-751
CPX-551/CPX-751
FDX-551
RA400Z
DHX-501/DHX-502 IPX-751
LPX-751
Description
Standard U.S detector base Low Profile base Sounder base Relay base Isolator
base
An Intelligent Photoelectric Smoke Detector provides analog measurements of
the optical smoke level in its chamber to the control panel. Also available:
an SDX-551TH with a 135° thermostat and a SDX-751 low profile photoelectric
detector.
An Intelligent Ionization Smoke Detector measures the level of combustion
products in its chamber using the ionization principle and reports this
measurement to the control panel. A CPX-751 Low Profile detector is also
available. Refer to Appendix C in the AFP-300/AFP-400 Programming Manual for
details on setting alarm sensitivity.
An Intelligent Thermal Sensor (140°F fixed temperature). Also available as an
FDX-551R which is a combination 135°F fixed and 15°F per minute rate of rise.
A Remote Single LED Annunciator that can be wired directly off of an
addressable detector for annunciation of that detector’s alarm status.
Duct Housings for the SDX-551 and CPX-551.
A microprocessor-based intelligent smoke detector that uses a combination of
photoelectric, ionization, and thermal sensing technologies.
An advanced intelligent photoelectric detector that uses a laser diode,
special optics, and signal processing to obtain extremely high sensitivity.
Table 1-8 Intelligent Detectors
1-12
www.PDF-Zoo.com
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
firealarmresources.com
Addressable Modules
6VWHP 2YHUYLHZ
$GGUHVVDEOH0RGXOHV
2YHUYLHZ
CMX Series Control Modules and MMX Series Monitor Modules provide an interface
between the control panel and conventional notification (CMX) and initiating
(MMX) devices. You can set each CMX and MMX module to respond to an address
with builtin rotary decimal switches. A blinking LED on an MMX or CMX
indicates communication between the module and the control panel.
0RGXOH’HVFULSWLRQV
Table 1-9 contains description of CMX and MMX series modules and other
addressable modules used with the control panel:
Option Monitor Modules (MMX-1, MMX-2)
MMX-101
Description
Addressable Monitor Modules for monitoring conventional initiating devices.
The MMX-1 is used for normally open contact alarm initiating devices, such as
manual pull stations, four-wire smoke detectors, heat detectors, waterflow,
security contacts, and supervisory devices. Use the MMX-2 for specific two-
wire smoke detectors in addition to normally open contacts. Wire supervised
circuits as NFPA Style B or Style D circuits.
An Addressable Module that is functionally similar to an MMX-1 Monitor Module
(Style B circuits only), but offered in a smaller package for mounting
directly in the electrical box of the device being monitored. It does not
include a blinking LED or a magnetic test switch.
Control Modules (CMX)
Loop Isolator Module (ISO-X))
Addressable Control Modules used as Notification Appliance Circuits (NACs) to
power and supervise compatible, UL-listed notification appliances. Wire
supervised circuits as NFPA Style Y or Style Z. Breaking the two built-in tabs
allows using the CMX as a Form-C control relay. A CMX comes with a
thermoplastic cover for mounting to a 4-inch square mounting box.
The ISO-X is an automatic switch that opens the circuit voltage to a
communications loop branch(es) whenever a fault is detected on that circuit.
The remainder of the communications loop leading up to the ISO-X continues to
operate, unaffected by the fault.
BGX-101L)
A dual action addressable manual pull station featuring a key-lock reset. The pull station includes an MMX-101 and responds to an address set with built-in rotary decimal switches.
Table 1-9 Addressable Modules
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
1-13
www.PDF-Zoo.com
firealarmresources.com
6VWHP 2YHUYLHZ
End-of-Line Devices
(QGRI/LQH’HYLFHV
Table 1-10 contains a list of the end-of-line devices that you can install in
an AFP-300/ AFP-400 system:
Option System Sensor (SSD) A2143-00
System Sensor (SSD) A2143-10
N-ELR Resistor plate (N-ELR)
Description
Notes
A 47K End-Of-Line Resistor (ELR) Assembly ELR used in the supervision of MMX-1 or MMX101 Monitor and CMX Control Module circuits.
Supplied with MMX or CMX modules.
The 3.9K End-Of-Line Resistor (ELR) Assembly used with the MMX-2.
Supplied with MMX-2 modules.
An N-ELR, required for Canadian installations, provides connection for a resistor to mount to an ELR plate.
· Use 2.2K for the MPS-400 output.
· Use 4.7K for ICM-4, ICE-4, VCM-4, VCE-4, and DCM-4.
· Use 47K for CMX, MMX-1, and MMX-101 modules.
Table 1-10 End-of-Line Devices
1-14
www.PDF-Zoo.com
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
firealarmresources.com
Annunciation Modules
6VWHP 2YHUYLHZ
$QQXQFLDWLRQ0RGXOHV
2YHUYLHZ
This section contains brief descriptions and the model numbers of annunciator
modules that can be connected to the control panel. Communication between the
control panel and annunciators takes place over a two-wire serial interface
connected to an EIA-485 connector (TB4) on the CPU. For detailed wiring
requirements, refer to the appropriate Annunciator manuals.
$QQXQFLDWRU&RQWURO0RGXOH5$&05
The ACM-8R provides the AFP-300 and AFP-400 with a mappable relay control
module. ACM-8R relays can be selected for mapping anywhere in the system
memory map (in groups of eight). Features of the ACM-8R include the following:
· Provides eight Form-C relays with 5 A contacts. · Tracks any group of eight
zones within the system.
/’06HULHV/DPS’ULYHU0RGXOHV
The LDM-32 Lamp Driver Annunciator Module provides 32 alarm lamp driver
outputs for connection to a custom graphic annunciator. You can also set the
LDM-32 with a DIP switch for 16 alarm, 16 trouble and 16 switch inputs for
control of such system functions as Signal Silence and System Reset.
· Lamp Driver Annunciator Expander Module (LDM-E32) Expands the LDM-32 by 32
system points, to a maximum of 64 points.
· Relay Expander Module (LDM-R32) Provides the LDM-32 or LDM-E32 with 32 dry
Form-A (normally open) contacts.
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
1-15
www.PDF-Zoo.com
firealarmresources.com
6VWHP 2YHUYLHZ
Annunciation Modules
$QQXQFLDWRU&RQWURO6VWHP$&6
The ACS series annunciator and control system provides the AFP-300 and AFP-400
with up to 32 remote annunciators, each with a capacity of 64 points. Table
1-11 contains brief descriptions of ACS annunciators. For detailed
information, refer to the ACS Manual.
Module
Features
Annunciator Control Module16AT (ACM-16AT)
The ACM-16AT provides features for audible and visual indication of alarm and trouble conditions at each annunciator. These features include: 1) 16 red alarm LEDs; 2) 16 yellow trouble LEDs; 3) 16 momentary touchpad switches for controlling each point; 4) a system trouble LED; 5) an Online/Power LED; 6) a local sounder; 7) a Silence/Acknowledge switch; and remote functions.
Annunciator Expander Module (AEM-16AT)
The AEM-16AT, identical in size and appearance to the ACM-16AT, expands the ACM-16AT by 16 system points. An ACM-16AT can support up to three AEM-16ATs, to a provide a maximum of 64 system points.
Annunciator Control Module32AT (ACM-32A)
Annunciator Expander Module-32A (AEM-32A)
1RWH $Q $(0$7 FDQQRW EH XVHG WR H[SDQG DQ $&0$
The ACM-32A provides features for audible and visual indication of alarm and
trouble conditions at each annunciator. These features include: 1) 32 red
alarm LEDs; 2) a system trouble LED; 3) an Online/Power LED; 4) a local
sounder; and 5) a Silence/Acknowledge switch.
The AEM-32A, identical in size and appearance to the ACM-32A, expands the ACM-
32A by 32 system points. An ACM-32 can support one AEM-32A, providing a
maximum of 64 system points. Note: An AEM-32A cannot be used to expand an ACM-
16AT.
Table 1-11 ACM-16AT/AFM-16AT Modules
$QQXQFLDWRU)L[HG0RGXOHV
Annunciator Fixed Modules (AFM-16AT and AFM-32A) provide the control panel
with discrete display and control points. AFMs turn their LEDs on and off as
directed by the CPU, and also report switch activations to the CPU for action.
You can only use one AFM in a system. Each annunciator’s address is fixed at
address 1.
· AFM-16AT The AFM-16AT contains 16 red alarm and 16 yellow trouble LEDs, a
system trouble LED, an Online/Power LED, and a local sounder, and switches for
control panel Acknowledge, Alarm Silence, and System Reset. Use the AFM-16AT
for systems that require 16 or fewer annunciation points.
· AFM-32A The AFM-32A contains 32 red alarm LEDs, a system trouble LED, an
ON LINE/POWER LED, and a local panel sounder with a silence/acknowledge
switch. The AFM-32A is fixed at address 1, and will not accept expander
modules.
