NOTIFIER NION-16C48M Fire Alarm System Owner’s Manual
- June 9, 2024
- NOTIFIER
Table of Contents
NION-16C48M Fire Alarm System
UniNet 2000 NION-16C48M (NION-48M)
Instruction Manual
Version 2
NION-16C48M (NION-48M)
Technical Manuals Online! – http://www.tech-man.com
firealarmresources.com
A Document 52004
10/10/02 Rev
52004:A
ECN 02-232
2
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
Technical Manuals Online! – http://www.tech-man.com
firealarmresources.com
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm systemtypically made up of smoke mable materials, etc.).
detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification capabilitycan provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be
The Manufacturer recommends that smoke and/or heat detec- tested at least once per year by a qualified fire protection spe-
tors be located throughout a protected premise following the
cialist. Heat detectors are designed to protect property, not
recommendations of the current edition of the National Fire
life.
Protection Association Standard 72 (NFPA 72), manufacturer’s recommendations,
State and local codes, and the recommendations contained in the Guide for
Proper Use of System Smoke Detectors, which is made available at no charge to
all installing dealers. A study by the Federal Emergency Management Agency (an
agency of the United States government) indicated that smoke detectors may not
go off in as many as 35% of all fires. While fire alarm systems are designed
to provide early warning against fire, they do not guarantee warning or
protection against fire. A fire alarm system may not provide timely or
adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such
as in chimneys, in or behind walls, on roofs, or on the other side of closed
doors. Smoke detectors
IMPORTANT! Smoke detectors must be installed in the same room as the control
panel and in rooms used by the system for the connection of alarm transmission
wiring, communications, signaling, and/or power. If detectors are not so
located, a developing fire may damage the alarm system, crippling its ability
to report a fire.
Audible warning devices such as bells may not alert people if these devices
are located on the other side of closed or partly open doors or are located on
another floor of a building. Any warning device may fail to alert people with
a disability or those who have recently consumed drugs, alcohol or medication.
Please note that:
· Strobes can, under certain circumstances, cause seizures in people with
conditions such as epilepsy.
also may not sense a fire on another level or floor of a build-
· Studies have shown that certain people, even when they
ing. A second-floor detector, for example, may not sense a first-floor or
basement fire.
Particles of combustion or “smoke” from a developing fire may not reach the
sensing chambers of smoke detectors because:
hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner’s responsibility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
· Barriers such as closed or partially closed doors, walls, or chimneys may
inhibit particle or smoke flow.
· Smoke particles may become “cold,” stratify, and not reach the ceiling or
upper walls where detectors are located.
· Smoke particles may be blown away from detectors by air outlets.
· Smoke particles may be drawn into air returns before reaching the detector.
· In rare instances, the sounding of a warning device can cause temporary or
permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power
fails, the system will operate from standby batteries only for a specified
time and only if the batteries have been properly maintained and replaced
regularly.
Equipment used in the system may not be technically compatible with the
control. It is essential to use only equipment listed for service with your
control panel.
The amount of “smoke” present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizingtype sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer’s recommendations, and UL and NFPA standards. At a minimum, the requirements of Chapter 7 of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer’s representative. Maintenance should
Smoke detectors cannot be expected to provide adequate
be scheduled monthly or as required by National and/or local
warning of fires caused by arson, children playing with
fire codes and should be performed by authorized professional
matches (especially in bedrooms), smoking in bed, and violent fire alarm installers only. Adequate written records of all in-
explosions (caused by escaping gas, improper storage of flam- spections should
be kept.
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
Precau-L-4-2002.p65
3
Technical Manuals Online! – http://www.tech-man.com
firealarmresources.com
Installation Precautions
Adherence to the following will aid in problem-free installation with long- term reliability:
WARNING – Several different sources of power can be connected to the fire
alarm control panel. Disconnect all sources of power before servicing. Control
unit and associated equipment may be damaged by removing and/or inserting
cards, modules, or interconnecting cables while the unit is energized. Do not
attempt to install, service, or operate this unit until this manual is read
and understood.
CAUTION – System Reacceptance Test after Software Changes. To ensure proper
system operation, this product must be tested in accordance with NFPA 72
Chapter 7 after any programming operation or change in site-specific software.
Reacceptance testing is required after any change, addition or deletion of
system components, or after any modification, repair or adjustment to system
hardware or wiring.
All components, circuits, system operations, or software functions known to be
affected by a change must be 100% tested. In addition, to ensure that other
operations are not inadvertently affected, at least 10% of initiating devices
that are not directly affected by the change, up to a maximum of 50 devices,
must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49° C/32-120° F and at
a relative humidity of 85% RH – 93% per ULC – (non-condensing) at 30° C/86° F.
However, the useful life of the system’s standby batteries and the electronic
components may be adversely affected by extreme temperature ranges and
humidity. Therefore, it is recommended that this system and all peripherals be
installed in an environment with a nominal room temperature of 15-27° C/60-80°
F.
Verify that wire sizes are adequate for all initiating and indicating device
loops. Most devices cannot tolerate more than a 10% I.R. drop from the
specified device voltage.
Like all solid state electronic devices, this system may operate erratically
or can be damaged when subjected to lightning-induced transients. Although no
system is completely immune from lightning transients and interferences,
proper grounding will reduce susceptibility. Overhead or outside aerial wiring
is not recommended, due to an increased susceptibility to nearby lightning
strikes. Consult with the Technical Services Department if any problems are
anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit
boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or
punching of the enclosure. When possible, make all cable entries from the
sides or rear. Before making modifications, verify that they will not
interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Overtightening may damage
threads, resulting in reduced terminal contact pressure and difficulty with
screw terminal removal.
Though designed to last many years, system components can fail at any time.
This system contains static-sensitive components. Always ground yourself with
a proper wrist strap before handling any circuits so that static charges are
removed from the body. Use static-suppressive packaging to protect electronic
assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming
manuals. These instructions must be followed to avoid damage to the control
panel and associated equipment. FACP operation and reliability depend upon
proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and can radiate radio frequency
energy and if not installed and used in accordance with the instruction
manual, may cause interference to radio communications. It has been tested and
found to comply with the limits for class A computing device pursuant to
Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable
protection against such interference when operated in a commercial
environment. Operation of this equipment in a residential area is likely to
cause interference, in which case the user will be required to correct the
interference at his own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise
emissions from digital apparatus set out in the Radio Interference Regulations
of the Canadian Department of Communications. Le present appareil numerique
n’emet pas de bruits radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le Reglement sur le
brouillage radioelectrique edicte par le ministere des Communications du
Canada.