1-16
www.PDF-Zoo.com
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
firealarmresources.com
Peripheral Displays and Printers
6VWHP 2YHUYLHZ
3HULSKHUDO’LVSODVDQG3ULQWHUV
2YHUYLHZ
The control panel is compatible with the following printers and display
devices:
· LCD-80 display · PRN-4 printer · Keltron Remote Printer · CRT-2 Display
Terminal For installation instructions for these devices, refer to Section 2.
/&”LVSOD
The LCD-80 alphanumeric display module is an AFP-300/400 ancillary device that
provides two modes of operation: Terminal, where it acts as a display
repeater; and ACS, where it acts as an alphanumeric annunciator. The LCD-80
features the following:
· 80-character LCD display that backlights under normal and alarm conditions.
· Control switches for Acknowledge, Signal Silence, and System Reset, all made
operational by an optional AKS-1 switch. · Time/date display field. ·
Annunciator backbox ABF-1 package with optional AKS-1 key switch and phone
jack options. · Remote operation (mounts up to 6,000 feet from the control
panel). · Local panel sounder with alarm/trouble resound.
3515HPRWH3ULQWHU
The PRN-4 is an optional printer that connects directly to the control panel
through TB1 on the CPU and can be located up to 50 feet from the control
panel. It features the following:
· Provides a printed record (80 columns of data on standard 9″ x 11″ tractor-
feed paper) of all system events (alarm, trouble) and status changes within
the system.
· Time-stamps the printout with the current time-of-day and date.
.HOWURQ5HPRWH3ULQWHU0RGHO96
The VS4095 is a two-color (red/black), 40-column 24 VDC that can print 50
messages in 90 seconds. This printer connects to the control panel through TB1
on the CPU and mounts in a separate cabinet next to the control panel. The
VS4095 meets UL fire and security requirements for an ancillary device. For
more information on the Keltron printer, contact the manufacturer (Keltron
Corp., Waltham, MA). Refer to Section 2 for installation instructions.
&577HUPLQDO
The optional CRT-2 terminal connects to the control panel via the EIA-485
serial interface TB2. The CRT-2–can control and view events, points and
history reports, control the system (Acknowledge, Alarm Silence, and System
Reset). With a CRT-2 installed, you can also change important system operating
parameters, such as enable/ disable of addressable points, change alarm and
pre-alarm sensitivities, clear verification counters, clear history, and set
the pre-alarm action level. A CRT-2 displays 26 lines by 80 columns and can be
located up to 50 feet from the control panel.
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
1-17
www.PDF-Zoo.com
firealarmresources.com
6VWHP 2YHUYLHZ
Notification Circuit and Control Modules
1RWLILFDWLRQ&LUFXLWDQG&RQWURO0RGXOHV
2YHUYLHZ
The control panel supports the following notification and control modules: ·
Indicating Circuit Module (ICM-4) · Indicating Circuit Expander (ICE-4) ·
Control Relay Module (CRM-4) · Control Relay Expander (CRE-4) · Auxiliary
Relay Module (ARM-4)
‘HVFULSWLRQVRI0RGXOHV
Table 1-12 contains descriptions of the notification circuit and control
modules that can be used with the control panel:
$X[LOLDU %HOO 3RZHU &DEOH 31 3URYLGHG ZLWK ,&0 DQG ,&( PRGXOHV
Module ICM-4
$50 +DUQHVV 31 )RU FRQQHFWLQJ WKH $50 WR WKH GULYLQJ UHOD PRGXOH
ICE-4 CRM-4
, 1’ ,& $ 7,1 & , 5& 8, 7 UH HQ RQ
<HOORZ 2 I I 2 Q 2 II
CRE-4
6OLGHLQ /DEHOV 3URYLGHG ZLWK ,&0 DQG &50 PRGXOHV
ARM-4
Function
Circuit Rating
Provides four Notification Appliance Circuits for Style Y or Style Z operation. Circuits are field-programmable to respond to a single initiating zone, a group of zones, or all initiating zones.
Maximum signaling current is 3 A of total current, limited by the power supply.
Expands the ICM-4 to a total of eight Notification Appliance Circuits (Style Y or Style Z).
Identical to the ICM-4.
Provides four standard dry Form-C relay contacts. Each relay is fieldprogrammable to respond to a single initiating device circuit, a group of circuits, or all initiating device circuits. Each relay features manual On/Off control switches and can be disabled or enabled.
Contacts rated for 5 A at 120 VAC or 28 VDC (resistive).
Expands the capacity of the Control Relay Module (CRM-4) to eight Form-C alarm relays.
Identical to the CRM-4.
Provides four auxiliary Form-C relays that can be controlled by a CRM-4 or CRE-4 relay module.
Normally-open contacts rated for 20 A and the normally-closed contacts are rated for 10 A at 125 VAC and 30 VDC (resistive).
Table 1-12 Notification Circuit and Control Relay Modules
1-18
www.PDF-Zoo.com
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
firealarmresources.com
Voice Alarm Equipment
6VWHP 2YHUYLHZ
9RLFH$ODUP(TXLSPHQW
2YHUYLHZ
Voice Alarm equipment provides a manual or automatic supervised paging system
for transmitting voice messages (information, instructions, directions) on a
selective or all call basis. For more details, refer to Section 4, Voice Alarm
System.
$XGLR0HVVDJHHQHUDWRU$0
The heart of a voice evacuation system, the Audio Message Generator (AMG-1)
provides a variety of tones, including a slow whoop, yelp, yeow, siren, hi/lo,
or steady tone. A built-in microphone allows for paging through speaker
circuits. Optionally, you can install up to four digitally-recorded voice
messages into the AMG-1 from the following:
· two factory prerecorded VROM voice messages; · two user-defined messages in
the AMG-1; · two user-defined messages (up to 24 seconds long) into an AMG-1
with optional
VRAM-1 memory chips installed (one per VRAM). You can create both user-defined
messages through the AMG-1 built-in microphone, or download user-defined
messages from a standard audio cassette recorder.
$XGLR7RQHHQHUDWRU$7
The Audio Tone Generator (ATG-2) is similar to the AMG-1, but provides tones
and microphone only (no message). It can provide two simultaneous tones for
dual-channel applications.
)LUH)LJKWHUV7HOHSKRQH))7))76
The FFT-7 (Fire Fighters Telephone) provides the Voice Alarm System with fire
fighter’s telephone capability. With the FFT-7 or FFT-7S, up to seven
telephones can hold a simultaneous conversation.
9RLFH&RQWURO0RGXOH9&0
The Voice Control Module-4 provides the system with up to four Style Y or
Style Z speaker circuits. Moving a jumper on the VCM-4 configures the module
for driving FFT-7 (Fire Fighter Telephone) circuits. When configured for
telephone circuits, the VCM-4 accepts its signal directly from an FFT-7/FFT-
7S. Add an optional VCE-4 Voice Control Expander to the back of the VCM-4 to
provide telephone or speaker circuits 5-8.
‘XDO&KDQQHO0RGXOH’&0
The DCM-4 Dual Channel Module provides the system with the capability to
select one of two types of audio sources for switching to a specified speaker
circuit. The DCM-4 provides up to four circuits.
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
1-19
www.PDF-Zoo.com
firealarmresources.com
6VWHP 2YHUYLHZ
Cabinet Hardware
&DELQHW+DUGZDUH
&DELQHW2YHUYLHZ
The control panel can be installed into one of two main cabinet
configurations:
· A CAB-400AA for compact systems (CPU, MPS-400, and one option module). Door
hinges are right-hand mounted and the door opens 180 degrees.
· A CAB-X3 cabinet for larger systems comes in four sizes (CAB-A3, CAB-B3,
CAB-C3, or CAB-D3). A CAB-X3 consists of two basic components–a Surface-
mounted Backbox (SBB-X3) and a door (DR-X3). Hinges are fieldselectable for
left- or right-hand mounting.
· Options for CAB-X3 cabinets include: 1) a Wire Channel (WC) option which
provides a pair of wire trays for neater routing of wire between tiers (rows)
in the cabinet (order one pair per cabinet tier); and 2) a trim ring option
(TR-X3) for semi-flush mounting (TR-A3N, TR-B3N, TR-C3N, TR-D3N).
A key-locked door includes a pin-type hinge, a window, two keys, and the
necessary hardware to mount the door to the backbox. The backbox contains
numerous knockouts to provide easy access to the cabinet and to simplify
conduit installation.
&+60&KDVVLV’UHVV3DQHO$VVHPEO
The CHS-4M contains expansion modules that extend beyond the first row in the
CAB-X3 cabinet. One CHS-4M is needed for each additional row of system
modules. The CHS-4M includes the CHS-4 Chassis, the MP-1 Module Dress Panel,
and the Expander Row Ribbon Cable.