Precau-L-4-2002.p65
Acclimate PlusTM, HARSHTM, NOTI·FIRE·NETTM, ONYXTM, and VeriFireTM are trademarks, and FlashScan® and VIEW® are registered trademarks of NOTIFIER®. NIONTM and UniNetTM are trademarks of NIS. NISTM and NOTIFIER® Integrated SystemsTM are trademarks and NOTIFIER® is a registered trademark of Fire·Lite Alarms, Inc. Echelon® is a registered trademark and LonWorksTM is a trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. LEXAN® is a registered trademark of GE Plastics, a subsidiary of General Electric Company.
4
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
Technical Manuals Online! – http://www.tech-man.com
firealarmresources.com
Contents
Section 1: NION-16C48M (NION-48M) Installation……………………………… 7
1.1 Description of the NION-16C48M ………………………………………………………………………….. 7 Figure
1-1: NION-16C48M Board Layout …………………………………………………………………………. 7
1.2 NION Components ……………………………………………………………………………………………….. 8 Figure 1-2: NION-
16C48M Components ………………………………………………………………………….. 8
1.3 Installation Conditions …………………………………………………………………………………………. 9 1.4 SMX
Transceiver Connection …………………………………………………………………………………. 9
Figure 1-3: SMX Transceiver Installation ……………………………………………………………………………. 9 1.5
Cabinet Installation – NISCAB-3 …………………………………………………………………………… 10
Figure 1-4: NION-16C48M Cabinet Installation ………………………………………………………………. 10 1.6
NION Power Requirements …………………………………………………………………………………. 11
Figure 1-5: MPS24BRB Power Supply ………………………………………………………………………………. 11 1.7 NION-
16C48M Operation …………………………………………………………………………………… 12
Figure 1-6: NION-16C48M Operation LEDs ……………………………………………………………………. 12 1.8
Input Configuration ……………………………………………………………………………………………. 13 1.9 Discrete or
Switched Voltage Inputs (21 – 24 and 45 – 48) ……………………………………… 13
Figure 1-7: Switched Voltage Input Jumpers …………………………………………………………………….. 14
1.10 Output Configuration ………………………………………………………………………………………… 15
Figure 1-8: Output Relays and NC/NO Jumper Settings …………………………………………………….. 15
1.11 Software Configuration …………………………………………………………………………………….. 15 1.12 NION-
16C48MTB Terminal Boards …………………………………………………………………….. 16
Figure 1-9: 16C48MTB Terminal Board Mounting ……………………………………………………………… 16
Figure 1-10: Ribbon Cable Mapping ………………………………………………………………………………. 16 1.13
Terminal Board Input/Output Connections ………………………………………………………….. 17 Figure
1-11: Terminal I/O Mapping ……………………………………………………………………………….. 17 Figure 1-12:
I/O Point Connections ………………………………………………………………………………… 17
Section 2: NION-16C48M Plug-In Application …………………………………… 19
2.1 Plug-In Selection and Configuration …………………………………………………………………….. 19 Figure
2-1: NION Plug-In Selection and Configuration Form ……………………………………………… 19
2.2 Mapping Plug-ins With NIONs …………………………………………………………………………….. 20 Figure 2-2:
Network Configuration Window …………………………………………………………………….. 20
2.3 NION I/O Configuration ……………………………………………………………………………………… 21 Figure 2-3:
16C48M I/O Configuration ………………………………………………………………………….. 21
2.4 Time Codes ………………………………………………………………………………………………………… 24 Figure 2-4: Time
Code Configuration ……………………………………………………………………………… 24
2.5 Universal Time Codes and Time Code Groups ………………………………………………………. 25 2.6
Holiday Codes ……………………………………………………………………………………………………. 25
Figure 2-5: Holiday Code Configuration …………………………………………………………………………. 25 2.7
Functional Properties of the 16C48M ……………………………………………………………………. 26
Index ………………………………………………………………………………………….. 31
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
5
Technical Manuals Online! – http://www.tech-man.com
firealarmresources.com
Foreword
The contents of this manual are important and must be kept in close proximity
of the hardware. If building ownership is changed, this manual and all other
testing and maintenance information must also be passed to the current owner
of the facility. A copy of this manual was shipped with the equipment and is
also available from the manufacturer.
This equipment has been designed to comply with standards set forth by the
following regulatory agencies:
NFPA Standards National Fire Protection Association Standards 72. National
Electric Code (NFPA 70). Life Safety Code (NFPA 101).
Underwriters Laboratories U.S. Documents UL-864 Control Units for Fire
Protective Signaling Systems. UL-1076 Proprietary Burglar Alarm Units and
Systems.
Underwriters Laboratories Canada Documents CAN/ULC-S524-M91 Standard for
Installation of Fire Alarm Systems. CAN/ULC-S527-M99 Standard for Control
Units for Fire Alarm Systems.
Other Requirements of the Local Authority Having Jurisdiction (LAHJ).
WARNING: Improper installation, maintenance, and lack of routine testing could
result in system malfunction.
Introduction
The NION-16C48M is a plug-in component of the UniNet Workstation. The NION-
16C48M provides a gateway to the network for discrete monitored devices,
equipment and control panels that have dry contacts.
This system is suitable for proprietary systems listed under:
NFPA 72-1993 Proprietary Service. UniNet consists of graphical workstations
monitoring and controlling local or remote twisted pair or fiber optic
networks. Remote network monitoring is achieved through the use of a Building
Communications Interface (BCI), which has a maximum capacity of 32 nodes. Each
Local Area Server (LAS) has a maximum capacity of 200 nodes, using twisted
pair or fiber-optic cabling. A twisted pair network topology (FT-10) may be a
maximum length of 6000 feet per network segment with no T-taps, allowing
communications between 64 nodes in each segment. In addition, FT-10 allows
dedicated runs of 8000 feet point-to-point or multiple T-taps within 1500 feet
of any other node on the segment. Fiber-optic cable runs can be configured in
either a bus or ring topology with up to 8db of attenuation between nodes. The
network is supervised for shorts, opens and node failures as dictated in Style
4 wiring.
The network power is 24 VDC nominal and receives operating power from a power
limited, filtered source listed for use with fire protective signaling units.
Network Installation M anual Workstation
System Utilities BCI ver. 3-3
Local Area Server
51539 51540 51592 51543 51544
UniLogic AM2020/AFP1010 Instruction M anual
UniTour IRM/IM UniNet Online
Related Documentation
6
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
Technical Manuals Online! – http://www.tech-man.com
firealarmresources.com
51547 52020 51550 51591 51994
1
Section 1: NION-16C48M (NION-48M) Installation
1.1 Description of the NION-16C48M
The NION-16C48M (16 Control, 48 Monitor) is a discrete input/output interface used on the UniNet 2000 network. All of the system components are based on LonWorks (Local Operating Network) technologies. The NION-16C48M provides a gateway to the network for discrete monitored devices, equipment and control panels that have dry contacts.