([SDQGHU 5RZ 5LEERQ &DEOH 31
&+6 &KDVVLV
03 0RGXOH ‘UHVV 3DQHO
)LJXUH &+6 &KDVVLV
&+6/&KDVVLV
The low-profile CHS-4L chassis mounts into a CAB-X3 cabinet. Use the CHS-4L
chassis to mount AA-30 audio amplifiers, Audio Message Generators, Fire
Fighters Telephones, or Audio Visual Power Supplies.
1-20
www.PDF-Zoo.com
)LJXUH &+6/ &KDVVLV
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
firealarmresources.com
Cabinet Hardware
2YHUYLHZ
&$%$
6VWHP 2YHUYLHZ
&$%;6HULHV&DELQHWV
This section contains mounting information for CAB-X3 Series Cabinets. Each
cabinet assembly includes a door and backbox. The following lists each CAB-X3
Series cabinet assembly: · CAB-A3 one mounting tier · CAB-B3 two mounting
tiers · CAB-C3 three mounting tiers · CAB-D3 four mounting tiers An
optional TR-A3 trim ring is available for use with an A-size cabinet (24-1/8″W
by 22-5/16″H). Replacement parts: DR-A3 door; SBB-A3 backbox.
&$%%
)LJXUH &$%$ 0RXQWLQJ ‘LPHQVLRQV
An optional TR-B3 trim ring is available for use with a B-size cabinet
(24-1/8″W by 30-13/16″H). Replacement parts: DR-B3 door; SBB-B3 backbox.
)LJXUH &$%% 0RXQWLQJ ‘LPHQVLRQV
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
1-21
www.PDF-Zoo.com
firealarmresources.com
6VWHP 2YHUYLHZ
Cabinet Hardware
An optional TR-C3 trim ring is available for use with a C-size cabinet
(24-1/8″W by 39-7/16″H). Replacement parts: DR-C3 door; SBB-C3 backbox.
)LJXUH &$%& 0RXQWLQJ ‘LPHQVLRQV
An optional TR-D3 trim ring is available for use with a D-size cabinet
(24-1/8″W by 48-3/16″H). Replacement parts: DR-D3 door; SBB-D3 backbox.
)LJXUH &$%’ 0RXQWLQJ ‘LPHQVLRQV
1-22
www.PDF-Zoo.com
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
firealarmresources.com
Cabinet Hardware
&$%$$ 2YHUYLHZ
6VWHP 2YHUYLHZ
&$%$$&DELQHWV
The CAB-400AA is a backbox and door that can contain a small AFP-300/AFP-400
system. (A small system supports up to twelve NACs and consists of a CPU and
one option module, such as an ICM-4/ICE-4.) Modules mount to rails in the CAB-
400AA, eliminating the need for optional chassis assemblies. Mounting methods
include surface-mounting or semi-flush mounting on a wall between 16-inch-on-
center studs. Table 1-13 lists the components included in the CAB-400AA:
Component BE-300AA
BE-400AA
CAB-300AA and CAB-400AA (includes DP-400AA) DP-400AA
BM-1 TR-500
Description
BE-300AA A package that includes a CPU-300, an MPS300PCA, a transformer
assembly, and a two-position CPU-400 ribbon cable.
BE-400AA A package that includes a CPU-400, an MPS400PCA, a transformer
assembly, and a two-position CPU-400 ribbon cable.
A backbox (14.5″ wide by 17″ tall by 5″ deep) and door (14.57″ wide by 17.25″
tall by 1.5 ” deep).
An Inner Dress Panel for covering the backbox area surrounding the modules.
The DP-400AA is required for Canadian installations.
Blank module for covering an unused panel or module.
Trim ring that provides for semi-flush mounting of the CAB-400AA cabinet
&$%$$ /LPLWDWLRQV &$%$$ ‘LPHQVLRQV
Table 1-13 CAB-400AA Components and Options · Limited power supply capacity (one AVPS-24 expander). · The backbox can hold 12 amp-hour batteries only. · Maximum of one module in addition to the CPU. · No voice evacuation capability. Figure 1-13 shows the CAB-400AA dimensions:
)LJXUH &$%$$ %DFNER[ DQG ‘RRU $VVHPEO
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
1-23
www.PDF-Zoo.com
firealarmresources.com
1RWHV
1-24
www.PDF-Zoo.com
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
firealarmresources.com
Preparing for Installation
,QVWDOODWLRQ
,QVWDOODWLRQ
3UHSDULQJIRU,QVWDOODWLRQ
8QSDFNLQJ WKH 6VWHP Unpack the system as follows:
Step
Action
1
Carefully unpack the system and inspect for shipping damage.
2
Select a location for the control panel in a clean, dry, vibration-free area with
moderate temperature.
%HIRUH LQVWDOOLQJ WKH ILUH DODUP VVWHP UHDG WKH IROORZLQJ
· Install the system in a readily accessible area with sufficient room to
easily install and maintain the control panel.
· Locate the top of the cabinet approximately 60 inches above the floor with
the hinge mounting on the left.
· Count the number of conductors needed for all devices and find the
appropriate knockouts.
· Review the installation precautions at the front of this manual.
· All wiring must comply with the National and/or Local codes for fire alarm
systems.
· Do not draw wiring into the bottom 9 inches of the cabinet, except when
using the BB-17 or BB-55. This prevents interference between the power supply
and batteries.
6WDQGDUGV DQG &RGHV In addition, installers should be familiar with the
following standards:
· NEC Article 300 Wiring Methods.
· NEC Article 760 Fire Protective Signaling Systems.
· Applicable Local and State Building Codes.
· Requirements of the Local Authority Having Jurisdiction.
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
2-1
www.PDF-Zoo.com
firealarmresources.com
,QVWDOODWLRQ
Installation Checklist
,QVWDOODWLRQ&KHFNOLVW
&DXWLRQ 0DNH VXUH WR LQVWDOO VVWHP FRPSRQHQWV LQ WKH SUHFLVH RUGHU LQ WKH FKHFNOLVW
)DLOXUH WR GR VR FDQ GDPDJH WKH FRQWURO SDQHO DQG RWKHU VVWHP FRPSRQHQWV
Table 2-1A contains an installation checklist for installing, wiring, and testing an AFP-300/AFP-400 system:
Task
U Mount the CAB-X3 Cabinet Door (CAB-400AA has a pre-mounted door.)
U Mount CHS-4 and CHS-4L chassis in CAB-X3 cabinets.
U Mount the SBB-X3 or CAB-400AA backbox to the wall.
U Mount the MPS-400 to the backbox.
U If using additional power supplies, mount to the AVPS-24 to the backbox or
chassis.
U Mount optional Auxiliary Relay Modules (ARM4).
U Connect the power cables to the MPS-400 and any AVPS-24s, while the
terminals are accessible.
Refer to…
“Installing a Cabinet Door” on page 2-4.
“Installing a Chassis (CAB-X3 Series Cabinets)” on page 2-6.
“Mounting a Backbox (SBB-X3 and CAB-400AA)” on page 2-7.
“Mounting an MPS-400 Power Supply” on page 2-8.
“Mounting an Optional AVPS-24 Power Supply” on page 2-10.
“Installing an Auxiliary Relay Module (ARM-4)” on page 2-11
“Field Wiring the MPS-400 Power Supply” on page 2-32.
&DXWLRQ ‘R QRW FRQQHFW SRZHU DW WKLV WLPH
U If installing panel modules (such as ICM-4,
“Installing Expander Row Ribbon
CRM-4, VCM-4), connect Expander Row Ribbon Cables for Panel Modules” on page
Cables (PN 71088) to the CPU.
2-15.
U Install the CPU module in the top left cabinet position.
“Installing the CPU” on page 2-18
U Connect the Power Ribbon and Power Harness between the CPU and the MPS-400/ MPS-400PCA.
“Connecting the CPU to the MPS-400” on page 2-19.
U Install panel module expander boards (ICE-4, CRE-4, VCE-4).
“Mounting Expander Modules (CRE-4, ICE-4, VCE-4)” on page 2-20
U Mount panel modules (ICM-4, CRM-4, VCM-4) to the chassis or backbox.
“Mounting Panel Modules (CRM4, ICM-4, VCM-4) onto a Chassis” on page 2-21.
U Connect the Row Ribbon Cables to the panel modules.
“Installing Expander Row Ribbon Cables for Panel Modules” on page 2-15.
U Mount optional modules (such as 4XTM, UZC-256, UDACT).
“Installing a 4XTM Module (Remote Station Fire Alarm)” on page 2-22. “Installing a UZC-256 Module” on page 2-24.
U Install optional Voice Alarm System components. Section 4.
U Field-wire each module.
“Field-Wiring the Modules” on page 2-25.
2-2
www.PDF-Zoo.com
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
firealarmresources.com
Installation Checklist
,QVWDOODWLRQ
Task
U Install optional peripheral devices, such as a printer, personal computer,
or CRT-2 terminal.