The NION-16C48M connects a LonWorks FT-10 or fiber optic network with discrete monitored devices and conventional control panels. It provides a single, two- way communication channel for discrete inputs and outputs. NIONs are specific to the type of network to which they connect (FT-10 or fiber). The transceiver type must be specified and ordered separately when ordering the NION.
The NION is also available in a depopulated version – the 48M NION. It is identical in all aspects to the 16C48M, except the 48M board has no output relays.
The NION can be powered by any power limited, filtered source with battery backup which is UL or ULC listed, as appropriate for your area, for use with fire protective signaling units. Power must be supervised or placed within 20 ft of the NION with connections run in conduit.
The NION mounts in an enclosure (NISCAB-3) with conduit knockouts. It cannot be rack mounted.
TB1 Power Connector
– +
SMX Module Stand-
Configuration
offs
Status LEDs Network EPROM Battery Backup
CPU
Not Used
NION Program EPROM
SMX Module Connector Reset Pin Comm. LEDs Binding Pin
Input LEDs
Terminal Board 1 Ribbon Cable Connectors
Output Relays 1 – 16
Not included on the NION-48M
Figure 1-1: NION-16C48M Board Layout
NOTE: Use only wire for power limited systems. Power limited wire runs use
type FPLR, FPLP, FPL or equivalent cabling per NEC 760.
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
Technical Manuals Online! – http://www.tech-man.com
firealarmresources.com
Configuration Jumpers for Inputs 21 – 24 and 45 – 48 Configuration Legend for
Inputs 21 – 24 and 45 48 Terminal Board 2 Ribbon Cable Connectors
7
The NION-16C48M is designed to be wired to control panels and the network through plug-in terminal strips.
The NION-16C48M has the following features:
Accepts normally open or normally closed dry contact inputs in any
combination. Control outputs are SPDT relays rated at 2.5A @ 30 VDC. Powered
from a power limited, supervised, filtered source with battery backup which is
UL or ULC listed, as
appropriate for your area, for use with fire protective signaling units. Point
status LEDs for each input and output NION status, Binding status (service),
and Network status LEDs. Inputs can be configured as either two-state
unsupervised or four-state supervised with EOL resistors. Eight
of the inputs are configurable for switched voltage monitoring. Transformer
coupled network connection using SMX style transceivers. Software configurable
from the workstation plug-in utility. Transient protection to 2400V on all
terminals. Included wall mount enclosure (NISCAB-3).
1.2 NION Components
The following illustration displays components included and required to install a NION-16C48M on the network.
All of these items must be ordered separately.
16C48MTB Terminal Boards
Each NION uses two terminal boards
which mount directly on the mother board
NOTE: Line cord not included.
with stand-offs. These boards provide terminal connections to monitored inputs
and outputs.
16C48M Mother Board
The NION motherboard contains all relays, LEDs, CPU, configuration jumpers,
network interface, firmware and terminal board connections.
Transformer Assembly
One 4000TA, 110VA transformer and connector.
SMX Network Transceiver
One SMX transceiver daughter board is required for local network connection. Three styles are available for different topologies and media. This daughter board mounts on the mother board with a header strip and two standoffs.
NISCAB-3
The NION-16C48M mounts in a locking cabinet with a Lexan dress plate. (12.25″H
X 9.25″W X 2.75″D)
MPS24BRB Power Supply
The MPS24B supplies 2.0A of 24VDC regulated power to operate the NION. Up to 200mA of resettable auxiliary power is also available. This supply contains an integral battery charger which can support 6.5 to 17AH batteries.
Figure 1-2: NION-16C48M Components
8
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
Batteries
The cabinet provides space for 12AH batteries. To use 17AH capacity batteries
use the BB-17 battery box.
Technical Manuals Online! – http://www.tech-man.com
firealarmresources.com
1.3 Installation Conditions
The NION-16C48M can be installed in the following environmental conditions:
Temperature range of 0ºC to 49ºC (32°F – 120°F). 93% humidity non-condensing
at 30ºC (86°F).
1.4 SMX Transceiver Connection
Install the standoffs onto the 16C48M board, then connect JP1 of the
transceiver to J4 of the 16C48M motherboard. Lastly, secure the transceiver to
the standoffs with screws.
NOTE: Always observe ESD precautions when working with electircal hardware.
Transceiver mounting standoffs
Transceiver mounting standoffs
J4 16C48M board
J4 SMX Header on 16C48M board
JP1 SMX Transceiver
Figure 1-3: SMX Transceiver Installation
JP1 Transceiver Connector
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
9
Technical Manuals Online! – http://www.tech-man.com
firealarmresources.com
1.5 Cabinet Installation – NISCAB-3
The NION-16C48M is installed into a standard wall mount enclosure, the
NISCAB-3. This enclosure has a locking door and mounting hardware for the
16C48M assembly (motherboard, terminal boards and network transceiver),
MPS24BRB power supply, transformer and batteries.
Mounting the enclosure to its wall position 1) Use the provided key to unlock
the enclosure cover. 2) Remove the enclosure cover. 3) Mount the enclosure to
the wall. Refer to the enclosure mounting hole layout below. 4) Mount the
MPS24BRB power supply and transformer to the stand-offs in the back of the
cabinet using the provided hardware. 5) Mount the 16C48M motherboard to the
mounting rails in the same manner.
Distances can vary between the NION and monitored equipment, but the maximum
wire resistance must not exceed 500 ohms. The type of hardware used is at the
discretion of the installer, but must be in accordance with local code
requirements.
Figure 1-4: NION-16C48M Cabinet Installation
10
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
Technical Manuals Online! – http://www.tech-man.com
firealarmresources.com
1.6 NION Power Requirements
The NION-16C48M is powered by the MPS24BRB power supply, which uses 110VAC,
1.8A(max.) of power and provides 2.0A of 24VDC power and battery backup in
accordance with local code requirements. The MPS24BRB contains a built in
battery charging circuit capable of supporting 6.5 to 17AH 24VDC batteries.
Alternately, the NION can be powered by any power limited, regulated 24 VDC
source which is UL or ULC listed, as appropriate for your area, for use with
fire protective signaling units. For replacement part orders, specify MPS24BRB
for Replacement Board.
Power Supply Connections to the NION
Power connections from the MPS24BRB to the NION must be as follows:
TB1 on the 16C48M motherboard to pins 3 and 4 of TB2 on the MPS24BRB.
Terminals on both boards are labelled for proper connections.
Cut JP1 to make auxiliary power non-resettable.
Do not cut.
Normally Closed Trouble Contacts
Contacts open when the main power supply enters a trouble condition.
Not Used
Removal disables battery charging.
Transformer Connection
AC Power Reset
Secondary Power
27.6VDC, 6.5 to 17AH. Supervised and power-limited. Fast charge = 0.75 amps
(typical), trickle charge = 20mA (typical).
Battery Battery +
Common
Earth Ground
Connect to chassis with a grounding cable assembly (Cable #71073).
Hot Neutral Earth/Service Ground
Primary Power
110VAC, 1.8 amps max.
+24VDC NION Power
Circuit is power-limited, RMS-regulated, non-resettable, 2.0 amps max.
-+
Auxiliary 24VDC Power
200mA max. Power limited, filtered, regulated and resettable.
Figure 1-5: MPS24BRB Power Supply
NOTE: Always remove power from the NION before making any changes to switch settings and removing or installing option modules, SMX network modules and software upgrade chips or damage may result.
NOTE: Use only wire for power limited systems. Power limited wire runs use type FPLR, FPLP, FPL or equivalent cabling per NEC 760.
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
11
Technical Manuals Online! – http://www.tech-man.com
firealarmresources.com
1.7 NION-16C48M Operation
The NION-16C48M is configured and operated over the network from a workstation
using the NION-16C48M Plug-In configuration utility. The only operation
information involving the hardware is the LEDs which display the status of
various parts of the NION. The LEDs (as shown below), operate in the following
fashion:
NION Status LED – The NION status LED shows the status of the NION itself. If
the LED is flashing slowly, the NION is operating normally. If the LED is on
solid, then the NION is not functioning properly.
Network Status LED – The Network status LED shows the status of the neuron
chip that interfaces the NION to the Echelon network. If this LED is flashing,
then the neuron chip is operating properly. If it is unlit, then the neuron
chip is not operating, or not bound to the network.
Network Packet LED – The Network Packet LED indicates when information is sent
or received over the network. This LED will flash for activity in this manner.
Service LED – The Service LED indicates the binding status of the NION. If
this LED is flashing, the NION is unbound. If this LED is lit, that indicates
that the neuron chip is not running or has reached an unrecoverable error.
When bound, the LED is unlit.
Input LEDs – Input LEDs indicate the current status of each input. Each LED
will display the following patterns for each device status:
Point Disable – The LED will flash once every seven seconds.
Point Disarm/Override with Input Active or Input Normal – The LED will flash
three times in rapid succession once every three seconds.
Point Arm/Disarm/Override with Wire Open – The LED will flash rapidly (about
20 times a second) continuously.
Point Arm/Disarm/Override with Wire Short – The LED will flash slowly (about
once a second) continuously.
Point Armed with Input Active – The LED remains in the ON state continuously.
Point Armed with Input Normal – The LED remains in the OFF state continuously.
Each time the node is reset, all the LEDs will cycle once to test operation.
Output LEDs – Output LEDs indicate the status of each relay output. If an
Output LED is off, then the associated output is not activated. If the LED is
On, then the output is activated. Refer to section 1.7.7 for the location of
output LEDs. Not used on the NION-48M.
Serial Communications Activity LED – This LED flashes when information is
transmitted via the EIA-232 serial interface (not used for this application).
Network Packet
Network Status NION Status
Serial
Service
Input LEDs 1
8
48
Figure 1-6: NION-16C48M Operation LEDs
12
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
Technical Manuals Online! – http://www.tech-man.com
firealarmresources.com
1.8 Input Configuration
Inputs can be configured as tracking (default) or latching for two-state
unsupervised or four-state supervised operation. In addition, 8 inputs (21 –
24, 45 – 48) can be configured to monitor switched voltage inputs.
Configuration of two-state/four-state and tracking/latching operation is
performed in the workstation plug-in. Configuration of switched voltage
operation is done by setting jumpers on the 16C48M motherboard. These jumpers
are grouped in an area beneath the terminal boards.
NOTE: Two-state, unsupervised inputs cannot be used for fire applications.
1.9 Discrete or Switched Voltage Inputs (21 – 24 and 45 – 48)
Inputs 21 through 24 and 45 through 48 can be configured to operate as
discrete, two-state unsupervised or fourstate supervised inputs or, switched
voltage (SV) inputs. Each input can be individually configured for maximum
flexibility. To define the function of each of these inputs, four jumpers must
be set. These jumpers are grouped together for easy identification. Figure 1-7
shows the location of these jumper groups and a breakdown of each jumper
setting for the defined functions.
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
13
Technical Manuals Online! – http://www.tech-man.com
firealarmresources.com
Configuration Jumpers for Inputs 21 – 24
Configuration Jumpers for Inputs 45 – 48
For SV inputs, close pins 1 and 2. For Discrete, close pins 2 and 3.
Factory jumper setting. Do not change.
For SV inputs close pins 1 and 2. For Discrete close pins 2 and 3.
For SV inputs, close the following pins to select the monitored voltage:
5VDC – 1 and 2 12VDC – 3 and 4 30VDC – 5 and 6 60VDC – 7 and 8
Single Input Jumper Group
Pin 1
Pin 2
Pin 3
Horizontal Jumpers
Pin 3 Pin 2 Pin 1
Vertical Jumpers
Jumper Pin Key
Pins 8 6 4 2
Pins 7 5 3 1 Jumper Blocks
Figure 1-7: Switched Voltage Input Jumpers
14
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
Technical Manuals Online! – http://www.tech-man.com
firealarmresources.com
1.10 Output Configuration
The NION-16C48M provides 16 SPDT relay outputs. The relays are rated at 2.5A @
30VDC. They can be wired for normally open or normally closed operation. All
rated loads are resistive. Inductive and tungsten loads will be lower. For
special applications, consult with a NOTIFIER® applications engineer.
Output relays are located at the bottom of the 16C48M motherboard and
correspond (from left to right) to outputs one through sixteen. Above each
relay is its related LED and below is a corresponding jumper to set the output
for normally open or normally closed operation. Refer to the diagram below for
jumper settings.
Output LED
16C48M Motherboard
Output Relay (Typical)
Output Relays 1 – 16
Pin 1
Pin 3
Output Operation Jumper Set the jumper across pins 1 and 2 for normally closed operation. Set the jumper across pins 2 and 3 for normally open operation.
Figure 1-8: Output Relays and NC/NO Jumper Settings
For information on output terminal connections, refer to section 1.12 NION-
16C48MTB Terminal Boards.