U Wire the Signaling Line Circuits. U Connect AC power to the MPS-400 — but do
not
connect batteries.
U Check AC power–but do not connect batteries.* U Program the control panel. U
Connect the batteries.
U Field test the system.
Refer to…
“Installing Remote Printers and CRTs” on page 2-35.
“Wiring a Signaling Line Circuit (SLC)” on page 2-39.
“Field Wiring the MPS-400 Power Supply” on page 2-32 “AC and Battery Power
Connections (MPS-400” on page 233.
Table 2-2.
AFP-300/AFP-400 Programming Manual.
“AC and Battery Power Connections (MPS-400″ on page 233.
Section 3.
Table 2-1 Installation Checklist
Table 2-2 contains a checklist for checking the system with AC power applied:
&DXWLRQ :KLOH FKHFNLQJ $& SRZHU PDNH VXUH EDWWHULHV DUH QRW FRQQHFWHG
Component
U The CPU U Each module
U Each AVPS-24
Status
The green AC Power indicator on; the system Trouble indicator on because of no
battery power.
The yellow Trouble indicator may come on for approximately 10 seconds after
applying AC power. (This only applies to an unconfigured system.)
The yellow Trouble indicator comes on because batteries are not connected.
Table 2-2 AC Power Checklist
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
2-3
www.PDF-Zoo.com
firealarmresources.com
,QVWDOODWLRQ
Installing a Cabinet Door
,QVWDOOLQJD&DELQHW’RRU
&DELQHW’RRU0RXQWLQJ*XLGHOLQHV
Cabinet doors mount in a left- or right-hand opening configuration, providing
easier access for installation and service when two control panels are mounted
in a confined area or side-by-side (as shown in Figure 2-1). The doors can be
opened barn door style, creating an open work space. Before mounting any
equipment in the backbox, make sure to attach the two hinges and the two
alignment tabs. In this type of installation it is necessary to leave enough
space between cabinets to insert a key into the locks on the door frames.
/HIWKDQG PRXQWHG GRRU
5LJKWKDQG PRXQWHG GRRU
)LJXUH &DELQHW ‘RRU 0RXQWLQJ 3RVLWLRQV
1RWH 3ODFLQJ WKH GRRU RQ WKH ORZHU VWXG ILUVW SURYLGHV D SODFH IRU WKH GRRU WR UHVW ZKLOH FRPSOHWLQJ WKH DVVHPEO
+RZWR,QVWDOOD&DELQHW’RRU&$%;RQO
You can mount hinges on the left or right. The drawings and text refer to a
left-mounted example. For right hand mounting, substitute right for left in
the instructions. Follow the instructions in the installation table and refer
to the drawings.
Step Action
1
Insert the door hinges (A) into the top and bottom slots.
(Figure 2-2 and Figure 2-3).
2
Attach the mounting nuts and secure the hinges to the backbox studs so the small
hole on the outer tab faces out.
3
Thread the stud (B), from the bottom up, into the bottom hinge first. Place the
grounding star washer and the lower corner of the door onto the stud.
4
Align the door on the backbox so the door sits directly under the top hinge. Thread
the remaining stud (B) into the top hinge and through the hole in the top of the
door. The door should now swing freely.
Table 2-3 Cabinet Door Installation Instructions ,QVWDOOLQJ D 7RS +LQJH Figure 2-2 shows how to mount a top hinge on a door:
1RWH 7KH LQVWDOODWLRQ LV WKH VDPH IRU WKH WRS DQG WKH ERWWRP ULJKW FRUQHU RI WKH EDFNER[
6WXG % +LQJH $
7RS /HIW &RUQHU
2-4
www.PDF-Zoo.com
)LJXUH ,QVWDOOLQJ D 7RS +LQJH
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
firealarmresources.com
Installing a Cabinet Door
,QVWDOODWLRQ
,QVWDOOLQJ D %RWWRP +LQJH Figure 2-3 shows how to mount a bottom hinge on a door:
%RWWRP /HIW &RUQHU 6WDU ZDVKHU
6WXG %
+LQJH $
)LJXUH ,QVWDOOLQJ D %RWWRP +LQJH
,QVWDOOLQJWKH’RRU$OLJQPHQW7DEV
1. Install the door alignment tabs (C) in the unused slots on the top and
bottom of the backbox. (In Figure 2-4, the door mounts on the left, leaving
unused slots on the right). Secure the alignment tab (C) to the stud (b) with
nut provided.
2. Punch out the knockout for the door lock on the side opposite the hinge.
1RWH $OLJQPHQW WDEV NHHS WKH 3. Install the lock mechanism (Figure 2-5).
GRRU OLQHG XS ZLWK WKH EDFNER[
$OLJQPHQW WDE &
2SHQ
)LJXUH ,QVWDOOLQJ WKH ‘RRU $OLJQPHQW 7DEV
,QVWDOOLQJ D ‘RRU /RFN Figure 2-5 shows how to install a door lock:
/RFNHG
‘RRU ORFN 7KH GRRU ORFN PHFKDQLVP DV
YLHZHG RQ D OHIWKDQG PRXQWHG GRRU
,QVWDOO GRRU ORFN KHUH
)LJXUH ,QVWDOOLQJ WKH ‘RRU /RFN
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
2-5
www.PDF-Zoo.com
firealarmresources.com
,QVWDOODWLRQ
Installing a Chassis (CAB-X3 Series Cabinets)
,QVWDOOLQJD&KDVVLV&$%;6HULHV&DELQHWV
2YHUYLHZ
This section contains instructions for installing a CHS-4 chassis (Figure 2-6)
and a CHS-4L chassis (Figure 2-7) into a CAB-X3 cabinet.
,QVWDOOLQJD&+6&KDVVLV
To install a CHS-4 chassis, follow these instructions: 1. Place the CHS-4
chassis over the screw mounts on the cabinet. 2. Connect a ground cable (PN
71033) to one of the screw mounts. 3. Secure the assembly with the two nuts
provided. Repeat this step for each CHS-4 chassis in the cabinet.
&RQQHFWLQJ WKH JURXQGLQJ FDEOH 31 &RQQHFW WKH JURXQGLQJ FDEOH EHWZHHQ 036 HDUWK JURXQG WHUPLQDOV DQG DW OHDVW RQH FKDVVLV
)LJXUH ,QVWDOOLQJ D &+6 &KDVVLV
,QVWDOOLQJD&+6/&KDVVLV
Use the CHS-4L chassis for mounting an AMG-1, FFT-7, or AA-30. To mount a CHS-
4L, follow the steps for installing a CHS-4 chassis.
&RQQHFWLQJ WKH JURXQGLQJ FDEOH 31 &RQQHFW WKH JURXQGLQJ FDEOH EHWZHHQ 036
HDUWK JURXQG WHUPLQDOV DQG DW OHDVW RQH FKDVVLV
2-6
www.PDF-Zoo.com
)LJXUH ,QVWDOOLQJ D &+6/ &KDVVLV
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
firealarmresources.com
Mounting a Backbox (SBB-X3 and CAB-400AA)
,QVWDOODWLRQ
0RXQWLQJD%DFNER[6%%;DQG&$%$$
This section provides instructions for mounting an SBB-X3 or CAB-400AA backbox. Follow these guidelines when mounting a backbox:
&DXWLRQ 8QOHVV RX DUH IDPLOLDU ZLWK WKH SODFHPHQW RI FRPSRQHQWV ZLWKLQ WKLV EDFNER[
RQO XVH WKH NQRFNRXW ORFDWLRQV SURYLGHG IRU FRQGXLW HQWU
· Mount a backbox on a surface in a clean, dry, vibration-free area. Install the cabinet by following the instructions in Table 2-4.
· Locate the backbox so that the top edge is 66 inches above the surface of the finished floor.
· Mount the backbox using the four mounting holes in the back surface of the
backbox.
.HKROHV SODFHV
0RXQWLQJ KROHV SODFHV
)LJXUH 0RXQWLQJ D &DELQHW %DFNER[
&DXWLRQ :KHQ UHPRYLQJ D &38 ERDUG SODFH WKH ERDUG LQ D VDIH FOHDQ SODFH $YRLG VWDWLF
GLVFKDUJH ZKLFK FDQ GDPDJH WKH ERDUG
Step
Action
1
Remove the CPU board by loosening the four screws in the corners of the board.
(Two permanent standoffs support the CPU board in the center.)
2
Mark and pre-drill holes for the top two keyhole mounting bolts.
3
Install two upper fasteners in the wall so the screw heads protrude approximately
1/2”.
4
Using the keyholes, mount the backbox over the two screws.
5
Mark the two holes, remove the backbox and drill the mounting holes.
6
Mount the backbox, then install and tighten the remaining fasteners.
7
When the location is dry and free of construction dust, reinstall the CPU board.
Table 2-4 Mounting a Cabinet Backbox
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
2-7
www.PDF-Zoo.com
firealarmresources.com
,QVWDOODWLRQ
Mounting an MPS-400 Power Supply
0RXQWLQJDQ0363RZHU6XSSO
0RXQWLQJDQ036LQWRD&$%;&DELQHW
This section contains instructions for mounting an MPS-400 into a CAB-X3
(Figure 29 and Figure 2-10) and for mounting an MPS-400 into a CAB-400AA
(Figure 2-11).
The MPS-400 mounting assembly consists of the MPS-400 module attached to
mounting chassis. To install the MPS-400 into CAB-A3, CAB-B3, CAB-C3, or
CAB-D3 cabinets, follow these steps.
1. Place the MPS-400 assembly into the cabinet so the MPS-400 chassis bracket
engages the support bracket on the cabinet as shown in Figure 2-9:
036 FKDVVLV EUDFNHW
&$%; VXSSRUW EUDFNHW
036 $VVHPEO
&$%; &DELQHW
)LJXUH 3ODFLQJ DQ 036 RQWR D 6XSSRUW %UDFNHW
2. Secure the bottom of the MPS-400 to the bottom cabinet support with the
mounting screws as shown in Figure 2-10:
2-8
www.PDF-Zoo.com
0RXQWLQJ VFUHZV
)LJXUH 0RXQWLQJ DQ 036 LQWR D &$%;
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
firealarmresources.com
Mounting an MPS-400 Power Supply
,QVWDOODWLRQ
0RXQWLQJDQ036LQWRD&$%$$
Figure 2-11 shows how to install an MPS-400PCA and two transformer assemblies
into a CAB-400AA cabinet. To mount MPS-400PCA components, follow these steps:
Step
Action
1
Mount the MPS-400PCA PC board into the cabinet using the four mounting
screws.
2
Mount the two 100VA transformer assemblies to the cabinet using the four
mounting nuts and lockwashers.
3
Connect the transformer assembly wires to plugs P1 and P2 on the MPS-400PCA
PC board.
Figure 2-11 shows how to mount an MPS-400 to a CAB-400AA cabinet:
&$%$$
036 PRXQWLQJ VFUHZV SODFHV
036
036 3 DQG 3
1XW DQG ORFNZDVKHUV SODFHV
9$ 7UDQVIRUPHUV 31
)LJXUH 0RXQWLQJ DQ 0363&$ LQWR D &$%$$
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
2-9
www.PDF-Zoo.com
firealarmresources.com
,QVWDOODWLRQ
Mounting an Optional AVPS-24 Power Supply
0RXQWLQJDQ2SWLRQDO$9363RZHU6XSSO
2YHUYLHZ
You can mount an AVPS-24 into a CAB-X3 series cabinet (on a CHS-4 or CHS-4L
chassis) or in the upper right corner of a CAB-400AA. A CRM-4, a ICM-4, a
DCM-4, or a VCM-4 can mount above the AVPS-24 as long as you do not use an
expander module (CRE-4, ICE-4, or VCE-4).
,QVWDOODWLRQ
To mount an AVPS-24, refer to Figure 2-12 and follow these steps:
Step
Action
1
Place the AVPS-24 module onto the screw mounts on the CHS-4 or CHS-4L
chassis as shown in Figure 2-12.
2
Install the two mounting nuts.
3
Tighten the mounting nuts until the module is secure.
Figure 2-12 shows how to mount an AVPS-24 onto a CHS-4L chassis:
&+6 &+6/
$936
1XW DQG ORFNZDVKHU SODFHV
)LJXUH 0RXQWLQJ DQ $936 3RZHU 6XSSO
2-10
www.PDF-Zoo.com
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
firealarmresources.com
Installing an Auxiliary Relay Module (ARM-4)
,QVWDOODWLRQ
,QVWDOOLQJDQ$X[LOLDU5HODRGXOH$50
2YHUYLHZ
1RWH )RU HDVH RI LQVWDOODWLRQ DQG VHUYLFH PRXQW WKH $50 PRGXOH LQ D GHGLFDWHG SRVLWLRQ RQ WKH FKDVVLV LI DYDLODEOH ZLWK QR PRGXOH RU H[SDQGHU ERDUG DERYH LW 7KH $50 FDQ DOVR PRXQW LQ WKH XSSHU ULJKW FRUQHU RI WKH &$%$$
The ARM-4 module can be driven by a CRM-4 or a CRE-4. Each ARM-4 can support
one CRM-4 or one CRE-4. If using auxiliary relays for both modules, mount two
ARM-4s in separate positions. Place the ARM-4 against the CHS-4 chassis in any
one of eight positions relative to the CRM-4 or CRE-4 (Figure 2-13). You can
also install the ARM-4 directly below the CRM-4 or CRE-4. Select a position on
the CHS-4 chassis for the ARM-4:
$50
&50 RU &5(
)LJXUH 0RXQWLQJ 3RVLWLRQV IRU DQ $50
0RXQWLQJWKH$500RGXOHWRD&+6&KDVVLV
1. Select a mounting position for the ARM-4 module on the CHS-4 chassis. 2.
Secure the two loose standoffs to the screw mounts on the CHS-4 chassis at the
selected location for the ARM-4. Make sure to install existing standoffs in
the locations shown in Figure 2-14:
6WDQGRII SODFHV
0RGXOH UHWDLQLQJ VFUHZ SODFHV
$50 PRGXOH
)LJXUH 0RXQWLQJ DQ $50 WR D &+6 &KDVVLV
3. Position the ARM-4 module over the existing standoffs on the chassis;
then, fasten the ARM-4 module to the chassis with the two module retaining
screws as shown in Figure 2-14.
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
2-11
www.PDF-Zoo.com
firealarmresources.com
,QVWDOODWLRQ
Installing an Auxiliary Relay Module (ARM-4)
:LULQJWKH$500RGXOH
1. Connect one end of the ARM-4 cable to plug P1 on the ARM-4 (Figure 2-15).
2. Connect the other end of the ARM-4 cable to jumper JP5 on the CRM-4 or
CRE-4
driving the ARM-4 module (Figure 2-15):
$50
$50 &DEOH 31
&50 RU &5( -3
)LJXUH &RQQHFWLQJ WKH $50 WR D &50&5(
2-12
www.PDF-Zoo.com
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
firealarmresources.com
Connecting the MPS-400 Power Cables
,QVWDOODWLRQ
&RQQHFWLQJWKH0363RZHU&DEOHV
036(OHFWULFDO&RQQHFWLRQV
MPS-400 electrical connections include the following:
· Primary AC power source 120 VAC, 50/60 Hz, 3.0 A or 240 VAC, 50/60 Hz, 1.5 A from line voltage source.
· Secondary power source 24 VDC from batteries, installed in the control panel (or in an optional battery cabinet), provides backup power if the system loses primary power. Secondary (battery) power is required to support the system during loss of primary power.
:DUQLQJ
5HPRYH DOO SRZHU VRXUFHV WR HTXLSPHQW ZKLOH FRQQHFWLQJ HOHFWULFDO FRPSRQHQWV
/HDYH WKH PDLQ SRZHU EUHDNHU RII XQWLO LQVWDOODWLRQ RI WKH HQWLUH VVWHP LV FRPSOHWH
0DNH VXUH WR VHW WKH 9ROWDJH 6HOHFWLRQ 6ZLWFK 6 WR WKH FRUUHFW YROWDJH
&RQQHFWLQJWKH036WR$&3RZHU7%
Connect primary power to the MPS-400 as follows:
Step Action
1
Set the Voltage Select Switch (S9 on the MPS-400) to match the incoming AC line
voltage (120 VAC or 230 VAC).
2
Turn off the breaker at the main power distribution panel and remove the plastic
insulating cover from TB1.
3
Connect the system primary power source.
4
Connect the service ground to TB1-3 (labeled EARTH).
5
Connect the primary Neutral line to TB1-2 and the primary Hot line to TB1-4
(marked HOT).
6
When finished making connections, reinstall the plastic insulating cover over TB1
(Switch S9 on the MPS-400).
Table 2-5 Connecting AC (Primary) Power
&RQQHFWLQJWKH%DWWHULHV0367%7%
Install batteries in the control panel cabinet or in a separate battery cabinet which can be mounted up to 20 feet away from the control panel.
:DUQLQJ ‘R QRW FRQQHFW WKH %DWWHU ,QWHUFRQQHFW &DEOH 31 DW WKLV WLPH 0DNH
WKLV FRQQHFWLRQ DIWHU LQLWLDO VVWHP SULPDU SRZHUXS
Connect the battery as follows:
Step
Action
1
Connect the battery positive terminal to TB1 terminal 6 (+).
2
Connect the battery negative terminal to TB1 terminal 7 ().