1.11 Software Configuration
In order to utilize all features available with the NION-16C48M, the 16C48M
Plug-In utility must be configured at the system workstations. Features
include a scheduler for all inputs and outputs and configuring each input as
normally open or normally closed. 16C48M Device Addressing Device addressing
at the workstation uses the following convention:
Inputs – IN1 through IN48 Outputs – OUT1 through OUT16 The NION-48M requires
input addresses only.
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
15
Technical Manuals Online! – http://www.tech-man.com
firealarmresources.com
1.12 NION-16C48MTB Terminal Boards
The Terminal Boards
The NION-16C48M incorporates two terminal daughter boards which are mounted
directly to the motherboard using included stand-offs. Both terminal boards
are identical and interchangeable. Each terminal board is connected to the
motherboard via included ribbon cables (four per terminal board). Point
designation for each terminal is determined by the position of the terminal
board on the motherboard. Refer to the diagrams below for terminal board
mounting and ribbon cable connections.
Mounting Stand-off
Mounting Stand-off
Terminal Board 1
Terminal Board 2
Mounting Stand-off This stand-off is also used to attach the motherboard to the cabinet.
Cable Sockets P1 – P4 Cable Sockets P1 – P8
Mounting Stand-off
Figure 1-9: 16C48MTB Terminal Board Mounting
Ribbon cables have universal ends and are keyed for proper connection. The motherboard has eight cable sockets, P1 through P8. Each terminal board has four sockets labelled P1 through P4. Terminal board one (T1) is mounted on the left and terminal board two (T2) is mounted on the right. The chart below maps the motherboard sockets to the terminal board sockets.
Motherboard Socket
P1 P2 P3 P4 P5 P6 P7 P8
Terminal Board
T1 T1 T1 T1 T2 T2 T2 T2
Terminal Socket
P1 P2 P3 P4 P1 P2 P3 P4
Figure 1-10: Ribbon Cable Mapping
16
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
Technical Manuals Online! – http://www.tech-man.com
firealarmresources.com
1.13 Terminal Board Input/Output Connections
Each terminal board has four rows of plug-in screw terminal connectors to land input and output points. All inputs are rated at 5VDC nominal, 2.5mA maximum current and 500 ohms maximum resistance. The inputs and outputs map to the connectors as described by the following diagrams (Outputs are not included on the 48MTB):
Terminal Board 1
Terminal Board 2
Inputs 1 – 8
Inputs 25 – 32
Inputs 9 – 16
Inputs 33 – 40
Inputs 17 – 24
Inputs 41 – 48
Outputs 1 – 8
Outputs 9 – 16
P1
P4
P1
P4
P2
P3
P2
P3
Figure 1-11: Terminal I/O Mapping
NOTE: For each terminal connector the inputs and outputs are numbered from left to right.
Input Terminals (A – H represent any 8 inputs)
Ground
Four-state Input Wiring
Input
R-1K resistor
A B C DE F G H
Output Terminals (A – H represent any 8 outputs)
Ground
R-3.3K resistor
A B C DE F G H
NOTES: Wiring Distance – Each input can accept up to 400 ohms of added line resistance. No specification is given for maximum wire length.
Use only wire for power limited systems. Power limited wire runs use type
FPLR, FPLP, FPL or equivalent cabling per NEC 760.
Figure 1-12: I/O Point Connections
NOTE: Input ground is common except for inputs 21 – 24 and 45 – 48 when they are used for switched voltage monitoring.
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
17
Technical Manuals Online! – http://www.tech-man.com
firealarmresources.com
NOTES
18
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
Technical Manuals Online! – http://www.tech-man.com
firealarmresources.com
2
Section 2: NION-16C48M Plug-In Application
2.1 Plug-In Selection and Configuration
Plug-In applications are independently operating software applications that
are linked to specific NION types. They interface with the workstation at the
network level. Configuration files act to create new menu options by defining
‘macro’ commands or sequences of information for communicating with specific
devices. Configuration files relate to specific devices, and their options are
accessed through device menu options or macro definitions.
Plug-Ins are designed to be configured automatically when the network
monitoring system software is installed. There may be occasions, however, when
a plug-in will need to be configured manually. This is done using the NION
Plug-In Application Selection and Configuration form. To configure the
16C48M/48M NION Plug-In, follow these steps:
1. Select the appropriate 16C48M/48M NION in the NION Type combo box.
NOTE: The related hardware must be installed to utilize the related features
provided by the plug-in.
Menu Items/Commands Available for Current Plug-In
Click Here to Change Current Linked Plug-In
In this example, the device types listed are pertinent to the Disable Input
command.
Local Area Server and Wide Area Server are the two possibilities. If there is
a
restriction for the selected NION, it will be displayed
here.
Figure 2-1: NION Plug-In Selection and Configuration Form
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
19
Technical Manuals Online! – http://www.tech-man.com
firealarmresources.com
2. Click Change… to modify the current plug-in for the selected device. This
will access a file selection dialog showing the Plugin directory. Select the
.CFG or .EXE file associated with the desired plug-in and click on OK.
3. The commands associated with the selected plug-in will now appear in the
Available Icon Menus display. These are the commands that can now be assigned
to a macro function using the Macro Editor, or assigned to a Functional Button
on the Floor Plan Display. These options will automatically appear on the
pulldown menu for the selected device (provided the current workstation has
control of the device).
Clicking on an available command will cause the Device Type for Chosen Menu
display to show what devices are affected by the chosen command. Some commands
will affect all device types, others will have specific types only. When
creating devices to use plug-in commands be sure they are defined as one of
the appropriate types.
When the plug-in has been configured, click OK to close the Plug-In Selection
and Configuration Form.
2.2 Mapping Plug-ins With NIONs
In order for plug-in applications to function, they must be linked with the
nodes or devices to which they correspond. In most cases this is done
automatically, and each recognized node is linked to the appropriate plug-in
application.
There may be times when nodes and devices are not automatically read and
updated by the workstation, and links are not established. Therefore, it is
advised that this one-time linking process be checked when assigning new plug-
ins, and if the device type has not been automatically assigned, then assign
it manually. This can be done in the Network Configuration Window. This window
is opened by selecting Tools, Network Administration.
Site Node
Panel
Device Site (w/ No Nodes
or Devices)
Unassigned Device Type
Identified Device Type
Figure 2-2: Network Configuration Window
To obtain information about a specific node, single click on the desired node, then select Edit, Inquire NION Type From Node, and the NION type will automatically be displayed. Add Node/Delete Node will add or delete a node from the list displayed in the window. Select Exit when finished.
NOTE: Plug-ins often have configuration forms for the related NIONs. These configuration tools can only be accessed from the device pop-up menus. Therefore, before any configuration of the NION can be done, a device must be assigned to the node.
20
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
Technical Manuals Online! – http://www.tech-man.com
firealarmresources.com
2.3 NION I/O Configuration
The NION-16C48M can be configured to operate using dedicated application plug- ins (16C48M.cfg and .exe). The plug-in application provides tools to configure these NIONs with automated I/O scheduling. Each input can be scheduled for automated Arm and Disarm and each output for Activate and Deactivate. Each input also has configurable event status and contact configuration. Three configuration parameters are set using three forms:
I/O Configuration Time Codes Holiday Codes
NOTES: Output features are not available on the NION-48M.
Latching input points and real-time clock features are supported in NION
firmware version 2.27 and later.
The Get Time button at the bottom left of the screen will display the current date/time in the Inquire Real-Time Clock frame. The time displayed is that of the NIONs real-time clock. This feature allows the user to verify that the NION is set to the same time as the Workstation.
Figure 2-3: 16C48M I/O Configuration
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
21
Technical Manuals Online! – http://www.tech-man.com
firealarmresources.com
Configurations defined in the plug-in are downloaded and stored in the NIONs.
The appropriate collection of configuration forms can be accessed through the
device menu of any defined 16C48M device icon.
Each input on the 16C48M can have the following parameters defined:
Input State Configuration Device Type Event Status Delay Time Codes There are
five buttons which are common to all three tabs: Apply, Cancel, Done, Save and
Load. After making any changes to settings, click on Apply to apply the
changes, Cancel to exit without changing, and Done to save changes and exit.
The tabs also allow saving and loading of the I/O configuration, time code
configuration, and holiday code assignments. These can be used to duplicate
one node configuration to any number of other nodes, or to back up your
configuration. To save the current assignments, click the Save button. To load
a previously saved I/O 16C48M configuration, click the Load button.The device
type and event status are selected from standard lists of system recognized
types and codes. The device type corresponds to the physical definition of the
input.
NOTE: It is possible for the icon device type to be different from the device
type programmed in the plug-in. Example: The icon is defined as a digital
input, and the plug-in defines the same point as a smoke detector. When an
event occurs, the icon device type will display “digital input” but the device
type in the event description will be “smoke detector”.
The event status defines how an off-normal event for each point will be
reported. To select a device type or event status for an input, click on the
desired field and select a definition from the combo box.
The delay field is defined in seconds from 0 to 255. For inputs, the delay
time prevents the NION from reporting an ON condition for the defined amount
of time. A zero in this field will cause instantaneous reporting. This feature
can be used for de-bouncing inputs or as a door-ajar alarm. The Momentary
field for outputs defines how long an output is activated for momentary
commands.
Up to five time codes can be assigned to each point (inputs and outputs).
These are selected from a combo box listing all available time codes (1 – 30).
In order for the time code to work, it must be defined in the Time Codes tab
of the plug-in. All time codes are inactive by default.
22
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
Technical Manuals Online! – http://www.tech-man.com
firealarmresources.com
On 16C48M and 48M NIONs, each of the 48 inputs has a contact configuration
property. Inputs contacts may be configured in one of nine different ways.
Options include:
Not Configured – for unused inputs.
2 State Normally Open (Non-Latching) – normally open input reporting active
and normal.
2 State Normally Closed (Non-Latching) – normally closed input reporting
active and normal.
4 State Normally Open (Non-Latching) – normally open input reporting active,
normal, short and open.
4 State Normally Closed (Non-Latching) – normally closed input reporting
active, normal, short and open.
Latched 2 State Normally Open – normally open input reporting active and
normal; when the input changes to an active state, it is latched, and the
point will not clear until the Clear Latched Points command is performed.
Latched 2 State Normally Closed – normally closed input reporting active and
normal; when the input changes to an active state, it is latched, and the
point will not clear until the Clear Latched Points command is performed.
Latched 4 State Normally Open – normally open input reporting active, normal,
short and open; when the input changes to an active state, it is latched, and
the point will not clear until the Clear Latched Points command is performed.
Latched 4 State Normally Closed – normally closed input reporting active,
normal, short and open; when the input changes to an active state, it is
latched, and the point will not clear until the Clear Latched Points command
is performed.
To configure a large block of inputs to the same state option on a NION, use
the Multiple State Configuration box on the I/O Configuration form. Simply
enter the range of input points in the From and To fields, select the desired
state option in the Configure As combo box then click the Set State button to
finish.
Latching Inputs
When inputs are configured to be latching and in the armed mode, a transition
to an off-normal state is latched. This means that the node will report the
input active event, then it will cease to monitor that input point until it is
explicitly released by the operator. This is done by right clicking on any
related device icon on the Workstation screen and selecting Clear Latched
Points. NOTE: Latched points are cleared on a global basis, with all points on
the NION being cleared simultaneously. When the node receives the command to
clear latched points, it will resume event monitoring for the points in
question (assuming they are no longer active), then it will report the current
state of the input. If a node receives a command to clear a latched point and
the point is still active, it will ignore the command, except in the case of a
Disable command. If the point receives a Disable command, it will send a
Return to Normal event followed by a Disable event.
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
23
Technical Manuals Online! – http://www.tech-man.com
firealarmresources.com
2.4 Time Codes
To add a time code, enter a start/stop time and the days of the week to which
the time code is assigned. It is also possible to specify if the time code
applies on holidays by checking or unchecking the box labeled “Hol” in the
Time Codes Form.
Each defined time code must contain a start time, stop time, and at least one
day upon which it applies (although it is possible to set a time code for
holidays only). Times are based on a twenty four hour clock and minutes are
inclusive.. Therefore, to set a time code to end at midnight the code must be
defined as 23:59.
Time codes can have a wide range of applications which include (but certainly
are not limited to), specifying times a door is unlocked or locked, activating
a point or output on a set schedule, setting times that an individual can
access certain locations, etc. The application of time codes and their related
data depends entirely on the application or device that implements them.
Figure 2-4: Time Code Configuration
24
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
Technical Manuals Online! – http://www.tech-man.com
firealarmresources.com
2.5 Universal Time Codes and Time Code Groups
The Universal Time Code Editor or UTE is a utility that allows the definition,
viewing, and editing of UniNet Universal Time Codes. These time codes can be
imported into the NION configuration scheduler. The Universal Time code Editor
provides a method of managing time codes from a centralized utility, and
allows importing and transfer of time codes among various applications.
These time codes are defined by the same parameters as time codes described
above. In addition, these time codes can be collected into groups and named.