Table 2-6 Connecting Batteries
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
2-13
www.PDF-Zoo.com
firealarmresources.com
,QVWDOODWLRQ
Connecting the MPS-400 Power Cables
&RQQHFWLQJ )RXU:LUH 6PRNH ‘HWHFWRU 9’& 3RZHU 036 7%
MPS-400 TB2 terminals TB2-5 (+) and TB2-6 () provide up to 1.25 A of current for four-wire smoke detectors. A system reset removes the 24 VDC power from MPS-400 TB2. 24 VDC low-noise four-wire smoke detector power is power-limited but must be supervised. To provide supervision, install an end-of-line listed power supervision relay. Connect the power supervision relay in series with an Initiating Device Circuit (IDC). The four-wire power circuit energizes the power supervision relay.
1RWLILFDWLRQ $SSOLDQFH 3RZHU 9’&
TB2 terminals TB2-1 (+) and TB2-2 () provide up to 1.25 A of nonresettable lownoise current for powering notification appliances. TB2 terminals TB2-3 (+) and TB2-4 () also provide 1.25 A of nonresettable low-noise current. TB2 terminals TB2-5 (+) and TB2-6 () provide 1.25 A of resettable power.
&DXWLRQ ‘XULQJ VVWHP UHVHW SRZHU UHPDLQV DW WHUPLQDOV 7% 7% 7% DQG 7%
1RWH 2Q WKH 036 %HOO 3RZHU +DUQHVV WKH IRUN OXJV PXVW EH FXW RII DQG ZLUHV
VWULSSHG IRU
FRQQHFWLRQ WR WKH 036
$QQXQFLDWRU 3RZHU 9’&
Power ACS annunciators from the four-wire smoke detector outputs, or from one of the NAC power outputs. All outputs provide the filtered, low-noise, power- limited source required by the annunciators. The power run to the annunciators is supervised by the annunciator (for a Loss of Communications error). Annunciator wiring must run separate from NAC wiring. You can use any of the NAC outputs, but do not connect an NAC to the output selected for powering the annunciators.
6VWHP +DUQHVV &RQQHFWLRQV
Make system connections as follows as shown in Table 2-7:
For…
Connect…
Internal system power AMG-1 power
Signaling between the CPU and the MPS
The power harness (75396 for CAB-400AA/75395 for CAB 3 series) from J6 on the
MPS to J6 on the CPU.
A power harness from J1 on the MPS to P1 on the AMG-1. You can feed this same
power to other boards or modules that require internal power.
A power ribbon (75398 for CAB-400AA/75394 for CAB 3 series) to J2 on the MPS.
6VWHP 3RZHU &RQQHFWLRQV
Table 2-7 System Harness Connections
Figure 2-16 contains a block diagram that shows system power connections
between the MPS-400 and AFP-300/AFP-400 system components:
3RZHU +DUQHVV IRU &$%$$ IRU &$% VHULHV
3RZHU ULEERQ IRU &$%$$ IRU &$% VHULHV
3RZHU +DUQHVV RU
– &38
– 3RZHU +DUQHVV
Standard Optional
3
3 $0* RSWLRQDO
3 ))7 RSWLRQDO
– – 036 –
)LJXUH 6VWHP 3RZHU +DUQHVV &RQQHFWLRQV
2-14
www.PDF-Zoo.com
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
firealarmresources.com
Installing Expander Row Ribbon Cables for Panel Modules
,QVWDOODWLRQ
,QVWDOOLQJ([SDQGHU5RZ5LEERQ&DEOHVIRU3DQHO0RGXOHV
Expander Row Ribbon Cables (PN 71088) connect panel modules (ICM-4, CRM-4,
VCM-4) to the CPU. Figure 2-17, Figure 2-18, and Figure 2-19 show typical
wiring connections using Row Ribbon Cables.
,QVWDOOLQJ5RZ5LEERQ&DEOHVIRU&$%%&$%&DQG&$%’ &DELQHWV
Figure 2-17 shows typical wiring connections using Expander Row Ribbon Cables
to connect the CPU to two rows of panel modules. In Figure 2-17, P indicates a
panel module. For example, P1.1 indicates panel module 1, circuit number 1.
([SDQGHU 5RZ 5LEERQ &DEOH 31
&38 RQO 1&
1&
*URXS RI SDQHO PRGXOHV LQ ILUVW FDELQHW URZ
– ILUVW PRGXOH URZ
– VHFRQG PRGXOH URZ
&38
3²3
3²3
([SDQGHU 5RZ 5LEERQ &DEOH 31
*URXS RI SDQHO PRGXOHV LQ VHFRQG FDELQHW URZ
3²3
3²3
3²3
3²3
)LJXUH ,QVWDOOLQJ ([SDQGHU 5RZ 5LEERQ &DEOHV &$%%²&$%’
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
2-15
www.PDF-Zoo.com
firealarmresources.com
,QVWDOODWLRQ
Installing Expander Row Ribbon Cables for Panel Modules
,QVWDOOLQJ5RZ5LEERQ&DEOHVIRU&$%&DQG&$%’&DELQHWV
Figure 2-18 shows typical wiring connections to connect the CPU to two rows of
panel modules.
1RWH ,Q WKH ILJXUH ´3µ LQGLFDWHV D SDQHO PRGXOH )RU H[DPSOH 3 LQGLFDWHV SDQHO
PRGXOH FLUFXLW QXPEHU
&38 RQO
([SDQGHU 5RZ 5LEERQ &DEOH 31
*URXS RI SDQHO PRGXOHV LQ VHFRQG FDELQHW URZ
3²3
3²3
([SDQGHU 5RZ 5LEERQ &DEOH 31
3²3
3²3
*URXS RI SDQHO PRGXOHV LQ WKLUG FDELQHW URZ
3²3
3²3
3²3
3²3
)LJXUH ,QVWDOOLQJ ([SDQGHU 5RZ 5LEERQ &DEOHV &$%& DQG &$%’
2-16
www.PDF-Zoo.com
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
firealarmresources.com
Installing Expander Row Ribbon Cables for Panel Modules
,QVWDOODWLRQ
,QVWDOOLQJ5RZ5LEERQ&DEOHVIRUD&$%$$&DELQHW
Figure 2-19 shows typical wiring of the CPU to a row of panel modules:
1RWH ,Q WKH ILJXUH ´3µ LQGLFDWHV D SDQHO PRGXOH )RU H[DPSOH 3 LQGLFDWHV SDQHO
PRGXOH FLUFXLW QXPEHU
&38 RQO
– QRW XVHG
– PRGXOH URZ
)LUVW ([SDQGHU 5RZ &$%$$ 5LEERQ &DEOH 31
3²3
)LJXUH ,QVWDOOLQJ DQ ([SDQGHU 5RZ 5LEERQ &DEOH &$%$$
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
2-17
www.PDF-Zoo.com
firealarmresources.com
,QVWDOODWLRQ
Installing the CPU
,QVWDOOLQJWKH&38
,QVWDOOLQJWKH&38LQWRD&KDVVLV
To install the CPU into a chassis, follow these steps.
1. Insert the two tabs of the CPU module into the two left-most chassis
slots, angling the front end of the module into position as in Figure 2-20:
&+6 &KDVVLV
&38
6ORWV
)LJXUH ,QVHUWLQJ D &38 LQWR D &KDVVLV
2. Push the back end of the module down into the cabinet and pull down until
the upper board engages the slots on the chassis as shown in Figure 2-21:
0RGXOH VFUHZV SODFHV
6ORWV
)LJXUH 6HFXULQJ D &38 WR D &KDVVLV
3. Align the module screws with the thread-holes on the chassis and secure in
place.
2-18
www.PDF-Zoo.com
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
firealarmresources.com
Installing the CPU
,QVWDOODWLRQ
&RQQHFWLQJWKH&38WRWKH036
Connect the CPU to the MPS-400 using the Power Harness and the Power Ribbon
Cable as shown in Figure 2-22:
&38 3RZHU
&38 RQO
–
3RZHU +DUQHVV
&$%$$
&$%
– 6LJQDO
&38
3RZHU 5LEERQ &DEOH
&$%$$
&$%
– –
036
3LQ 6WULSH
– $X[LOLDU 7URXEOH &DEOH VHH QRWH – 6HFXULW 7DPSHU 6ZLWFK XVHG DV D MXPSHU RQ QRQVHFXULW VVWHPV VHH QRWH – =RQH &RGHU ,QSXW VHH QRWH
1RWH 5HIHU WR 6HFWLRQ ´$SSOLFDWLRQVµ IRU LQVWUXFWLRQV RQ XVLQJ FRQQHFWRUV – – DQG –
)LJXUH &RQQHFWLQJ WKH &38 WR WKH 036
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
2-19
www.PDF-Zoo.com
firealarmresources.com
,QVWDOODWLRQ
Mounting Expander Modules (CRE-4, ICE-4, VCE-4)
0RXQWLQJ([SDQGHU0RGXOHV&5(,&(9&(
Table 2-8 contains illustrations and instructions for mounting an expander
module to a CRM-4, ICM-4, or VCM-4 module:
Step
Action
1
Remove one module support screw
and set it aside for later use.