Using this method, large numbers of time codes can be referenced by a single
definition.
The display boxes on the right of the form contain all available time codes
defined within the UTE. To add any of these codes to the NION time codes grid,
simply click and drag the desired definition from the display on the right
into the grid on the left.
For more information on the Universal Time Code Editor, refer to the
Workstation manual.
2.6 Holiday Codes
Holiday codes define what dates are considered holidays by a particular site
or location. The holiday code editor allows the definition of multiple
calendars, each with up to 75 holidays. A counter at the bottom of the
holidays form shows the number of currently defined holidays. In addition, a
list of common U.S.A. holidays is provided for ease of use. Selecting a
checkbox for a common holiday marks that holiday on the calendar.
Using the buttons labeled Restore and Clear, it is possible to create and
delete calendars. To define holidays, simply select the appropriate calendar
to modify and select the dates on the calendar to define as a holiday. Or use
the common holidays, which also marks the dates on the calendar.
Keep in mind that every calendar must contain at least one holiday code. Any
calendar that does not contain any holiday codes is not saved by the system.
Holiday codes are commonly used to specify separate time code schedules for
set holidays, but like time codes, the actual usage depends on the application
or device in which they are implemented.
Figure 2-5: Holiday Code Configuration
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
25
Technical Manuals Online! – http://www.tech-man.com
firealarmresources.com
2.7 Functional Properties of the 16C48M
There are several properties involved with the operation of inputs and outputs
on discrete point NIONs. Each of these properties must be considered carefully
when configuring points and I/O schedules.
Input Properties The two main properties of any discrete NION input are its
mode and state.
Mode – The mode of an input is a logical condition assigned to the point which
controls the way data from the input is handled, recorded or annunciated. Each
input on a NION may be placed in one of four operational modes. These are:
ARM DISARM OVERRIDE DISABLE
State – The state of the input is the actual physical status of the point
being monitored. The four states are:
Input Active Input Normal Open Circuit Short Circuit
The NION reports different point states based on the current operational mode
of the input.
Rules for Mode Change Commands The mode of any input may be changed by one of
three methods:
Scheduled – time codes defined in the plug-in. When a time code becomes active
(Start Time) the input is disarmed. When the time code expires (Stop Time) the
input is armed. During the intermediate time between start and stop, the
scheduler will not automatically alter the mode of an input.
Manual – user action. Such action can only be initiated from the workstation.
Automatic – UniLogic equation execution. After evaluating an equation,
UniLogic may execute an action which
sends a command to the NION.
Scheduled, manual and automatic are all equivalent in priority. As each mode
change command is received it is given priority over any previously received
command.
NOTE: There are exceptions to the rule of equal priority between mode change
commands. These exceptions are noted as follows and in the detailed
description of each mode in the following paragraphs.
26
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
Technical Manuals Online! – http://www.tech-man.com
firealarmresources.com
One exception to this rule concerns trouble conditions. When a point enters a
trouble state (Open Circuit or Short Circuit) and the point is not currently
in Disabled mode, a trouble condition is immediately reported. Until the
trouble condition clears, the point may only be moved to Disabled mode. All
other mode change commands are ignored. If the point is moved to Disabled
mode, a TROUBLE OFF event is generated prior to the DISABLE event.
When the trouble condition clears and if the point is not Disabled, then
control of the point defaults to the Scheduler which immediately Arms or
Disarms the point according to the time code.
ARM – When a point is in Armed mode it monitors the state of the input and
reports trouble, input active and input normal conditions. The following rules
apply:
1. Any time an input point transitions into the Armed mode, an ARMED event
will immediately be reported. If the point is active, an INPUT ACTIVE event
will be sent immediately after the ARM event.
2. A point in trouble cannot be Armed. When an Arm command is received by a
point that is in trouble the command will be ignored.
Disarm – When a point is in Disarmed mode it does not monitor alarms for the
input point. It will report trouble conditions, but will not report input
active or input normal conditions. The following rules apply:
1. If a point is in an off-normal condition (input active) and a Disarm
command is received the resulting action is based on the origin of the
command. A. If the command originated from a Manual operation the point will
be Disarmed. A return to normal event will be sent before the point is
Disarmed. B. If the command is a Scheduled or Automatic function the point
will not be Disarmed until it returns to normal. When the point returns to
normal, the schedule will be checked and the point will immediately be Armed
or Disarmed according to the schedule.
2. A point in trouble cannot be Disarmed. When a Disarm command is received
by a point that is in trouble the command will be ignored.
Manual Override – This mode functions the same as Disarm with one exception:
When a point is placed in Override mode it will ignore the next Arm command
sent by the Scheduler.
In addition, when a point is in Override mode it will respond to mode change
commands issued manually (user action) or automatically (UniLogic).
Disable – Disable is a maintenance feature to remove input points from the
system. When a point is Disabled it is removed from the system indefinitely. A
Disabled point does not monitor the state of the input and thus will not
report trouble, input active or input normal conditions. Point can only be
Disabled and Enabled manually (user action). The following rules apply:
1. To return a point to the system a user must manually Enable it. When the
point is enabled it is immediately moved to an Armed or Disarmed mode, as
directed by the Scheduler. If the point is in trouble at the time the Enable
command is sent, an enable event will be reported followed by a trouble event.
2. When a point is in the Disabled mode it will not respond to commands by
the Scheduler or UniLogic. 3. When a point is in an off-normal condition when
it is Disabled a return to normal event will be sent before
the Disable event.
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
27
Technical Manuals Online! – http://www.tech-man.com
firealarmresources.com
Special Operational Scenarios – Inputs There is only one way to permanently
Arm an input point; remove all Scheduling and Automatic control for the point
and manually Arm it.
There are three ways to permanently Disarm an input point:
1. Manually Disable the point. 2. Assign an “Always” or 24/7 time code to the
point in the Scheduler and remove all automatic control. 3. Manually Disarm
the point after removing all scheduled and automatic control for the point.
If a point subject to scheduled control needs to be Disarmed prior to the
scheduled time, manually Disarm it.
If a point subject to scheduled control needs to delay entering the Armed
mode, place the point in Override mode. The point can be issued a Manual Arm
command later.
Rules for Output State Changes As with inputs, there are three ways to
initiate operational state changes for outputs:
Scheduled – time codes defined in the plug-in. When a time code becomes active
(Start Time) the output is activated. When the time code expires (Stop Time)
the output is deactivated. During the intermediate time between start and
stop, the scheduler will not automatically alter the state of an output.
Manual – user action. Such action can only be initiated from the workstation.
Automatic – UniLogic equation execution. After evaluating an equation,
UniLogic may execute an action which
sends a command to the NION.