0RGXOH VXSSRUW
VFUHZ
2
Replace the module support screw
with one module standoff.
0RGXOH VWDQGRII
3
Repeat Steps 1 and 2 for the three remaining module support screws.
4
Insert pins on the Expander Module
into connector on the module. Make
([SDQGHU 0RGXOH
sure the pins are in line; then, press
the two boards together until the
boards snap into place.
0RGXOH
5
Install the four module support
screws (removed earlier) through the
back of the Expander Module and 0RGXOH VXSSRUW
into the standoffs.
VFUHZ
2-20
www.PDF-Zoo.com
Table 2-8 Installing an Expander Module
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
firealarmresources.com
Mounting Panel Modules (CRM-4, ICM-4, VCM-4) onto a Chassis
,QVWDOODWLRQ
0RXQWLQJ3DQHO0RGXOHV&50,&09&0RQWRD&KDVVLV
To install a module onto a CHS-4 chassis, follow these steps.
1. Angle the module into the chassis so that the upper board edge slips into
the chassis slots as shown in Figure 2-23:
&KDVVLV
6ORWV
)LJXUH ,QVHUWLQJ D 0RGXOH WR D &+6 &KDVVLV
2. Push the upper end of the module into the slots in the chassis. Secure the
module to the chassis with the two module screws (Figure 2-24).
0RGXOH VFUHZ
)LJXUH 6HFXULQJ D 0RGXOH WR D &+6 &KDVVLV
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
2-21
www.PDF-Zoo.com
firealarmresources.com
,QVWDOODWLRQ
Installing a 4XTM Module (Remote Station Fire Alarm)
,QVWDOOLQJD;700RGXOH5HPRWH6WDWLRQ)LUH$ODUP
0RXQWLQJWKH0RGXOH
Install the 4XTM module by following these steps:
Step Action
1
Install the standoffs (provided) into the holes next to TB1 on the MPS-400 board.
2
Carefully align the pins on the MPS-400 PC board with the connector on the 4XTM
board.
3
Press firmly on the 4XTM board until the board locks in place on the standoffs.
4
Screw the 4XTM board to the standoffs.
Table 2-9 Mounting a 4XTM Module Figure 2-25 shows where to mount a 4XTM module on the MPS-400 board:
6WDQGRII
7%
;70
036
)LJXUH 0RXQWLQJ D ;70 0RGXOH
;70(OHFWULFDO5HTXLUHPHQWV
Electrical requirements for local energy municipal Box service (NFPA 72-1993
Auxiliary Protective Fire Alarm System) are:
Supervisory current
5.0 mA
Trip current Coil voltage
0.35 A (subtracted from NAC power) 3.65 VDC
Coil resistance
14.6 ohms
1RWH 7KH /RFDO (QHUJ 0XQLFLSDO %R[ &LUFXLW LV QRQSRZHUOLPLWHG 0DLQWDLQ DW OHDVW D LQFK VSDFLQJ EHWZHHQ WKH 0XQLFLSDO %R[ &LUFXLW ZLULQJ DQG DOO SRZHUOLPLWHG FLUFXLW ZLULQJ
Electrical requirements for remote station service (NFPA 72-1993 Remote Station Protective Fire Alarm System) are:
Wire resistance (panel and trip coil)
Maximum of 3.0 ohms
Maximum load for each circuit
10 mA
Reverse polarity output voltage
24 VDC (nominal) 28 VDC (max)
2-22
www.PDF-Zoo.com
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
firealarmresources.com
Installing a 4XTM Module (Remote Station Fire Alarm)
,QVWDOODWLRQ
&RQQHFWLQJWKH;700RGXOH
Push the Disconnect Switch (Figure 2-26) down to prevent unwanted activation
of the Municipal Box during testing of the control panel.
· The 4XTM Disconnect LED lights while the Municipal Box is disconnected; and
· The CPU System Trouble LED lights to indicate disconnected and/or open
circuit conditions on the Municipal Box.
During trouble conditions, you can transmit a trouble indication through an
open circuit signal on the Alarm Reverse-Polarity output. Do this by cutting
the TBL jumper (Figure 2-26). Figure 2-26 shows connections to the 4XTM with
polarities shown in the activated position:
7%/ -XPSHU ‘LVFRQQHFW 6ZLWFK
5HPRWH $ODUP
SRZHUOLPLWHG
²
5HPRWH 7URXEOH
SRZHUOLPLWHG
²
1R FRQQHFWLRQ
0XQLFLSDO %R[
²
QRQSRZHUOLPLWHG
:LULQJ IURP WKHVH WHUPLQDOV FDQ H[LW WKH SURWHFWHG SUHPLVHV
‘LVFRQQHFW /(‘
)LJXUH ;70 7UDQVPLWWHU 0RGXOH 3RODULWLHV VKRZQ LQ DFWLYDWHG SRVLWLRQV
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
2-23
www.PDF-Zoo.com
firealarmresources.com
,QVWDOODWLRQ
Installing a UZC-256 Module
,QVWDOOLQJD8=&0RGXOH
2YHUYLHZ
You can mount the UZC-256 into a CAB-X3 or a CAB-400AA. This section shows how to install the UZC-256 both ways. For information on configuring the UZC-256 module, refer to Section 5, “Applications.”
&$%; ,QVWDOODWLRQ
The UZC-256 mounts beneath the third and fourth modules on the CHS-4 chassis, to the right of the CPU. Install the module as follows:
1. Thread the supplied three hex standoffs to the mounting studs on the CHS-4 chassis (Figure 2-27).
0RGXOH
&+6
&+6 &KDVVLV
,QVHUWLQJ QORQ VWDQGRII DQG VHOIWDSSLQJ VFUHZ
8=& 0RGXOH
0RXQWLQJ VFUHZV WKUHH SODFHV +H[ VWDQGRII WKUHH SODFHV
&$%$$ ,QVWDOODWLRQ
)LJXUH 0RXQWLQJ D 8=& WR D &+6
2. Place the module onto the CHS-4 as shown in Figure 2-27; then, insert and
tighten the mounting screws.
You can also mount the module to the upper right corner of the CAB-400AA
Series cabinet as follows:
1. Place the module into the CAB-400AA as shown in Figure 2-28.
&$%$$ &DELQHW
0RGXOH
&$%$$
8=& 0RGXOH
6HOIWDSSLQJ VFUHZ WKUHH SODFHV
,QVHUWLQJ QORQ VWDQGRII DQG VHOIWDSSLQJ VFUHZ
)LJXUH 0RXQWLQJ WKH 8=& LQWR D &$%$$ &DELQHW
2. Attach the module to the CAB-400AA with the self-tapping screws.
2-24
www.PDF-Zoo.com
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
firealarmresources.com
Field-Wiring the Modules
,QVWDOODWLRQ
)LHOG:LULQJWKH0RGXOHV
This section contains instructions for the following: · Notification Appliance
Circuit (NAC) Wiring · Field-wiring a ICM-4 and an ICE-4 (NFPA Style Y and Z)
· Field-wiring a CRM-4 and the CRE-4 · Field-wiring the MPS-400 Power Supply ·
Field-wiring an ARM-4
1RWH 7RWDO LQ WKHVH ILJXUHV DVVXPHV WKDW QR QRWLILFDWLRQ DSSOLDQFH SRZHU LV GUDZQ IRU DQ RWKHU SXUSRVH
1RWLILFDWLRQ$SSOLDQFH&LUFXLW1$&:LULQJ
The total current available from any group of Notification Appliance Circuits
(NACs) cannot exceed the following: · 3.0 A when powered from the AVPS-24; or
· 1.25 A when powered from an MPS-400 output. Figure 2-29 shows the bottom
wire connections of the ICM-4 and the ICE-4 modules:
%ODFN ZLUH ² %OXH ZLUH
&RQQHFWRU 2ULHQWDWLRQ
036 %HOO 3RZHU +DUQHVV
)LJXUH ,&0,&( &RQQHFWRU
7SLFDO 3RZHU 6XSSO 1RWLILFDWLRQ $SSOLDQFH &LUFXLW &RQILJXUDWLRQV
036,&01$&&RQILJXUDWLRQV
Figure 2-30, Figure 2-31, Figure 2-32, Figure 2-33, and Figure 2-34 show
typical power supply (MPS-400 and AVPS-24) to NAC configurations.