Scheduled, manual and automatic are all equivalent in priority. As each state
change command is received it is given priority over any previously received
command.
There are six different states for output points: Output On Output Off
Automatic Output On Automatic Output Off Momentary Output On Momentary Output
Off
As an output point transitions through any of these states the appropriate
state change event is broadcast on the network.
Output points can transition directly from one off-normal state to another
without a return to normal event between. Example: If a point is in an
Automatic Output On state it can transition directly to a Momentary Output On
state.
A manually issued Momentary Output On is executed as a Momentary Output On
followed by a Momentary Output Off. The pulse time is dictated by the
Momentary field on the I/O Configuration form of the plug-in.
28
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
Technical Manuals Online! – http://www.tech-man.com
firealarmresources.com
Special Operational Scenarios – Outputs There are two ways to permanently
activate an output point:
1. Remove all Scheduling and Automatic control for the point and manually
activate it (Manual Output On). 2. Assign an “Always” or 24/7 time code to the
point in the Scheduler and remove all automatic control
There is only one way to permanently deactivate an output point; remove all
Scheduling and Automatic control for the point and manually deactivate it
(Manual Output Off).
If a point subject to scheduled control needs to be activated prior to the
scheduled time, issue a Manual Output On command.
If a point subject to scheduled control needs to be deactivated prior to the
scheduled time, issue a Manual Output Off command.
Reset Conditions When a soft node reset (workstation command) or a hard node
reset (power down or reset button) occurs, all input points are assumed to be
in the Armed mode (see exception below). As part of the boot sequence, the
scheduler will immediately modify input modes and output states as needed. An
event will be generated for every point on the node.
For hard reset only, all outputs are deactivated in the hardware.
During a node reset, any input point that was in a Disabled mode at the time
of the reset will remain in the Disabled mode.
Memory Loss on the 16C48M Because the 16C48M uses battery backed configuration
memory, the following rules apply:
1. Each time the node is reset a memory check is performed to ensure database
integrity. If at any time a discrepancy is found, the memory will be formatted
to a default state and a MEMORY LOSS event will be broadcast on the network.
2. Default Memory Configuration – all input points are configured to four-
state Normally Open contacts, with 0 second reporting delay. The input points
will default to device type Digital Input with the event code Addressable
Input On/Off.
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
29
Technical Manuals Online! – http://www.tech-man.com
firealarmresources.com
NOTES
30
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
Technical Manuals Online! – http://www.tech-man.com
firealarmresources.com
Index
Symbols
M
.cfg files 20 16C48M Device Addressing 15 NION-16C48M 7
Board Layout 7 Components 8 Description 7 Device Addressing 15 Device Types 20
Installation Requirements 9 Power Requirements 12 2 State Normally Closed
(Non-Latching) 23 2 State Normally Open (Non-Latching) 23 4 State Normally
Closed (Non-Latching) 23 4 State Normally Open (Non-Latching) 23
C
Cabinet Installation 11 Clear Latched Points 23
Mapping Plug-ins With NIONs 20 MPS24BRB 12
N
Network Configuration Window 20 NION
Device Types 20 NION Components 8 NION Configuration
Delay Field 22 NION Power Requirements 12 NION Power Supply Connections 12
NION-16C48MTB Terminal Board 16
Installation 16 Node
Assigning Device Types to, 20
O
D
Delay Field 22 Device Addressing 15 Discrete Inputs 13
G
Get Time 21
I
Input Configuration 13 Input Terminal Board Connections 17 Inputs
Switched Voltage 14 Installation Conditions 9
L
Latched 2 State Normally Closed 23 Latched 2 State Normally Open 23 Latched 4
State Normally Closed 23 Latched 4 State Normally Open 23 Latching Inputs 23
Output Configuration 15 Output Terminal Board Connections 17
P
Plug-In Selection and Configuration 19 Power Requirements 12 Power Supply
Connections 12
R
Ribbon Cable Mapping 16
S
Set State 23 SMX Transceiver Installation 9 Software Configuration 15 Switched
Voltage Input
Jumpers 14 Switched Voltage Input Jumpers 14 Switched Voltage Inputs 13
T
Terminal Board Installation 10 Terminal Boards 16
Installation 16 Time Deisplay 21 Transceiver Installation 9
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
31
Technical Manuals Online! – http://www.tech-man.com
firealarmresources.com
Limited Warranty
NOTIFIER® warrants its products to be free from defects in materials and
workmanship for eighteen (18) months from the date of manufacture, under
normal use and service. Products are date stamped at time of manufacture. The
sole and exclusive obligation of NOTIFIER® is to repair or replace, at its
option, free of charge for parts and labor, any part which is defective in
materials or workmanship under normal use and service. For products not under
NOTIFIER® manufacturing date-stamp control, the warranty is eighteen (18)
months from date of original purchase by NOTIFIER®’s distributor unless the
installation instructions or catalog sets forth a shorter period, in which
case the shorter period shall apply. This warranty is void if the product is
altered, repaired or serviced by anyone other than NOTIFIER® or its authorized
distributors or if there is a failure to maintain the products and systems in
which they operate in a proper and workable manner. In case of defect, secure
a Return Material Authorization form from our customer service department.
Return product, transportation prepaid, to NOTIFIER®, One Fire-Lite Place,
Northford, Connecticut 06472-1653.
This writing constitutes the only warranty made by NOTIFIER® with respect to
its products. NOTIFIER® does not represent that its products will prevent any
loss by fire or otherwise, or that its products will in all cases provide the
protection for which they are installed or intended. Buyer acknowledges that
NOTIFIER® is not an insurer and assumes no risk for loss or damages or the
cost of any inconvenience, transportation, damage, misuse, abuse, accident or
similar incident.
NOTIFIER® GIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF MERCHANTABILITY, FITNESS
FOR ANY PARTICULAR PURPOSE, OR OTHERWISE WHICH EXTEND BEYOND THE DESCRIPTION
ON THE FACE HEREOF. UNDER NO CIRCUMSTANCES SHALL NOTIFIER® BE LIABLE FOR ANY
LOSS OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL OR CONSEQUENTIAL, ARISING
OUT OF THE USE OF, OR INABILITY TO USE NOTIFIER® PRODUCTS. FURTHERMORE,
NOTIFIER® SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE
IN THE COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USE OF
ITS PRODUCTS.
This warranty replaces all previous warranties and is the only warranty made
by NOTIFIER®. No increase or alteration, written or verbal, of the obligation
of this warranty is authorized.
“NOTIFIER®” is a registered trademark.
32
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
Technical Manuals Online! – http://www.tech-man.com
firealarmresources.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>