036
036 %HOO 3RZHU +DUQHVV 7% DQG 7% $
–
–
,&0
– ,&(
(LJKW 1$& &LUFXLWV WKDW VKDUH $
)LJXUH 036 1$& &RQILJXUDWLRQ (LJKW 1$&V
Figure 2-31 shows a block diagram that uses four NACs:
036
036 %HOO 3RZHU +DUQHVV 7% DQG 7% $
– ,&0
–
7ZR 1$& FLUFXLWV WKDW VKDUH $ IURP 036 7% DQG 7%
7ZR 1$& FLUFXLWV WKDW VKDUH $ IURP 036 7% DQG 7%
7% DQG 7% $
)LJXUH 036 1$& &RQILJXUDWLRQ )RXU &LUFXLWV
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
2-25
www.PDF-Zoo.com
firealarmresources.com
,QVWDOODWLRQ
$936,&0 1$& &RQILJXUDWLRQV
Field-Wiring the Modules
Figure 2-32 shows a block diagram that uses four NACs:
036 %HOO 3RZHU +DUQHVV 7% DQG 7% $
036 7%
– ,&0
7ZR 1$& FLUFXLWV WKDW VKDUH $ IURP 036 7% DQG 7%
036 %HOO 3RZHU +DUQHVV 7% DQG 7% $
– ,&0
7ZR 1$& FLUFXLWV WKDW VKDUH $ IURP 036 7% DQG 7%
)LJXUH 036 1$& &RQILJXUDWLRQ )RXU &LUFXLWV
Figure 2-33 shows typical NAC configurations using AVPS-24 power supplies:
$936 $X[LOLDU %HOO 3RZHU &DEOH – $936 3 $
,&0
$936 $X[LOLDU %HOO 3RZHU &DEOH $936 3 $
– – ,&0 –
,&0
)RXU 1$&V WKDW VKDUH $ RI RQH $936 (LJKW 1$&V WKDW VKDUH WKH WRWDO $ RI WKH VHFRQG $936
$936
–
$X[LOLDU %HOO 3RZHU &DEOH
,&0
$936 3 $
)RXU 1$&V WKDW VKDUH $ RI RQH $936
$936 $X[LOLDU %HOO 3RZHU &DEOH
–
,&0
$936 3 $
)RXU 1$&V WKDW VKDUH $ RI RQH $936
)LJXUH $936 1$& &RQILJXUDWLRQ
Figure 2-34 shows a block diagram that uses two AVPS-24 power supplies to power an
ICM-4 or ICE-4). If doing this, cut jumpers JP1 and JP2 located above J5 and J6:
-3
-3
–
–
$936 $936
,&0,&( -XPSHUV – ,&0 –
7ZR FLUFXLWV WKDW VKDUH $ RI RQH $936 7ZR FLUFXLWV WKDW VKDUH $ RI RQH $936
)LJXUH $936 1$& &RQILJXUDWLRQ 7ZR $936V
2-26
www.PDF-Zoo.com
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
firealarmresources.com
Field-Wiring the Modules
,QVWDOODWLRQ
)LHOG:LULQJDQ,&0DQGDQ,&(1)3$6WOH<DQG=
Guidelines for field-wiring include the following:
· Notification Appliance Circuits (NACs) are supervised, power-limited, and
can connect to an energy-limited cable.
· Use only the compatible, UL-listed notification appliances listed in the
Device Compatibility Document.
· Wire notification appliances according to the manufacturer’s instructions.
· Maximum current per circuit is 3.0 A. Maximum current per module depends on
the type of power supply (MPS-400 or AVPS-24).
· Canadian installations require model N-ELR End-of-Line Resistor Assembly
(Style Y only).
· Size NAC wiring so the voltage drop does not exceed the minimum rated
voltage of the notification appliance used as the last device on the circuit.
· For zone coded applications, refer to the UZC-256 manual.
· The ICM-4 is California Code programmable (microprocessor Rev. B or higher).
To program for California Code, cut diode D35.
7SLFDO 1)3$ 6WOH < 1$&
7SLFDO 1)3$ 6WOH = 1$&
. ZDWW (/5 31
8/OLVWHG 9’& 3RODUL]HG %HOOV
-XPSHUV IRU XQXVHG FLUFXLWV
-XPSHUV IRU XQXVHG FLUFXLWV
8/OLVWHG 9’& 3RODUL]HG +RUQV
% $ $¤ %¤ % $ $¤ %¤
% $ $¤ %¤ % $ $¤ %¤
/IS]OXK )LJXUH )LHOG:LULQJ DQ ,&0
Positions E, F, G, and H are active only with the ICE-4 installed. You can
also install a CRE-4 module on the ICM-4, connected as shown in Figure 2-36:
,&( PRGXOH
,&0 PRGXOH
)LJXUH )LHOG:LULQJ DQ ,&(
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
2-27
www.PDF-Zoo.com
firealarmresources.com
,QVWDOODWLRQ
&50 DQG &5( :LULQJ *XLGHOLQHV
&50 DQG &5( &RQQHFWLRQV
Field-Wiring the Modules
)LHOG:LULQJD&50DQGWKH&5(
· These Form-C silver alloy relay contacts are for medium duty switching or
pilot duty (Figure 2-37).
· UL contact ratings are 5 A @ 125 VAC (resistive) or 30 VDC (resistive) and 2
A @ 125 VAC (inductive). For more information, refer to Appendix F, UL Power-
limited Wiring Requirements.
· Activation of a CRM-4 or CRE-4 relay occurs automatically when an alarm is
detected on a selected (programmed) Initiating Device Circuit.
· Positions E, F, G, and H are active only with the CRE-4 board installed.
Figure 2-37 shows typical connections for field-wiring a CRM-4/CRE-4 module:
2SWLRQDO &5( &RQWURO 5HOD ([SDQGHU
7SLFDO FRQQHFWLRQV IRU D WSLFDO )RUP& FRQWURO 5HOD LQ VWDQGE SRVLWLRQ
&50
2-28
www.PDF-Zoo.com
)LJXUH )LHOG:LULQJ D &50&5( 0RGXOH
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
firealarmresources.com
Field-Wiring the Modules
,QVWDOODWLRQ
$936 :LULQJ 2YHUYLHZ
)LHOG:LULQJDQ2SWLRQDO$9363RZHU6XSSO
This section covers wiring an AVPS-24. Use TB2 terminals for a power circuit
run to CMX control modules. Table 2-10 lists connections between the AVPS-24
and the MPS-400. For wiring, see Figure 2-38, Figure 2-39, or both.
$936 :LULQJ ‘LDJUDPV
AVPS-24 Pin
Function
Connect to MPS-400…
TB1-1
Earth ground in
Chassis or earth ground terminal
TB1-2
Secondary power (24 VDC) positive (+) connection TB1-6 (+)
TB1-3 TB1-4 TB1-5 TB1-6
Secondary power (24 VDC) negative () connection Primary power (120 VAC) neutral connection Primary power (120 VAC) hot connection Earth ground out
TB1-7 () TB-2 (neutral) TB1-4 (hot) TB1-3 (earth ground)
Table 2-10 AVPS-24 to MPS-400 Connections
Plug the Auxiliary Bell Power Harness to the connector J5 on the ICM-4 or the
ICE-4 NAC modules as shown in Figure 2-38:
,&0 PRGXOH
1RWH 7KH $X[LOLDU %HOO 3RZHU +DUQHVV SURYLGHV 9’& VSHFLDO SXUSRVH SRZHU XQILOWHUHG XQUHJXODWHG SRZHUOLPLWHG $ PD[LPXP WR 1$& PRGXOHV
%OXH ZLUH $X[LOLDU %HOO 3RZHU +DUQHVV 31
$936 PRGXOH
,&( PRGXOH %ODFN ZLUH
7HUPLQDO 7%
7R – $X[ 7URXEOH RQ WKH 036
7URXEOH /(‘
7HUPLQDO 7%
)LJXUH :LULQJ DQ $936 WR DQ ,&( RU DQ ,&0
Figure 2-39 shows a block diagram for connecting or changing multiple AVPS-24
power supplies:
7R – $X[ 7URXEOH RQ WKH 036
)LUVW $936
/DVW $936
)LJXUH :LULQJ 0XOWLSOH $936V
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97
2-29
www.PDF-Zoo.com
firealarmresources.com
,QVWDOODWLRQ
Field-Wiring the Modules
)LHOG :LULQJ 2YHUYLHZ
1RWH 5HIHU WR WKH ‘HYLFH &RPSDWLELOLW ‘RFXPHQW IRU GHWHFWRU DQG SRZHU
VXSHUYLVLRQ UHODV
)LHOG:LULQJ)RXU:LUH6PRNH’HWHFWRUV6WOH%DQG6WOH’
This section shows how to wire initiating devices which require 24 VDC operating power. Figure 2-41 shows wiring for Style D connections and Figure 2-42 shows wiring for Style B connections.
1. Connect the Power Supervision Relay coil (A77-716B) leads to the last detector base 24 VDC screw terminal.
2. Calculate the maximum allowable resistance in the 24 VDC detector power wiring as follows:
5PD[
9RP 1,V 1$,D ,U
Where:
Rmax Vom
N Is NA
Ia Ir
the maximum resistance of the 24 VDC wi
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>